The Application of Circuit Breakers to Reduce Downtime in Datacentres



Similar documents
Applications for Infrared Thermography at Computer Centers

Reverse-feed applications for circuit breakers

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

SELECTION OF FINAL CIRCUIT PROTECTION

Engineering Series Ratings: Is It Practical?

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Increased power protection with parallel UPS configurations

F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China

ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS

Application of Four-Pole Circuit Breakers within Data Centers

Alternate Methods to Short Circuit Breaker Coordination

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Electrical Shore Connections / Cold Ironing

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS

How To Choose A Transformer

Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application

Nothing s BetterThan the Original MODAN Power Distribution Systems

Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers

CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2

Fundamentals of Power

Part 1 System Modeling & Studies for Existing Systems

ATS - Automatic Changeover

Fuses. Introduction. Measuring is knowing. Who chooses?

Arc Terminator Active Arc-Resistant Switchgear

Extend the Life of Existing Switchgear

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

Paralleling Switchgear

Secondary Unit Substations

Low Voltage Switchgear

Breaking and protection devices

New standardized approach to arc flash protection

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002

Statement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

Primary and Secondary Electrical Distribution Systems

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering

Mission Critical Data Center Systems

Designed for uptime. Defining data center availability via a tier classification system

GE Protection and Control Business Department. Page 1 Date 5/11/99

Data Center Site Infrastructure Tier Standard: Topology

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

Arc Flash Mitigation & Selective Co-ordination

Overload Protection in a Dual-Corded Data Center Environment

Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation

Unified requirements for systems with voltages above 1 kv up to 15 kv

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

THEME Competence Matrix - Electrical Engineering/Electronics with Partial competences/ Learning outcomes

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Safety By Design. Strategies for Electrical Contractors

Safe and secure distribution of medium voltage with AX1

Minimizing Impact of Electric Utility Outages with Backup Generation

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System

415V DISTRIBUTION FOR GREEN DATA CENTERS

SENTRON Switching and Protection Devices Air Circuit Breakers

Tmax MCCBs. Molded case circuit breakers. Tmax

Earth Fault Detection Basics in Theory

Arc Flash Energy Mitigation Techniques

Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability

SIVACON The Versatile Low-Voltage Switchboard

Low Voltage Transformer Through-Fault Protection: A System Approach

The following components are common to most cubicles; this example is an ABB HK cubicle.

Switchgear Application Issues for Mission Critical Power Systems, Part One

A Quick Primer on Data Center Tier Classifications

more than a breaker it s a breakthrough Compact NSX

C.I.8.2 Offsite Power System. C.I Description

Sentron Series Circuit Breakers

High Availability for Non-Traditional Discrete and Process Applications Ensuring Continuous Operations With Increased Controller Reliability

Power products and systems. Intelligent solutions for power distribution Zone concept

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

Green Computing: Datacentres

Power Monitoring for Modern Data Centers

21 st Century Facilities

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A

Switchgear and Metal-Enclosed Bus

IZM ACB/Circuit-breakers. Robust safety. Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors

Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

Isolated-Parallel UPS Configuration

Eaton Automatic Transfer Switches

Data Center Site Infrastructure Tier Standard: Topology

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

Relion. Power system protection and automation reference Fast substation busbar protection with IEC and GOOSE

PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions

415V DISTRIBUTION FOR GREEN DATA CENTERS

Permissible ambient temperature Operation Storage, transport

New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE

What will MV switchgear look like in the future? by Jean-Marc Biasse

Arc Flash Safety in 400V Data Centers

Transcription:

The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the electrical distribution systems of datacentres: To protect plant (transformers, generators, UPS, cables) from damage in the event of overcurrents To provide a route for power from the source of electrical energy to the data processing racks To provide a means of isolation for all or part of the electrical distribution system, thereby facilitating maintenance To prevent electrical shock To prevent fire Every Watt of power used by data processing racks is transmitted through several circuit breakers in series. Their selection, co-ordination and operation are therefore critical for the operation of the datacentre. This paper will describe circuit breaker selection methods and available circuit breaker technology which can contribute to reduced downtime in datacentres. It is divided into issues related to topology (or system layout) and sustainability (performance over time). - 1 -

Contents Topology 3 Fault Level 3 Control Circuit Redundancy 4 Discrimination 4 Zone Interlocking 5 Sustainability 6 Overheating 6 Fire Risk 6 Maintain-ability 7 Circuit Monitoring 7 Conclusions 8 References 9-2 -

Topology The topology of an electrical system is determined by the layout of its elements and interconnections. The choice of circuit breaker and at various points can influence the system topology and vice versa. Fault Level A circuit breaker must be able to interrupt the maximum prospective short-circuit fault level (Ipsc) at its point of installation. Until now, this has restricted the topology of the distribution system as most engineers have designed layouts which restrict the maximum Ipsc to the levels of commonly available switchgear and circuit breakers (50 to 65kA). This is usually achieved by limiting the power fed through each main low-voltage switchboard, therefore requiring a higher number of switchboards and feeder cables to service a given load. The topology of distribution systems for large loads can be simplified by feeding more power through low-voltage switchboards and circuit breakers, provided they can perform correctly at the correspondingly higher fault levels. In the example shown below, the topology of system supplying 4MW of processing load is simplified by using a switchboard and circuit breakers rated for a fault level of 100kA. If the system was for a tier III or tier IV datacentre, the switchboard and circuit breakers are simply duplicated to maintain system + system. Tier classifications also require that switchboards and circuit breakers are type-tested for the fault levels at which they are intended. i - 3 -

The photograph below illustrates an assembly which was been independently type-tested at 100kA. Control Circuit Redundancy The concept of redundancy is familiar to designers of datacentres. The use of redundant components in a system increases its resilience. Redundancy is commonly applied at the level of Uninterruptable Power Supply (UPS) selection, and for the selection of backup diesel generation to ensure that failure of a single UPS or generator does not cause downtime. The operation (closing and opening) of main circuit breakers is usually controlled by the activation of internal closing and opening coils by external control signals. In fact the signal to bring a redundant UPS or generator which cost tens of thousands of pounds online can depend on something as trivial as closing coil in an Air Circuit Breaker (ACB) costing as little as forty pounds. It makes sense therefore, for circuit breakers switching expensive and critical plant, to include redundant closing and opening coils which facilitate duplication of control circuits. Some ACB manufacturers offer double closing and opening coils as an option. ii The addition of an extra closing coil could ensure that a UPS module or diesel generator gets switched into circuit despite a failure in the normal control circuit. Discrimination A circuit breaker is, by definition, a device which opens electric circuits in the event of overcurrents. However in a datacentre, it is important to maintain the supply of electricity to the load for as great a proportion of time as possible; in other words, circuits should remain closed where possible. How can these apparently conflicting requirements be resolved? If a circuit is overloaded or contains a short-circuit, it is essential that the supply of electricity is removed, otherwise fire or explosion may occur within a short time (seconds, minutes or hours for overloads, depending on their magnitude, and milliseconds for short-circuits). However, by employing the correct selection of circuit breakers, and carefully co-ordinating their characteristics and settings, a designer can ensure that only the circuit breaker directly upstream of the fault or overload opens. Circuit breakers further upstream should be unaffected, remaining closed and continuing to supply their remaining loads. If two circuit breakers in series are co-ordinated in this manner, they are said to exhibit discrimination, or selectivity. Discrimination between series circuit breakers on overload faults can usually be established by comparing their tripping characteristics graphically. Discrimination between Moulded Case Circuit Breakers (MCCBs) on short-circuit faults depends on the minimum interruption times and breaker unlatching currents, which are more problematic for the engineer to obtain and analyse. It is therefore usually necessary to consult - 4 -

data from manufacturers to confirm if series devices will discriminate at a particular Ipsc. This analysis and consultation should take place early in the design process, as it may be necessary to use breakers of varying physical size to achieve short-circuit discrimination. This cannot take place after the switchboard has been manufactured without incurring cost. Discrimination between circuit breakers where an ACB is the upstream device is easier to establish, provided the ACB has a short-time withstand (Icw) rating of at least Ipsc. In other words, the ACB must be capable or passing, or withstanding, the maximum potential through-fault current for long enough to allow the downstream device to open. This means that in the example of the 100kA switchgear described under the heading Fault Level, full discrimination is possible if the upstream ACBs have an Icw rating of 100kA. If the ACB has an Icw rating lower than Ipsc, discrimation with downstream devices is not guaranteed. Zone Interlocking The method of discrimination between ACBs described above relies on upstream ACBs having longer short-circuit trip time delays than downstream ACBs. In consequence, the furthest upstream, or incoming, ACB requires the longest time delay. Although necessary for discrimination, this is not always desirable. In the case of a short-circuit fault directly downstream of the incoming ACB, the Ipsc will be greater than for a fault anywhere else in the system, and it would be beneficial to interrupt it as quickly as possible. Zone interlocking provides a solution to the dilemma described above. It is a method of providing short-circuit discrimination without introduced time delays. Rather than forcing upstream breakers to delay opening for all faults, it allows the incoming breaker to trip immediately for a fault directly downstream, but inhibits it from tripping for a through fault on a part of the circuit protected by another breaker. The logic of its operation is as follows: If the fault is on a part of the circuit protected by a downstream breaker, the downstream breaker trips with no intentional time delay, while sending a fault-present signal to all upstream ACBs. On receipt of a fault-present signal, an upstream ACB is inhibited from tripping, and only the downstream ACB opens. If the fault is directly downstream of the incoming ACB (not present in any downstream ACBs), no fault-present signal is received, and the incoming ACB trips immediately, overriding any time delay. The adoption of a zone interlocking scheme enables total discrimination between ACBs, while limiting the exposure of the switchboard to short-circuit faults directly downstream of the incoming ACB. - 5 -

Sustainability Sustainability is a measure of the resilience of a system throughout its operational lifetime. Factors which affect sustainability include: Maintain-ability Susceptibility of the system and components to human error Procedures Training It is notable that these factors all involve the interaction of human beings with the system. This is in contrast to the topology, which is an inherent function of the system layout. Research shows that problems related to sustainability are more likely (70%) to cause downtime in datacentres than problems related to topology (30%). Overheating Prevention of overheating in low-voltage switchgear is commonly attempted by including a thermal imaging survey in the maintenance regime. Thermal imaging relies on human intervention in several aspects: Operators must perform and interpret the survey correctly The maintenance procedure must include thermal imaging surveys often enough to reduce the likelihood of overheating between surveys The maintenance procedure must be followed It is apparent that a failing in any one of these aspects could lead to an undetected overheating problem. Some modern circuit breakers allow for a form of condition-based temperature monitoring to be achieved. For example, the temperature of the main contacts of the circuit breaker may be monitored by sensors which provide an alarm via the protection relay if a temperature threshold is exceeded. This can be seen either as an improvement on, or a complement to thermal imaging surveys, that is, real-time, continuous temperature monitoring is achieved without reliance on human intervention. Fire Risk Fire is one of the few events which can cause downtime in even the most well-designed and best-run datacentres. Wiring regulations in the UK state that a Residual Current Device (RCD) with a residual current trip setting of not more than 300 milliamperes can be effective in preventing fire caused by leakage currents to earth. iii A very efficient means of providing this level of protection on distribution circuits is to use a Circuit Breaker with Residual current protection (CBR). The most modern types of CBR have the residual current protection included within the standard frame of a Moulded Case Circuit Breaker (MCCB). No additional RCDs are therefore required, which simplifies the design of the switchgear systems. Indeed, CBRs can provide great flexibility, allowing for wide setting ranges for residual current tripping, adjustable time delays and even alarm-only non-trip settings for critical loads. iv - 6 -

Maintain-ability A tier IV data centre with a system-plus-system configuration must allow for concurrent maintenance, that is, it should be possible for any path or component to be taken out of service for maintenance or repair with no disruption to the load. An elevated risk of disruption is permitted during maintenance, but it is obviously desirable that this risk should exist for the shortest possible time. An example is shown below of a design innovation which inherently and obviously improves repair-ability and maintain-ability of ACBs. All withdrawable ACBs include a set of connections which carry current from the chassis (fixed part) to the body (withdrawable part). The connections always take the form of a sprung contact-cluster assembly, which, as an important current-carrying connection, may need maintenance or repair. Traditional ACB designs have the sprung contact-cluster mounted on the chassis part. As the supply-side connections will be live, maintenance or close inspection requires a full shutdown of the host switchboard by upstream isolation. Conversely, if the spring contact-clusters are mounted on the body, they can be easily and quickly maintained or repaired on withdrawal of the body, with the rest of the switchboard remaining in service. Circuit Monitoring Prompt and effective operational decisions must be informed by accurate information. In an electrical circuit which is critical to the operation of a datacentre, the measurement and recording of the following parameters provides essential information: Voltage Current Energy Power Factor It is possible to use circuit breakers rather than separate instruments to measure, record and transmit these parameters. Circuit breakers with microprocessor-based protection relays have current and voltage sensors built-in, and only require additional data processing capability to function as multimeters and energy analysers. Many models also offer very advanced functionality such as fault data recording, harmonic analysis and transmission of data over communications networks. - 7 -

Conclusions Knowledgeable application of circuit breakers in a datacentre electrical distribution system can ensure not only that equipment is protected from overcurrents, but that it is less likely to incur downtime. Furthermore, downtime can be minimised by careful consideration of products relating to their maintainability. It is important that designers of electrical systems for datacentres not only understand the theoretical evaluation of switchgear, but that they visit and talk to manufacturers to find out how to better apply their products. - 8 -

References i Tier Classifications Define Site Infrastructure Performance. W. Pitt Turner IV, John H. Seader, P.E., and Kenneth G. Brill. The Uptime Institute. ii TemPower 2 ACB Double Breaker Two Steps Ahead No. 08-I55E. Terasaki Electric (Europe) Ltd. iii BS 7671: 2008 IEE Wiring Regulations 17 th Edition iv TemBreak 2 CBR, Circuit Breaker with Residual Current Protection. No. 08-P41E. Terasaki Electric (Europe) Ltd. - 9 -