Isolated-Parallel UPS Configuration

Size: px
Start display at page:

Download "Isolated-Parallel UPS Configuration"

Transcription

1 Isolated-Parallel UPS Configuration 1

2 Inhalt 1 Introduction IP systems configuration Projects Conclusions

3 Abstract The isolated-parallel UPS configuration has become well established in the marketplace as a system solution for medium-sized and large computer centers. It enables huge savings to be made in UPS units and therefore contributes to an improvement in the efficiency of the overall system. At the same time, the reliability of isolated-parallel systems (IP systems) is comparable to the most reliable Tier 4 system configurations [5]. This white paper deals with the operating principles of IP systems, the integration of Diesel engines, the UPS topologies and the types of energy storage devices that are suitable for this application. Then follows an overview of project-specific designs which illustrates the flexibility and performance of IP systems. 3

4 1 Introduction Power-critical facilities are tending to be larger and have an increasing number of sensitive loads, requiring more and more highly-reliable electrical power. Direct paralleling of UPS systems see Figure 1 is a commonly used method for increasing the available output power and for providing redundancy. A simple arrangement for safeguarding the power supply is an N+X redundant-parallel configuration, with N denoting the number of UPS units needed to supply the load, and X representing the number of redundant units. Figure 1 Parallel UPS configuration Since in this configuration several units are supplying the same paralleling bus, the redundant-parallel scheme is limited to around 5 to 6 MVA at low voltages and is virtually impossible to maintain during operation. Even though the simple N+X redundancy ensures high availability, it is highly probable that a failure of the common bus will cause complete failure of the supply to the loads. To avoid this "single point of failure", a second, isolated bus can be used. In order to achieve full redundancy, the systems need to be realized so that each bus is able to supply the full load. Therefore this so-called N+N redundant system configuration, shown in Figure 2, needs twice the number of UPS units to supply the load. As a result, many of these units are only partially loaded and are not operated at optimum efficiency. Such a system will not therefore be the first choice if a "green" UPS solution is the primary consideration, but nevertheless should still be considered because of its extremely high reliability. Like the parallel-redundant scheme, this also has limited capacity at low voltages. 4

5 Figure 2 System-redundant UPS configuration with static transfer switches (STS) Another way of avoiding the central bus is to abandon paralleling of UPS units. This results in the so-called isolated-redundant configuration, which is shown in Figure 3. In this configuration each UPS supplies its dedicated load while one or more redundant UPS units are running in the standby mode, ready to supply the load if one of the UPS units fails. Figure 3 Isolated-redundant UPS configuration with static transfer switches (STS) Both the isolated-redundant and system-redundant configuration require additional equipment, such as a central load management system and static transfer switches for single-feed loads to switch to the alternate power source in the event of failure of one UPS. A disadvantage of the insulated-redundant configuration is that there is no option for automatic load sharing between modules and the fact that one or more UPS units are running in idle mode, i.e. without supplying a load. When combined with Diesel engines, this results in engines running in idle mode during power system failures, which reduces engine performance if this occurs over several hours. 5

6 In 2005, the idea of a new system configuration was born the so-called isolated-parallel system (IP system). The basic development goal of this new configuration was to avoid the disadvantages of the conventional UPS configurations described above and to combine their advantages in a new highly-reliable system topology. This topology allows repeated paralleling of UPS modules combined with automatic load sharing and high efficiency while ensuring fault insulation between the load buses of the individual units. 2 IP systems configuration In an IP system (see Figure 4) each UPS is connected to a common bus (IP bus) via a choke (IP choke). The loads are supplied directly from the UPS units. The job of the IP choke is to reduce fault current to an acceptable level while ensuring adequate load sharing among the UPS units. Abbildung 4 Basic design of an IP system This load sharing enables the IP system to be designed as a simple N+X redundant configuration and the number of redundant units can be reduced to a minimum. Since in this case each UPS unit is run at a high-efficiency operating point, IP systems represent an energy-saving power supply for "green" data centers and other facilities where high reliability and energy efficiency are extremely important. 6

7 Load sharing In normal operation each load is supplied from the power grid via the associated UPS. Where the UPS units are equally loaded, no power is transferred thru the IP chokes. Each UPS unit independently regulates its output voltage to the specified nominal value. Any voltage differences are absorbed by the IP chokes so that, even in the absence of reactive current control, no reactive current is exchanged between the UPS units. In an uneven load distribution, each UPS still predominantly feeds its dedicated load. Loads which are greater than the average load of the system receive additional active power from the UPS with the lower load via the IP bus (see Figure 5). The power flow and the natural load sharing among the UPS units is determined by the combination of the phase angles between the respective UPS output buses and the impedances of the IP chokes. Figure 5 Example of load sharing in an IP system consisting of 16 UPS modules The load-dependent phase angle at the UPS unit between the supply system and the UPS output is the main factor with regard to natural load sharing. Different phase angles between the UPS outputs due to differing loads, result in active power flow thru the IP chokes located between the units. This active power is directed so that it flows from the unit with the lower load with a small phase angle to the unit with the higher load with the greater phase angle and consequently ensures load equalization between the units. Therefore no active load equalization control is necessary during power grid operation. A suitable UPS topology to achieve this load-dependent phase angle in a natural way is a rotary UPS with an internal coupling choke, as shown in Figure 9. Looking at the mechanisms of natural load sharing in IP systems, it is obvious that a direct connection between any location downstream of the UPS and the power grid would significantly disturb the system. This connection would eliminate the phase angle between the power grid and the load, so that the loads of the whole IP system would be supplied by 7

8 this bypass via the IP bus. Therefore before a UPS unit or its load is switched to bypass, it is imperative that it is first disconnected from the IP bus to avoid this overload situation. However, an IP system would not really be an advantage compared to existing system topologies if there were to be no alternate solutions to this kind of bypass operation. Should a UPS fail suddenly and without warning, its associated load continues, nevertheless, to be connected to the IP bus via the IP choke and power is automatically supplied to it via this connection. As Figure 6 shows, in this operating mode each of the remaining UPS units contributes to the supply to the affected load which, furthermore, also continues to be protected against power failures by the UPS sets.. Figure 6 Example of a redundant supply to a load in an IP system in the event of failure of one UPS Since the affected load is now supplied via the IP chokes, its supply voltage is reduced by the voltage drop across these chokes. Appropriate design of the IP chokes can result in a supply voltage deviation at the load of less than 10% of the nominal voltage and is therefore within the permissible range defined by the ITI Curve [3] for the continuous supply. Up to this point, despite the failure of one UPS, absolutely no switching operations are therefore required to ensure the continuous supply of power to the load. The voltage drop across the IP chokes can be further reduced by connecting the load directly to the IP bus by means of a pair of switches. Figure 7 shows an IP system in which the IP bus is extended to a ring. The additional part is termed an IP return bus and, like other parts of the IP bus, can be used as a bypass for the loads. An additional pair of switches on the load bus enables no-break load transfer between the UPS output and the IP return bus. This enables controlled insulation of an individual UPS from the IP system and also reconnection to this system in order to carry out maintenance operations, for example, without having to interrupt the UPS supply to the load. 8

9 Figure 7 IP-system with the load of UPS #2 directly supplied via the IP return bus Short-circuit response The main reason for using IP topology is that possible short-circuits due to the use of IP chokes have only minor effects on the loads. In spite of this, short-circuits must also be insulated in an IP system as quickly as possible, both to meet the safety requirements and to keep interference on the power supply to the loads to within the limits specified by the ITI Curve. In the event of a short-circuit at the load shown in Figure 8 the effects on the whole system are relatively minor since two IP chokes are always connected in series between the short-circuit and the remaining loads. With suitably designed IP chokes the dynamic voltage sag at the unaffected loads is less than 10% of the nominal voltage. 400 V UPS 1 UPS 2 UPS 3 UPS ka 1166 A 10,5kA 1166 A IP-Bus Figure 8 load side of UPS #2. 46,5 ka 387 V 0 V 387 V 387 V Load 1 Load 3 Load 10 (40ms) 1 Example of fault circuit distribution in an IP system with a short-circuit on the 9

10 The IP bus is the central element of an IP system. A short-circuit on the IP bus has repercussions for all UPS units and their loads connected to them and is therefore a particularly critical event for the entire system. Compared to a short-circuit in the load distribution system, in the event of a short-circuit on the IP bus, only one IP choke is located in each case between the short-circuit and the UPS output or the load. As a result, in this case the voltage sag at the loads is much larger than the voltage sag in the case of a short-circuit in a load distribution system. With a low subtransient UPS reactance, the initial voltage sag at the load is limited to a value below 30%. For sensitive computer power supplies, according to the ITIC curve such a voltage sag is permissible for a maximum period of 500 ms. A protection concept which is specially tailored to the requirements of the IP system enables a short-circuit on the IP bus to be selectively insulated within 70 ms and at the same time enables the section of the IP system that is not directly affected to remain fully operational. Although this involves a less serious short-circuit for the loads, these numbers make it clear that it is advisable to take measures by which a possible short-circuit on the IP bus can be largely eliminated. The use of busbar systems, for example, which because of their compact construction are well-suited to isolating the IP bus from external effects, can contribute to a short-circuit-proof design. An essentially simple design using components with the lowest possible interference susceptibility, such as outgoing circuits and switch connections, likewise contributes to the prevention of possible short-circuits. UPS system An IP system consists of a number of UPS systems. Such a UPS system comprises the following main components: a UPS with an energy storage device, an IP choke for linking the UPS unit to the IP bus and the breakers necessary for the safe operation of the system. Figure 9 shows a system utilizing a rotary UPS. 10

11 Figure 9 Example of a UPS system utilizing a Piller UNIBLOCK UBT rotary UPS and a separate Diesel generator. 1 Public utility power grid 2 IP bus 3 IP return bus 4 Rotary UPS flywheel energy storage device 5 Diesel generator for long-term power supply interruptions (optional) 6 IP choke (with choke circuit-breaker) 7 Breaker pair for bypass transfer 8 IP bus disconnecting switches 9 Load An IP system is not limited to one special type of UPS installation. If, however, it is desirable to make optimum use of the advantages of such a system, then a rotary UPS with internal coupling choke is mandatory. Its high short-circuit capacity and its natural load sharing makes this type of UPS the best choice for an IP system. Rotary Diesel UPS systems are a suitable solution for bridging long-term power supply interruptions. Alternately, rotary UPS units combined with external Diesel generators connected to the UPS output can also be employed. 11

12 Even though a UPS in an IP system can be equipped with any kind of energy storage device, for stability reasons a bidirectional-operating energy storage device, such as an electricallycoupled flywheel is to be preferred. Otherwise, if batteries or electromagnetic clutches are used, the UPS system should be able to supply power and take up power equally in order to ensure the stability of the entire system, for example in the event of sudden changes in load. Control The control of voltage, current and frequency, plus all synchronization operations are realized by the controllers in the respective UPS unit. The UPS also controls its associated breakers and ideally, if required, should also be able to synchronize itself to other voltage systems, such as the IP bus, for example. A so-called system control is assigned to each UPS system. This is the central unit for operating and monitoring the UPS system. A mimic diagram which visualizes the status of the UPS system and also enables safe operation of the system is located at the front end of each system control. At the same time, the system control monitors all essential voltages, currents, phase angles and performance data of the associated UPS system. Signal lines between the system control and the UPS enable the functions of the UPS needed for system integration to be controlled, but without impairing the basic functionality of the individual UPS units. If required, the control of a separate Diesel generator integrated in the system, as well as its synchronization, can be realized by the system control. A digital communications interface allows easy integration of the system control in a building management system (BMS). Another PLC, the so-called master control, serves as primary control and monitoring for the entire IP system. Because of its central function, it consists of two redundant controls which communicate with the system control via a redundant digital communications bus. The master control collects the measurement data from the system controls and continuously compares the system utilization with the available UPS capacity. The data resulting from this comparison are sent back to the system control which, on the basis of these data, is able to react with the correct measures to a possible overload situation or to the failure of one UPS. The master control also controls the restoration of the power supply for the individual UPS systems and therefore enables a controlled transfer of the load of the IP system to the utility power grid. Figure 10 shows the arrangement of controls of an IP system. 12

13 Figure 10 Steuerung eines IP-Systems: Anordnung der Systemsteuerungen (S), der Mastersteuerungen (M) und der redundanten Kommunikationsleitungen Additional control cables which interconnect the individual system controls, enable the exchange of all the most important signals, even in the unlikely event of simultaneous failure of both master controls. An IP system can therefore be safely operated without a master control and with little restriction of its functionality. Operating modes In the power grid mode each UPS is connected to the power grid and supplies active and reactive power to its dedicated load. At the output side the UPS is connected via the IP choke to the IP bus, which enables independent control of the output voltage while equalizing active power with the other UPS units. The energy storage devices are fully charged and the Diesel engine is switched off. In the event of a power failure, each UPS is automatically isolates itself from the power grid and for the time being the load is supplied by the energy storage device of the UPS. From this moment on, the load sharing between the UPS units is controlled by a droop function, which is based on a power/frequency characteristic implemented in each UPS. Because the same characteristic is present in each UPS, no communication regarding the load sharing is 13

14 required between the individual systems. After the Diesel engines are started, the supply to the load is automatically transferred from the energy storage device of the UPS to the Diesel engine, so that the energy storage device can be recharged and, if required, again becomes fully available. To ensure load sharing also in the Diesel mode, each Diesel engine is controlled by the associated UPS via its internal droop function, irrespective of whether the engine is mechanically connected to the generator of the UPS (Diesel UPS) or an external Diesel generator is used. From a control point of view, due to this integration an external Diesel generator is also an integral part of the UPS system and the combination of UPS and Diesel generator can be considered as one unit. A special control structure in the UPS, in combination with the bidirectional energy storage device, enables active frequency and phase stabilization, which is also effective in the Diesel mode. The restoration of the power supply to the individual UPS systems is verified by the master control. Following a predefined power grid stabilization period and after all energy storage devices have been recharged, the master control ensures that the UPS systems are restored in sequence to the power grid mode. This procedure also enables high-power IP systems to be switched back to the supply system, without causing sudden, excessive load fluctuations in the power grid. Synchronization to the power grid uses a common synchronization voltage, which is obtained centrally from the main incoming supply. The shared use of this synchronization voltage as the preferred source, as well as the line voltage at each individual UPS as redundancy, ensures uniform synchronization of all systems, even if the line voltage may not be available to some UPS systems. As soon as the first UPS system is reconnected to the grid, the load sharing between the UPS systems which are still partially in the Diesel mode, can no longer be realized via the regular droop function because the system is now limited to the constant frequency of the power grid. Therefore, a new control method for load sharing had to be developed when operating at a fixed frequency. This new control, which was developed and patented by Piller Group GmbH, is called Delta Droop Control (DD control) and enables load sharing in mixed grid and Diesel mode, without the UPS systems having to communicate with each other regarding the load sharing. DD control is based on the physical characteristics of the individual IP system and enables each UPS unit in Diesel mode to adjust its power output at the units in grid mode, without the need for a central control unit. 14

15 Figure 11 Example of the load flow in an IP system: UPS #1 is already in grid mode, while units #2 to #16 are still in Diesel mode and their load sharing is controlled by the DD control. Stability An electrical network whose elements are interconnected by chokes has a slight tendency to oscillations which can be caused by sudden changes in the load distribution resulting from load fluctuations, Diesel engine starts and power outages. In this case, each load fluctuation at a UPS initially causes a change in the phase angle between the power grid and the UPS output. This change delayed by the IP chokes - is then transmitted to the other UPS units until, resulting from the new load distribution, a new operating point of the entire system has been established. To prevent this process from producing oscillations, transient frequency changes which inevitably occur as a result of changes in phase angles, must be effectively attenuated. So that this can happen, irrespective of the polarity of the load change, the energy storage device of the UPS should be able to absorb power of the same order of magnitude as it can also supply. Maintainability Assuming a redundant system configuration, the option to transfer the load from a UPS system to the IP return bus allows maintenance of a UPS system while its load is safely supplied by the remaining UPS units via the IP bus. 15

16 Additional breakers in the IP bus ideally on both sides of the IP choke connections as shown in Figure 9 allow sections of the IP bus to be insulated so that maintenance work can be carried out even on the IP choke and the IP bus itself. The IP system remains fully functional during maintenance, since the resulting sections of the IP bus are always connected by the IP return bus and the IP bus therefore continues to be available as an alternate supply for the load. By utilizing DD control it is also possible to carry out maintenance on the incoming feeder of a UPS system, with only the affected UPS then running in Diesel mode and the remaining UPS units able to remain in grid mode. Summarizing the above-mentioned functions, the IP system is probably the simplest system topology which, combined with maximum reliability, can be maintained during operation. All other solutions with similar maintainability (system redundancy, isolated redundancy and distributed redundancy) have a far more complex infrastructure requiring more maintenance, which in this case is possibly also subject to greater risks. Efficiency The high efficiency of an IP system is obtained because its very high reliability is achieved using a small number of redundant UPS units. Combined with load sharing, all UPS units can therefore be operated in a working point with high efficiency. In an IP system with a total power of 20 MW, for example, UPS units can be operated at 94 % capacity utilization. In a system redundant arrangement with similar high reliability the UPS units have only a maximum utilization of 45%. Consequently, there is a difference in the electrical efficiency of the individual UPS units of 3 to 4 %. This translates as a potential energy loss of around 5 to 7 GWh per year and therefore additional operating costs of up to (based on a price of 10 ct/kwh), not including additional costs of the increased cooling requirement. In addition to the advantages described above, an IP system therefore also constitutes a "green" solution and meets the economic requirements of a modern data center. 16

17 3 Projects The first isolated-parallel system was developed in 2007 for a data center in Ashburn, Virginia, [2]. It supplies a total load of 36 MW. The installation consists of two separate IP systems, each equipped with 16 Piller UNIBLOCK UBT 1670 kva UPS units with flywheel energy storage devices in a 14+2 redundant configuration. Each UPS is backed up by a separate 2810 kva Diesel generator, which is connected to the load bus downstream of the UPS and is able to supply critical as well as general loads. Since the success of the initial installation, further data centers with IP systems have been commissioned worldwide, many of which are in the order of 10 to 20 MW. 4 Conclusions The isolated-parallel system uniquely enables the advantages of combining isolatedredundant and parallel-redundant UPS configurations. It enables: distributed redundancy between the UPS units with simultaneous decoupling of the respective load buses and therefore the simple design of large, parallel UPS systems with several outputs. What also distinguishes the IP system from other systems are the outstanding maintainability and the unique fault tolerance, which ensure an extremely reliable and robust power supply for highavailability data centers, for example. Due to the use of flywheel energy storage devices and the possibility of realizing large UPS systems of up to 20 MW in low-voltage technology, the IP system is particularly suited to applications in which minimizing space requirement and maximizing return on capital are of the highest priority. By reducing the redundant UPS units to a minimum and avoiding systems which run in the standby mode, in addition to an extremely "green" solution, the IP system is an excellent choice when a safe and ecologically acceptable power supply is demanded. 17

18 References [1] Mike Mosman, Iso-Parallel Rotary UPS Configuration, 7x24exchange, 2005 Fall Conf., [2] Mike Mosman, An Isolated-Parallel UPS System for a large Data Center, 7x24exchange, 2007 Fall Conf., [3] Published by Information Technology Industry Council, revised 2000 [4] Ralf Briest, Kevin Collins, Hilmar Darrelmann, Mike Mosman Load Sharing and Stability Analyses of Iso-Parallel UPS Systems PCIM Europe 2007 [5] Frank Herbener, Reliability of UPS Piller White Paper No. 054 Frank Herbener, Piller Group GmbH, Frank.Herbener@piller.com, Germany White Paper No / Mrz

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran A_lashkarara@hotmail.com Seyed Ali NABAVI NIAKI University of Mazandaran

More information

NO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM

NO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM NO-BREAK KS 7e Concentrated Energy e 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM Data Centre owners, operators and designers are required to meet ever increasing and

More information

Increased power protection with parallel UPS configurations

Increased power protection with parallel UPS configurations Increased power protection with parallel UPS configurations Making the selection between Centralized Bypass and Distributed Bypass systems Janne Paananen Application Engineer, Large Systems Group Eaton

More information

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it

More information

Guidelines for ATS selection: How to choose the right transfer solution for your power application.

Guidelines for ATS selection: How to choose the right transfer solution for your power application. Power topic #7012 Technical information from Cummins Power Generation Inc. Guidelines for ATS selection: How to choose the right transfer solution for your power application. > White Paper By Gary Olson,

More information

APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.

APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract. USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS Abstract This application note describes the necessary procedure to use a standard Pacific Power Source Model

More information

Cahier technique no. 196

Cahier technique no. 196 Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for

More information

Asia Pacific Regional Power Quality Seminar 28-31 March 2005, Marriot Putrajaya, Malaysia. Voltage Source Converter based Power Quality Solutions

Asia Pacific Regional Power Quality Seminar 28-31 March 2005, Marriot Putrajaya, Malaysia. Voltage Source Converter based Power Quality Solutions Asia Pacific Regional Power Quality Seminar 28-31 March 2005, Marriot Putrajaya, Malaysia Voltage Source Converter based Power Quality Solutions Olivier Suter ABB Holdings Sdn. Bhd., Div. APAN Automation

More information

Chapter 1. Network Structures

Chapter 1. Network Structures Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V

More information

Chapter 5. System security and ancillary services

Chapter 5. System security and ancillary services Chapter 5. System security and ancillary services 1 Introduction Markets for electrical energy can function only if they are supported by the infrastructure of a power system. System should continue to

More information

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING

More information

ELECTRONIC POWER SYSTEMS

ELECTRONIC POWER SYSTEMS ELECTRONIC POWER SYSTEMS TRADEOFFS BETWEEN SINGLE-PHASE & THREE-PHASE POWER WHITE PAPER: TW0057 1 Executive Summary Modern Electronic Systems are quite often powered from a three-phase power source. While

More information

FIT TIER 2 Application

FIT TIER 2 Application FIT TIER 2 Application Application Information The below information Auto-Fills from your registration information: Building Permit Application Date: Project Completion Date: Name: Address: City: State:

More information

Nuclear Power Plant Electrical Power Supply System Requirements

Nuclear Power Plant Electrical Power Supply System Requirements 1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the

More information

30 ms High Speed Transfer System (HSTS) Product Description

30 ms High Speed Transfer System (HSTS) Product Description 30 ms High Speed Transfer System (HSTS) Product Description 2 30 ms High Speed Transfer System (HSTS) Product Description Content Page 1 General 5 1.1 Description of the 30 ms high speed transfer system

More information

Minimizing Impact of Electric Utility Outages with Backup Generation

Minimizing Impact of Electric Utility Outages with Backup Generation Minimizing Impact of Electric Utility Outages with Backup Generation Introduction of the Speaker Michael Dempsey, PE Senior Electrical Engineer Carter & Burgess, Inc. Energy & Power Solutions Facility

More information

High-Availability Power Systems, Part II: Redundancy Options

High-Availability Power Systems, Part II: Redundancy Options Liebert July 2003 High-Availability Power Systems, Part II: Redundancy Options SUMMARY High-Availability power systems require Reliability, Functionality, Maintainability, and Fault Tolerance. A few UPS

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

Wide Area Monitoring Current Continental Europe TSOs Applications Overview

Wide Area Monitoring Current Continental Europe TSOs Applications Overview Wide Area Monitoring Current Continental Europe TSOs Applications Overview Version 5 System Protection & Dynamics Working Group 20th September 2015 1. Content 1. Content... 2 2. Introduction... 3 3. Main

More information

The Application of Circuit Breakers to Reduce Downtime in Datacentres

The Application of Circuit Breakers to Reduce Downtime in Datacentres The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the

More information

Comparative study for cables and busbars

Comparative study for cables and busbars Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary

More information

SSPI-APPN OTES: PARALLEL C ONNECTIONS

SSPI-APPN OTES: PARALLEL C ONNECTIONS There are two distinct reasons to connect power supplies in parallel: Current Sharing and Redundancy. Combining of these reasons is common, and there are many ways to implement them. The unique considerations

More information

Designed for uptime. Defining data center availability via a tier classification system

Designed for uptime. Defining data center availability via a tier classification system Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center

More information

415V DISTRIBUTION FOR GREEN DATA CENTERS

415V DISTRIBUTION FOR GREEN DATA CENTERS White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International

More information

MGE Galaxy 7000. 160/200/250/300/400/500 kva Power efficiency for business continuity

MGE Galaxy 7000. 160/200/250/300/400/500 kva Power efficiency for business continuity MGE Galaxy 7000 160/200/250/300/400/500 kva Power efficiency for business continuity Performance three-phase power protection with high adaptability to meet the unique requirements of medium to large data

More information

POWER TRANSMISSION FROM OFFSHORE WIND FARMS

POWER TRANSMISSION FROM OFFSHORE WIND FARMS POWER TRNSMISSION FROM OFFSHORE WIND FRMS Thorsten Völker University of pplied Sciences Bremerhaven Germany BSTRCT The future for wind power generation in Germany is offshore wind energy. The preferred

More information

The Different Types of UPS Systems

The Different Types of UPS Systems The Different Types of UPS Systems By Neil Rasmussen White Paper #1 Revision 5 Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics.

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

AC COUPLED HYBRID SYSTEMS AND MINI GRIDS

AC COUPLED HYBRID SYSTEMS AND MINI GRIDS , Michael; Hermes, Matthias SMA Technologie AG Hannoversche Str. 1-5 34266 Niestetal GERMANY E-mail: Michael.@SMA.de E-mail: Matthias.Hermes@SMA.de 1. INTRODUCTION Distributed supply based on renewable

More information

Advanced Protection of Distribution Networks with Distributed Generators

Advanced Protection of Distribution Networks with Distributed Generators Date:- 8 10 March 2011 Venue: University of Manchester EES-UETP Course title Advanced Protection of Distribution Networks with Distributed Generators Peter Crossley Director of the Joule Centre School

More information

Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply. www.siemens.com/siestorage

Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply. www.siemens.com/siestorage Totally Integrated Power SIESTORAGE The modular energy storage system for a reliable power supply www.siemens.com/siestorage Totally Integrated Power (TIP) We bring power to the point. Our products, systems,

More information

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB

More information

The electrical energy produced at the gen

The electrical energy produced at the gen 300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

The Different Types of UPS Systems

The Different Types of UPS Systems White Paper 1 Revision 7 by Neil Rasmussen > Executive summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics. Each of these UPS types is

More information

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems System Grounding and Ground-Fault Protection Methods for -Supplied Power Systems Bill Brown, P.E., Square D Critical Power Competency Center 1. INTRODUCTION The use of solid grounding for -supplied power

More information

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Power over Ethernet technology for industrial Ethernet networks

Power over Ethernet technology for industrial Ethernet networks Power over Ethernet technology for industrial Ethernet networks Introduction Ethernet networking has grown beyond office and home usage to become a very successful protocol suite used in many industrial

More information

Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template

Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Application Note Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Author Jens Baumeister jens.baumeister@omicron.at Date

More information

Earth Fault Detection Basics in Theory

Earth Fault Detection Basics in Theory Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star

More information

Interconnection of Generators to EDI s Distribution System

Interconnection of Generators to EDI s Distribution System Interconnection of Generators to EDI s Distribution System May 22, 2002 This document sets forth the guidelines for connecting a power producing facility to the Alberta Interconnected Electric System through

More information

The Different Types of UPS Systems

The Different Types of UPS Systems Systems White Paper 1 Revision 6 by Neil Rasmussen Contents Click on a section to jump to it > Executive summary There is much confusion in the marketplace about the different types of UPS systems and

More information

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe NETWORKS ESB Networks Response to ERGEG Consultation on Voltage Quality Regulation in Europe Date: 22 February 2007 Distribution System Operator ESB Networks Page 1 of 12 Contents 1.0 INTRODUCTION...3

More information

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check

More information

415V DISTRIBUTION FOR GREEN DATA CENTERS

415V DISTRIBUTION FOR GREEN DATA CENTERS White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International

More information

HVDC-VSC: transmission technology of the future

HVDC-VSC: transmission technology of the future A bi-pole ± 285 kv HVDC line sandwiched between 3-phase 400 kv HVAC lines. HVDC-VSC: transmission technology of the future A new hybrid HVDC circuit technology using voltage source converters is only half

More information

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price

More information

Liebert APM from 30-150 kw. The Compact Row-Based UPS With FlexPower Technology TM

Liebert APM from 30-150 kw. The Compact Row-Based UPS With FlexPower Technology TM Liebert APM from 30-150 kw The Compact Row-Based UPS With FlexPower Technology TM Emerson Network Power, a division of Emerson, is a global company that combines technology with design to supply innovative

More information

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER 1 KARUNYA CHRISTOBAL LYDIA. S, 2 SHANMUGASUNDARI. A, 3 ANANDHI.Y 1,2,3 Electrical

More information

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters

More information

Technical Information Short-Circuit Currents Information on short-circuit currents of SMA PV inverters

Technical Information Short-Circuit Currents Information on short-circuit currents of SMA PV inverters Technical Information Short-Circuit Currents Information on short-circuit currents of SMA PV inverters Content During grid failures as for example voltage dips, all PV inverters may generate currents that

More information

UPS Topologies & Architectures. Don Lemmon Tubbesing Solutions (214) 690-6866 don@tubbesing.com

UPS Topologies & Architectures. Don Lemmon Tubbesing Solutions (214) 690-6866 don@tubbesing.com UPS Topologies & Architectures Don Lemmon Tubbesing Solutions (214) 690-6866 don@tubbesing.com Tubbesing Solutions & Tubbesing Solutions Mike Farrell Mobile No. (214) 355-0493 Tubbesing Solutions Portfolio

More information

HVDC 2000 a new generation of high-voltage DC converter stations

HVDC 2000 a new generation of high-voltage DC converter stations HVDC 2000 a new generation of high-voltage DC converter stations Improved performance and robustness, shorter lead times and faster delivery, plus reduced maintenance needs, were the development goals

More information

DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS

DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display

More information

RIELLO ELETTRONICA. Master HP

RIELLO ELETTRONICA. Master HP RIELLO ELETTRONICA Master HP LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTRES TELECOM- MUNICATIONS DEVICES E-BUSINESS (Servers Farms, ISP/ASP/POP) INDUSTRIAL PROCESSES INDUSTRIAL PLCS ELECTRO- MEDICAL DEVICES

More information

Context: significant penetration of DG = increased risks for system security

Context: significant penetration of DG = increased risks for system security Distributed Generation: towards an effective contribution to power system security IEEE Tampa GM 2007: Panel on Impact of Dispersed Generation on Power System structure & security Bruno Meyer Outline Context:

More information

1+1 PROTECTION WITHOUT RELAYS USING IDT82V2044/48/48L & IDT82V2054/58/58L HITLESS PROTECTION SWITCHING

1+1 PROTECTION WITHOUT RELAYS USING IDT82V2044/48/48L & IDT82V2054/58/58L HITLESS PROTECTION SWITCHING 1+1 PROTECTION WITHOUT RELAYS USING IDT82V2044/48/48L & IDT82V2054/58/58L APPLICATION NOTE AN-357 1.0 INTRODUCTION In today's highly competitive market, high quality of service, QOS, and reliability is

More information

Piller Rental. Nothing protects quite like Piller. High performance containerized UPS systems. www.piller.com

Piller Rental. Nothing protects quite like Piller. High performance containerized UPS systems. www.piller.com Piller Rental High performance containerized UPS systems Nothing protects quite like Piller www.piller.com 2 Nothing protects quite like Piller Index History of reliability 3 Piller Rental 4 Available

More information

Theoretical review. Contents

Theoretical review. Contents Theoretical review Contents Supplying sensitive loads... 2 Types of electrical disturbances...2 Main disturbances in low-voltage electrical power...3 UPSs... 4 The UPS solution...4 UPS applications...5

More information

Industrial Ethernet How to Keep Your Network Up and Running A Beginner s Guide to Redundancy Standards

Industrial Ethernet How to Keep Your Network Up and Running A Beginner s Guide to Redundancy Standards Redundancy = Protection from Network Failure. Redundancy Standards WP-31-REV0-4708-1/5 Industrial Ethernet How to Keep Your Network Up and Running A Beginner s Guide to Redundancy Standards For a very

More information

Design of electrical power system for a 1000MW nuclear power generating station

Design of electrical power system for a 1000MW nuclear power generating station Design of electrical power system for a 1000MW nuclear power generating station K Raja, K Yesunadam Dept. of Electrical & Electronics Engineering, Lingaya s Institute of Management & Technology, Vijayawada,

More information

The Application and Benefits of Multi-phase Auto-reclosing

The Application and Benefits of Multi-phase Auto-reclosing he Application and Benefits of Multi-phase Auto-reclosing etsuya Miyoshi*, Atsushi Kasai* Abstract - In this paper we explain the disadvantages in using single- and three-phase auto-reclosing on double

More information

Anti-blackout system for grid connected solar installations (Solsafe concept)

Anti-blackout system for grid connected solar installations (Solsafe concept) Anti-blackout system for grid connected solar installations (Solsafe concept) General description The Solsafe concept is a system which will automatically switch from a grid feeding inverter connected

More information

Overload Protection in a Dual-Corded Data Center Environment

Overload Protection in a Dual-Corded Data Center Environment Overload Protection in a Dual-Corded Data Center Environment White Paper 206 Revision 0 by Neil Rasmussen Executive summary In a dual-corded environment, the loss of power on one path will cause the load

More information

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Standards in Marine Power Systems APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Need is Driven by Electrification Oasis of the Seas DDG

More information

APPLICATION NOTE. Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution

APPLICATION NOTE. Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution APPLICATION NOTE Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution INCREASING PV HOSTING WITH EMPOWER TM SOLUTION Executive Summary Distributed solar photovoltaic

More information

Understanding Power Impedance Supply for Optimum Decoupling

Understanding Power Impedance Supply for Optimum Decoupling Introduction Noise in power supplies is not only caused by the power supply itself, but also the load s interaction with the power supply (i.e. dynamic loads, switching, etc.). To lower load induced noise,

More information

Qualitative Analysis of Power Distribution Configurations for Data Centers

Qualitative Analysis of Power Distribution Configurations for Data Centers Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,

More information

Inverter / Charger Installation General Operations and AC and DC Connections

Inverter / Charger Installation General Operations and AC and DC Connections Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better

More information

Rule 5.500 Fast Track Analysis for National Life Insurance Co.

Rule 5.500 Fast Track Analysis for National Life Insurance Co. Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers

CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers CEMEP UPS The high environmental performance solution for power supply to high-availability data centers Exchanges of information and communication needs are growing at an exponential rate. That growth

More information

INTEGRAL REMOTE MANAGEMENT SOLUTION cirwatt b series

INTEGRAL REMOTE MANAGEMENT SOLUTION cirwatt b series Communication system for the management of electrical installations INTEGRAL REMOTE MANAGEMENT SOLUTION cirwatt b series MID Approval Technology for energy efficiency PLC Communications (Power Line Communication)

More information

Critical-Power Automatic Transfer Systems Design and Application

Critical-Power Automatic Transfer Systems Design and Application Critical-Power Automatic Transfer Systems Design and Application Bill Brown, P.E., Jay Guditis, Square D Critical Power Competency Center 1. INTRODUCTION An important requirement of mission-critical electric

More information

30-120 3 Phase Modular Finally the benefits of Modular ups are for all

30-120 3 Phase Modular Finally the benefits of Modular ups are for all MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion

More information

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES UNINTERRUPTIBLE POWER SUPPLIES 9900A >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES 9900A The 9900A UPS system uses the most advanced IGBT in both the converter and inverter with Digital Signal Processor (DSP)

More information

4KVA/5KVA Parallel Installation Guide

4KVA/5KVA Parallel Installation Guide 4KVA/5KVA Parallel Installation Guide 1. Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to 4 units. The supported maximum

More information

Leaders in high-power LV Switchboard Design. 6300A 100kA LV Naturally Ventilated Switchboard. www.prismpower.co.uk

Leaders in high-power LV Switchboard Design. 6300A 100kA LV Naturally Ventilated Switchboard. www.prismpower.co.uk Leaders in high-power LV Switchboard Design 6300A 100kA LV Naturally Ventilated Switchboard www.prismpower.co.uk The UK leads Europe in high-power LV Switchboard Design 6300A 100kA LV Naturally Ventilated

More information

SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction

SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to

More information

Transfer Equipment Controls

Transfer Equipment Controls Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment

More information

Voltage Events. Smart Energy & Power Quality Solutions. Lahnau, April 2013. Voltage drops

Voltage Events. Smart Energy & Power Quality Solutions. Lahnau, April 2013. Voltage drops Lahnau, April 2013 Voltage Events Voltage drops Voltage drops can lead to huge problems for example, to the drop-out of production processes and to product or process quality problems. Such voltage drops

More information

Power Quality. Uninterruptible Power Supply

Power Quality. Uninterruptible Power Supply Quality Uninterruptible Supply In the electrical system environment, power disturbances will occur. These can be caused by faults on the distribution system, the operation of nearby equipment, lightning

More information

Bypass transfer switch mechanisms

Bypass transfer switch mechanisms Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration

More information

Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions

Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions Dr. Detlev Kirsten & Herbert Piereder Solid State SSFCL

More information

4.0 UPS dedicated to ICT for unmatched energy savings

4.0 UPS dedicated to ICT for unmatched energy savings 4.0 UPS dedicated to ICT for unmatched energy savings Introducing UPSaver by Borri, a new modular UPS series for the ICT industry, totally configurable, quickly scalable, with high efficiency and low TCO.

More information

Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous Inverter System

Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous Inverter System Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous Inverter Go Electric Inc. www.goelectricinc.com 1 Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous

More information

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

Power network telecommunication

Power network telecommunication www.siemens.com Power network telecommunication Teleprotection Answers for infrastructure and cities. Binary I/O The best protection against high-voltage grid failures When it comes to managing power networks,

More information

Technical Comparison of On-line vs. Line-interactive UPS designs

Technical Comparison of On-line vs. Line-interactive UPS designs Technical Comparison of On-line vs. Line-interactive UPS designs By Jeffrey Samstad Michael Hoff White Paper #79 Executive Summary UPS systems below 5000VA are available in two basic designs: line-interactive

More information

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

Chapter 9 Balanced Faults

Chapter 9 Balanced Faults Chapter 9 alanced Faults 9.1 Introduction The most common types of fault are (in order) single-line-to-ground fault, line-to-line fault, and double-line-to-ground fault. All of these are unbalanced faults.

More information

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION REPORT ON NETWORK RELIABILITY ASPECTS OF THE CHOICE LINE VERSUS CABLE FOR

More information

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University PURPOSE: The purpose of this lab is to introduce PSS/E. This lab will introduce the following aspects of PSS/E: Introduction to

More information

Paralleling Switchgear

Paralleling Switchgear Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information