DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE
|
|
|
- Philomena Cobb
- 10 years ago
- Views:
Transcription
1 DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE Molex Premise Networks
2 EXECUTIVE SUMMARY The term data centre usually conjures up an image of a high-tech IT environment, about the size of a football pitch, full of equipment from a vast array of vendors with enough air conditioning to keep the occupants of the penguin enclosure in a zoo happy. This technical article discusses issues around data centre technologies and concepts.
3 Definition of a Data Centre The term data centre usually conjures up an image of a high-tech IT environment, about the size of a football pitch, full of equipment from a vast array of vendors with enough air conditioning to keep the occupants of the penguin enclosure in a zoo happy. Modern businesses are highly dependant on these IT facilities.. In fact, the term data centre applies to any space specifically allocated for cabinets or frames, housing network equipment that is either a source of services to other network devices (typically distributed over generic cabling) the receivers of services from an external telecommunications network (such as a PABX or ADSL connection) or a source of services to an external network (typified by data hosting facilities). We also generally assume a data centre to be a multi-client environment, with services to maintain that environment provided by a third party. The term is however equally applicable to the main communications room within an end-users internal network. In other words, a data centre may be a server room, an equipment room or a co-location facility. The Rise of the Data Centre Modern businesses are highly dependant on these IT facilities and care needs to be taken to ensure the environment created to house them supports their continued trouble free operation. In recent years there has been a growth of managed data centres. Whilst this may be an outsourcing move to save money, I believe it is more likely that network owner are increasing aware of their businesses IT dependency, but lack the budget or the cross-discipline expertise to cater for it in-house. This requires co-ordination between a number of technical services including electrical, HVAC, networking, fire detection and suppression and the wide area telecommunications service provider. The technologies and concepts examined in this article are equally applicable to both single client and multi-client environments, making it easy to see why the later is an attractive option to a busy network manager with limited resources. Applicable standards Currently there are no standards specifically written to govern cabling implementation in these spaces, although EN Part 5 is on its way to fill this void. Using the familiar media of optical fibre and balanced copper cabling, a hierarchical approach is employed, similar to BS(EN)50173 Part 2, Generic cabling for office premises. Within the data centre we will see Main Distributors (perhaps accommodating a core switch), supporting Zone Distributors (possibly a workgroup switch or cross connect supporting an aisle of racks), connecting to Equipment Outlets (expected to be located within the equipment racks). The will also be the addition of an External Network 3
4 Interface and its associated cabling, for connection to the outside world and the service providers network. None of this should prove problematic to a competent installation organisation, and is bound to be the subject of further articles after the document is published. Key Issues for the Network Operator Regardless of the size of the data centre there are three common priorities shared by their owner, operators and occupiers; Flexibility, Accessibility and Reliability...there are three common priorities... Flexibility, Accessibility and Reliability Flexibility A flexible infrastructure enables a wide range of types of equipment to be accommodated, and the hierarchical approach to data centre cabling that EN50173 Part 5 is proposing looks set to deliver that. In a client owned and operated data centre there is often more control over the equipment deployed, the inherent flexibility being used as a safeguard against future developments in technology, or change of IT strategy. Within a co-location or hosting facility however, flexibility is a pre-requisite for day-to-day operation. Client equipment can arrive at short notice, and require immediate connection and commissioning to keep any down time to minimum, and to ensure that service level agreements are met. The requirement to deploy a wide variety of equipment within the data centre can have an effect on the physical elements of the building. The load limit of the floor may need to be considered, whether that is the structural floor or any access floor system attached to it. The average server rack is unlikely to present any problems, but large un-interruptible power supplies and storage area network silos may need special consideration. This is clearly best achieved during the design stages of the building, not the fit-out. Accessibility Access is clearly important. The equipment will not install and configure itself, so personnel access will be needed for this scheduled event. This has a knock on effect on the sizing of the data centre, as space will be needed for the technicians to work and to manoeuvre equipment. BS(EN) is some help here, advising that a 1.2-meter clearance around cabinets is required. Ideally data centre sizing should then simply be a case of working of how many racks you have, then adding the required clearance to their overall dimension. Access for equipment is also an issue with the size of doors, proximity to lifts and access to loading bays all needing consideration. Many installers will have encountered this problem, with a 800mm cabinet not fitting through a 2 6 door. Simply specifying double doors goes a long was to solving this sort of issue, and again this is much easier and 4
5 cheaper at the data centre design stage, rather than when equipment is being installed! Network availability is of crucial importance to the operation of the data centre. Having decided that the equipment within the data centre is mission critical to the business, the case of unscheduled downtime from equipment failure also needs consideration here. It is clear that in the event of a failure, the deployment of technicians will be required, so access to the site must be arranged often in compliance with strict security policies. Obviously access to the equipment and its associated cabling will also be required, which is likely to involve opening cabinets and raising floor tiles. It is important to understand that whilst this enables repair work to be undertaken, it also exposes other equipment (either directly or via a shared cabling infrastructure) to the technician, and the threat of human error cannot be ignored. Procedures need to be in place to minimise this risk. Reliability Network availability is of crucial importance to the operation of the data centre. It underpins its very existence. It is important to realise however that the need for accessibility and flexibility can have a negative effect on Reliability. Ultimate accessibility can lead to a lack of control of personnel on site, making the data centre prone to human error. Ultimate flexibility can require multiple connections in a circuit to allow for reconfiguration. Having more connections builds in more points of failure. It would seem a balance needs to be struck, and a method needs to be found to quantifying the likely reliability of data centre based upon its constituent parts. The four tiers described by the Uptime Institute in the USA is such a system, which is worth investigating further. Recognising both the impracticality and the extremely high cost required to achieve the holy grail of % (five-nines) availability, they instead propose four more attainable levels, as follows. nn nn nn nn Tier I - Single path for power and cooling distribution, no redundant components, % availability. Tier II - Single path for power and cooling distribution, redundant components, % availability. Tier III - Multiple power and cooling distribution paths, but only one path active, redundant components, concurrently maintainable, % availability. Tier IV - Multiple active power and cooling distribution paths, redundant components, fault tolerant, % availability. It is easy to see how the Tier IV approach can deliver more resilience that a Tier I installation, demonstrated by its anticipated unscheduled downtime of under 27 minutes per annum, compared to Tier I at nearly 29 hours, but this is at significant cost. In its N+1 configuration, it is also 5
6 worth noting that during a failure in a Tier IV data centre, Tier II reliability is available. Designing to N+2 or N+N fixed this, but is generally cost prohibitive. An expedited repair would be in order, and this is where Intelligent Infrastructure Management (IIM) systems become invaluable. Network management tools have been available for many years to monitor data traffic, but the cabling has always been a blind spot. Now we are not only able to detect an unauthorised disconnection, but relate it to its physical location within the data centre and also inform the appropriate helpdesk services of the failure so that remedial action can be scheduled. No services, other than those used in the data centre, should pass through it... Associated Building Services Before looking at the other services required within the data centre, it is worth pointing out what should not be there. No services, other than those used in the data centre, should pass through it, reducing the risk of flooding or contamination of the equipment environment. Whilst services such as access control, CCTV and lighting are required, the key services are seen as air conditioning, power and fire detection and suppression. Air Conditioning The aim of temperature control within a data centre is to cool the cabinet mounted equipment, keeping it within its operation temperature range, not to cool the air outside it. Enclosed cabinets can inhibit the free flow of chilled air enabling hot-spots to develop so some clever design is required to overcome this. The concept of hot and cold aisles is often adopted. Adjacent bays of cabinets are configured with their equipment facing forward towards a chilled air outlet in the aisle between them. The cold air is then drawn by the equipment fans through the rack. This exits as warm air to the rear with the resulting convection currents acceleration the whole process, thus creating alternating hot and cold aisles. How effective this is can depend upon the specific equipment which will effect air flow. Open frames can help here, as can forced ventilation with fan trays. Ideally any HVAC system should also create a slight positive pressure, to help reduce the ingress of dust and other contaminants into the room. Power A generous allocation of mains power will be required for any data centre. The exact power requirement will depend upon a number of factors, not just the consumption of the network equipment installed. Lighting will need to be factored in. A significant load is likely to be draw by the HVAC plant. Even on stand-by, UPS will draw a load. The level of resilience within the data centre will also have an impact. Quite simply the more equipment that has been provided as a back up (be that network equipment or back up HVAC and lighting), the more power will be required to cater for it, and in turn the higher the running costs. 6
7 In the design of the power distribution system, it is not uncommon to have two feeds to each cabinet. In turn these may be fed from different distribution boards, even from different feeds from the energy company. Several general-purpose power outlets to cater for the occasional power tool or vacuum cleaner should also be provided. These should be clearly labelled, and never used to power rack mounted equipment. The risk of inadvertent disconnection is unacceptably high. In the design of the power distribution system, it is not uncommon to have two feeds to each cabinet. Fire detection and Suppression Although seldom mandated by fire regulations non-corrosive gas suppression systems are often desirable where high value equipment is located. Where a more conventional sprinkler system is used, a dry-pipe system is desirable, where by a POC (product of combustion) detector needs to be tripped to prime the pipes, in addition to an individual sprinkler head bursting due to heat build-up. This goes a long way to prevent the accidental discharge of the system, and the flooding that goes with it. The very minimum that should be considered are wire cages around the sprinkler heads if a wet pipe system is installed. 7
8 Clearly careful design is required in the planning of a data centre. Whilst it is possible to achieve almost total network availability, this comes at a price to high for most to pay. Managing the clients expectations from the outset is crucial if an acceptable compromise is to be reached. Ultimately the question to ask is How valuable is your data?. CONCLUSION 2013 Molex 8
TIA-942 Data Centre Standards Overview WHITE PAPER
TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and
About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services
About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier
Colocation Selection Guide. Workspace Technology Ltd
Colocation Selection Guide Workspace Technology Ltd Technology House 5 Emmanuel Court Reddicroft Sutton Coldfield West Midlands B72 1TJ Tel 0121 354 4894 Fax 0121 354 6447 www.workspace-technology.com
in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.
DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure
Sovereign. The made to measure data centre
Sovereign D ATA C O N N E C T The made to measure data centre Prime Location Within touching distance of everything that s important. 2 Your Customer-Centric Data Centre For the vast majority of organisations
MARULENG LOCAL MUNICIPALITY
MARULENG LOCAL MUNICIPALITY Data Centre Physical Access and Environmental Control Policy Draft: Data Centre Access Control and Environmental Policy Page 1 Version Control Version Date Author(s) Details
Rules of Conduct and Safety
Rules of Conduct and Safety ETISALAT DATA CENTER RULES - V2.4 Contents Definitions... 2 Introduction... 3 Safety Instructions... 3 Upon entering the Data Center... 3 Privacy Notice / Camera Surveillance...
hong kong//china data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Hong Kong, China. We can colocate standard rack-mountable servers or
Data Center Infrastructure & Managed Services Outline
Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists
Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport
Welcome Zenium Istanbul One provides 12,000 square metres of high specification technical space across three purpose-built data centers. It is Turkey s first wholesale data center offering; the data halls
singapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Singapore. We can colocate standard rack-mountable servers or other
Onsite Support: 24/7/365 onsite team. Security: 24/7/365 onsite manned security and CCTV. Monitoring: 24/7/365 Environmental monitoring and management
Zen DC1 Our Services: Colocation Cloud Solutions Managed Hosting Dedicated Servers Zen DC1 - Key Facts Size: 10,000 sq ft Capacity: 150 rack capacity Ownership: 100% independently owned, operated and managed
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
Colocation Service Definition. SD008 v1.3 Issue Date 19 Feb 09
Colocation Service Definition SD008 v1.3 Issue Date 19 Feb 09 Colocation Service Definition Service Overview InTechnology offers secure data centre environments for your business critical systems, applications
REVIEWED ICT DATA CENTRE PHYSICAL ACCESS AND ENVIROMENTAL CONTROL POLICY
LI_M_POPO PROVINCIAL GOVERNMENT :;:ED.JBl-C ()F SO"';-H AFR;IC. ':.,. DEPARTMENT OF CO-OPERATIVE GOVERNANCE, HUMAN SETTLEMENTS & TRADITIONAL AFFAIRS REVIEWED ICT DATA CENTRE PHYSICAL ACCESS AND ENVIROMENTAL
Georgia Tech Aerospace Server French building Server Room. Server Room Policy Handbook: Scope, Processes and Procedure
Georgia Tech Aerospace Server French building Server Room Server Room Policy Handbook: Scope, Processes and Procedure Version History Version/Status Release Date Comments 1.1/Draft 1.2 1.3 1.4 1.5 1.6
Capgemini UK Infrastructure Outsourcing
Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
OPERATOR - FACILITY ADDRESS - DATE
. Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.
HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE
HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation AIRFLOW MANAGEMENT COLD AND HOT AISLE CONTAINMENT DC ASSESSMENT SERVICES Achieving true 24/7/365
ASX Australian Liquidity Centre. ASXCoLo
ASX Australian Liquidity Centre ASXCoLo Australian Liquidity Centre Location The ASX Australian Liquidity Centre is located at: Gore Hill Business Park 219-247 Pacific Highway Artarmon. NSW, 2064 The location
Datacentre Studley. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk
Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. At we own and manage 30,000 square feet of highly available, geographically diverse
Safeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive
Co-Location Services Safeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive optimum performance 24x7. SERVICE
Pacnet Hong Kong CloudSpace2 Technical Specifications. Upholding the Principles of Efficiency and Sustainability in Data Center Design
POWERING A CONNECTED ASIA Pacnet Hong Kong CloudSpace2 Technical Specifications Upholding the Principles of Efficiency and Sustainability in Data Center Design Our purpose-built, 5,000 m 2 Pacnet Hong
Data Centre Services. JT Rue Des Pres Data Centre Facility Product Description
JT Rue Des Pres Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room environment with protected and backup power, security and bandwidth. Data Centre
Data Centers, Information Technology and Low Current Services
Data Centers, Information Technology and Low Current Services 1 Data Centers and Low Current Services SDT offers a wide-ranging variety of professional services to Data Centres and Low Current operators.
Infrastructure & Software
Managed Services We can provide you with a fully managed service more than simply hosting or co-location but a full end-to-end and single point of contact service. Infrastructure & Software Datacentres
7QUESTIONSYOUNEEDTOASKBEFORE CHOOSINGACOLOCATIONFACILITY FORYOURBUSINESS
7QUESTIONSYOUNEEDTOASKBEFORE CHOOSINGACOLOCATIONFACILITY FORYOURBUSINESS ExecutiveBrief P a g e 1 Executive Brief 7 Questions You Need to Ask Before Choosing a Colocation Facility for Your Business Choosing
NIGERIA S PREMIUM DATA CENTRE
NIGERIA S PREMIUM DATA CENTRE TIER III DESIGN CERTIFIED SECURE RELIABLE SCALABLE 1 WHY WOULD YOU WANT TO BUILD A DATA CENTRE? IT TAKES MILLIONS OF US DOLLARS TO BUILD AN EFFICIENT DATA CENTRE. A KEY ASSET,
Frankfurt Data Centre Overview
Technical Services Briefing Document Frankfurt Data Centre Overview Version 2.1 Contents Introduction... 3 TelecityGroup Data Centre in Frankfurt... 4 Data Centre Characteristics... 4 Technologies in Use
Security+ Guide to Network Security Fundamentals, Fourth Edition. Chapter 13 Business Continuity
Security+ Guide to Network Security Fundamentals, Fourth Edition Chapter 13 Business Continuity Objectives Define environmental controls Describe the components of redundancy planning List disaster recovery
Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s"
Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s" Data centre Standard EN50173-5 : "Telecommunications Infrastructure for Data Centre s Due, 2006 Gary Highton,
Data Centre Basiglio, Milan Flexible, advanced and efficient by design.
Data Centre Basiglio, Milan Flexible, advanced and efficient by design. TelecityGroup Via Francesco Sforza 13 Milano 3 City 20080 Basiglio MI Italy Tel: +39 02 36679500 [email protected] www.telecitygroup.it
This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits.
This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. DCD, DCOM, DCE DESIGN IMPLEMENTATION BEST PRACTICE OPERATION & MANAGEMENT DATA
POWERING A CONNECTED ASIA. Pacnet Hong Kong CloudSpace1 Technical Specifications. Asia s Pioneering Facility with Direct Subsea Cable Access
POWERING A CONNECTED ASIA Pacnet Hong Kong CloudSpace1 Technical Specifications Asia s Pioneering Facility with Direct Subsea Cable Access Our purpose-built, 300 m 2 Pacnet Hong Kong CloudSpace1 (HKCS1)
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
19 Site Location, Design and Attributes. Site Location, Design and Attributes
1 Site Location, Design and Attributes The Primary Data Center shall be physically located on Oahu, Hawaii. 2 Site Location, Design and Attributes The Primary Data Center shall be located at least 1 mile
Best Practices for Wire-free Environmental Monitoring in the Data Center
White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com [email protected] Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for
Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment
How to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
Virtual Data Centre Design A blueprint for success
Virtual Data Centre Design A blueprint for success IT has become the back bone of every business. Advances in computing have resulted in economies of scale, allowing large companies to integrate business
(Examples of various colocation sites)
Overview The largest factor involved in maintaining business servers today are the fixed costs associated with data centers. The Colocation Environment is an outsourcing model whereby a colocation company
A LOOK AT INTELLIGENT INFRASTRUCTURE MANAGEMENT. Krzysztof Ojdana, Product Manager TECHNICAL ARTICLE. Molex Premise Networks
A LOOK AT INTELLIGENT INFRASTRUCTURE MANAGEMENT Krzysztof Ojdana, Product Manager TECHNICAL ARTICLE Molex Premise Networks The inherent flexibility of structured cabling - the ability to move users within
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
Intelligent. Buildings: Understanding and managing the security risks
Version 2 IET Sector Insights Intelligent Buildings: Understanding and managing the security risks More efficient and cost-effective use of the built environment is increasingly being driven by economic
Data Centre. Design and Project Management. from concept to completion
C O N S U L T I N G Data Centre Design and Project Management from concept to completion Computer rooms are the heart of most businesses today. Yet I see so many that have been patched together, are in
Rittal Liquid Cooling Series
Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
How To Write An Infrastructural Standard For Data Center Infrastructure
Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers
Co-location service from Bell. Version 1.0 April 10, 2007. Updated as of 4/10/2007 1
Co-location service from Bell Version 1.0 April 10, 2007 Updated as of 4/10/2007 1 Contents 1. Introduction... 3 2. Service features... 3 3. Installation guidelines... 4 3a. Equipment installation in racks...
Upgrading the PRS datacentres: space requirement. S. S. Mathur, GM-IT, CRIS
Upgrading the PRS datacentres: space requirement S. S. Mathur, GM-IT, CRIS PRS / UTS scenario: then and now Year 2000 PRS: 600 locations UTS: 0 locations Year 2008 PRS 1600 locations E-ticketing Passengers
Standard Comms Rooms Specification
Standard Comms Rooms Specification Room Configuration Electrical General Distribution Boards Small Power Lighting Containment Fire Detection General To be defined in the project brief but should meet requirements
melbourne//australia data center specifications internet + intellectual property + intelligence tel: +61 2 9948 8888 fax: +61 2 9948 1111
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Melbourne,. We can colocate standard rack-mountable servers or other
2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms
Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Equinix Telecity Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 [email protected] www.telecitygroup.se
NeuStar Ultra Services Physical Security Overview
NeuStar Ultra Services Physical Security Overview Mission-critical network operations must have the highest standards of quality, security and reliability. NeuStar Ultra Services currently locates its
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Greening Commercial Data Centres
Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively
Portable Energy Efficient Data Centre Solution
Portable Energy Efficient Data Centre Solution Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354 6447 www.workspace-technology.com
Server Monitoring & Management Services
Server Monitoring & Management Services Monitor and manage your applications and servers under enterprise-class monitoring solutions, and protect your business from planned and unplanned downtime. ITI
Case Study Nottingham Trent University
Data Centre Solutions...energy efficient by design Case Study Nottingham Trent University Nottingham Trent University deploys Modular Data Centre Technology (MDC) Designed & Manufactured by Workspace Technology
Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD
Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,
Data Centre Services. JT First Tower Lane Data Centre Facility Product Description
JT First Tower Lane Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room enviroment with protected incoming power supplies, state-of-the-art security
Data Centre Infrastructure Assessment
Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.
Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary
Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
Data Centre Outsourcing a Buyer s Guide
Data Centre Outsourcing a Buyer s Guide The inside guide to deciding whether to outsource your data centre facility and operations and how to select an appropriate partner. This Guide will help you Determine
South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime
South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in
vcloud SERVICE Virtual Tech in partnership with Equinix - vcloud Service
vcloud SERVICES vcloud SERVICE Virtual Tech offers competitive pricing on vcloud hosted services at our world class Tier 4 data centre facility fully equipped with redundant power, cooling, internet connectivity
Data Centers and Mission Critical Facilities Operations Procedures
Planning & Facilities Data Centers and Mission Critical Facilities Operations Procedures Attachment A (Referenced in UW Information Technology Data Centers and Mission Critical Facilities Operations Policy)
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Document Details. 247Time Backup & Disaster Recovery Plan. Author: Document Tracking. Page 1 of 12
Document Details Title: Author: 247Time Backup & Disaster Recovery Plan Document Tracking Page 1 of 12 TABLE OF CONTENTS 1 INTRODUCTION... 3 1.1 OVERVIEW... 3 1.2 DEFINED REQUIREMENT... 3 2 DISASTER OVERVIEW...
GAS HEATING IN COMMERCIAL PREMISES
ENERGY EFFICIENCY OFFICES GAS HEATING IN COMMERCIAL PREMISES www.energia.ie www.energia.ie Typically, energy reductions of 10% or more can be made easily through maintenance and low cost improvements.
Your responsibilities if you have an automatic fire alarm. A handy guide for owners and responsible persons
Your responsibilities if you have an automatic fire alarm A handy guide for owners and responsible persons Kent Fire and Rescue Service Contents Your responsibilities if you have an automatic fire alarm
Data Center Checklist
Data Center Checklist The use of colocation and services has continued to increase, rapidly becoming the solution of choice for organizations requiring an efficient, secure, cost-effective way to manage
DATA CENTRE DATA CENTRE MAY 2015
DATA CENTRE DATA CENTRE MAY 2015 CONCERTHOUSE MUSIC Concerthouse Music Data Centre services are located in the Equinix Internet Business Exchange (IBX ) Centre at Mascot. This IBX offers the highest level
san francisco//usa data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in San Francisco, USA. We can colocate standard rack-mountable servers
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Knürr CoolAdd The universal retrofit solution against overheating in server racks. Rack & Enclosure Systems
Knürr CoolAdd The universal retrofit solution against overheating in server racks Rack & Enclosure Systems Knürr CoolAdd When cold air is no longer enough! Data centers are subject to constant changes:
Containment Solutions
Containment Solutions Improve cooling efficiency Separate hot and cold air streams Configured to meet density requirements Suitable for commercial and SCEC endorsed cabinets Available for retrofit to SRA
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
Datacentre London 1. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk
Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. At we own and manage 30,000 square feet of highly available, geographically diverse
Energy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
How To Co-Location On Nextgen (Networking)
Category Terms Part 2A: Co-location Services 1. Application These terms apply to all Co-location services we provide and form part of our customer contract with you. They must be read in conjunction with
Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
Power to the adaptable data center
Business Unit Manager, Data Center Solutions, Eaton s electrical group IT managers have more options than ever to tailor the power infrastructure to their unique data center and business requirements.
Data Centre Best Practices Summary
Data Centre Best Practices Summary Delivering Successful Technology Rooms 1 END2END s Data Centre Best Practices END2END design Data Centres/Computer Rooms based on 7 major principles: Understanding the
Eni Green Data Center - Specification
Eni Green Data Center - Specification Green IT Adopting the principles of sustainable development is one of the key missions in the field of information technology today. 2% of the world s CO2 emissions