Green Computing: Datacentres
|
|
|
- Cathleen Ryan
- 9 years ago
- Views:
Transcription
1 Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material January 25,
2 This lecture Datacentre design Efficiency metrics Energy-proportional computing Initiatives Seminar groups Datacentre visit 2
3 This lecture Datacentre design Efficiency metrics Energy-proportional computing Initiatives Chapter 4 and 5 of the 1 st Edition of the e-book on the course web (2009) 3
4 Datacentres Datacenters are buildings where multiple servers and communication gear are co-located because of their common environmental requirements and for physical security needs, and ease of maintenance. Barroso and Hölzle Luiz André Barroso and Urs Hölzle. The Datacenter as a Computer - An Introduction to the Design of Warehouse-Scale Machines. Morgan & Claypool Publishers, 2009 (120 pages). Note: a nd Edition of this book (156 pages) is also available with more Google-oriented updates. Most of the basic material in the 2009 is still worthwhile to study. 4
5 Datacentre energy consideration Data centres total energy consumption in 2012 was about 270 TWh, which was about 2% of the global electricity consumption, and they had a growth rate of over 4% per year during W. Van Heddeghem, et al. Trends in worldwide ICT electricity consumption from 2007 to 2012, Computer Communications, Volume 50, Elsevier, 2014.
6 IT Architectural overview Server 6 Image (left) under CC license by MrLinsky on Wikimedia
7 Energy use at a datacentre Datacentre overhead Server consumption From Luiz André Barroso and Urs Hölzle, 2009, Data (Right chart) from one Google facility 2007.
8 Power and cooling systems 8 Graphic provided courtesy of DLB Associates
9 Power system components Primary switchgear Breakers for protection Transformers (10-20kV to V) Diesel generators Switched on in case of utility power failure Uninterruptible Power Supply (UPS) Batteries for short term energy provision Functionality Switch energy source between mains power (from utility) and power from Diesel generators Sustain system power with batteries during mains power failure Power feed conditioning 9
10 Power system components Power Distribution Units (PDUs) Break a higher voltage line into several circuits V line to many V circuits that feed the servers A ground short (in server or power supply) will only break one circuit Distribute energy to each rack Provide redundancy (A-side, B-side) so that with a power supply failure fast switching can take place 10
11 Cooling system Computer Room Air Conditioning (CRAC) Blows cold air under the floor plenum Cold air moves to front of server racks (cold aisle) Cold air flows through server racks Warm air is expelled in the back (warm aisle) 11
12 Cooling: operational range Datacentre cannot operate without cooling CRAC units cool the room's air Liquid coolant is pumped from chillers or cooling towers Coils are kept cool (12-14 ºC) with liquid coolant Warm air is pushed through the coils by fans Cold air (16-20 ºC) is moved to the floor plenum Air reaches the servers at ºC 12
13 Free cooling Much more efficient than chillers Cool the coolant to much lower temperatures before reaching the chiller Cooling tower Glycolbased radiator Fans to push air from outside 13 Image (left) under CC license by Frobles on Wikimedia Image (right) under CC license by cbpowerindustrial on Flickr
14 Redundancy and reliability Redundancy for fault tolerance and during maintenance Applied to both power and cooling systems Configurations: N+1, N+2, 2N Type Availability Description Tier I 99.67% Single path for power & cooling. No redundancy (N) Tier II 99.74% Single path for power & cooling. Redundancy (N+1) Tier III 99.98% Tier IV % Tier Classification (ANSI/TIA 942) Multiple paths for power & cooling (only one active). Concurrently maintainable. Redundancy (N+1) Multiple active paths for power & cooling. Redundancy in both paths (min (N+1)) W.Pitt Turner IV, J.H.Seader, K.G.Brill. Tier classifications define site infrastructure performance, Uptime Institute, White Paper 14
15 Container-based datacentres Server racks, power distribution and heat exchange inside a container!! Highly efficient cooling High server density 15 Image from Wikimedia by user Sun Microsystem
16 This lecture Datacentre design Efficiency metrics Energy-proportional computing Initiatives 16
17 Sources of efficiency losses Power systems Element Losses Transformers 0.50% UPSs 7-12% Highly efficient UPSs 3% Low-voltage power ( V) cables 1-3% Cooling Fans that move cool and warm air Mix of cool and warm air during long paths Too low temperature selection ºC better than targetted 20 ºC 17
18 Energy efficiency metrics Power Usage Effectiveness (PUE) Proposed by The Green Grid association Efficiency of the IT support infrastructure PUE= Total facility power Total IT equipment power Historic data: PUEs between 1.5 and 2.0 Google, Microsoft, Apple have reported PUEs around 1.1X C. Beladi. Green Grid datacenter power efficiency metrics: PUE and DCiE. White paper Recent data: 18
19 Location matters One quarter of Singapore data centers have PUE higher than 3, Japan and Australia claim average PUE of 2.2 and 2.25 respectively (APAC datacenter survey, April 2013) Facebook Luleå: 1.08 (Computer Sweden, 7 Feb 2013) Image:
20 Facebook live dashboard
21 Energy efficiency metrics PUE has to be used carefully Example: Server fans in IT-PAC Microsoft datacentre container module Facility power IT equipment power IT-PAC airflow management is improved Server fans are no longer required PUE increases Overall energy consumption reduced despite PUE increase Other aspects must be taken into account 21
22 Energy efficiency metrics Green Grid's Datacentre Performance Efficiency (DCPE) DCPE= Amount of computational work Total energy used Barroso and Hölzle propose: DCPE = 1/PUE. 1/SPUE. Computation/Total energy to electronics Computing efficiency IT equipment efficiency Building facilities efficiency 22
23 Energy efficiency metrics Server Power Usage Effectiveness (SPUE) Efficiency of the IT infrastructure Losses in power supply, voltage regulator modules, server fans SPUE= Total server input power Total useful power Useful power Consumption of electronics directly involved in computation E.g. motherboard, disks, CPU, DRAM... Servers have SPUEs between 1.6 and 1.8 (Barroso &Hölzle 2009) State of the art servers should be less than 1.2!!! 23
24 Energy efficiency metrics Total Power Usage Effectiveness (TPUE) Show efficiency of electromechanical overheads. TPUE= PUE SPUE Example: 2.0 PUE 1.6 SPUE TPUE= = 3.2 For each productive Watt another 2.2 W consumed!!! 24
25 This lecture Datacentre design Efficiency metrics Energy-proportional computing Initiatives 25
26 Load and energy efficiency Most of the time spent in no energy-efficient load regions Activity profile of 5000 Google servers in 6 months Image from Luiz André Barroso and Urs Hölzle. The Datacenter as a Computer
27 Load and energy efficiency Almost no time in idle state In low load there are several hundreds of queries Load spread out over all available servers Optimised for performance and/or availability Sustainable approach Concentrate load in a few servers Switch off unused servers But!!! More software complexity Energy for data distribution 27
28 Recall from lecture 2 Consumption proportional to the load Ideal linear function without constants Energy (%) Load (%) Ideal energy proportional server Traditional server Traditional server data based on data from Barroso and Hölzle
29 Energy proportional computing Capacity to adapt consumption to load Device Dynamic power CPU 3.0x Memory 2.0x Disks 1.3x Network switches 1.2x More hardware improvements are required!!! Meanwhile only option is to switch off hardware!!! 29
30 Energy spent: revisited CPU a larger proportion of energy costs than that reported in 2009! Luiz André Barroso and Urs Hölzle. The Datacenter as a Computer, 2 nd Edition 2013
31 This lecture Datacentre design Efficiency metrics Energy-proportional computing Initiatives 31
32 Current specifications ENERGY STAR Program Requirements for Computer Servers 2.0 (Dec 2013) Includes active consumption as opposed to just idle consumption Requirements for Datacenter Storage 1.0 establishes maximum consumption of storage products 2014: Microsoft joined Facebook to lead the Open Compute Project on servers microsoft-contributes-cloud-server-designs-to-the-open-computeproject.aspx 32
33 EU Code of Conduct for Datacentres European action to reduce consumption of datacentres Best practices for datacentres operators V3.0 Guide (Feb 2011) Operators register and commit to their application Roles of applicant Participant Operator of datacentre or equipment in it Commitments Annual reporting of energy consumption Implementation of some of the best practices Endorser Supports the initiative and participants 33
34 EU Code of Conduct for Data Centres Scope of the best practices Datacentre utilisation, management and planning IT equipment and services Cooling Datacentre power equipment Other equipment Building Monitoring Best practice expected implementation Immediate During software install or update During new IT introduction or replacement During building of datacenter or retrofit Optional 34
35 This lecture Datacentre design Efficiency metrics Energy-proportional computing Initiatives Seminar groups Datacentre visit 35
36 Seminar groups We had 65 students confirming interest of which 61 are registered in webreg 2 students had to be turned down, so make the best of the opportunity to attend the course! 36
37 Datacentre visit Visit at Ericsson planned for Wed 2/3 Prompt gathering at to start the visit 37
38 Questions?
Green Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
Cloud Computing Data Centers
Cloud Computing Data Centers Dr. Sanjay P. Ahuja, Ph.D. 2010-14 FIS Distinguished Professor of Computer Science School of Computing, UNF Warehouse-Scale Data Center (WSC) Design. Example: a data center
CarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense
CarbonDecisions The green data centre Why becoming a green data centre makes good business sense Contents What is a green data centre? Why being a green data centre makes good business sense 5 steps to
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs Topics The Why? The How? Conclusion The Why? Drivers for Green IT According to Forrester Research, IT accounts
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance. Chapter 8: 8 Guide for assessing GHG emissions of Data Centers
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance Chapter : Guide for assessing GHG emissions of Data Centers DRAFT March 0 Table of Contents GHG Protocol ICT Sector
AbSTRACT INTRODUCTION background
february 20, 2007 GREEN GRID METRICS: Describing Datacenter Power Efficiency Technical Committee White Paper white paper 1 Abstract The Green Grid is an association of IT professionals seeking to dramatically
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
Data Centers: Definitions, Concepts and Concerns
Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
Energy Efficiency Monitoring in Data Centers: Case Study at International Hellenic University. George Koutitas, Prof. L. Tassiulas, Prof. I.
UTH and IHU (CI)-WP4 Energy Efficiency Monitoring in Data Centers: Case Study at International Hellenic University Plenary Meeting Gent, February-2012 George Koutitas, Prof. L. Tassiulas, Prof. I. Vlahavas
How To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
DataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical
EU Code of Conduct for Data Centre Efficiency
EU Code of Conduct for Data Centre Efficiency A Green Practice Accredited by British Computer Society (BCS) EU Code of Conduct for Data Centre Efficiency Local Organizer Practices in Data Centre Industry
Data Center Energy Use, Metrics and Rating Systems
Data Center Energy Use, Metrics and Rating Systems Steve Greenberg Energy Management Engineer Environmental Energy Technologies Division Lawrence Berkeley National Laboratory October 31, 2007 Today s s
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
Last time. Data Center as a Computer. Today. Data Center Construction (and management)
Last time Data Center Construction (and management) Johan Tordsson Department of Computing Science 1. Common (Web) application architectures N-tier applications Load Balancers Application Servers Databases
Datacenter Efficiency
EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon
ICT and the Green Data Centre
ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by
Data Center Equipment Power Trends
Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
Energy Efficiency and Availability Management in Consolidated Data Centers
Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal
Enabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
Data Center Facility Basics
Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
Metering and Managing University of Sheffield Data Centres. Chris Cartledge Independent Consultant [email protected]
Metering and Managing University of Sheffield Data Centres Chris Cartledge Independent Consultant [email protected] Summary ICT Electricity Use Footprint Data Centre Electricity Use European
Energy Management Services
February, 2012 Energy Management Services Data centers & IT environments are often critical to today s businesses, directly affecting operations and profitability. General & Mechanical Services has the
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
Increasing Data Center Efficiency through Metering and Monitoring Power Usage
White Paper Intel Information Technology Computer Manufacturing Data Center Efficiency Increasing Data Center Efficiency through Metering and Monitoring Power Usage To increase data center energy efficiency
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE
THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
Australian Government Data Centre Strategy 2010-2025
Australian Government Data Centre Strategy 2010-2025 Better Practice Guide: Data Centre Power June 2013 17/06/2013 4:12 PM 17/06/2013 4:12 PM Contents Contents 2 1. Introduction 3 Scope 3 Policy Framework
SoSe 2014 Dozenten: Prof. Dr. Thomas Ludwig, Dr. Manuel Dolz Vorgetragen von Hakob Aridzanjan 03.06.2014
Total Cost of Ownership in High Performance Computing HPC datacenter energy efficient techniques: job scheduling, best programming practices, energy-saving hardware/software mechanisms SoSe 2014 Dozenten:
Best Practices. for the EU Code of Conduct on Data Centres. Version 1.0.0 First Release Release Public
Best Practices for the EU Code of Conduct on Data Centres Version 1.0.0 First Release Release Public 1 Introduction This document is a companion to the EU Code of Conduct on Data Centres v0.9. This document
Ch. 4 - Topics of Discussion
CPET 581 Cloud Computing: Technologies and Enterprise IT Strategies Lecture 6 Cloud Platform Architecture over Virtualized Data Centers Part -2: Data-Center Design and Interconnection Networks & Architecture
THE GREEN DATA CENTER
GREEN IT THE GREEN DATA CENTER WHERE ECOLOGY MEETS ECONOMY We truly live in an information age. Data Centers serve a very important purpose they provide the global community with nearly unlimited access
Data Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
Building a data center. C R Srinivasan Tata Communications
Building a data center C R Srinivasan Tata Communications Introduction Data Center as defined by TIA 942 A building or a portion of a building whose primary function is to house a computer room and its
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
European Code of Conduct for Data Centre. Presentation of the Awards 2014
European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
Server Technology, Inc.
Server Technology, Inc. Cabinet Power Monitoring, Management & Control Within the Data Center White Paper STI-100-011 2010-Sept-27 by Calvin Nicholson, Senior Director Software and Strategic Alliances,
Data centres that deliver [email protected]
Data centres that deliver [email protected] DATA CENTRE INFRASTRUCTURE MANAGEMENT (DCIM) DCIM solutions are designed to collect and manage information about a data centre s assets, resource use
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Data Center Energy Efficiency Looking Beyond PUE
Data Center Energy Efficiency Looking Beyond PUE No Limits Software White Paper #4 By David Cole 2011 No Limits Software. All rights reserved. No part of this publication may be used, reproduced, photocopied,
European Code of Conduct for Data Centre. Presentation of the Awards 2016
European Code of Conduct for Data Centre Presentation of the Awards 2016 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
Introduction to Datacenters & the Cloud
Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview
Case Study. Cool and green: Citigroup s Frankfurt Data Center
Zug, April 16, 2015 Cool and green: Citigroup s Frankfurt Data Center In Frankfurt, Siemens helps optimize Citigroup s data center. When it comes to building automation, security technology and power supply,
Electrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
How To Use Rittal'S Rizone
RiZone Data Centre Infrastructure Management Enclosures Power Distribution Climate Control IT INFRASTRUcTURe SOFTWARE & SERVICEs RiZone Data Centre Infrastructure Management What can the RiZone Data Centre
Optimization of energy consumption in HPC centers: Energy Efficiency Project of Castile and Leon Supercomputing Center - FCSCL
European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable Energies and Power Quality (ICREPQ 12) Santiago de Compostela
The Pros and Cons of Modular Systems
The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated
Greening Commercial Data Centres
Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
Office of the Government Chief Information Officer. Green Data Centre Practices
Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain
Data Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
Measuring Power in your Data Center
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There
Data centre energy efficiency metrics. Existing and proposed metrics to provide effective understanding and reporting of data centre energy
Existing and proposed metrics to provide effective understanding and reporting of data centre energy Liam Newcombe Data Centre Specialist Group 1 Introduction... 2 2 Summary... 6 3 Overview of metrics...
Reducing the Annual Cost of a Telecommunications Data Center
Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities
White Paper RiZone The Rittal Management Software for IT infrastructures
White Paper RiZone The Rittal Management Software for IT infrastructures Bernd Hanstein Klaus Hendlmeier Thorsten Weller Copyright 2009 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg 35745
Capacity Planning in the Modern Datacenter
in the Modern Datacenter SERVER TECHNOLOGY - INDUSTRY BRIEF -001 July 2015 Executive Overview Today s datacenter managers oversee more infrastructure than ever, with an exponential increase in complexity
Optimizing IT costs with Cloud. Tarmo Tikerpäe Datacenter SSP Microsoft Corporation
Optimizing IT costs with Cloud Tarmo Tikerpäe Datacenter SSP Microsoft Corporation BENEFITS Speed Scale Economics Cloud Trend: 70% 2 weeks to deliver new services vs. 6-12 months with traditional solution
Data Centre Energy Efficiency: A Call To Action
Data Centre Energy Efficiency: A Call To Action Vic Smith, The Green Grid, EMEA Technical Work Group Chair Dell, Senior Strategic Technologist Agenda Overview of The Green Grid Mission Community of Members
Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary
Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features
2014 Best Practices. for the EU Code of Conduct on Data Centres
EUROPEAN COMMISSION DIRECTORATE-GENERAL JRC JOINT RESEARCH CENTRE Institute for Energy and Transport Renewable Energies Unit 2014 Best Practices for the EU Code of Conduct on Data Centres 1 Document Information
2014 Best Practices. The EU Code of Conduct on Data Centres
2014 Best Practices The EU Code of Conduct on Data Centres 1 Document Information 1.1 Version History Version 1 Description Version Updates Date 5.0.1 2014 Review draft Comments from 2013 stakeholders
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
A Market Transformation Programme for Improving Energy Efficiency in Data Centres
A Market Transformation Programme for Improving Energy Efficiency in Data Centres Paolo Bertoldi, European Commission Joint Research Centre ABSTRACT The European Code of Conduct for Data Centres is a voluntary
Data Center Infrastructure Management: ERP for the Data Center Manager
Data Center Infrastructure Management: ERP for the Data Center Manager 1 2 Topics What s DCIM & the ERP Analogy Why DCIM How DCIM Works How DCIM Helps 3 DCIM by Definition DCIM is a system that collects
How To Benchmark Power Production
Energy Benchmarking Service for Data Centre Industry in Hong Kong and Initial Findings Simon Lam Acting Deputy Director, Business Marketing & Development Department, CLP Power Agenda 1. Introduction: Why
Smarter Data Centers. Integrated Data Center Service Management
Smarter Data Centers Integrated Data Center Service Management Approx. 3.500 ton CO² is generated by: Diesel Car-6l /100 km 20.000 km Airplane 5 * Brussels-Barcelona Server, 1.5 A, 24*7*365*3.000 Kwhr
Server Technology, Inc.
Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill
About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services
About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier
GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE
WHITE PAPER #6 GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE EDITORS: CHRISTIAN BELADY, MICROSOFT CONTRIBUTORS: ANDY RAWSON, AMD JOHN PFLEUGER, DELL TAHIR CADER, SPRAYCOOL PAGE 2 ABSTRACT
Measuring Energy Efficiency in a Data Center
The goals of the greening of the Data Center are to minimize energy consumption and reduce the emission of green house gases (carbon footprint) while maximizing IT performance. Energy efficiency metrics
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
