Electrical Shore Connections / Cold Ironing
|
|
|
- Susanna Underwood
- 10 years ago
- Views:
Transcription
1 STANDARD FOR CERTIFICATION No Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through is the officially binding version The content of this service document is the subject of intellectual property rights reserved by Det Norske Veritas AS (DNV). The user accepts that it is prohibited by anyone else but DNV and/or its licensees to offer and/or perform classification, certification and/or verification services, including the issuance of certificates and/or declarations of conformity, wholly or partly, on the basis of and/or pursuant to this document whether free of charge or chargeable, without DNV's prior written consent. DNV is not responsible for the consequences arising from any use of this document by others.
2 FOREWORD DNV is a global provider of knowledge for managing risk. Today, safe and responsible business conduct is both a license to operate and a competitive advantage. Our core competence is to identify, assess, and advise on risk management. From our leading position in certification, classification, verification, and training, we develop and apply standards and best practices. This helps our customers safely and responsibly improve their business performance. DNV is an independent organisation with dedicated risk professionals in more than 100 countries, with the purpose of safeguarding life, property and the environment. Standards for Certification Standards for Certification (previously Certification Notes) are publications that contain principles, acceptance criteria and practical information related to the Society's consideration of objects, personnel, organisations, services and operations. Standards for Certification also apply as the basis for the issue of certificates and/or declarations that may not necessarily be related to classification. Det Norske Veritas AS July 2014 Any comments may be sent by to [email protected] This service document has been prepared based on available knowledge, technology and/or information at the time of issuance of this document, and is believed to reflect the best of contemporary technology. The use of this document by others than DNV is at the user's sole risk. DNV does not accept any liability or responsibility for loss or damages resulting from any use of this document.
3 CHANGES CURRENT Page 3 CHANGES CURRENT General This document supersedes Standard for Certification No. 2.25, January Text affected by the main changes in this edition is highlighted in red colour. However, if the changes involve a whole chapter, section or sub-section, normally only the title will be in red colour. Det Norske Veritas AS, company registration number , has on 27 th November 2013 changed its name to DNV GL AS. For further information, see Any reference in this document to Det Norske Veritas AS or DNV shall therefore also be a reference to DNV GL AS. Main changes July 2014 General The standard has been aligned with industry practice. Sec.3 System design requirements [3.6]: Reference to IEC standard has been added. [3.6] and [3.7]: Requirement to monitoring of earthing connection has been deleted. [3.9.1], [3.9.2], [3.11] and [3.12]: Requirement to automatic closing of earth fault switch has been deleted. [3.13]: Requirement to tripping of CB in case of failure of protecting earthing connection and requirement to energy measurement (kwh counter) have been deleted. Editorial corrections In addition to the above stated main changes, editorial corrections may have been made.
4 Contents Page 4 CONTENTS CHANGES CURRENT General Introduction Availability Verification and certification Documentation Certification of components On-board survey System design requirements Stand by generator Transfer of power Shore connection box Voltage and frequency Selectivity / discriminative disconnection System earthing Protective earthing Galvanic isolation Switchgear Plugs and sockets Cable management system Interlocks Protection, monitoring and alarms Instrumentation Installation requirements General Marking Cables...9 CHANGES HISTORIC... 10
5 Sec.1 General Page 5 1 General 1.1 Introduction This standard for certification is related to design, installation, and verification of electrical shore connections intended for regular use in harbour for all types of vessels. Typical design intention is vessels following regular routes with frequent visits to the same ports, with port calls lasting more than 4 hours. An electrical shore connection system can be seen as comprising four aspects: system functionality in way of circuit breakers and earthing switches: - System functionality in way of circuit breakers and earthing switches are considered in this standard for certification, and functional requirements to the electrical shore connection as a total system are given. control system interface between the shore and the ship: - Control system interface between the shore and the ship is considered in this standard for certification, and requirements are given to necessary functionality. However, the physical installation on shore is not covered by the certification. ship side electrical equipment and installations: - Ship side electrical equipment and installations shall comply with relevant parts of the DNV Rules for Ships Pt.4 Ch.8, and the installation is part of the certification based on this standard. shore side electrical equipment and installation: - Shore side electrical equipment and installation is governed by national requirements to shore side electrical installations, and is not verified as part of a certification based on this standard. Each vessel shall be designed and verified for each port where it will use the electrical shore connection. Operational features with respect to power availability during loading and unloading are not considered as part of certification. This standard for certification shall apply as the basis for the issue of certificate for electric shore connection for the on-board installation when this has been verified in accordance with the process described, and compliance with the technical requirements ensured. While a type approval may be issued for a specific system design and component specification, a vessel specific certificate and/or declaration requires that the vessel have been verified together with the installation in the specified port. 1.2 Availability The availability of the shore power supply depends on the utility systems onshore. However, this standard requires that a stand-by generator on-board is automatically started and connected upon loss of power from shore. Additionally, this standard does not require that discriminative protection in the vessel s electric distribution system is functional while powered by a shore connection. A short circuit in the vessel s electric distribution system may therefore, in worst case, result in a black-out. Hence, use of shore power supply during loading and unloading operations in port must be evaluated with respect to criticality of electric power supply. This standard for certification does not consider any critical cargo operations, and assumes that the vessel will stay safe in case a power interruption occurs. 2 Verification and certification 2.1 Documentation When an electrical shore connection shall be certified in compliance with this standard for certification, it shall be constructed in accordance with plans approved by the Society. The following documentation shall be submitted for approval or for information: functional description including description of instrumentation, interlocks, monitoring and alarms overall single line diagram system earthing diagram and description load calculation for electrical shore connection supply electrical documentation of shore connection switchboard and the cubicle in the main switchboard associated with the electrical shore connection. (Including switchboard layout and arrangement drawings, and schematics with information on protection, synchronisation, breaker interlocks, undervoltage trips, remote control circuits as relevant.) data sheets for high voltage cables short circuit calculation and discrimination analysis
6 Sec.3 System design requirements Page 6 assembly schedules and technical data with internal power cable and busbar dimensions as well as tables with switchgear rating for power circuits (e.g. making and breaking capacity) internal arc withstanding report for high voltage switchgear harmonic distortion calculations for systems fed from frequency converters test procedure for quay and sea trial, including vessel - harbour control signal interface operational manual. For standard designs the case by case approval may be replaced by the type approval scheme. 2.2 Certification of components Product certification of electrical components necessary for the electric shore connection is generally not required by this standard for certification, but may be requested by the customer as a contractual item for purchase of equipment. An exception is the electric shore connection cable which shall be delivered with NV product certificate or be type approved if it belongs to the shipboard installation. Verification is performed by document review and site survey. 2.3 On-board survey On-board survey shall be performed as part of the certification process, and focuses on the installation on board as well as on the functionality of the electrical shore connection system. On-board inspections shall be performed in order to evaluate that: the electrical installation is in accordance with the accepted or approved information and in accordance with the requirements in this standard for certification the craftsmanship is acceptable. Function tests shall be performed in order to evaluate that the installation complies with the requirements in this standard for certification. The function testing shall verify that required interlocks is working properly. 3 System design requirements 3.1 Stand by generator While the electric shore connection is supplying power to the vessel, at least one of the vessel s generators shall be in standby. I.e. this generator shall be automatically started and connected to the main switchboards in case of blackout (loss of power supply from shore). 3.2 Transfer of power In order to transfer power between the vessel s supply and shore, means for synchronization shall be arranged in the vessel s main switchboard. 3.3 Shore connection box A separate shore connection box is not required if the main switchboards breaker has overcurrent protection. The short circuit protection of the cable between the shore supply circuit breaker and the main switchboard s shore power incoming feeder shall be performed by the short circuit protection on the shore side supply system. 3.4 Voltage and frequency When a vessel is powered by shore power supply, the system voltage and frequency of the shore utility supply must match the system voltage and frequency of the vessel. A system design where parts of the vessel s consumers are powered by a shore connection with a different frequency than the nominal frequency of the vessel is acceptable (e.g. reefer load powered by 50 HZ shore power on a 60 Hz vessel). Also a system design with two electrical shore power connections, one with 50 Hz, and one with 60 Hz, is acceptable. 3.5 Selectivity / discriminative disconnection This standard for certification does not require that the vessel s distribution system has full discrimination during electrical shore power supply. Limitations in the selectivity shall be described in the description of the system. Guidance note: A vessel s electrical distribution system is designed for a maximum short circuit current with respect to mechanical strength and circuit breaker rating. The system s discriminative properties (i.e. that the circuit breaker closest to a short circuit will trip, leaving the healthy part of the vessel s electrical distribution system operational) depends on maximum and minimum values of the prospective short circuit current of the electric generation and distribution system on board. In order to maintain discriminative protection in the vessel s distribution system, the shore power
7 Sec.3 System design requirements Page 7 supply must have a short circuit capacity within the max and min values of the vessel s network. Typically when frequency converter is used, the short circuit level may be too low to achieve full discrimination. ---e-n-d---of---g-u-i-d-a-n-c-e---n-o-t-e System earthing The vessel s designed system earthing is to be maintained in electrical shore connection operation. The selected design solution must be described in the documentation of the system. Guidance note: IEC Publication Utility connections in port - Part1: High voltage shore connection (HVSC) systems - general requirements may be referred to with regard to compatibility assessments between ship-and-shore, coordination of safety interlocks, protection and general guidance. ---e-n-d---of---g-u-i-d-a-n-c-e---n-o-t-e Protective earthing A separate conductor for protective earthing shall be connected between the hull of the vessel and the ground on the shore. Earth fault protection shall disconnect the shore power supply, both the shore side circuit breaker and the vessel s main switchboard feeder breaker. 3.8 Galvanic isolation For high voltage electrical shore connections, the shore side distribution system and the vessel s distribution system shall be galvanically separated. When this separation is performed by a transformer, this shall have separate windings for the primary and the secondary side. The transformer can be installed either on shore, or on board. If a power transformer is installed on board for adaptation of the electric shore connection system voltage and the main switchboard voltage, the transformer shall include overvoltage protection, protecting the vessel against lightning impulse over voltages. It is recommended that the same safeguards against overvoltage are applied when the transformer is installed on shore. Guidance note: Direct earthing of the lower voltage system, or the use of voltage limitation devices, are considered adequate protection. Alternatively, an earthed screen between the primary and secondary windings may be used. 3.9 Switchgear ---e-n-d---of---g-u-i-d-a-n-c-e---n-o-t-e Circuit breakers Electrical shore connection systems shall be equipped with circuit breakers suitable for isolation and interruption of possible short circuit currents, together with earthing switches, at both the shore side and the ship s side of the shore connection. The shore side circuit breaker shall have short circuit protection and under-voltage trip, disconnecting the electrical shore connection in case of loss of shore side distribution power. The incoming feeder in the vessel s main switchboard shall, in addition to overcurrent and bi-directional short circuit protection, also have an under-voltage trip, disconnecting the shore power supply in case of loss of power on the incoming feeder Earthing switches High voltage electrical shore connection systems shall be equipped with earth switches at both sides of the cable connecting the vessel to shore enabling safe discharge of the cable and safe handling of the plug and socket Plugs and sockets The shore connection cable shall be connected by plug and socket connection. Plugs and sockets shall be designed in such a way that incorrect connection is not possible. Further, connection with power on should not be possible. The plug and socket system shall be of a type tested design.
8 Sec.3 System design requirements Page Cable management system There shall be installed equipment enabling efficient cable handling and connection. The equipment shall ensure mechanical tension control of the cable and provide alarm at high cable tension to a manned position. At high high tension, the shore connection shall be automatically disconnected Interlocks Circuit breakers that are part of the electrical shore connection system, inclusive on board circuit breakers for generators, earthing switches and others, shall have necessary interlocks preventing any hazardous switching operations. These interlocks shall be described in the documentation. The following interlocks shall be provided: Automatic opening of circuit breakers: - Upon high high mechanical tension of shore connection cable - By missing confirmation of healthy protective earthing connection - By emergency disconnection signal - Short circuit detection on either side of the shore connection cable. Operation of the plug and socket: - When the plug and socket is manually operated, it shall not be possible to insert or withdraw the plug unless the circuit breakers are open. An attempt to insert or withdraw the plug shall initiate opening of circuit breakers. For automatically operated plug and socket, the same feature shall be implemented in the control system Protection, monitoring and alarms General A control system shall be arranged on-board the vessel for the electric shore connection system. This system shall trip both shore side breaker and main switchboard incoming feeder in case of: earth fault short circuit / overcurrent shore side under voltage cable break. There shall be an interlock preventing closing of shore circuit breaker unless plug and socket is correctly connected and eventual earthing switches opened. Upon opening of the shore side circuit breaker an earth switch shall connect all phases of the cable to earth, to discharge the cable and ensure connection to earth. It shall not be possible to open the earth switch unless the shore connection is connected and protective earth connection between the vessel and shore is verified. Closure of circuit breakers shall not be possible if confirmation of proper protective earthing connection is not confirmed. If proper earthing connection is lost, the breakers shall open. Activation of protective functions (including high cable tension and emergency disconnection) shall give an alarm to a continuously manned location Emergency disconnection An independent system for emergency disconnection shall be arranged with emergency stop push buttons. There shall be one emergency stop button in each of the following locations: at the ship s side where the electrical shore connection is located, where the cable management system is handled, at the shore connection switchboard, and at a continuously manned location. Activation of emergency stop shall result in disconnection of circuit breakers and closing of earthing switches. Opening, or release, of the plug and socket may be a manual operation Instrumentation Electric shore connection systems shall be equipped with the following instrumentation: phase sequence indicator voltmeter ampere meter in each phase or fitted with ampere meter switch.
9 Sec.4 Installation requirements Page 9 4 Installation requirements 4.1 General The on board electrical installations for the electrical shore connection system shall comply with the installation requirements given in DNV Ship Rules Pt.4 Ch.8 Sec Marking All high voltage equipment shall be marked with high voltage warning sign. 4.3 Cables A flexible shore connection cable can be arranged either on board the vessel or situated at key. In both situations a cable handling system must be arranged. All cables installed on board shall be DNV type approved or case by case approved.
10 CHANGES HISTORIC Page 10 CHANGES HISTORIC Note that historic changes older than the editions shown below have not been included. Older historic changes (if any) may be retrieved through January 2012 edition Main changes: This is a new document which replaces previous requirements in the ship rules, Clean+ chapter.
Cable Trays and Ducts (Metallic)
p pproval roramms for U rcos orasato Mutual coto (M)No. 2.9 STANDARD FOR CERTIFICATION Approval Programmes Type Approval Programmes for EU recognised organisation Mutual Recognition (MR) No. MR-P009 Cable
DNVGL-RU-0050 Edition October 2014
RULES FOR CLASSIFICATION DNVGL-RU-0050 Edition October 2014 The content of this service document is the subject of intellectual property rights reserved by ( DNV GL ). The user accepts that it is prohibited
General Description of The CMC- Services
STANDARD FOR CERTIFICATION No.1.1 General Description of The CMC- Services JANUARY 2013 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version The
HIGH VOLTAGE SHORE CONNECTION
Guide for High Voltage Shore Connection GUIDE FOR HIGH VOLTAGE SHORE CONNECTION NOVEMBER 2011 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 Copyright 2011
Fuel Treatment and Conditioning Systems
RULES FOR CLASSIFICATION OF Ships PART 6 CHAPTER 14 NEWBUILDINGS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS Fuel Treatment and Conditioning Systems JULY 2006 This chapter has been amended since the
DNVGL-CP-0393 Edition December 2015
CLASS PROGRAMME Type approval DNVGL-CP-0393 Edition December 2015 The electronic pdf version of this document, available free of charge from http://www.dnvgl.com, is the officially binding version. FOREWORD
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
DNVGL-CP-0209 Edition March 2016
CLASS PROGRAMME Type approval DNVGL-CP-0209 Edition March 2016 The electronic pdf version of this document, available free of charge from http://www.dnvgl.com, is the officially binding version. FOREWORD
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
SURGE PROTECTIVE DEVICES
SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood
Gas Detector System, Portable/Fixed Oxygen Analysis and Gas Detection Equipment
STANDARD FOR CERTIFICATION No. 2.9 TYPE APPROVAL PROGRAMME NO. 7-473.30/31 / MED A.1/3.30/54 Gas Detector System, Portable/Fixed Oxygen Analysis and Gas Detection Equipment SEPTEMBER 2011 The content of
Management of Safety and Environmental Protection (SEP)
RULES FOR CLASSIFICATION OF Ships / High Speed, Light Craft and Naval Surface Craft PART 7 CHAPTER 3 SHIPS IN OPERATION Management of Safety and Environmental Protection (SEP) JULY 2006 This chapter has
Low Voltage Switchboards The Best Technical Solution for Your Ship
The Best Technical Solution for Your Ship Wärtsilä SAM Electronics Optimal Power Distribution The uninterrupted supply of power to systems and consumers onboard modern ships is an extremly important matter.
Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
How To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager
New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager 2 1SDC200039B0201 New SACE Emax 2 for UL 1066 Circuit breakers switch power SACE Emax 2 manages it. SACE Emax 2 is the new benchmark of
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
Chapter 1. Network Structures
Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V
ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA
MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
CREW MANNING OFFICES, PRIVATE RECRUITMENT AND PLACEMENT SERVICES
STANDARD FOR CERTIFICATION NO. 3.404 CREW MANNING OFFICES, PRIVATE RECRUITMENT AND PLACEMENT SERVICES OCTOBER 2007 FOREWORD (DNV) is an autonomous and independent foundation with the objectives of safeguarding
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT User Manual SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 - e-mail: [email protected]
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation
Crew manning offices, private recruitment and placement services
STANDARD DNVGL-ST-0030 Edition March 2015 Crew manning offices, private recruitment and placement services The electronic pdf version of this document found through http://www.dnvgl.com is the officially
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
The Application of Circuit Breakers to Reduce Downtime in Datacentres
The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket
Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
NET METERING SUB-CODE. for Connecting Renewable Energy Generating Systems to the Distribution Network in Ghana
for Connecting Renewable Energy Generating Systems to the Distribution Network in Ghana JANUARY 2015 1 Table of Contents PART A: BACKGROUND... 1 1 Introduction... 1 1.1 Objective... 1 1.2 Status... 1 2
The following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV
MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
UFES Active protection for switchgear
Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document
Earth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
Specification guide no. 9 Active harmonic conditioner from 20 to 480 A
Active harmonic conditioner from 20 to 480 A Contents 1 - Installations concerned... 2 1.1 - New installations... 2 1.2 - Existing installations... 2 2 - General... 2 2.1 - Scope... 2 2.2 - Applicable
AUSTIN ENERGY INTERCONNECTION GUIDE FOR CUSTOMER-OWNED POWER PRODUCTION FOR FACILITIES UP TO 10MW A INTERCONNECTION CLASSIFICATIONS...
AUSTIN ENERGY INTERCONNECTION GUIDE FOR CUSTOMER-OWNED POWER PRODUCTION FOR FACILITIES UP TO 10MW TABLE OF CONTENTS PAGE INTRODUCTION... 4 A INTERCONNECTION CLASSIFICATIONS... 5 B. APPLICATION PROCESS
Dynamic Positioning Systems
RULES FOR CLASSIFICATION OF Ships PART 6 CHAPTER 7 NEWBUILDINGS SPECIAL EQUIPMENT AND SYSTEMS ADDITIONAL CLASS Dynamic Positioning Systems JULY 2011 This chapter has been amended since the main revision
STANDARD. Maritime training providers DNVGL-ST-0029:2014-04 DNV GL AS
STANDARD DNVGL-ST-0029:2014-04 Maritime training providers The electronic pdf version of this document found through http://www.dnvgl.com is the officially binding version. The documents are available
USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES
USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES 204.CAxxx 204.CBxxx 204.UBxxx 204.WBxxx MP36289 1 ZP90856-GB-6 INDICE 1 SYSTEM DESCRIPTION... 4 1.1 MODES OF OPERATION... 4 2 USER INTERFACE... 6 2.1
21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence
The following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer [email protected]. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer [email protected] Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters
S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
Connection of micro-generation to the electricity distribution network
Connection of micro-generation to the electricity distribution network Network recommendation YA9:09 Sivu 1(20) CONTENTS INTRODUCTION...3 1. MARKINGS AND DEFINITIONS...3 2. DEFINITION OF MICRO-GENERATION
PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions
PMCS Integrated Energy Management Solution Unlock the Full Potential of Power Networks Through Integration Power Management Control System (PMCS) is a highly customizable, fully integrated end-to-end Energy
User Manual 1K/2K/3K Online UPS
User Manual 1K/2K/3K Online UPS Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4. Operation...
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Nu-Lec Training Modules
PTCC Controller Nu-Lec Training Modules Product Training Operator Training PTCC The Basics An overview of the construction and physical features of the Pole Top Control Cubicle PTCC Operation and Features
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component
Reverse-feed applications for circuit breakers
Technical Publication PU01200001E Contents Description Page Intoduction.......................................................................... 2 breaker classifications..........................................................
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design
Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,
www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.
s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
Regulation IO-6.0: Electrical Safety Regulations
Regulation IO-6.0: Electrical Safety Regulations 6.1 Workmanship & Material 6.2 Electrical Conductors 6.3 Overcurrent Protective Devices 6.4 Precautions against Earth Leakage and Earthfault Currents 6.5
TECHNICAL SPECIFICATIONS FOR 1.5 KVA ONLINE UPS
Capacity Technology Inverter Technology Noise Level Operating Temperature Humidity Harmonic Distortion Total DC bus voltage Battery recharge time (After Complete discharge) to 100% charge Crest Factor
Part 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
on-line LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTERS internet centers (isp/asp/pop) industrial plcs industrial applications
ZP110 on-line UPS 1, 2, 3, 6, 10kVA single/single phase LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTERS internet centers (isp/asp/pop) industrial plcs Emergency Devices (Lights/Alarms) Electro-Medical Devices
Extend the Life of Existing Switchgear
Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2
IT Power Solutions CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2 Thomas B. Jones 1 Introduction Operators and managers consider outages, operational
Application of Four-Pole Circuit Breakers within Data Centers
Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor
MOUNTING AND OPERATING INSTRUCTIONS
MOUNTING AND OPERATING INSTRUCTIONS CF 51/55 1. Delivery CF 51/55-1 calculator with battery (optionally with mains power supply) - 1 wall mounting bracket - package with material for sealing, screws, wall
Molded Case Circuit Breaker Specifications Bulletin Number 140U-D
Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents
Bimetallic Overload Relay Specifications
Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions
Engineering Specification
Engineering Specification Electrical 33KV AC INDOOR SWITCHGEAR NON-WITHDRAWABLE Owner: Approved by: Chief Engineer, Electrical Neal Hook Chief Engineer Electrical Authorised by: Version 2.1 Issued May
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
Challenges of Protection and Control System Verification on DP3 vessels with Focus on Ride Through Fault and Blackout
Author s Name Name of the Paper Session DYNAMIC POSITIONING CONFERENCE October 15-16, 2013 POWER SESSION Challenges of Protection and Control System Verification on DP3 vessels with Focus on Ride Through
Integrated management systems Ship operating companies
Integrated management systems Ship operating companies Safety, Quality, Environment and Occupational Health and Safety DNV Maritime Preamble Organisations of all kinds are increasingly concerned about
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
Installation instructions for Series NRX INCOM communications adapter module
4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010) Effective July 2015 Supersedes October 2010 IL01301033EH04 Installation instructions for Series NRX INCOM communications adapter module Instructions apply
FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5
T5 TC-L PCA T5 BASIC lp Y II, 1 80 W BASIC T5 Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A1 BAT 1 Noise-free precise control via DSI signal,
TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012
TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets 17th April 2012 Session 2 Technological challenges to cope with in TWENTIES field tests
Eaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy
Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility
Advantages of Fixed Circuit Breaker Switchgear
Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker
TYPE CERTIFICATION OF WIND TURBINES
TYPE CERTIFICATION OF WIND TURBINES March 2003, rev. 9 DET NORSKE VERITAS, DANMARK A/S Building 114 Frederiksborgvej 399 P. O. Box 49 DK-4000 Roskilde Denmark Email: [email protected]
Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125
Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
TYPE APPROVAL CERTIFICATE
TYPE APPROVAL CERTIFICATE Certificate No: TAA0000034 This is to certify: That the Peripheral Equipment with type designation(s) Remote I/O LB/FB/MFT Issued to Pepperl+Fuchs GmbH Mannheim, Germany is found
PLAN APPROVAL DOCUMENTATION TYPES DEFINITIONS
RULES FOR CLASSIFICATION OF SHIPS / HIGH SPEED, LIGHT CRAFT AND NAVAL SURFACE CRAFT / OFFSHORE GENERAL REGULATIONS PART 0 CHAPTER 3 PLAN APPROVAL DOCUMENTATION TYPES DEFINITIONS JULY 2008 This booklet
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications Model #: SU3000RTXL3U 3000VA online 3U rack / tower UPS Enhanced serial communications