Safety By Design. Strategies for Electrical Contractors
|
|
|
- Agnes Fowler
- 10 years ago
- Views:
Transcription
1 Safety By Design Strategies for Electrical Contractors
2 Introduction Engineering and system design significantly impact worker safety System design provides opportunity to eliminate/minimize workers exposure to electrical hazards Before worker has a chance to be exposed
3 Design Considerations Design practices that enhance personnel electrical safety: Choosing OCPDs for maximum current limitation Selecting rejection-style (Class J, R, T, L) fuses Selecting shunt-trip option for switches of 800+ amps Choosing Type 2 protection for motor controllers Installing finger-safe products, covers, insulating barriers Install HP-Rated Disconnects within Sight of Every Motor or Driven Machine Installing selectively coordinated OCPDs Selecting impedance-grounded systems Installing cable limiters Installing windows for infrared viewing Marking equipment with NEC and NFPA 70E compliant arc-flash labels
4 Design Considerations (Continued) Design practices that enhance personnel electrical safety: Installing main overcurrent protection Breaking larger loads/feeders into smaller ones Lowering adjustable instantaneous trip settings Properly utilizing short-time delay Utilizing zone-selective interlocking Utilizing arc reducing maintenance switches Utilizing differential relaying Utilizing arc-flash relays Utilizing crowbar devices for arc-flash mitigation Installing remote monitoring Selecting arc-resistant switchgear Installing remote racking of power circuit breakers Installing remote opening and closing of switches, circuit breakers
5 Upgrade Considerations Upgrade practices that enhance personnel electrical safety: Upgrading fuses for greater current limitation Upgrading circuit breakers for greater current limitation Cutting in current limiting fuses, current limiting CBs, current limiting cable limiters Lowering adjustable instantaneous trip settings Adjusting short-time delay settings Marking equipment with NEC and NFPA 70E compliant arc-flash labels Installing arc-flash relays with primary side disconnecting means Installing crowbar devices for arc-flash mitigation Evaluate existing interrupting ratings and rectify if required Sizing Under-Utilized Circuits with Lower Ampere Rated Current- Limiting Fuses or CBs
6 Arcing Fault Basics Bolted Short-Circuit Arcing Fault R 1. Equations: Bolted I = V/R Bolted Arcing I = V/(R Bolted +R Arc ) 2. Arc in air results in additional resistance A B A B 3. Result: arcing fault current is lower than bolted fault current
7 Arc Flash Statistics Results of an electrical industry 10-year study of 120,000 workers 125 Injuries per year 77% electrical arc injuries 21% permanent disabilities 2.4% fatalities Based on ED France data, IEEE Presentation from M. Capelli-Schellpfeffer, M.D. Electrical Trauma Research Pogram (University of Chicago)
8 Arc Flash Statistics Skin Temperature Tolerance Relationship Skin Temperature Time of skin temperature Damage caused 110 F 6 Hours Cell breakdown starts 158 F 1 sec. Total cell destruction 176 F 0.1 sec Curable burn 200 F 0.1 sec Incurable 3 rd degree burns Exposed skin has a limited ability to protect the body from the high temperatures of electrical arcs
9 NFPA 70E & AWARENESS OF ARCFLASH (Article Work Involving Electrical Hazards) NFPA 70E Put Arc Flash Dangers On The Safety Map - Many Studies Have Been Commissioned In This area
10 Arc Flash Sequence of Events
11 Light & Heat is Evident
12 Plasma & Debris Can Be Seen
13 Debris is Usually Present
14 More Light Heat Plasma & Debris
15 The Event Engulfs Those Within The Zone
16 The Event Can Reach Those Standing Near
17 Results Sound ft. T2 >225 C / 437 F T3 P1 >2160 lbs/sq.ft T1 > 225 C / 437 F 50 C / 122 F > Indicates Meter Pegged
18 Why is an Arc a Hazard?
19 Work Involving Electrical Hazards Bolted Fault Arcing Fault Systems must be designed and are tested for worst case conditions. Most equipment is not tested for arcing faults. The Amount of Energy Released Is Based on The Amount of Current and Time
20 Choosing OCPDs for maximum current limitation Designs using current-limiting ability of OCPDs can enhance electrical safety One of the most important decisions impacting arc flash hazards Energy released during arcing fault depends upon: Magnitude of the arcing current that flows Time duration the arcing current flows Current-limiting OCPDs can reduce the energy released during arcing fault OCPDs can either be current-limiting type or non-currentlimiting type
21 Current Limitation of OCPDs Non Current-Limiting Current-Limiting Renewable & Class H Fuses Typical MCCB ICCB LVPCB MCCB: Molded Case Circuit Breaker ICCB: Insulated Case Circuit Breaker LVPCB: LV Power Circuit Breaker CL: Current-Limiting CL MCCB MCCB w/limiter Oversized Class RK5 Fuses Medium Degree of Current Limitation Class RK1 Class J Class CC Class L Class T Fuses Best Current- Limitation
22 Current Limitation of OCPDs Non-current-limiting OCPDs Renewable, Class H fuses: outdated, not current-limiting, not recommended Typical molded case circuit breakers, insulated case circuit breakers, low-voltage power circuit breakers not listed and marked as currentlimiting May not significantly reduce level of shortcircuit currents Take longer to open For arcing faults in instantaneous trip region, the higher the fault current, the greater the incident energy Non Current-Limiting Renewable & Class H Fuses Typical MCCB ICCB LVPCB
23 Current Limitation of OCPDs Current-limiting OCPDs Different types of current-limiting devices provide different degrees of protection For the same ampere rating, the fault current at which they become current-limiting varies based on the type Typically, once in the current-limiting range of an OCPD, the arc flash incident energy does not significantly increase as fault current increases
24 Current Limitation of OCPDs CL MCCBs are a better choice than standard MCCBs MCCB with fused limiters: size the limiter as low as practical Limiters typically oversized Not as good as fuse (in switch) sized properly for load Class RK5 fuses offer good arc flash mitigation The best current-limitation Class RK1 fuses Class J fuses Class CF Class CC fuses Class L fuses Class T fuses
25 Current Limitation of OCPDs Illustrates potential benefits of using the most current-limiting overcurrent protective devices I 2 t values are maximums that UL Standards allow for these products Commercially available products may have lower values Arc flash incident energy generally directly proportional to I 2 t let-thru The lower the I 2 t let-thru by an OCPD, the lower the arc flash incident energy
26 Current Limitation of OCPDs 200A Dotted line represents the available fault current that could flow with 50,000A available fault current Shown are the maximum I p let-through permitted by the UL product standards for various types of OCPDs The lower the value the better for protection
27 Current L imitation of OCPDs 200A vs. 400A
28 Design of OCPD Important Time Current Characteristics Fuses and CBs have different profiles for incident energy versus fault current Under arcing fault conditions, overcurrent protective devices operate based on arcing current OCPD characteristics and arcing current magnitude determine incident energy: For standard non-current limiting circuit breakers, when the arcing current is in their instantaneous trip region, as the arcing current increases, the incident energy increases With current-limiting OCPDs in their current-limiting range, as the arcing current increases, the incident energy generally does not increase Arcing currents, if self sustaining, in the long time region of an OCPD s characteristics will typically result in higher incident energies
29 Incident Energy vs Arcing Current Understanding These Curves How to read this information 1. If the available three phase bolted short-circuit current is known (10,000A ), 2. Under arcing fault conditions, the arcing current then would be the value shown by the 3. Which then causes the circuit breaker to operate at the yellow dot 3 on CB time-current curve. (always use the maximum or total clear time) 4. This results in this specific arcing current releasing thermal energy measured at a specific distance from the arc fault source: 4
30 Incident Energy vs Arcing Current Understanding These Curves How to read this information 1. If the available three phase bolted short-circuit current is known (10,000A ), 2. Under arcing fault conditions, the arcing current then would be the value shown by the 3. Which then causes the circuit breaker to operate at the yellow dot 3 on CB time-current curve. (always use the maximum or total clear time) 4. This results in this specific arcing current releasing thermal energy measured at a specific distance from the arc fault source: 4
31 Incident Energy vs Arcing Current Circuit Breakers This illustrates that the incident energy can be high when the arcing current is less than the instantaneous trip, if arcing fault can self-sustain
32 Incident Energy vs Arcing Current Circuit Breakers This illustrates that the incident energy is lowest when the arcing current is a just above the instantaneous trip setting
33 Incident Energy vs Arcing Current Circuit Breakers This illustrates for higher arcing currents in the circuit breaker s instantaneous trip region, the incident energy increases. This is applicable for non-current-limiting circuit breakers
34 Incident Energy vs Arcing Current Various Type Circuit Breakers When the arcing current is less than the instantaneous trip of any circuit breaker (yellow) 2. CBs with short-time delay permit the highest incident energy (red) 3. When non-current limiting circuit breakers operating in their instantaneous trip region (blue) 4. Incident energy curve when arcing current is in instantaneous trip region for current-limiting circuit breaker (green)
35 Incident Energy vs Arcing Current Circuit Breakers This illustrates for circuit breakers with short-time delay (no instantaneous trip), the incident energy is much higher and increases as the fault current increases.
36 Incident Energy vs Arcing Current Current- Limiting Fuses Next four slides cover currentlimiting fuses Shown is incident energies for two different Class fuses
37 Incident Energy vs Arcing Current Current- L imiting Fuses This illustrates that the incident energy can be highest when the arcing current is lower than the current-limiting range, if arcing fault can self-sustain
38 Incident Energy vs Arcing Current Current- Limiting Fuses This illustrates as arcing current increases, the fuse clears faster (compared to previous slide) and results in reduced incident energy
39 Incident Energy vs Arcing Current Current- Limiting Fuses This illustrates when arcing current is in the current-limiting range of a fuse, the fuse clears in less than ½ cycle and resulting incident energy is low even for higher faults (incident energy curve is flat) Arcing currents beyond current-limiting threshold of fuse do not show increased arc flash level
40 Incident Energy vs Arcing Current Current- Limiting Fuses This illustrates comparison of Class RK1 fuses vs Class RK5 fuses Class RK1 fuses are more current-limiting and provide better arc flash protection for a lower range of arcing faults
41 Selecting rejection-style (Class J, R, T, L) fuses Rejection-style Class J, T, R, L fuses are physically size-rejecting Fuses of different class cannot be accidentally put into service - They won t fit Can not install fuse with lower voltage ratings, lower interrupting ratings, lower current limiting ability Class L Class T Class R Class J
42 Selecting shunt-trip option for switches of 800+ amps Switches that shunt trip to open all 3 poles when first fuse opens can reduce arc flash energy levels
43 Choosing Type 2 protection for motor controllers Type 1 Protection of Motor Starters Before During After Motor starters are susceptible to extensive damage if not specified to be protected by OCPDs that can provide Type 2 protection Illustrated above: sequence of photos of short-circuit current testing for motor starter with Type 1 protection Type 1 protection is itself a potential arc flash hazard if the fault occurs with a worker near and enclosure door open.
44 Choosing Type 2 protection for motor controllers Type 2 Protection of Motor Starters Before During After Motor starters specified to be protected by OCPDs that provide Type 2 protection increase electrical safety Illustrated above: sequence of photos of short-circuit current testing for motor starter with Type 2 No Damage Protection
45 Understanding the Hazards Associated with Electrical Work: Electrical Shock Electrocutions were the fifth leading cause of death from 1980 through 1995
46 Installing finger-safe products, covers, insulating barriers to Help Minimize Electrical Shock Hazard Also, reduces probability of initiating an arcing fault
47 Fusible Finger-safe Panelboards for Improved Electrical Safety UL 98 disconnect with CUBEFuse branch circuits Service branch fuses without opening trim Fuse Rejection, Interlock, and Indication 47
48 Install HP-Rated Disconnects within Sight of Every Motor or Driven Machine In-sight motor disconnect: More likely to be used to lockout equipment into electrically safe work condition prior to doing work Readily available as emergency disconnect
49 Installing selectively coordinated OCPDs Selective coordination: act of isolating overcurrent condition from remainder of electrical system by opening only one overcurrent protective device ahead of the overcurrent Eliminates unnecessary power outages Enhances personnel safety because electrical worker is exposed only at problem circuit
50 Selective Coordination: Act of Isolating Faulted Circuit from Remainder of Electrical System Selective coordination: Main Arc Flash Hazard 12.3 cal/cm 2 Faults isolated by only nearest upstream OCPD Eliminates unnecessary power outages upstream Feeder Feeder Arc Flash Hazard 6.7 cal/cm 2 Typically arc flash hazard greater for larger circuits upstream Enhances personnel safety because electrical worker is exposed only at problem circuit Branch Arc Flash Hazard 1.6 cal/cm 2 Branch circuit fault only opens branch OCPD Upstream OCPDs do not open
51 Selecting impedance-grounded systems Impedance-Grounded Wye Systems Reduce Probability of Dangerous Arcing Faults Initiated Line to Ground Impedance between transformer Wye center point and ground First line to ground fault will not create high-level arc flash event However, a high incident energy arc flash can still be initiated between two phases or three phases
52 Impedance-Grounded Wye Systems Reduce Probability of Dangerous Arcing Faults Initiated Line to Ground First line to ground fault, restricted to low current Does not cause dangerous arc flash (current too low) Does not propagate to three phase arcing fault Does not open OCPD (current to low)
53 Impedance-Grounded Wye Systems Reduce Probability of Dangerous Arcing Faults Initiated Line to Ground Should troubleshoot and remove first fault before a second line to ground fault occurs: high current line to line fault results
54 Installing cable limiters Often the only short-circuit protection for (unprotected) service conductors Utilized to provide short-circuit protection for tap conductors which are also unprotected (sometimes at 10X their rating)
55 Installing windows for infrared viewing Eliminates the need to open doors or remove covers No energized parts for accidental contact No accidental arc-flash incidents from opening/closing, loose screws, etc.
56 Marking equipment with NEC and NFPA 70E compliant arc-flash labels Marking/labeling electrical equipment with arc flash hazard or warning can reduce occurrence of serious injury or death Various requirements and options NEC Section NFPA 70E (C)
57 Arc Flash Hazard Warning Labels New Installations NEC Section (since 2002 NEC) requires field marking with arc flash warning label on certain new equipment installations Not required to include specific arc flash hazard detailed information
58 Marking New Equipment with Arc Flash Hazard 2012 NFPA 70E Section 130.5(C) requires marking equipment with incident energy or level of PPE when arc flash hazard analysis is performed Benefit: qualified worker can readily know the hazard Other important information can also be included on label such as shock hazard info See example on next slide
59 Marking New Equipment with Arc Flash Hazard
60 Installing main overcurrent protection
61 Breaking larger loads/feeders into smaller ones 28,000A Available Short Circuit Current Cal/cm 18 Incident Energy 1600A 800A 28,000A Available Short Circuit Current 1.22 Cal/cm 18 Incident Energy 800A MCC MCC MCC M M M M M M M M M M M M
62 Lowering adjustable instantaneous trip settings Some circuit breakers have adjustable instantaneous trip (IT) settings Adjusting to lower instantaneous trip may lower arc flash incident energy If set too low, may incur nuisance tripping Lowering IT setting may negatively affect selective coordination
63 Properly utilizing short-time delay Short-time delay (STD) mechanisms can be set to provide selective coordination and provide arc-flash protection at the same time Arc flash hazard increases with length of time current is permitted to flow Exception: if zone selective interlocking, arc reducing maintenance switch, differential relaying, or equivalent are used (see next six topics)
64 Time In Seconds Properly utilizing short-time delay T2 Long Time Pickup Long Time Delay NO Short Time Delay Trip Curve Of Breaker NOT Utilizing Short Time Delay Max Clearing Time T2 For Arcing Current Ia = ~ 15 Sec Ia Instantaneous Pickup Multiples of Rated Current
65 Time In Seconds Properly utilizing short-time delay Short Time Pickup Long Time Pickup Long Time Delay Short Time Delay Trip Curve Of Breaker Utilizing Short Time Delay Max Clearing Time T1 For Arcing Current Ia = ~.9 Seconds 1.0 Short Time Delay 0.1 T1 Instantaneous Override 0.01 Ia Multiples of Rated Current
66 Utilizing zone-selective interlocking Circuit breakers with zone selective interlocking have current sensing elements that communicate. With fault on load side of CB 3, CB3 sends restraint signal to CB2 and CB1. Time current curves are as depicted.
67 Operation of Zone-Selective Interlocking When fault is between CB2 and CB3, CB3 does not send a restraint to CB2, CB2 sends a restraint to CB1, and CB2 opens as fast as it can (instantaneous trip) rather holding to its short-time delay setting.
68 Operation of Zone-Selective Interlocking When fault is between CB1 and CB2, CB2 and CB3 do not send restraint to CB1, so CB1 opens as fast as it can (instantaneous trip) rather holding to its short-time delay setting.
69 Zone Selective Interlocking M1 SD= 0.5S 35kA fault current F1 F2 X F3 SD= 0.3S SD= 0.3S SD= 0.3S Without ZSI = 0.5 S: 43.7 Cal/cm 2 DANGER! With ZSI = 0.08 S: 7.0 Cal/cm 2 FR Shirt & Pants
70 Utilizing arc reducing maintenance switches - Reduces Exposure Levels for Workers Control switch turns off shorttime delay function while working in arc flash protection boundary Where short-time delay is utilized Option allows circuit breaker to trip without intentional delay if arc flash started while worker is in arc flash protection boundary
71 Utilizing arc reducing maintenance switches Normally CB 1 trips by short-time delay setting When arc flash reducing maintenance switch is utilized, CB 1 trip setting is adjusted to instantaneous
72 Utilizing arc reducing maintenance switches Arc Flash Reduction Maintenance Switch High Avail Fault Current Digitrip 610 & Arcflash Reduction Maintenance Switch Normal settings 10.7 cal With Arcflash Reduction Maintenance Switch 2.2 cal
73 Utilizing differential relaying The CTs and relay are configured to sum the currents entering and subtracting the sum of the currents exiting via the normal conducting paths. If a fault occurs on the bus with a current magnitude greater than the relay set point, the relay signals the disconnects to interrupt. 87B Bus Differential Relay Circuit breakers or fused switches Current transformers
74 Utilizing arc-flash relays 13 kv 480V Switchgear Arc Flash Relay Signal Open Circuit Breaker Output Current Input Light Sensor Input Light Sensor Arc Flash Relay processes signals from Light Sensor Inputs and Current Sensor Inputs. If an arcing fault occurs in the LV switchgear, (1) a Light Sensor sees the light and communicates to the Arc Flash Relay, (2) a Current Unit Sensor sees uncharacteristic current flow and communicates with the Arc Flash Relay. An andgate checks for signals from both the Light Sensor and the Current Sensor and then sends a signal to trip the primary side circuit breaker or vacuum interrupter.
75 Utilizing crowbar devices for arcflash mitigation Several types of crowbar devices intentionally create bolted faults or arcing faults in parallel with the accidental arcing fault Lower impedance than an accidental arcing fault Available arcing fault current takes path of least impedance Quick enough to divert the harmful arcing fault energy away from the worker
76 Installing remote monitoring Remote Monitoring: Enables Troubleshooting, Diagnostics without Opening Enclosures Remote monitoring of voltage, current levels reduces exposure to electrical hazards Displays on enclosure exteriors or computer port on exterior or networked
77 Selecting arc-resistant switchgear Arc-Resistant (Arc Diverting) Switchgear Withstands Internal Arcing Faults Arc by-products vented via louvers Arc-resistant equipment is designed with features that divert hot gases, pressures from internal arcing fault If indoors, typically requires duct work Only applicable when doors closed and latched
78 Selecting arc-resistant switchgear During the studies and tests conducted by Eaton Electrical, it was found that the internal arcing phenomenon consists of two stages: A dynamic phase and a thermal phase.
79 Selecting arc-resistant switchgear The Dynamic Phase Within 10 milliseconds of arc inception, the pressure inside a switchgear enclosure could reach a level as high as 4232 lb./square-foot. With this rate of rise, containment cannot be accomplished. Actual testing is the only way to prove an arcresistant design. Arc resistant switchgear includes a pressure-relief vent to allow the dynamic phase to dissipate.
80 Selecting arc-resistant switchgear The Thermal Phase While the arc is burning and expanding, copper bus bar will vaporize, insulation will disintegrate and paint will burn. If the fault persists beyond 30 cycles, the arc can burn through steel. Arc Resistant Switchgear does not protect personnel from: Toxic gases which are vented due to internal faults Inappropriate location of the equipment within a building The loud noise that result from an internal fault Damage resulting from doors being open or panels being removed.
81 Selecting arc-resistant switchgear The diagram above shows the dynamic pressure is at its highest point in the first cycle after the fault occurs.
82 Installing remote racking of power circuit breakers Important to move workers outside the arcflash boundary- further from potential arc source for hazardous operations: Remote-controlled motorized racking devices Extended length hand-operated racking tools
83 Installing remote racking of power circuit breakers Racking circuit breakers into energized circuit is a very hazardous task Remote racking permits worker to be outside of arc flash protection boundary and rack in/out a circuit breaker
84 Installing remote racking of power circuit breakers VS. Physical Separation Of Individuals From Arc Flash Boundaries Place Individuals Outside Of Harms Way
85 Installing remote opening and closing of switches, circuit breakers Permits worker to control operation from safe distance (outside the arc flash protection boundary) Electric Motor Operator
86 Installing remote opening and closing of switches, circuit breakers Without With Physical Separation Of Individuals From Arc Flash Boundaries Place Individuals Outside Of Harms Way
87 Upgrading fuses for greater current limitation If existing electrical system is fusible, consider replacing older fuses or less current-limiting fuses with newer, more current-limiting fuses where possible Over the decades, advancements in fuse capabilities: use the more recent and best There may be different type fuses that fit in the same mountings that mitigate the arc flash hazard better: see next slide
88 The Upgrade & Consolidation to Class RK1 Fuses
89 Upgrading circuit breakers for greater current limitation Non-Current Limiting Current Limiting
90 Cutting in current limiting fuses, current limiting CBs, current limiting cable limiters Locations with dangerous arc-flash energy levels Locations with medium to high available short-circuit currents Space and ownership are the big issues to overcome
91 TIME IN SECONDS Lowering adjustable instantaneous trip settings Some circuit breakers have adjustable instantaneous trip (IT) settings Adjusting to lower instantaneous trip may lower arc flash incident energy If set too low, may incur nuisance tripping Lowering IT setting may negatively affect coordination CURRENT IN AMPERES 600A CB 10X IT 5X IT K 10K 100K Adjustable IT CB.tcc Ref. Voltage: 480 Current in Amps x 1
92 Time In Seconds Adjusting short-time delay settings T Short Time Pickup Long Time Pickup Long Time Delay Short Time Delay Review the settings and associated time-current curves It is often possible to adjust settings to pick up and open quicker on expected arcing fault current Ia Instantaneous Override Multiples of Rated Current Short Time Delay Trip Curve Of Breaker Utilizing Short Time Delay Max Clearing Time T1 For Arcing Current Ia = ~100 Seconds
93 Time In Seconds Adjusting short-time delay settings T Short Time Pickup Long Time Pickup Ia Long Time Delay Short Time Delay Instantaneous Override Multiples of Rated Current In this case, time to trip was reduced from 100 seconds to ½ second, simply by adjusting the short time pickup Short Time Delay Trip Curve Of Breaker Utilizing Short Time Delay Max Clearing Time T2 For Arcing Current Ia = ~0.5 Seconds
94 Marking equipment with NEC and NFPA 70E compliant arc-flash labels Many premise owners conduct arc flash hazard analysis & shock hazard analysis for entire premises and label the premise electrical equipment Facilitates more efficient operation Especially when qualified workers do routine tasks such as checking for the absence of voltage Process for premise wide labeling: Accurate single-line diagram Short-circuit current study Arc flash hazard analysis Affix labels
95 Updating Arc Flash Hazard Information requires an arc flash hazard analysis to be updated when a major change occurs or to periodically be reviewed, not to exceed five years Electrical system changes can affect available arc flash incident energy, required level of PPE for electrical equipment Electrical system changes may alter Available short-circuit current Time duration for fuses or circuit breakers to interrupt arcing current
96 Updating Arc Flash Hazard Information Changes that may affect the available arc flash incident energy and required level of PPE Upstream transformer replaced with different % Z and/or greater KVA rating (changes available short-circuit current) A fuse or circuit breaker type, amp rating, or setting is changed (changes time to interrupt arc fault current) Circuit conductor size or length is changed (changes available short-circuit current) Alternate power sources added or deleted
97 Installing arc-flash relays with primary side disconnecting means 13 kv 480V Switchgear Arc Flash Relay Signal Open Circuit Breaker Output Current Input Light Sensor Input Light Sensor Arc Flash Relay processes signals from Light Sensor Inputs and Current Sensor Inputs. If an arcing fault occurs in the LV switchgear, (1) a Light Sensor sees the light and communicates to the Arc Flash Relay, (2) a Current Unit Sensor sees uncharacteristic current flow and communicates with the Arc Flash Relay. An andgate checks for signals from both the Light Sensor and the Current Sensor and then sends a signal to trip the primary side circuit breaker or vacuum interrupter.
98 Installing crowbar devices for arcflash mitigation Several types of crowbar devices intentionally create bolted faults or arcing faults in parallel with the accidental arcing fault Lower impedance than an accidental arcing fault Available arcing fault current takes path of least impedance Quick enough to divert the harmful arcing fault energy away from the worker
99 Evaluate existing interrupting ratings and rectify if required Interrupting Rating Maximum current that a circuit breaker or fuse can safely interrupt under standard test conditions. Serious safety hazard when available shortcircuit current exceeds an OCPD s interrupting rating Adequate interrupting rating required per National Electric Code Section and OSHA (b)(4). This OSHA regulation is applicable no matter what the of age of system
100 Interrupting Rating Misapplication (videos) 10,000A IR, 600V 14,000A IR, 480V Class H Fuse Circuit Breaker 50,000 Available 50,000A Available Click on image to play video Click on image to play video Violates NEC and OSHA (b)(4)
101 Inadequate Interrupting Rating Fuse Test (still photos) 10,000A IR, 600V Class H Fuse with 50,000 available short-circuit
102 Inadequate Interrupting Rating Circuit Breaker Test (still photos) 14,000A IR, 480V Circuit Breaker with 50,000 available short-circuit 480V
103 Modern current-limiting fuses have interrupting ratings of 200kA and 300kA Circuit breakers are available in a wide range of interrupting ratings up through 200kA Adequate Interrupting Rating Fuse Test 300,000A IR, 600V Class J Fuse with 50,000 available short-circuit Click on image to play video Before, during and after test
104 Evaluate existing interrupting ratings and rectify if required Electrical system changes result in higher available short-circuit currents Might exceed interrupting rating of existing OCPDs Existing OCPDs must be reevaluated for sufficient interrupting rating Conduct short-circuit current analysis of facility Check to insure each OCPD s interrupting rating is equal to or greater than the available short-circuit current at OCPD s line terminals Series rated systems may be an exception, but should be properly evaluated
105 Sizing Under-Utilized Circuits with Lower Ampere Rated Current-Limiting Fuses or CBs Measure actual load current
106 Summary Electrical systems can be designed or upgraded to eliminate or reduce electrical hazards for personnel Key factors to reduce arc-flash injuries Reduced Arcing Time Limited Arcing Current Increased Working Distance Easily Accessible Disconnecting Means Key factor to reducing shock and electrocution Finger Safe Construction, Covers, Barriers Increased Working Distance Easily Accessible Disconnecting Means
107 Thank You! Any Questions? Feel Free to Contact Us Tim Crnko Vince Saporita
Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer [email protected]. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer [email protected] Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
misconceptions about arc-flash hazard assessments
misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.
Understanding Arc Flash
Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which
HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE
Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
Part 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
Arc Flash Energy Mitigation Techniques
Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal
Arc Flash Mitigation & Selective Co-ordination
Arc Flash Mitigation & Selective Co-ordination Michael Hodder March 2015 Overview This seminar will provide information on: Mitigating arc flash hazards Selective Coordination What can we do to make these
Choosing the Best Solution for Reducing Arc Energy
CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors
How to reduce exposure to arc flash hazards
GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety
ELECTRICAL SAFETY RISK ASSESSMENT
ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures
ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com]
ARC FLASH HAZARD MITIGATION ARC FLASH HAZARD MITIGATION NWHA TECHNICAL SEMINAR May 17, 2012 Richard D Reese Power Systems Manager Industrial Tests, Inc. Rocklin, California [[email protected]; 916-660-2837]
Fault Characteristics in Electrical Equipment
1. Introduction Proper design and installation of electrical equipment minimizes the chance of electrical faults. Faults occur when the insulation system is compromised and current is allowed to flow through
Mission Critical Data Center Systems
Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,
Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.
Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible
Introduction to Arc Flash
Introduction to Arc Flash Worker Training of Electrical Hazards Including Arc Flash SH-16614-7 This material was produced under grant number SH-16614-7 from the Occupational Safety and Health Administration,
Roadmap to Compliance with NFPA 70E Arc Flash Requirements
Roadmap to Compliance with NFPA 70E Arc Flash Requirements TAHFM Interlink 2015 March 30, 2015 Antony Parsons, Ph.D., P.E. Schneider Electric Engineering Services 1 2 How do we get to Reliable Power? >
NFPA 70E Updates Affect Your Most Valuable Assets
NFPA 70E Updates Affect Your Most Valuable Assets EXECUTIVE SUMMARY Electrocution is a well-known hazard associated with direct contact with electrical energy. According to the U.S. Department of Labor,
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit
Engineering Series Ratings: Is It Practical?
Engineering Series Ratings: Is It Practical? By the National Electrical Manufacturers Association The 2005 National Electrical Code (NEC) introduces a change regarding series ratings for circuit breakers
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
Technical Guide. SKM Arc Flash Line Side vs. Load Side
SKM Arc Flash Line vs. Load The option of choosing the line-side or the load-side arc flash incident energy for arc flash labels is an important decision when performing an arc flash hazard analysis. When
Low Voltage Switchgear
Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering
What s up with Arc Flash?
What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS
A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS By: Gabriel Arce, ABB, San Luis Potosi, Mexico Casey McCollum, ABB, Houston, TX John
Arc Flash Mitigation. Executive summary. by Antony Parsons, Ph.D., P.E.
by Antony Parsons, Ph.D., P.E. Executive summary Arc flash events can result in significant injury to workers, including severe burn injuries. The most effective arc flash safety programs are not those
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA
RISK MITIGATION for ELECTRICAL WORK Feb 2013 San Diego CA Agenda I. RISK Define the Risks Arc Flash Review II. MITIGATION 3 Easy Steps New Designs Vs. Existing Systems III. DUKE UNIVERSITY EXAMPLE I. Risk
New standardized approach to arc flash protection
New standardized approach to arc flash protection Samuel Dahl Juha Arvola Tero Virtala Arcteq Relays Ltd Arcteq Relays Ltd Arcteq Relays Ltd Wolffintie 36 F 11 Wolffintie 36 F 11 Wolffintie 36 F11 65200
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software Abstract: The nature of explosive equipment failures, and the rate of serious burn injuries in the electrical industry
Low Voltage Circuit Breakers. Arc flash hazards
Low Voltage Circuit Breakers Arc flash hazards Index Low voltage selectivity with ABB circuit breakers Introduction... 2 Definitions, acronyms and terms used... 3 Electrical arcs and their dangerous effects
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents
2008 Eaton Corporation. All rights reserved.
FlashGard TM Motor Control Center Electrical Safety Hazards Design Philosophy The Product 2008 Eaton Corporation. All rights reserved. Research studies say. Five to 10 arc flash explosions occur in electrical
Arc Flash Safety in 400V Data Centers
Arc Flash Safety in 400V Data Centers Strategies for protecting employees from underappreciated yet potentially deadly hazards By Dave G. Loucks PCM Solution Manager Eaton Corporation Executive summary
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Assessing The Hazards Of High and Low Voltage Single-Phase Arc-Flash By Albert Marroquin One common question
ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.
ARC FLASH HAZARD OVERVIEW Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH EXPERIENCE Christopher J. DeWaal, MS, MEM, PE, LEED AP, HACCP How did I get involved? A client
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection
Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection L. Kumpulainen, S. Dahl J. Ma Vamp Ltd, Finland Vamp Ltd, China 1 ABSTRACT This paper describes causes and characteristics
Fusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
Arc Flash Avoidance and its Application to Overhead Traveling Cranes
Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles
! WARNING Arc Flash and Shock Hazard Appropriate PPE Required
Arc Flash Hazard Labeling Do s and Don ts! WARNING Arc Flash and Shock Hazard Appropriate PPE Required 11' - 3" Flash Hazard Boundary 9 cal/cm2 Flash Hazard at 18 inches #3 PPE Level Cotton underwear plus
Alternate Methods to Short Circuit Breaker Coordination
Alternate Methods to Short Circuit Breaker Coordination Nguyen Perez, PE Senior Electrical Engineer 2600 Douglas Road, Suite 301 Coral Gables, Florida 305.529.1515 (p) www.brplusa.com Importance in Healthcare
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? Comparing apples-to-apples bids Plant Services Special Report A shock hazard analysis should be included as part of an arc
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Enhancing Personnel Safety with Arc Resistant Equipment
Enhancing Personnel Safety with Arc Resistant Equipment Carl Christian Power LV Offer Marketing Nashville, TN Sponsored by the Water Wastewater Competency Center 1 Enhancing Personnel Safety 5-10 Five
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B
SURGE PROTECTIVE DEVICES (SPDs) EXTERNAL SIDEMOUNT UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
CONDUCTOR SHORT-CIRCUIT PROTECTION
CONDUCTOR SHORT-CIRCUIT PROTECTION Introduction: This paper analyzes the protection of wire from fault currents. It gives the specifier the necessary information regarding the short-circuit current rating
UL Validated Testing of Arc-Resistant Motor Control Centers
UL Validated Testing of Arc-Resistant Motor Control Centers Ensure Protective Features Perform as Designed Larry Sifers Account Manager Littleton, CO Siemens Industry June 1st - 3rd, 2011 Western Mining
Analyzing Electrical Hazards in the Workplace
Analyzing Electrical Hazards in the Workplace By Dennis K. Neitzel, CPE AVO Training Institute, Inc. The need for analyzing electrical hazards in the workplace has been recognized by a small segment of
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS Paul A Zoubek, CSP, CIH Occupational Services, Inc. San Diego, CA 619-861 861-0612 [email protected] OCCUPATIONAL SERVICES, INC. BACKGROUND Update Update
Guidelines on the Short Circuit Current Rating for Industrial Control Panels
usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A
Power-Zone 4 Arc Resistant Low Voltage Switchgear
Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS
STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS David D. Roybal, P.E. Senior Member, IEEE Cutler-Hammer, Inc. 3697 Mount Diablo Boulevard Lafayette,
Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT
Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT Are You Ready For The New SCCR Marking Requirements? What Is A Short-Circuit Current Rating (SCCR)? SCCRs on components
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,
Implementation of arc flash mitigating solutions at industrial manufacturing facilities
Thought leadership White paper Implementation of arc flash mitigating solutions at industrial manufacturing facilities David B. Durocher Senior Member, IEEE Global Industry Manager Eaton 26850 SW Kinsman
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
Short-circuit, Protective Device Coordination & Arc Flash Analysis. By Albert Marroquin Operation Technology, Inc.
Short-circuit, Protective Device Coordination & Arc Flash Analysis By Albert Marroquin Operation Technology, Inc. Agenda Short-circuit Calculations for Arc Flash Analysis Protection and Coordination Principles
Sentron Series Circuit Breakers
Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of
4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS
4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED MEDIUM VOLTAGE
Sample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
Extend the Life of Existing Switchgear
Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...
2012 NFPA 70E. Ten Most Important Changes. John A. DeDad
2012 NFPA 70E Ten Most Important Changes John A. DeDad GE Energy Management 41 Woodford Avenue Plainville, CT 06062 USA 860-747-7344 [email protected] Abstract The 2012 Edition of NFPA 70E, Standard for
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it
MEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED
MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED CCG Facilities Integration Incorporated
Understanding the Standards Surrounding Arc Flash Hazards and Arc Resistant Equipment
Understanding the Standards Surrounding Arc Flash Hazards and Arc Resistant Equipment 1 Rev 5058-CO900E This presentation contains many hidden slides that are provided for the presenters information and/or
Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for
Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for data centers Executive Summary Every three years, the
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
A Comparison of Circuit Breakers and Fuses for Low-Voltage Applications
Data Bulletin 0600DB0601 2/2007 Cedar Rapids, IA, USA A Comparison of Circuit Breakers and Fuses for Low-Voltage Applications Tony Parsons, PhD, P.E., Square D / Schneider Electric Power Systems Engineering
SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
A Survey of Arc Flash Computation Methods and Mitigation Strategies By Dr. Carl J. Spezia
Volume 26, Number 2 - April 20 through June 20 A Survey of Arc Flash Computation Methods and Mitigation Strategies By Dr. Carl J. Spezia Peer-Refereed Perspective Papers Keyword Search Electricity Energy
Switchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
Siemens tiastar TM Motor Control Center (MCC) Siemens 2011. All rights reserved.
Siemens tiastar TM Motor Control Center (MCC) Siemens 2011. All rights reserved. tiastar Arc Resistant MCCs UL Validated Testing of Arc-Resistant Motor Control Centers page 2 tiastar Arc Resistant MCCs
Motor Protection Voltage Unbalance and Single-Phasing
Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the
Low Voltage Transformer Through-Fault Protection: A System Approach
Data Bulletin 7400DB1001 Nashville, TN USA Low Voltage Transformer Through-Fault Protection: A System Approach Introduction Low Voltage Transformer Protection Criteria NEC Article 450 Transformers and
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a
SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E
SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program
Application of Four-Pole Circuit Breakers within Data Centers
Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1
OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010
OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010 By: Martin Robinson, Level III Thermographer 18-1030-0005 Rev. A The National Fire Protection Association (NFPA)
IMPROVING SELECTIVITY & ARC-FLASH PROTECTION THROUGH OPTIMIZED INSTANTANEOUS PROTECTION SETTINGS Copyright Material IEEE Paper No.
MPROVNG SELECTVTY & ARC-FLASH PROTECTON THROUGH OPTMZED NSTANTANEOUS PROTECTON SETTNGS Copyright Material EEE Paper No. ESW 2012 EEE. Reprinted, with permission, from authors, Marcelo E. Valdes, Steve
The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS
The Other Hazard of Electricity Larren Elliott Ph.D. Lindsay Polic, CSP, REHS Presenters Larren Elliott Ph.D. EORM Electrical Safety Service Partner 45 years practical and hands-on industrial experience
Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited
Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section
Protection Considerations to Mitigate Arc-Flash Hazards
1 Protection Considerations to Mitigate Arc-Flash Hazards echnical Report to the Substation Subcommittee of the Power Systems Relaying Committee Working Group: Chair: K. Zimmerman, Vice Chair: R.A. Hedding,