Arc Flash Safety in 400V Data Centers
|
|
|
- Jacob Townsend
- 10 years ago
- Views:
Transcription
1 Arc Flash Safety in 400V Data Centers Strategies for protecting employees from underappreciated yet potentially deadly hazards By Dave G. Loucks PCM Solution Manager Eaton Corporation Executive summary Tight budgets and rising interest in energy efficiency have many U.S. companies looking to switch from 120V power to 400V power in their data centers. However, while operating a data center at 400V significantly decreases energy waste, it also dramatically increases the magnitude and impact of arc flash events. Indeed, while arc flashes in a 120V data center generally produce minor, temporary wounds, comparable incidents in a 400V data center can easily result in permanently disabling and disfiguring injuries or even death. This white paper discusses the potentially lethal hazards associated with arc flash events in a 400V data center, and then describes steps that businesses can take to reduce the frequency, severity and harmfulness of such incidents. Table of contents The rise of the 400V data center...2 Preventing arc flash events in a 400V environment Perform a hazard analysis Select appropriate personal protective equipment Conduct employee safety training Leverage parallel redundant architectures Use circuit breakers instead of fuses Deploy arc flash safety products... 4 Conclusion...7 About Eaton...7 About the author...7
2 Page 2 of 7 The rise of the 400V data center In the U.S., utilities typically deliver power at 480V. Most U.S. data centers, however, operate at 120V/208V. As a result, they must use a series of mechanisms to transform or step down power from the 480V at which it s received to the 120V at which it s consumed by servers and other infrastructure devices. Unfortunately, a small amount of energy gets lost as waste during each of those steps. One way to reduce such waste is to operate the data center at 400V, as organizations in most countries around the world already do. In a 400V data center, fewer voltage transformations occur along the power chain, resulting in reduced energy loss. Not surprisingly, then, many U.S. data centers are taking a close look at increasing their operating voltage from 120V to 400V. As they do so, however, it is important that they examine the potential safety implications of such a move, including the heightened risks associated with arc flash incidents. In a 120V/208V circuit, arcs tend to self-extinguish, so arc flash incidents are rarely capable of causing lifethreatening or permanently-disabling injuries. In a 400V circuit, by contrast, an accidental short circuit can initiate an arc that does not self-extinguish. As a result, 400V circuit arc flash events routinely ignite powerful explosions marked by searing heat, toxic fumes, blinding light, deafening noise and devastating pressure waves. Without proper protection, workers exposed to such blasts can suffer third-degree burns, collapsed lungs, loss of vision, ruptured eardrums, puncture wounds and even death. Eaton, for its part, provides mandatory arc flash training for all of its service personnel. Technicians are required to use lockout/tag out procedures (which ensure that equipment is not unexpectedly re-energized while technicians are working on it) and wear appropriate protective gear, including suits, helmets with face guards, safety glasses, safety shoes and protective gloves. Preventing arc flash events in a 400V environment No company should begin powering their data center at 400V before making careful preparations aimed at protecting their employees. The remainder of this white paper discusses six essential safety steps that data center managers should consider taking. 1. Perform a hazard analysis Proper arc flash safety is impossible without accurate measurements of the potential energy release associated with arc flash events. An arc flash hazard analysis can help you calculate those incident energy values, while also identifying arc flash risks along the power chain and strategies for mitigating them. Data center managers who lack direct and extensive experience with performing arc flash analyses within 400V environments should be certain to include a qualified power systems engineer in the arc flash hazard analysis process. 2. Select appropriate personal protective equipment Technicians in a 400V data center should never come within range of a potential arc flash incident unless they re wearing appropriate personal protective equipment (PPE), such as flame-resistant clothing, eye protection and gloves. For example, if live bus work is exposed, personnel should remain at least 10 feet away unless they re wearing appropriate PPE. The specific type of PPE worn depends on the calculated incident energy values. PPE shields wearers from the heat and light produced by arc flash explosions, and to a lesser extent from shrapnel and noise as well. PPE is available in varying degrees of strength offering varying degrees of protection. Electrical engineers and fire safety professionals have developed two standards to help organizations determine how much protection their employees require:
3 Page 3 of 7 IEEE : Created by the Institute of Electrical and Electronics Engineers (IEEE), one of the world s most respected technical professional associations, IEEE offers guidance on measuring the incident energy associated with arc flash events, as well as recommendations on how much PPE workers require based on those measurements. For more information, visit and search for NFPA 70E: Produced by the National Fire Protection Association, a non-profit organization dedicated to fire, electrical, building and life safety, NFPA 70E defines thresholds for appropriate PPE based on the severity of potential arc flash hazards. For more information, visit and search for NFPA 70E. Drawing on these two standards as well as the data collected during an arc flash hazard analysis, organizations can accurately calculate their Hazard Risk Category, which will in turn tell them what kind of PPE their employees should wear when working in arc flash danger zones. Data center managers should also ensure that any vendors or third-party service providers who perform maintenance procedures on their server infrastructure wear appropriate PPE at all times. Though arc flash safety standards like IEEE are extremely helpful tools, it is worth noting that they contain an important gap at present: single-phase-to-ground faults. Though IEEE provides energy calculations for three-phase arcing faults, it offers no guidance on single-phase-to-ground faults, which are much more common in servers and other information and communications technology equipment that operate on single-phase power. Instead, the standard assumes that ground faults will ether selfextinguish or escalate into a three-phase fault. In truth, however, the additional energy released by singlephase ground faults before they become three-phase faults can be substantial. This is because ground faults tend to be lower current faults that require more time for upstream protective devices to clear, while higher current three-phase faults are cleared quickly. Since present IEEE guidelines fail to take that additional energy into account, they may significantly underestimate the amount of protection that exposed workers require. Eaton and other leading companies have contributed substantial funding to a new joint NFPA/IEEE work effort aimed at updating the 2002 standard to include, among other things, singlephase arc flash testing. 3. Conduct employee safety training While providing appropriate PPE is a vital part of safeguarding technicians from arc flash hazards, thorough safety training should also be part of every company s strategy for mitigating arc flash dangers. When delivered by experienced and knowledgeable instructors, arc flash safety training can also help data center managers calculate potential short circuit currents, Hazard Risk Categories and safe boundary distances based on the IEEE and NFPA 70E standards. Organizations should also ensure that any vendors or third-party service providers working in their data center have received thorough safety training as well. 4. Leverage parallel redundant architectures Many organizations currently use parallel redundant power chain architectures in their data centers. At their most thorough, such schemes provide multiple, independent power paths all the way from utility mains to electrical load, so that if one path becomes unavailable due to a component failure or routine maintenance, the others can keep critical applications up and running.
4 Page 4 of 7 Figure 1. Creating multiple power paths all the way from utility mains to UPSs to IT equipment (ITE) can improve both reliability and safety. However, companies can temporarily use parallel redundant power architectures to promote safety rather than reliability, by manually de-energizing a power path before repairing or administering the IT equipment it supports. Though such a move briefly increases the risk of downtime, it also reduces the risk of arc flashrelated injuries. For most businesses in most situations, that s a tradeoff worth making. 5. Use circuit breakers instead of fuses Generally speaking, organizations have two options when selecting overcurrent protection technologies in a data center power system: fuses and circuit breakers. Though data center managers should consider a range of factors before making their choice, circuit breakers provide significant advantages with respect to arc flash safety due to the faster fault clearing time they provide during the kind of fault that occurs most commonly in a data center ground faults. In fact, IEEE Std (Gold Book), Table states that the likelihood of a ground fault is 2.5 to 70 times more likely than a phase-to-phase fault. Since ground fault current typically flows through non-copper conductors, the overall magnitude of the fault current is reduced. Under these lower current conditions, the very steep time-overcurrent curve typical of a current limiting fuse works against it. With a current limiting fuse, a slight decrease in fault current results in a large increase in clearing time. As a result, these reduced clearing speeds produce proportionally higher incident energy during a fault. With a circuit breaker, for any current level above the instantaneous trip pickup point (typically six to 10 times breaker handle rating), the incident energy decreases as the fault current decreases, as is common in a ground fault. For the fuse, the incident energy increases as the fault current decreases. For even lower incident energy levels, circuit breakers can be equipped with ground fault sensing. In circuit breakers with ground fault sensing, the instantaneous trip can occur at fault current levels below the breaker handle rating. This results in substantially lower arc flash incident energy. Even if a high current fault were to occur, breakers still provide the required protection. In fact, Eaton molded case circuit breakers operate so quickly, that for any current value above 15 times the handle rating of the breaker and below the withstand rating of the breaker, the incident arc energy released from a fault downstream of that breaker will always be no higher than Hazard Risk Category level 1. Furthermore, though technicians can turn fusible switches on or off remotely, changing or inspecting a fuse requires them to go into the panelboard, where they re exposed to potential arc flash events. Circuit breakers, by contrast, rarely require replacement and can be reset safely from outside the panel. 6. Deploy arc flash safety products Beyond wearing appropriate PPE, there are four main ways to lessen arc flash hazards: reduce arc flash durations, reduce arc flash currents, reduce the frequency of arc flash incidents and place protective physical barriers between arc flashes and data center personnel. With the help of safety products from Eaton and other manufacturers, data center managers can cost-effectively take advantage of all four strategies.
5 Page 5 of 7 Reduce arc flash durations The shorter an arc flash event lasts, the less energy it releases and hence the less danger it poses to nearby personnel. Organizations can use a variety of tools to interrupt arc flashes quickly, including these: Feeder protective devices with arc flash reduction maintenance system settings: During a fault, data center operators always prefer protective devices closest to the fault to trip before upstream devices, as that minimizes the number of servers impacted by the interruption of electrical power. Consequently, most companies select products with intentional delays in upstream protective devices that give downstream devices time to trip first. Unfortunately, however, such products also give arc flashes time to reach potentially deadly energy levels if the fault occurs between two protective devices, as current will flow longer than needed while the upstream device waits for the fault to be cleared by the downstream device. Since the downstream device does not see the fault, there is no reason to wait before clearing the fault by the upstream device. Feeder protective devices with maintenance system settings enable technicians to temporarily disable intentional delays along the power chain while they work with live electrical equipment, so as to shorten arc flash incidents and limit the energy they release. Be sure, however, to look for arc flash reduction maintenance systems that operate even faster than the circuit breaker s normal instantaneous clearing time. Such products include dedicated high-speed analog tripping circuitry that bypasses the circuit breaker trip unit. Modern electronic trip units use microprocessors to calculate currents and decide when to trip. The time delays introduced by executing this program code (not to mention boot-up time if the breaker is closed into a fault and the microprocessor is initially powered up), are eliminated by the analog bypass circuit. Zone selective interlocking: Though it doesn t provide as much arc flash incident energy reduction as a true analog bypass arc flash reduction maintenance system, zone selective interlocking (ZSI) offers the advantage of automatic operation. No maintenance switch must be activated. ZSI systems accomplish this by interconnecting inhibit signals between upstream main and downstream feeder breakers. Should a fault occur downstream of a feeder breaker, the feeder breaker sends an inhibit signal to the upstream main telling the main to wait and allow the feeder to clear the fault, if the feeder breaker sees the fault. The upstream main breaker maintains its time delays and remains closed during the fault. However, should a fault occur between the upstream main and the downstream feeder, the downstream feeder does not have any fault current flowing through it, so it does not send an inhibit signal to the upstream main. Consequently, the upstream main bypasses internal time delays and trips instantaneously. This reduces the arc flash incident energy released for faults that occur within electrical equipment between circuit breakers. Note that some manufacturers offer maintenance systems that manually disable the ZSI inhibit signal, essentially telling the upstream breaker to trip instantaneously during a fault. This does not provide improved arc flash reduction performance over a ZSI system, however, since a fault occurring between the main and feeder would trip the main instantaneously anyway. A better approach is to specify both ZSI and a true arc flash reduction maintenance system that utilizes the bypass analog circuit, which can trip the breaker faster than the instantaneous clearing time of the breaker. Bus differential schemes: These are coordinated zones of protection within an electrical system. When a fault occurs within a given zone of protection (i.e. between the main and feeder breakers), protective devices trip instantaneously, limiting arc flash durations while also confining arc flash damage to specific portions of your infrastructure. Bus differential systems are typically faster and more sensitive than ZSI systems, but require additional current transformers and relaying equipment. This tends to make bus differential systems more difficult to implement and more expensive than ZSI systems. Reduce arc flash currents Just as a shorter arc flash is less dangerous, the same is true (on a circuit breaker protected system 1 ) of an arc carrying a smaller amount of current. Among the many ways companies can reduce arc flash currents are these: 1 As discussed earlier, reducing current levels on systems protected by current limiting fuses can actually increase incident energy released during a fault.
6 Page 6 of 7 Current limiting reactors: Typically deployed in series with the three-phase conductors feeding the load, current limiting reactors restrict current under fault conditions. For example, low-voltage motor control centers can be supplied with three single-phase reactors that limit available short circuit current, resulting in a reduction of available arcing current during faults. High-resistance grounding systems: During ground faults, high-resistance grounding (HRG) systems provide a path for ground current via a resistance that limits current magnitude. That dramatically reduces the magnitude of line-to-ground faults and limits the scale of arc flash events. While HRG can be used on systems that service only three-phase loads, the US National Electrical Code prohibits using HRG on distribution systems providing loads that are connected line-to-neutral, as are most servers. This limits the practicality of an HRG system to the portion of a data center that powers cooling plants and other large three-phase loads. Reduce frequency of arc flash incidents Several technologies, including the following, can help data center managers decrease the likelihood of arc flash events happening at all: Predictive maintenance systems: Deteriorating insulation is the leading cause of arc-producing electrical failures. Identifying and repairing compromised insulation before it fails can help avert arc flash explosions. Predictive maintenance systems provide early warning of insulation failure in medium-voltage switchgear, substations, generators, transformers and motors. Remote monitoring, control and diagnostics software: With the help of power management systems, technicians can perform many administrative tasks remotely, rather than expose themselves to potential arc flash events. Power management applications also equip companies to remotely de-energize electrical equipment before data center personnel approach it. Figure 2: Power management software enables data center personnel to perform many tasks remotely rather than expose themselves to arc flash dangers.
7 Page 7 of 7 Erect protective physical barriers When all else fails, protective safety barriers offer vulnerable data center employees a critical last line of defense from the explosive power of arc flash incidents. Among the many varieties of such barriers are these: Arc-resistant switchgear: Properly-designed switchgear utilizes sealed joints, top mounted pressure relief vents, reinforced hinges and through-the-door racking to contain harmful gases and reduce injuries during arc flash explosions. Infrared windows: These allow technicians to complete thermal inspections of electrical switchgear without opening cabinets or doors. Leveraging their infrared thermography technology, operators can safely and quickly assess potential equipment problems without first de-energizing electrical circuits. Also, always keep equipment doors and access covers closed and fastened during normal operation, to keep arc flash energy contained. Conclusion Long common elsewhere in the world, 400V data centers are slowly gaining popularity in the U.S., at least partly because they eliminate 480V to 120V transformers and thus offer superior energy efficiency. Yet operating a data center at 400V poses arc flash risks far more severe than those found in a 120V data center. To protect their employees from disabling and even lethal injuries, organizations contemplating a move to 400V must carefully study the potential hazards and supply their people and facilities with appropriate PPE, circuit protective devices and training. By doing so, they will position themselves to enjoy all of the power-saving benefits 400V operation offers without needlessly endangering lives. For more information about arc flash hazards safety, visit About Eaton Eaton Corporation is a diversified power management company with 2009 sales of $11.9 billion. Eaton is a global technology leader in electrical components and systems for power quality, distribution and control; hydraulics components, systems and services for industrial and mobile equipment; aerospace fuel, hydraulics and pneumatic systems for commercial and military use; and truck and automotive drivetrain and powertrain systems for performance, fuel economy and safety. Eaton has approximately 70,000 employees and sells products to customers in more than 150 countries. For more information, visit About the author After receiving a BSEE from the University of Kentucky and his MSEE from the University of Pittsburgh, Dave Loucks has been serving the electrical industry for 31 years. He is a veteran with Eaton for 16 years and currently holds a position of PCM solutions manager. Dave has seven patents with one additional pending and is a senior member of the IEEE. Besides being certified as an Energy Manager by the Association of Energy Engineers, he is also a registered professional engineer in the Commonwealth of Pennsylvania. Tutorials on demand Download Eaton white papers to learn more about technology topics or explain them to customers and contacts. Maintenance bypass, paralleling, UPS topologies, energy management and more are demystified in complimentary white papers from our online library:
Data Center Forum. Forum focus: Arc Flash Safety in 400V Data Centers. Eaton's Global IT Newsletter Volume 5 Issue 3. Data Center Interactive
Eaton's Global IT Newsletter Volume 5 Issue 3. Data Center Forum Forum focus: Arc Flash Safety in 400V Data Centers IT Perspective Customer Voice Data Center Interactive Power through data center challenges.
Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer [email protected]. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer [email protected] Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
How to reduce exposure to arc flash hazards
GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not
Arc Flash Energy Mitigation Techniques
Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal
Fault Characteristics in Electrical Equipment
1. Introduction Proper design and installation of electrical equipment minimizes the chance of electrical faults. Faults occur when the insulation system is compromised and current is allowed to flow through
Distributed versus centralized power backup strategies
Distributed versus centralized power backup strategies Choosing the right UPS deployment architecture for your data center By Ed Spears Product Manager, Eaton Power Quality Solutions Operation Eaton Corporation
HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE
Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce
Optimizing Power Distribution for High-Density Computing
Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive
Arc Flash Mitigation & Selective Co-ordination
Arc Flash Mitigation & Selective Co-ordination Michael Hodder March 2015 Overview This seminar will provide information on: Mitigating arc flash hazards Selective Coordination What can we do to make these
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
Choosing the Best Solution for Reducing Arc Energy
CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors
Arc Flash Mitigation. Executive summary. by Antony Parsons, Ph.D., P.E.
by Antony Parsons, Ph.D., P.E. Executive summary Arc flash events can result in significant injury to workers, including severe burn injuries. The most effective arc flash safety programs are not those
Understanding Arc Flash
Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
What s up with Arc Flash?
What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition
Union County Public Schools. Facilities Department. Electrical. Safe Work Practices
1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County
Analyzing Electrical Hazards in the Workplace
Analyzing Electrical Hazards in the Workplace By Dennis K. Neitzel, CPE AVO Training Institute, Inc. The need for analyzing electrical hazards in the workplace has been recognized by a small segment of
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety
Safety By Design. Strategies for Electrical Contractors
Safety By Design Strategies for Electrical Contractors Introduction Engineering and system design significantly impact worker safety System design provides opportunity to eliminate/minimize workers exposure
INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010
ARC FLASH PROTECTION AND SAFETY MEASURES September 2010 Introduction Hazards of Electrical Energy Electrical Safety Program Safety-Related Work Practices Electrical Safety Procedures Presented By: Ken
Part 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
Increased power protection with parallel UPS configurations
Increased power protection with parallel UPS configurations Making the selection between Centralized Bypass and Distributed Bypass systems Janne Paananen Application Engineer, Large Systems Group Eaton
ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com]
ARC FLASH HAZARD MITIGATION ARC FLASH HAZARD MITIGATION NWHA TECHNICAL SEMINAR May 17, 2012 Richard D Reese Power Systems Manager Industrial Tests, Inc. Rocklin, California [[email protected]; 916-660-2837]
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,
Low Voltage Switchgear
Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering
Demystifying arc flash hazard management
Demystifying arc flash hazard management Presented by Matt Brazier Senior Electrical Engineer Gove Operations November 2013 Standard NFPA 70E IEEE 1584 AS/NZS 4836 TERMINOLOGY Arc arc flash hazard analysis
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.
Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible
Data Center Trend: Distributed Power in the White Space
Data Center Trend: Distributed Power in the White Space By Jason Anderson Product Line Manager Eaton Executive summary Cloud computing vendors and colocation data centers make every effort to maximize
Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection
Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection L. Kumpulainen, S. Dahl J. Ma Vamp Ltd, Finland Vamp Ltd, China 1 ABSTRACT This paper describes causes and characteristics
Electrical Safety in the Marine Environment
January 3, 2001 TEHNIAL BULLETIN 010 Electrical Safety in the Marine Environment Approach Boundaries Electrical Safety in the Marine Environment presented by adick orporation 1 Overview Electrical power
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? Comparing apples-to-apples bids Plant Services Special Report A shock hazard analysis should be included as part of an arc
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for
Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for data centers Executive Summary Every three years, the
ELECTRICAL SAFETY RISK ASSESSMENT
ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures
3053 Electrical Safety Training Program Course Outline
3053 Electrical Safety Training Program Course Outline The following outline summarizes the major points of information presented in the program. The outline can be used to review the program before conducting
ECE 586b Course Project Report. Auto-Reclosing
ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1
2008 Eaton Corporation. All rights reserved.
FlashGard TM Motor Control Center Electrical Safety Hazards Design Philosophy The Product 2008 Eaton Corporation. All rights reserved. Research studies say. Five to 10 arc flash explosions occur in electrical
Power Management for Server Virtualization
Power Management for Server Virtualization Strategies for preserving business continuity and data integrity in virtualized data centers By Hervé Tardy Vice President and General Manager Distributed Power
SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E
SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program
Arc Flash Safety Solutions
Overview Brochure Arc Flash Safety Solutions Aftermarket and Engineering Services Arc flash. The threat is real. An arc flash event releases a tremendous amount of energy in the form of thermal heat, toxic
Roadmap to Compliance with NFPA 70E Arc Flash Requirements
Roadmap to Compliance with NFPA 70E Arc Flash Requirements TAHFM Interlink 2015 March 30, 2015 Antony Parsons, Ph.D., P.E. Schneider Electric Engineering Services 1 2 How do we get to Reliable Power? >
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
New standardized approach to arc flash protection
New standardized approach to arc flash protection Samuel Dahl Juha Arvola Tero Virtala Arcteq Relays Ltd Arcteq Relays Ltd Arcteq Relays Ltd Wolffintie 36 F 11 Wolffintie 36 F 11 Wolffintie 36 F11 65200
misconceptions about arc-flash hazard assessments
misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.
NFPA 70E Updates Affect Your Most Valuable Assets
NFPA 70E Updates Affect Your Most Valuable Assets EXECUTIVE SUMMARY Electrocution is a well-known hazard associated with direct contact with electrical energy. According to the U.S. Department of Labor,
UL Validated Testing of Arc-Resistant Motor Control Centers
UL Validated Testing of Arc-Resistant Motor Control Centers Ensure Protective Features Perform as Designed Larry Sifers Account Manager Littleton, CO Siemens Industry June 1st - 3rd, 2011 Western Mining
ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.
ARC FLASH HAZARD OVERVIEW Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH EXPERIENCE Christopher J. DeWaal, MS, MEM, PE, LEED AP, HACCP How did I get involved? A client
Enhancing Personnel Safety with Arc Resistant Equipment
Enhancing Personnel Safety with Arc Resistant Equipment Carl Christian Power LV Offer Marketing Nashville, TN Sponsored by the Water Wastewater Competency Center 1 Enhancing Personnel Safety 5-10 Five
Power-Zone 4 Arc Resistant Low Voltage Switchgear
Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions
OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010
OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010 By: Martin Robinson, Level III Thermographer 18-1030-0005 Rev. A The National Fire Protection Association (NFPA)
RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA
RISK MITIGATION for ELECTRICAL WORK Feb 2013 San Diego CA Agenda I. RISK Define the Risks Arc Flash Review II. MITIGATION 3 Easy Steps New Designs Vs. Existing Systems III. DUKE UNIVERSITY EXAMPLE I. Risk
Modernizing Vintage Data Centers
Modernizing Vintage Data Centers Improving the reliability, efficiency and effectiveness of older computing facilities by upgrading their power and cooling systems By John Collins Segment Manager, Data
Circuit Breakers in Data Centers: The Hidden Danger
Circuit Breakers in Data Centers: The Hidden Danger How to efficiently protect critical IT equipment by choosing the most reliable overcurrent protection device for your Rack Power Distribution Unit. By
Arc Flash Avoidance and its Application to Overhead Traveling Cranes
Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it
Powering Converged Infrastructures
Powering Converged Infrastructures By Mike Jackson Product Manager Eaton Executive summary Converged infrastructures utilize virtualization and automation to achieve high levels of availability in a costeffective
The Application of Circuit Breakers to Reduce Downtime in Datacentres
The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the
The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS
The Other Hazard of Electricity Larren Elliott Ph.D. Lindsay Polic, CSP, REHS Presenters Larren Elliott Ph.D. EORM Electrical Safety Service Partner 45 years practical and hands-on industrial experience
Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System
Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Cory David Smith, Project Manager, ECOM Engineering Inc., and David Lawrence Smith, Principal, ECOM Engineering
A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS
A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS By: Gabriel Arce, ABB, San Luis Potosi, Mexico Casey McCollum, ABB, Houston, TX John
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS Claudio S. Mardegan [email protected] www.engepower.com Phone: 55 3579-8777
Alternative data center power
Alternative data center power A quantitative TCO comparison of 400V AC and 600V AC power systems Abstract Power efficiency has become a critical focus for IT and facilities managers as they struggle to
Maximizing UPS Availability
Maximizing UPS Availability A comparative assessment of UPS designs and deployment configurations for the highavailability data center By Chris Loeffler Product Manager, BladeUPS & Data Center Applications
Is an energy-wasting data center draining your bottom line?
Abstract Is an energy-wasting data center draining your bottom line? New technology options and power distribution strategies can dramatically reduce the cost and carbon footprint of your data center.
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
Introduction to Arc Flash
Introduction to Arc Flash Worker Training of Electrical Hazards Including Arc Flash SH-16614-7 This material was produced under grant number SH-16614-7 from the Occupational Safety and Health Administration,
THE reliability, cost, and safety of electricity and industrial
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 50, NO. 5, SEPTEMBER/OCTOBER 2014 1 The Journey of an Enterprise in a Process Industry Toward Improved Electrical Workplace Safety Greg M. Kemper, Senior
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application by Reza Tajali, P.E. Square D Company ABSTRACT In modern data centers, Uninterruptible Power Supplies (UPS)
3088 Lockout-Tagout Training Program Course Outline
3088 Lockout-Tagout Training Program Course Outline The following outline summarizes the major points of information presented in the course. The outline can be used to review the course before conducting
2012 NFPA 70E. Ten Most Important Changes. John A. DeDad
2012 NFPA 70E Ten Most Important Changes John A. DeDad GE Energy Management 41 Woodford Avenue Plainville, CT 06062 USA 860-747-7344 [email protected] Abstract The 2012 Edition of NFPA 70E, Standard for
Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering
LOW VOLTAGE CIRCUIT BREAKER GUIDELINES FOR DATA CENTERS Reliability requires consulting engineers and end users to grasp design, maintenance basics By Reza Tajali, P.E. Square D Power Systems Engineering
Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited
Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
Implementation of arc flash mitigating solutions at industrial manufacturing facilities
Thought leadership White paper Implementation of arc flash mitigating solutions at industrial manufacturing facilities David B. Durocher Senior Member, IEEE Global Industry Manager Eaton 26850 SW Kinsman
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software Abstract: The nature of explosive equipment failures, and the rate of serious burn injuries in the electrical industry
OSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance
OSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance deadlines require high-voltage facilities to take immediate
Mission Critical Data Center Systems
Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,
Sample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
Optimizing your Infrastructure for Cloud Computing
Optimizing your Infrastructure for Cloud Computing Best practices for managing a cloud IT environment By Chris Loeffler Data Center Applications Manager, Distributed Power Solutions Eaton Corporation Executive