Primary and Secondary Electrical Distribution Systems
|
|
|
- Geraldine Thompson
- 10 years ago
- Views:
Transcription
1 Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products
2 Utility Considerations Capacity Voltage and Sources Size of Metering Equipment Relaying Requirements Station Batteries
3 Utility Metering Requirements Dictated by the Utility EUSERC (as a reference) 15 kv: 48 W x 72 to 96 D 21 kv: 60 W x 96 D 38 kv: 72 W x 129 D
4 115 kv Substation Service (Approximately 80 by 75 )
5 Types of Systems Radial Primary-Selective Radial Loop-Primary Selective Secondary Selective Sparing Transformer Spot Network
6 Simple Radial System Simple, least costly Easy to coordinate No idle parts
7 Radial System
8 Primary and Secondary Radial
9 Loop Primary Radial Secondary
10 Loop Switching Substation Transformer
11 Loop Switching Pad Mount Transformer
12 Primary Selective Radial System Duplex or selector switch Spare primary incoming circuit Duration of outage from cable failure limited
13 Primary Selective Secondary Radial
14 Duplex Selector Switch
15 Selector Switch Single Structure
16 Secondary Selective System Normally operated as two electrically independent substations with tie breaker open Failure of either primary circuit affects only one bus Service restored by opening dead bus main and closing tie Operation can be made automatic Transformers not paralleled so fault currents similar to radial
17 Two-Source Primary Secondary Selective
18 Sparing Transformer System Alternative to Double-Ended Substations Single Common Backup Transformer Service restored by opening dead bus main and closing tie Operation can be made automatic Transformers not paralleled so fault currents similar to radial Location of substations limited (must be clustered)
19 Sparing Transformer
20 Spot Network Transformers paralleled on the secondary side Uses network protectors If primary voltage fails, associated protector automatically opens Other protector remains closed No dead time on bus, even momentarily Upon voltage restoration automatically synchronizes and re-closes Improved voltage regulation Secondary fault current increased
21 Spot Network
22 Primary Equipment Air Terminal Chamber Metal-Clad Switchgear Circuit Breaker and Relays Metal-Enclosed Switchgear Switch and Fuse Others (Reclosers and Interrupters)
23 Metal-Clad Switchgear Defined in ANSI C as metal enclosed power switchgear Removable (draw-out) type switching and interrupting devices Connect and disconnect position Major parts of the switchgear enclosed by grounded metal barriers for compartmentalization Automatic shutters that cover primary stabs or studs All primary bus conductors and connections covered with insulation material throughout
24 Protective Relays (ANSI Device Numbers) 27 - Undervoltage 47 - Phase sequence 49 - Thermal overload 50 - Instantaneous 51 - Time overcurrent 59 - Overvoltage 63 - Sudden pressure 67 - Directional overcurrent 86 - Lockout 87 - Differential
25 Metal-Enclosed Interrupter Switchgear Defined in ANSI C as metal-enclosed power switchgear Interrupter switches Power fuses (current limiting or non-current limiting) Bare bus and connections Instrument transformers Control wiring and accessory devices
26 Power Fuse Coordination Expulsion Inverse-time Easier to coordinate Current Limiting Steep straight line More difficult to coordinate
27 Pad Mounted Transformer Switching and Fusing LBOR Switch Oil Interruption Rated 200, 300, 400 A Isc = 12 ka Current Limiting and Expulsion Fuses Limited Sizes
28 Transformers
29 Unit Substation Transformers through 20,000 kva Maximum 69 kv Primary Maximum 34.5 kv Secondary Bushings wall mounted Part of a substation lineup Can be custom designed to meet custom dimensions
30 Padmount Transformers Up to 5,000 kva Maximum 34.5 kv Primary Maximum 600 V Secondary Weather resistant high and low voltage compartments Tamper-resistant Design No Fan Cooling Available 6
31 Network Transformers kva Maximum 34.5 kv Primary Maximum 600 V Secondary Used in areas of high load density Designed for use in a secondary network system in either subway or vault applications.
32 Dry Versus Liquid Transformers Dry No fluid to spill or burn Cost is higher than oil Resistant to moisture and chemical contamination Minimum maintenance UL Listing is available Liquid Lowest purchase price Hermetically sealed tank for harsh environments Lowest losses per purchase dollar Best balance of design properties- dielectric, thermal, and cost UL Listing is available
33 Liquid Filled Technology Benefits Lowest Purchase Cost Lowest Loss Per Purchase Dollar Ability to operate in adverse conditions Excellent Dielectric Properties Smaller Footprint Better losses Options available for Safety- Related and Environmentally Sensitive Applications
34 Dry Type Technology Benefits Environmentally Safe Non-flammable Minimal Maintenance Coordination Flexibility Higher Fan Cooled Rating
35 Comparison of Transformer Costs Liquid Filled Transformers Mineral Oil (Outdoor) 1.00 Vegetable Oil (Indoor/Outdoor) 1.20 Silicone (Indoor/Outdoor) 1.35 Pad Mounted 5% Less than Substation Design Dry Type Transformers Vacuum Pressure Impregnated 1.25 Vacuum Pressure Imp. - Epoxy 1.35 Cast Coil 1.55 to 2.0 Lower Temperature Rise 15% to 35% Outdoor Add 20%
36 Loss Evaluation I 2 R Losses = Total Losses (TL) - No Load Losses (NL) I 2 R Losses are proportional to the Load Factor Squared Load Factor = Actual Load kva/rated Base kva Operating Losses = No Load Losses + I 2 R Losses at the appropriate Load Factor
37 Loss Evaluation Example Losses in watts for a 1000 kva oil-filled transformer: 1,800 watts no load losses 15,100 watts full load losses Load losses are approximately 13,300 watts (15,100 1,800) At 0% load: 1,800 watts At 50% load: 1,800 watts + (13,300)(.5) 2 = 1,800 watts + 3,325 watts = 5,125 watts At 100% load: 1,800 watts + 13,300 watts = 15,100 watts At 110% load: 1,800 watts + (13,300)(1.1) 2 = 1,800 watts + 16,093 watts = 17,893 watts
38 Auxiliary Fan Cooling Liquid filled transformers Fan cooling - 15% (750 kva to 2000 kva) Fan cooling - 25% (2500 kva and above) Dry type transformers Fan cooling - 33% (All ratings)
39 Environment Maximum altitude 1000 m (3300 feet) Rating reduced 0.3% to 0.5% for each 100 m (330 feet) above that altitude Indoor and outdoor designs available Ambient 30 degree C (86 degree F) average over 24 hours 40 degree C (104 degree F) maximum
40 Transformers - Liquid Filled Insulation systems (Oil, Silicone, Vegetable Oil) Temperature rise 55 degree C 65 degree C Efficiency - 99% Overload capacity - ANSI C37.92 Auxiliary devices Temperature gauge Liquid level gauge Pressure vacuum gauge Sudden pressure relay Pressure relief device
41 Transformers - Dry type Insulation systems Varnish Polyester Silicone Epoxy Design types Dip and bake VPI Cast coil Insulation classes Class H 220 degree C Class F 185 degree C Class B 150 degree C
42 Transformers - Dry Type Temperature rise 150 degree C 115 degree C 100 degree C (epoxy) 80 degree C Efficiency 97% to 98% (typical) 99% (low temperature rise) Overload capacity - ANSI C57.96 Auxiliary devices Temperature gauge
43 Secondary Neutral Grounding Solid Grounding Impedance Grounding Low resistance High resistance Reactance
44 Secondary Equipment Air terminal chamber Busway Low voltage switchboard Molded Case Circuit breakers Metal-Enclosed Switchgear Low voltage Power circuit breakers
45 Low-Voltage Switchboards (UL891) Versus Metal-Enclosed Switchgear (UL1558)
46 Paralleling Switchgear
47 Low-Voltage Switchboards (UL891) Versus Metal-Enclosed Switchgear (UL1558) Molded Case Circuit Breakers (UL489) Insulated Case Circuit Breakers (UL489) Power Circuit Breakers (UL1066) Front Access or Rear Access Drawout or Fixed Mounted Manually or Electrically Operated
48 Low-Voltage Circuit Breaker Types Molded Case Circuit Breakers Tested in accordance with UL489 & Nema AB-1 Open Air Test - 80% (Optional 100%) Over Toggle Mechanism Sealed Case - Not Maintainable Applied in Switchboards/Panelboards Insulated Case Circuit Breakers Tested in accordance with UL489 & Nema AB-1 Open Air Test - 80% or 100% 2-Step Stored Energy Mechanism Sealed Case - Not Fully Maintainable Applied in Switchboards Power Circuit Breakers Tested in accordance with UL1066 & ANSI C37 Tested in the Enclosure - 100% 2-Step Stored Energy Mechanism Open Access - Fully Maintainable Applied in Metal-Enclosed Draw-out Swgr
49 Low-Voltage Circuit Breaker Typical Ratings Molded Case Circuit Breakers Frame Size: 100 through 3000 ampere Interrupting: 10/35/65/ Volts Limiters Available: 200 kaic Instantaneous: 10-13X Frame various X/R Insulated Case Circuit Breakers Frame Size: 400 (800) through 5000 ampere Interrupting: 65/85/ Volts Limiters Not Normally Available Inst./Short Time: 25/35/65 various X/R Power Circuit Breakers Frame Size: 800 through 5000 ampere Interrupting: 65/85/ Volts Limiters Available: 200 kaic Short Time: 35/65/85/100 X/R of 6.6
50 TCC with Power Circuit Breakers MCCB- 200A MCCB- 50A PCB- 2400A PCB- 800A PCB 2400 amp 480V, Microprocessor Trip, LS Frame size: 3200 A Sensor: 2400 LTPU: 1.0 f(s) = 2400 amp STPU: 5.0 f(s) = amp LTD: 7.00 sec. STD:.3 sec. No Instantaneous Trip PCB 800 amp 480V, Microprocessor Trip, LS Frame size: 800 A Sensor: 800 LTPU: 1.00 f(s) = 800 amp STPU: 5.0 f(s) = 4000 amp LTD: 7.00 sec. STD:.1 sec. No Instantaneous Trip MCCB 200 amp 480V, Microprocessor Trip, LSI Frame size: 250 A Trip: 200 A Inst. PU: 10.0*T = 2000 A MCCB 50 amp 480V, Thermal-Magnetic Trip Frame size: 100 A Trip: 50 A Inst. PU: Non adjustable
51 Maintenance - MCCBs and ICCBs Enclosed design requires little maintenance Terminal connections and trip units tightened to the proper torque values Inspect conductors Visually inspect and operate periodically Replacement parts are not available Repair, refurbishment, or remanufacture not recommended - replace damaged breakers
52 Maintenance - PCBs Designed to be serviced Replacement parts are available (contacts, pole assemblies, arc chutes) Inspection and maintenance program is recommended Keep it dry, keep it clean, keep it tight
53 Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products
STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS
STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS David D. Roybal, P.E. Senior Member, IEEE Cutler-Hammer, Inc. 3697 Mount Diablo Boulevard Lafayette,
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Atlanta Chapter IEEE Industry Applications Society
Atlanta Chapter IEEE Industry Applications Society Electrical Equipment Room Design Considerations presented at the Sheraton Buckhead Hotel Atlanta, Georgia November 20, 2006 Outline 1. Definitions 2.
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
Alternate Methods to Short Circuit Breaker Coordination
Alternate Methods to Short Circuit Breaker Coordination Nguyen Perez, PE Senior Electrical Engineer 2600 Douglas Road, Suite 301 Coral Gables, Florida 305.529.1515 (p) www.brplusa.com Importance in Healthcare
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
Fusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
This section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Primary Electric Distribution for Industrial Plants
PDH Course E242 Primary Electric Distribution for Industrial Plants Adolph A. Biss, P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
Sample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
Contents. Description. Product Selection Guide
.1 Medium Voltage Switchgear Introduction Indoor Type VCP-W Metal-Clad Switchgear Assembly (5/15 kv shown) Product Selection Guide Product Offering Chart Metal-Enclosed Contents Description Notes Additional
Choosing the Best Solution for Reducing Arc Energy
CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.
Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
Evaluating Fire- and Heat-Damaged Electrical Equipment
Evaluating Fire- and Heat-Damaged Electrical Equipment www.nema.org 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to heat
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT NETWORK SYSTEMS SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT NETWORK SYSTEMS SECTION SPECIFICATION EO-2022 REVISION 15 DECEMBER 2009 EFFECTIVE DATE DECEMBER
Extend the Life of Existing Switchgear
Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...
SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009
A Comparison of Contemporary Electrical Distribution Equipment Standards San Francisco IEEE Industry Applications Society May 26, 2009 What are Standards? Clearly defined performance characteristics Based
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
Step Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
GUIDELINES FOR WATER-DAMAGED ELECTRICAL EQUIPMENT
GUIDELINES FOR HANDLING WATER-DAMAGED ELECTRICAL EQUIPMENT NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION 1300 NORTH 17 TH STREET, SUITE 1752 ROSSLYN, VIRGINIA 22209 703 841-3200 703 841-5900 FAX WWW.NEMA.ORG
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical www.nema.org Evaluating Water-Damaged Electrical 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings
SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR
METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. 1.02 RELATED
Low Voltage Switchgear
Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering
4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS
4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED MEDIUM VOLTAGE
Switchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR
COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR Copyright Material IEEE Paper No. PCIC 2003-13 Eddie Wilkie Eaton Cutler-Hammer 3990 Old Tasso Road NE Cleveland, TN 37312 USA Abstract
Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application by Reza Tajali, P.E. Square D Company ABSTRACT In modern data centers, Uninterruptible Power Supplies (UPS)
Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy.
Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00 Answers for energy. Unit substation solution with type SIMOSEC primary switches, dry-type transformer
Schneider Electric Services: life-cycle solutions for electrical distribution equipment. Scopes of Work for Electrical Acceptance Testing
Scopes of Work for Electrical Acceptance Testing Schneider Electric Services: life-cycle solutions for electrical distribution equipment Make the most of your energy SM Scopes of Work for Electrical Acceptance
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics
LVA Take Offs in Bid Manager
Electrical Sales and Distributor Training Low Voltage Assemblies (LVA) LVA Take Offs in Bid Manager This job aid helps to define some of the common selection questions that are encountered when configuring
SERVICE-LIFE EVALUATIONS OF LOW-VOLTAGE POWER CIRCUIT BREAKERS AND MOLDED-CASE CIRCUIT BREAKERS
SERVICE-LIFE EVALUATIONS OF LOW-VOLTAGE POWER CIRCUIT BREAKERS AND MOLDED-CASE CIRCUIT BREAKERS Michael J Sprague Member, IEEE Cutler-Hammer, Inc. 130 Commonwealth Drive Warrendale, PA 15086 USA Abstract
MEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED
MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED CCG Facilities Integration Incorporated
Tmax MCCBs. Molded case circuit breakers. Tmax
Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high
Data Center Solutions. Envirotran HDC Transformers Deliver Superior Reliability and Efficiency for Substantial Savings Everyday
Data Center Solutions Envirotran HDC Transformers Deliver Superior Reliability and Efficiency for Substantial Savings Everyday Data Center Solutions As the demand for data centers grows, the industry s
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
Learning Module 13: Panelboards and Switchboards. 101 Basic Series
Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and
TRANSFORMER DICTIONARY
TRANSFORMER DICTIONARY AUTOTRANSFORMER A transformer that has only one winding per phase; part of the winding is shared between the primary and secondary CONDITION New - All materials and components are
Engineers Edge, LLC PDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior
261000 Medium Voltage Electrical Distribution
Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
Overview Brochure Integrated Power Distribution. Medium Voltage Assembly Solutions
Overview Brochure Integrated Power Distribution Medium Voltage Assembly Solutions Medium voltage assembly solutions Eaton, a premier leader in manufacturing power distribution and power protection equipment
Power Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
The following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
SECTION 16322 SUBSTATION TRANSFORMERS
SUBSTATION TRANSFORMERS PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install the primary and/or secondary substation transformers as specified herein and as shown on the contract
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium
Transfer switch BTPC open, closed or delayed transition
Transfer switch BTPC open, closed or delayed transition 150-4000 Amp Description The Cummins Power Generation BTPC series bypass isolation transfer switch combines an automatic transfer switch with a drawout
SWITCHGEAR. EGP Switchgear
SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all
Transfer Equipment Controls
Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment
Safety By Design. Strategies for Electrical Contractors
Safety By Design Strategies for Electrical Contractors Introduction Engineering and system design significantly impact worker safety System design provides opportunity to eliminate/minimize workers exposure
Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
Medium Voltage Motor Control Assemblies
Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................
Masterclad Medium Voltage Passive Arc-Resistant Switchgear
Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand
Application of Four-Pole Circuit Breakers within Data Centers
Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1
MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
Introduction. Upon completion of Basics of Electrical Products, you should be able to:
Table of Contents Introduction... 2 Siemens Industry, Inc... 4 Electric Power... 5 Residential Applications... 10 Commercial Applications... 20 Industrial Applications... 37 Manufacturing Applications...
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety
Part 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
Product overview brochure. ABB Medium Voltage Products Our one-stop approach for every medium voltage application
Product overview brochure ABB Medium Voltage Products Our one-stop approach for every medium voltage application Overview ABB meets every need for reliable, safe and energy-efficient medium voltage switchgear,
SECTION 16999 ELECTRICAL ACCEPTANCE TESTS
SECTION 16999 ELECTRICAL ACCEPTANCE TESTS PART 1 2. AND 3. COMBINED 1.1 SUMMARY A. Description of Systems 1. Furnish all labor, materials, test equipment, and technical supervision to perform and record
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software Abstract: The nature of explosive equipment failures, and the rate of serious burn injuries in the electrical industry
How to reduce exposure to arc flash hazards
GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not
ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet
ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before
OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F
OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
FEDERAL ELECTRICITY & WATER AUTHORITY
UNITED ARAB EMIRATES FEDERAL ELECTRICITY & WATER AUTHORITY SPECIFICATION FOR 433 VOLTS SWITCHGEARS (LVAC BOARD) LVAC SWITCHBOARDS I N D E X CLAUSE TITLE 1. GENERAL 2. TEMPERATURE RISE 3. BUSBARS 4. CONSTRUCTION
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
Advantages of Fixed Circuit Breaker Switchgear
Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker
32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw
,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted
Motor Protection Voltage Unbalance and Single-Phasing
Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions
01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety
PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it
Minimizing Impact of Electric Utility Outages with Backup Generation
Minimizing Impact of Electric Utility Outages with Backup Generation Introduction of the Speaker Michael Dempsey, PE Senior Electrical Engineer Carter & Burgess, Inc. Energy & Power Solutions Facility
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at