1 Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details of Service 4.0 Deliverables 5.0 Exclusions 6.0 Scope of Responsibility 7.0 Project Work Details 8.0 Pricing 9.0 Terms & Conditions The APC Data Center Power and Cooling Assessment Service provides an assessment and analysis of your data center facility and critical physical infrastructure components including the power systems, cooling systems, and rack configurations. APC will supply you with the information necessary to manage your facilities for optimum performance, extend the life of your hardware and strive for the highest level of network availability. The APC Data Center Power and Cooling Assessment Service offer a detailed review of your data center. APC professional services consultants will visit the site and collect data pertaining to: Environmental conditions Critical infrastructure capacity and utilization Cooling distribution and effectiveness Condition of power and cooling equipment With this data, APC will develop a comprehensive report that will include recommendations to: Address your specific concerns Correct deficiencies Optimize existing conditions Increase infrastructure capabilities Extend data center service life 2.0 Features & Benefits Features Comprehensive Data Center Power and Cooling Assessment Report. Measurement of existing environmental conditions. Measurement of the data center electrical infrastructure loads. Measurement of present temperature conditions using thermal imaging. Recommendations to optimize infrastructure utilization. Benefits Data center power and cooling utilization analysis identifies key infrastructure constraints that inhibit full space utilization. Indicates areas where temperature and humidity levels are not within tolerances established by industry standards and equipment manufacturers. Provides an accurate assessment of the actual data center power and heat loads; identifies excessive load conditions that can compromise existing reliability. Provides visual representation of excessive rack inlet temperatures and other potential hot spots within the data center. Identifies methods to maximize availability and the efficient use of power, cooling and space.

2 3.0 Details of Service The specific activities of this service are listed below. For each activity, APC will perform the work described. Activities Data Center Electrical Infrastructure Review Document Existing UPS and Configuration Document UPS Capacity and Utilization Document Static Transfer Switch Configuration Data Center Load Analysis Data Center Power Description Document nameplate data, manufacturer and configuration of the data center bulk power distribution equipment to include: main switchgear, switchboards, generator(s), automatic transfer switch (ATS) and other equipment as applicable. Identify redundancy of power distribution system. Perform a visual inspection of data center electrical equipment including: switchboard, generator(s), ATS, uninterruptible power supply (UPS) and UPS power distribution infrastructure, checking for improper installation practices, damaged equipment, and labeling of circuits. Review available maintenance records for the data center electrical equipment including: switchboard, generator(s) and ATS, and provide recommendations, where applicable, to improve practices. Document the generator fuel supply system and storage capacity. Document configuration, existing condition and nameplate data of the UPS and UPS power distribution infrastructure. Document configuration, existing condition and nameplate data of the battery system. Record input and output load measurements taken at the UPS. Identify and record preferred and alternate sources, document load readings, identify load balance and load transfer capabilities. Record, interpret and analyze displayed load values from metered power distribution units (PDU). Interpret and analyze measured load data collected from the data center, load panel boards taken during the assessment.

3 Activities Computer Room Air Conditioning (CRAC) System Characterization and Analysis Record Data Center Temperature and Humidity Levels Rack Analysis Infrared Thermography Air Distribution Effectiveness Data Center Cooling Description Visually assess the Computer Room Air Conditioning (CRAC) units. Check for general conditions, improper installation practices, damaged equipment and improper use. Identify the system type (i.e. direct expansion, water based or dry cooler, upflow or downflow) and document equipment manufacturer and model number. Document the rated capacity (based upon nameplate data and manufacturer nominal ratings) of the CRAC unit(s). Record and analyze supply and return temperatures, humidity, set points and operational modes to determine environmental conditions and where demand fighting may occur. Record and document room temperature levels to ensure that they are within ranges established by equipment manufacturers and recognized industry standards. Record average hot aisle and cold aisle temperatures. Identify conditions outside of recognized industry standards. Identify where air mixing is likely to occur and where blanking panels should be installed. Examine rack enclosures for airflow suitability. Identify airflow obstructions within, above, and below the rack environment. Detect and document areas where rack inlet temperatures exceed industry standards and guidelines using infrared thermography. Analyze rack arrangements for air distribution effectiveness. Identify the air distribution topology within the computer room. Evaluate the air distribution topology effectiveness relative to the computer room heat load. Measure airflow and temperature of the raised-floor air distribution system and overhead supply grills (if accessible). Identify possible obstructions and restrictions. Compare to nominal equipment nameplate data.

4 Deliverable Customer Identified Site Specific Issues Infrastructure Summary and Recommendations Data Center Electrical Infrastructure Analysis Data Center Electrical Distribution Analysis Data Center Cooling Infrastructure Analysis Data Center Cooling Distribution Analysis Data Center Analysis and Report Description Provide analysis and recommendations to address and correct customer specific issues within the data center using industry best practices. Provide a data center summary and recommendations to optimize the existing data center according to industry best practices. Provide a simplified one-line diagram from the main data center switchboard or separately derived source to critical load distribution panels, including transfer switches, UPSs, and generators. Tabulate and analyze the bulk power system within the data center. Provide recommendations where applicable. Determine bulk power utilization and identify limiting factors for increased power density within the data center. Project future growth load potential and analysis based on actual load measurements. Provide recommendations, where applicable, to optimize the operation and utilization of the generator infrastructure. Tabulate and analyze power distribution within the data center. Provide recommendations where applicable. Determine power distribution utilization and identify limiting factors for increased power density within the data center. Tabulate and analyze the bulk cooling distribution within the data center. Determine the bulk cooling utilization and identify limiting factors for increased power density within the data center. Report conditions that compromise bulk cooling effectiveness, where applicable, and provide recommendations to correct problems. Document and analyze the cooling distribution within the data center. Provide a cooling distribution floor plan of the data center identifying rack inlet air temperatures and tile airflow and temperature data, if applicable. Report conditions that compromise cooling distribution effectiveness, where applicable and provide recommendations to correct problems. Provide a floor plan of the existing data center depicting average hot and cold aisle temperatures, and raised floor supply tile airflow rates and temperature readings.

5 Deliverable Data Center Load Constraint Analysis Facilities Analysis Recommendations For Data Center General Recommendations Data Center Analysis and Report (cont.) Description Provide analysis of the infrastructure constraints and how the constraints limit increased data center loads. Document general facilities information. Provide a floor plan of the existing data center. If a floor plan is provided by the customer, it will be validated and updated as necessary to reflect the current operations. Provide analysis, scenarios and recommendations to optimize infrastructure utilization and availability. Provide power, cooling and infrastructure recommendations for each scenario. Provide conceptual floor plan depicting equipment layout for each recommended scenario. Provide general observations and recommendations for the data center infrastructure not covered in other sections of the report.

6 4.0 Deliverables APC will deliver a comprehensive data center assessment report to the customer that includes: Recommendations for specific actions addressing customer concerns. General recommendations to improve power, cooling and facility utilization. Identifying problem areas based on analysis performed using digital photography, thermal imaging, and actual field measurements. Tabular data collected from all the activities defined in Section 3.0, Details of Service. Three (3) hard copies and a PDF of the final report. An optional follow-up conference call to review the report and answer questions. 5.0 Exclusions The following items are outside the scope of this standard service offering. They can be integrated into a customized Statement of Work (SOW) at request of the customer. Contact an APC sales representative for more details. Specialized testing or commissioning Fire detection and fire suppression Physical security Structural analysis Circuit Tracing

7 6.0 Scope of Responsibility The items stated here are responsibilities of both APC and the customer. 6.1 APC RESPONSIBILITIES Assign a Professional Services Fulfillment Manager to the case. Initiate a meeting to: Review the assessment process and deliverables. Establish project stakeholders and key contacts. Review the Assessment Preparation Questionnaire to identify customer specific existing conditions and issues in the data center. Schedule an assessment and manage the complete assessment process through the APC Professional Services office. Perform an assessment of the customer site. Provide a written report to the customer of the completed field survey. 6.2 CUSTOMER RESPONSIBILITIES Complete and return the Assessment Preparation Questionnaire. This will identify issues or problems in the data center needing specific, detailed analysis and recommendations. Provide qualified personnel to take electrical panel readings on the day the APC Professional Services consultant performs the assessment. Provide qualified personnel for physical access to the data center, all infrastructure support areas and electric panels to be surveyed. These areas include, but are not limited to, the power systems within the data center and those feeding the data center from outside. Access to data center power systems will include: Generator. Service entrance. Uninterruptible power supplies. Breaker panels. Access to the internal and external cooling system components within the data center. Floor panel removal and sub-floor access. Provide building infrastructure one-line diagrams for the cooling and electrical systems, if available. Provide generator, switchgear, UPS and HVAC maintenance records, if available. Notify APC of any non-disclosure agreement, security clearance, safety or other certification requirements prior to arrival on site. Provide a single point of contact to assist during assessment.

8 7.0 Project Work Details The following details of the project specify the schedule, location and successful completion criteria. 7.1 SCHEDULE 1. All onsite services performed by APC are executed during the normal business hours of Monday through Friday from 8:00AM to 5:00PM, local time. Exceptions are national or provincial holidays. Services performed outside of normal working hours may incur additional charges. 2. The service will be scheduled as quickly as possible at the convenience of the customer. Delays in fulfilling the service caused by labor disputes of third parties, customer contracted services, or other unforeseen conditions may affect the schedule. APC will not be responsible for delays related to circumstances outside of its control. 7.2 ASSESSMENT PROCESS TIMELINE AND FLOW 1. Customer Purchase Order received by APC. 2. Assessment Preparation Questionnaire complete and returned to APC. 3. Site assessment scheduled with customer through APC Professional Services office. 4. Meet with IT, facility management and APC representative to coordinate site visit. 5. Site assessment performed at the customer location. 6. Customer Site Assessment Report completed. The actual and specific dates are not contracted due to the variability in each unique site assessment and analysis. 7.3 LOCATION The location of this project will be onsite. It will be discussed and approved by APC and the customer. 7.4 COMPLETION CRITERIA APC is expected to have finished its written duties when any of the following occurs: 1. APC completes all the items described in Section 4.0, Deliverables of this SOW. 2. This project and SOW are terminated for other reasons, within the APC customer agreement.

9 8.0 Pricing Part Number: QWPADCPC-MISC Pricing for the Data Center Power and Cooling Assessment varies depending on data center size, equipment, power capacity, cooling capacity, available existing documentation and location of the data center. To receive a price quote for your application, please visit or contact your APC sales representative. 9.0 Terms and Conditions APC standard Terms and Conditions apply. The information provided in this SOW cannot be used or duplicated, in full or in part. Other uses for this document are prohibited without written consent from APC. All documentation, photographs, thermal imaging or other information provided by the customer, or gathered at the customer site, will be for internal APC use only and used solely for the purpose of report generation, analysis and recommendations All rights reserved. All APC trademarks are property of American Power Conversion. Other trademarks are property of their respective owners. Specifications are subject to change without notice. Disclaimer: This information is reliable at the point of creation and may be subject to change.

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical

More information

Statement Of Work Professional Services

Statement Of Work Professional Services Statement Of Work Professional Services Data Center Cooling Analysis using CFD Data Center Cooling Analysis Using Computational Fluid Dynamics Service 1.0 Executive Summary Table of Contents 1.0 Executive

More information

Statement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

Statement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary Statement Of Work Professional Services Data Center Thermography Assessment Data Center Thermography Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits

More information

Statement Of Work Professional Services

Statement Of Work Professional Services Statement Of Work Professional Services Data Center Electrical Efficiency Assessment Data Center Electrical Efficiency Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0

More information

Energy Management Services

Energy Management Services February, 2012 Energy Management Services Data centers & IT environments are often critical to today s businesses, directly affecting operations and profitability. General & Mechanical Services has the

More information

DATA CENTER ASSESSMENT SERVICES

DATA CENTER ASSESSMENT SERVICES DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Cisco Data Center Facilities Assessment Service

Cisco Data Center Facilities Assessment Service Cisco Data Center Facilities Assessment Service Increase the availability, capacity, and life of your data center facility. Service Overview Data centers must respond to changing business needs, environmental

More information

Statement of Work. 1.0 Executive Summary. 2.0 Features & Benefits. Service. Software Education Service. Table of Contents

Statement of Work. 1.0 Executive Summary. 2.0 Features & Benefits. Service. Software Education Service. Table of Contents - 1 - StruxureWare TM for Data Centers Management Software Administrator Training Statement of Work StruxureWare TM for Data Centers Management Software Administrator Training Software Education Service

More information

Maintenance Service 1.1 ANNUAL PREVENTIVE MAINTENANCE 1.2 ON-SITE REMEDIAL SERVICES

Maintenance Service 1.1 ANNUAL PREVENTIVE MAINTENANCE 1.2 ON-SITE REMEDIAL SERVICES Maintenance Service Statement of Work 1.0 Executive Summary - 1 - UPS/PDU Advantage Ultra UPS/PDU Advantage Ultra Service Service Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details

More information

IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009

IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009 IT Cost Savings Audit Information Technology Report Prepared for XYZ Inc. November 2009 Executive Summary This information technology report presents the technology audit resulting from the activities

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.)

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) Felipe Visbal / March 27, 2013 HPPR Data Center Technologies Team Services Data Centers: Thermal Assessments

More information

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy

More information

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009 Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of

More information

Data center upgrade proposal. (phase one)

Data center upgrade proposal. (phase one) Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The

More information

LEVEL 3 DATA CENTER ASSESSMENT

LEVEL 3 DATA CENTER ASSESSMENT Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

HP Data Center Services

HP Data Center Services HP Data Center Services HP Technology Services - Per Event Services Technical data Enterprise-class data center facility infrastructures need to support both current IT objectives and new equipment and

More information

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms By Neil Rasmussen White Paper #49 Executive Summary Avoidable mistakes that are routinely made when installing cooling

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent

More information

Australian Government Data Centre Strategy 2010-2025

Australian Government Data Centre Strategy 2010-2025 Australian Government Data Centre Strategy 2010-2025 Better Practice Guide: Data Centre Power June 2013 17/06/2013 4:12 PM 17/06/2013 4:12 PM Contents Contents 2 1. Introduction 3 Scope 3 Policy Framework

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015

Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015 Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

Prediction Is Better Than Cure CFD Simulation For Data Center Operation.

Prediction Is Better Than Cure CFD Simulation For Data Center Operation. Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.

More information

Data Center Power Consumption

Data Center Power Consumption Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling

More information

Design Best Practices for Data Centers

Design Best Practices for Data Centers Tuesday, 22 September 2009 Design Best Practices for Data Centers Written by Mark Welte Tuesday, 22 September 2009 The data center industry is going through revolutionary changes, due to changing market

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs

Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level

More information

1.1 ANNUAL PREVENTIVE MAINTENANCE VISIT

1.1 ANNUAL PREVENTIVE MAINTENANCE VISIT Maintenance Service - 1 - Lead Acid Battery Frame On-Site Warranty Statement of Work 1.0 Executive Summary Lead Acid Battery Frame On-Site Warranty Service Service Table of Contents 1.0 Executive Summary

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,

More information

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus. DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure

More information

Using CFD for optimal thermal management and cooling design in data centers

Using CFD for optimal thermal management and cooling design in data centers www.siemens.com/datacenters Using CFD for optimal thermal management and cooling design in data centers Introduction As the power density of IT equipment within a rack increases and energy costs rise,

More information

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

The Pros and Cons of Modular Systems

The Pros and Cons of Modular Systems The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated

More information

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do?

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? 1 Thank you for attending today s session! Please let us know your name and/or location when you sign in We ask everyone to

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information

FNT EXPERT PAPER. // Data Center Efficiency AUTHOR. Using CFD to Optimize Cooling in Design and Operation. www.fntsoftware.com

FNT EXPERT PAPER. // Data Center Efficiency AUTHOR. Using CFD to Optimize Cooling in Design and Operation. www.fntsoftware.com FNT EXPERT PAPER AUTHOR Oliver Lindner Head of Business Line DCIM FNT GmbH // Data Center Efficiency Using CFD to Optimize Cooling in Design and Operation Energy is the biggest cost factor with the highest

More information

- 1 - StruxureWare TM Data Center Expert Periodic Maintenance. Software Integration Service. 1.0 Executive Summary. 2.0 Features & Benefits

- 1 - StruxureWare TM Data Center Expert Periodic Maintenance. Software Integration Service. 1.0 Executive Summary. 2.0 Features & Benefits Statement of Work - 1 - StruxureWare TM Data Center Expert Periodic Maintenance StruxureWare Data Center Expert Periodic Maintenance Software Integration Service Service 1.0 Executive Summary Table of

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

Increasing Data Center Efficiency through Metering and Monitoring Power Usage

Increasing Data Center Efficiency through Metering and Monitoring Power Usage White Paper Intel Information Technology Computer Manufacturing Data Center Efficiency Increasing Data Center Efficiency through Metering and Monitoring Power Usage To increase data center energy efficiency

More information

How to Meet 24 by Forever Cooling Demands of your Data Center

How to Meet 24 by Forever Cooling Demands of your Data Center W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the

More information

Five Nines and Infrared (IR) Testing at Data Centers

Five Nines and Infrared (IR) Testing at Data Centers Five Nines and Infrared (IR) Testing at Data Centers By Gregory R. Stockton 99.999% uptime five nines. That is what IT (information technology) customers are looking for. Uptime or availability at data

More information

Energy Efficiency and Availability Management in Consolidated Data Centers

Energy Efficiency and Availability Management in Consolidated Data Centers Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal

More information

Analysis of the UNH Data Center Using CFD Modeling

Analysis of the UNH Data Center Using CFD Modeling Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,

More information

Applications for Infrared Thermography at Computer Centers

Applications for Infrared Thermography at Computer Centers Applications for Infrared Thermography at Computer Centers By Eric Stockton CompuSCANIR, a division of Stockton Infrared Thermographic Services, Inc. 8472 Adams Farm Road Randleman, NC 27317 http://www.compuscanir.com/

More information

Reducing Data Center Energy Consumption

Reducing Data Center Energy Consumption Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate

More information

Strategies for Deploying Blade Servers in Existing Data Centers

Strategies for Deploying Blade Servers in Existing Data Centers Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200

More information

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

OPERATOR - FACILITY ADDRESS - DATE

OPERATOR - FACILITY ADDRESS - DATE . Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.

More information

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC

Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: info@itisltd.co.uk www.itisltd.com Introducing Computational

More information

Network-critical Physical Infrastructure (NCPI) Vulnerability Assessment

Network-critical Physical Infrastructure (NCPI) Vulnerability Assessment Network-critical Physical Infrastructure (NCPI) Vulnerability Assessment Explanation: Network-critical physical infrastructure (NCPI) is the foundation upon which IT networks reside. It consists of power,

More information

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer

More information

Center Thermal Management Can Live Together

Center Thermal Management Can Live Together Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots

More information

Using thermal mapping at the data centre

Using thermal mapping at the data centre Technical Using thermal mapping at the data centre by Gregory Stockton, CompuScanIR.com Cooling the servers in data centres efficiently is critical to increasing IT reliability, maintaining high performance,

More information

How Row-based Data Center Cooling Works

How Row-based Data Center Cooling Works How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that

More information

Imperial College 3 March 2009 Green Data Centers: An Overview

Imperial College 3 March 2009 Green Data Centers: An Overview Imperial College 3 March 2009 Green Data Centers: An Overview Updated: 26 Feb 09 LBNL s Data Center findings Benchmarking Efforts Energy Reduction Approaches Green Data Centers: An Overview 2 Scenarios

More information

Best Practices, Benefits and Economics of Load Testing IEEE PES Fort Worth, TX Chapter July 16, 2013

Best Practices, Benefits and Economics of Load Testing IEEE PES Fort Worth, TX Chapter July 16, 2013 Best Practices, Benefits and Economics of Load Testing IEEE PES Fort Worth, TX Chapter July 16, 2013 Mark Siira ComRent International 1 8/1/2013 Agenda Introduction Overview of Load Bank Testing Benefits

More information

Introducing AUDIT- BUDDY

Introducing AUDIT- BUDDY Introducing AUDIT- BUDDY Monitoring Temperature and Humidity for Greater Data Center Efficiency 202 Worcester Street, Unit 5, North Grafton, MA 01536 www.purkaylabs.com info@purkaylabs.com 1.774.261.4444

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

PX100 MBP with Configurable Distribution

PX100 MBP with Configurable Distribution PX100 MBP with Configurable Distribution High-performance, right-sized, 3-phase power protection with industry-leading efficiency, availability, and performance for small and medium data centers July 2012

More information

BRUNS-PAK Presents MARK S. EVANKO, Principal

BRUNS-PAK Presents MARK S. EVANKO, Principal BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations

More information

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that

More information

Boosting the Energy efficiency of a Server Room: experimental + virtual approach.

Boosting the Energy efficiency of a Server Room: experimental + virtual approach. Boosting the Energy efficiency of a Server Room: experimental + virtual approach. Nowadays, the increase in computing power allows the successful applications of the CFD simulation methods in civil environments.

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

Measure Server delta- T using AUDIT- BUDDY

Measure Server delta- T using AUDIT- BUDDY Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because

More information

ASX ITS Co-location Hosting Solution

ASX ITS Co-location Hosting Solution ASX ITS Co-location Hosting Solution Introduction The Australian Securities Exchange (ASX) is proposing to offer a Co-location hosting service to its Market Participants that will facilitate DMA and Algorithmic

More information

ISOMEDIA COLOCATION WWW.ISOMEDIA.COM/COLOCATION

ISOMEDIA COLOCATION WWW.ISOMEDIA.COM/COLOCATION ISOMEDIA COLOCATION WWW.ISOMEDIA.COM/COLOCATION Your business needs a robust infrastructure that is secure, cost effective and reliable in order to remain competitive in today s market. ISOMEDIA s colocation

More information

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich

More information

Reduce the cost and delays associated with troubleshooting with the help of round-the-clock Service Desk Support.

Reduce the cost and delays associated with troubleshooting with the help of round-the-clock Service Desk Support. Remote Support Reduce the cost and delays associated with troubleshooting with the help of round-the-clock Service Desk Support. SERVICE DEFINITION: REMOTE SUPPORT SERVICES ITI s Remote Support Service

More information

EMC PERSPECTIVE Managing Energy Efficiency in the Data Center

EMC PERSPECTIVE Managing Energy Efficiency in the Data Center EMC PERSPECTIVE Managing Energy Efficiency in the Data Center A tactical approach can deliver immediate problem resolution plus long-term savings and efficiencies Managing Energy Efficiency in the Data

More information

Security+ Guide to Network Security Fundamentals, Fourth Edition. Chapter 13 Business Continuity

Security+ Guide to Network Security Fundamentals, Fourth Edition. Chapter 13 Business Continuity Security+ Guide to Network Security Fundamentals, Fourth Edition Chapter 13 Business Continuity Objectives Define environmental controls Describe the components of redundancy planning List disaster recovery

More information

How to Build a Data Centre Cooling Budget. Ian Cathcart

How to Build a Data Centre Cooling Budget. Ian Cathcart How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options

More information

Data Center Energy Efficiency. SC07 Birds of a Feather November, 2007 Bill Tschudi wftschudi@lbl.gov

Data Center Energy Efficiency. SC07 Birds of a Feather November, 2007 Bill Tschudi wftschudi@lbl.gov Data Center Energy Efficiency SC07 Birds of a Feather November, 2007 Bill Tschudi wftschudi@lbl.gov Benchmark results helped to find best practices The ratio of IT equipment power to the total (or its

More information

Statement of Work. - 1 - Server Migration & Cable Management. Installation Services. Table of Contents. 1.0 Executive Summary. 2.0 Features & Benefits

Statement of Work. - 1 - Server Migration & Cable Management. Installation Services. Table of Contents. 1.0 Executive Summary. 2.0 Features & Benefits Installation Services Statement of Work - 1 - Server Migration & Server Migration & Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details of Service

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

Essential NCPI Management Requirements for Next Generation Data Centers

Essential NCPI Management Requirements for Next Generation Data Centers Essential NCPI Requirements for Next Generation Data Centers By Ted Ives White Paper #14 1 Executive Summary The management of physical infrastructure in data centers can no longer be considered independently

More information

11 Top Tips for Energy-Efficient Data Center Design and Operation

11 Top Tips for Energy-Efficient Data Center Design and Operation 11 Top Tips for Energy-Efficient Data Center Design and Operation A High-Level How To Guide M e c h a n i c a l a n a l y s i s W h i t e P a p e r w w w. m e n t o r. c o m When is Data Center Thermal

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information