Using the WAGO 750-340 PROFINET Coupler as Remote I/O with a Siemens S7 PLC



Similar documents
Accessing EtherNet/IP Network Variables in a WAGO with a ControlLogix PLC Application note

Remote Connection to a WAGO using a High-Speed Internet connection Application note

Configuration a Profibus-DP node using Step7 and WAGO-I/O components Application note

WAGO-I/O-SYSTEM in ABB robot control systems Application note

Ethernet/IP Comms between a WAGO and a Mettler Toledo JAGXTREME Terminal Application note

WAGO PFC 750-8xx Interface to Horner HMI Application note

Transmitting s in a local network with a WAGO CONTROLLER Application note

Ethernet PFC Sending Application note

Transmitting s with the WAGO IPC Application note

Connect Ethernet-Controller to TO-PASS web portal via GPRS-Router Application note

Using the SysLibFile.lib and the WagoLibFtp.lib for file access Application note

WAGO PFC as a MODBUS MASTER Application note

Sending / receiving SMS using a GSM modem Application note

Using library WagoLibMySQL to communicate with MySQL-Databases Application note

Application Note. WAGO EtherNet/IP Communications with a CompactLogix PLC Using Explicit Messaging. A500620e, English Version: 1.0.

Application note. A103202, English Version 1.0.1

Transmitting s with the library "WagoLibMail_02.lib" Application note

WAGO-I/O-SYSTEM. Using library WagoLibMSSQL_03.lib in CoDeSys 2.3 for interface to Microsoft SQL Server 200x. Application Note

EtherNet/IP communications between a WAGO PFC and a SICK IVC-2D Camera Application note

PROFINET IRT: Getting Started with The Siemens CPU 315 PLC

Modular I/O System ETHERNET StarterKit Quick Start ETHERNET Fieldbus Controller

1 Application Description Objective Goals... 3

PROCESS AUTOMATION PLANNING AND INTEGRATION INFORMATION LB8106* Integration in Siemens SIMATIC PCS 7

Service & Support. How can you establish a connection between an S PLC and SIMATIC NET OPC? S PLC, SIMATIC NET OPC.

CPU PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU PN/DP: Configuring an ET 200S as PROFINET IO device

WinCC. Communication Manual. Manual 2. This manual is part of the documentation package with the order number: 6AV6392-1CA05-0AB0 C79000-G8276-C156-01

Service & Support. How can you establish a connection between a S PLC and SIMATIC NET OPC? S PLC, SIMATIC NET OPC.

How-To-Do. Hardware Configuration SLIO CPU 014

TECHNICAL NOTE TNOI34

How-To-Do. EtherCAT Communication with CPU 300S

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE A5 Programming the CPU 314C-2DP

ABB industrial drives. Quick start-up guide Drive Manager for SIMATIC

Cisco - Configure the 1721 Router for VLANs Using a Switch Module (WIC-4ESW)

Modular I/O System Quick Start for WAGO-I/O-IPC /000-xxx Features

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODUL E04

PROFINET CPU 314C-2 PN/DP, PN/DP, PN/DP, PN/DP: Configuring the PROFINET interface

FAQ Communication over IE

Flexi Soft Ethernet IP: Implicit Messaging with a Omron PLC

8/23/13 Configuring the S7 Server for Windows NT 4.0 to Access S7-400 PLCs via the Siemens CP1613 Card for ISO (Industrial Ethernet)

LOGO! LOGO! App V.10. LOGO! app 1. Making basic settings and establishing a connection to LOGO! Using the device overview 3. Creating controls 4

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

SIMATIC NET. CP AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

HTML Code Generator V 1.0 For Simatic IT Modules CP IT, IT, IT

Applications & Tools. Configuration of Messages and Alarms in WinCC (TIA Portal) WinCC (TIA Portal) Application description December 2012

Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library. Deleting program block Main [OB1] Copying program blocks

Configuring the SST DeviceNet OPC Server

Adding a Modbus TCP Device to the Network. Setting Up Your Network

In this lab you will explore the Windows XP Firewall and configure some advanced settings.

Beckhoff TwinCAT. Configuring the TwinCAT I/O System

1-Port Wireless USB 2.0 Print Server Model # APSUSB201W. Quick Installation Guide. Ver. 2A

EZ-ZONE RMA & EtherNet/IP Configuration & Startup Using an Allen-Bradley CompactLogix PLC EtherNet/IP Fundamentals

IGSS. Interactive Graphical SCADA System. Quick Start Guide

Manual TC3 PLC HMI. TwinCAT 3. Version: Date: Order No.: TF1800

S7 for Windows S7-300/400

Lab - Configure a Windows XP Firewall

Application example and brief instruction 04/2015. LOGO! App V3.0. LOGO! 8 and LOGO! 7

L5354 ControlNet Communications Interface

Job Scheduler User Guide IGSS Version 11.0

THE KNX IP CONTROLLER. Taking Proven Technology to the Next Level

Profinet to EDV111 Series LED Signs Siemens Function Block Software Manual

Cover sheet PROFINET IO. SIMATIC MV440 Code Reading System. FAQ February Service & Support. Answers for industry.

Getting Started - SINAMICS Startdrive. Startdrive. SINAMICS Getting Started - SINAMICS Startdrive. Introduction 1

FINS Gateway For OMRON PLCs

WinCC Runtime Professional Readme SIMATIC HMI. WinCC V11 SP1. Readme WinCC Runtime Professional. Special considerations for Windows 7.

8/23/13 Configuring the S7 I/O Server for Windows 95 to Access S7 PLCs Via the Profibus Network

BECKHOFF. Application Notes. BC9000: Getting Started Guide. For additional documentation, please visit.

WAGO Software CODESYS Library WagoLibDiagnosticIDs.lib for accessing the internal diagnostics protocol

Anybus OPC Server. Application Note. Doc.Id. SCM Rev HMS Industrial Networks AB

Intel Active Management Technology with System Defense Feature Quick Start Guide

USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: Rev 6

Lab - Configure a Windows 7 Firewall

The goal is to program the PLC and HMI to count with the following behaviors:

1 Application Description System Topology Hardware and Software Requirements... 3

1 How configure S7 PLC in the configuration tool

Validity 1. Installation 2 SIMATIC. WinCC flexible Tag simulator Update 1. Readme

Application Note Profinet Modules

GE Proficy Machine Edition Profibus/Profinet SARTUP GUIDE

Cover sheet. Reading out the topology data of a PROFINET IO system SFB52 "RDREC" FAQ September Service & Support. Answers for industry.

Quick Guide: Troubleshooting Info from SNAP PAC Systems

AC 800M. EtherNet/IP DeviceNet Linking Device LD 800DN. Power and productivity for a better world TM SP1134

ebus Player Quick Start Guide

Siemens AG. SIMATIC S7 Ethernet 04/

Ethernet Interface Manual Thermal / Label Printer. Rev Metapace T-1. Metapace T-2 Metapace L-1 Metapace L-2

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE E05

Sharpdesk V3.5. Push Installation Guide for system administrator Version

S7-1500/S7-1500F Technical Data

Tutorial: Configuring GOOSE in MiCOM S1 Studio 1. Requirements

User Manual. Onsight Management Suite Version 5.1. Another Innovation by Librestream

ENPS-MF1. 1 USB Port. Multifunctional Print Server. Quick Installation Guide V1.0

xlogic App from Easy Electronic-Overview

ACU-1000 Manual Addendum Replacement of CPM-2 with CPM-4

QuickPanel Control DeviceNet Master Communications Card (IC754DVNM01) Quick Start Guide. Thursday September 20, 2007

SIMATIC. S7 300 PLC CPU 317T-2 DP: Controlling a virtual axis. Introduction. Preparation. Learning units 3. Further information 4.

Creating the project and hardware. TIA Portal. SIMATIC Creating the project and hardware. Introduction to the TIA Portal 1. Creating a project

EPSON Scan Server & EPSON TWAIN Pro Network

Pulse Redundancy. User Guide

TeamViewer Manual Wake-on-LAN

Downloading Driver Files

MDM Mass Configuration Tool User s Manual

Smart Control Center. User Guide. 350 East Plumeria Drive San Jose, CA USA. November v1.0

Transcription:

Using the WAGO 750-340 PROFINET Coupler as Remote I/O with a Siemens S7 PLC, English Version 1.0.0

2 General Copyright 2007 by WAGO Kontakttechnik GmbH & Co. KG All rights reserved. WAGO Kontakttechnik GmbH & Co. KG Hansastraße 27 D-32423 Minden Phone: +49 (0) 571/8 87 0 Fax: +49 (0) 571/8 87 1 69 E-Mail: info@wago.com Web: http://www.wago.com Technical Support Phone: +49 (0) 571/8 87 5 55 Fax: +49 (0) 571/8 87 85 55 E-Mail: support@wago.com Every conceivable measure has been taken to ensure the correctness and completeness of this documentation. However, as errors can never be fully excluded we would appreciate any information or ideas at any time. We wish to point out that the software and hardware terms as well as the trademarks of companies used and/or mentioned in the present manual are generally trademark or patent protected.

Table of Contents 3 TABLE OF CONTENTS 1 Important comments...4 1.1 Legal principles...4 1.1.1 Copyright...4 1.1.2 Personnel qualification...4 1.1.3 Intended use...4 1.2 Range of validity...5 1.3 Symbols...5 2 Description...6 3 Reference Material...6 4 Solution...7 4.1 Configure the S7 PLC in the STEP 7 HW-Configuration...8 4.2 Install the WAGO 750-340 GSD File...15 4.3 Configure the WAGO 750-340 in the STEP 7 HW-Configuration...17 4.4 Assign a Device Name to the WAGO 750-340...23 4.5 Download the hardware configuration to the S7 PLC...25 4.6 Testing the WAGO 750-340 in the ONLINE Mode...27

4 Important comments 1 Important comments 1.1 Legal principles 1.1.1 Copyright To ensure fast installation and start-up of the units described in this manual, we strongly recommend that the following information and explanation is carefully read and adhered to. This manual is copyrighted, together with all figures and illustrations contained therein. Any use of this manual which infringes the copyright provisions stipulated herein, is not permitted. Reproduction, translation and electronic and photo-technical archiving and amendments require the written consent of WAGO Kontakttechnik GmbH & Co. KG. Non-observance will entail the right of claims for damages. 1.1.2 Personnel qualification 1.1.3 Intended use The use of the product detailed in this manual is exclusively geared to specialists having qualifications in PLC programming, electrical specialists or persons instructed by electrical specialists who are also familiar with the valid standards. WAGO Kontakttechnik GmbH & Co. KG declines all liability resulting from improper action and damage to WAGO products and third party products due to non-observance of the information contained in this manual. For each individual application, the components supplied are to work with a dedicated hardware and software configuration. Modifications are only admitted within the framework of the possibilities documented in the manuals. All other changes to the hardware and/or software and the non-conforming use of the components entail the exclusion of liability on part of WAGO Kontakttechnik GmbH & Co. KG. Please direct any requirements pertaining to a modified and/or new hardware or software configuration directly to WAGO Kontakttechnik GmbH & Co. KG.

Important comments 5 1.2 Range of validity 1.3 Symbols This application note is based on the stated hardware and software of the specific manufacturer as well as the correspondent documentation. This application note is therefore only valid for the described installation. New hardware and software versions may need to be handled differently. Please note the detailed description in the specific manuals. Danger Always observe this information to protect persons from injury. Warning Always observe this information to prevent damage to the device. Attention Marginal conditions must always be observed to ensure smooth operation. ESD (Electrostatic Discharge) Warning of damage to the components by electrostatic discharge. Observe the precautionary measure for handling components at risk. Note Routines or advice for efficient use of the device and software optimization. More information References to additional literature, manuals, data sheets and INTERNET pages

6 Description 2 Description The purpose of this application note is to provide a step-by-step example of interfacing a Siemens S7 PLC with PROFINET Scanner to the WAGO 750-340 PROFINET Coupler. 3 Reference Material This procedure has been tested with, but is not limited to, the following hardware and software: Siemens CPU315F-2 PN/DP Processor/PROFINET Scanner Siemens SIMATIC Manager STEP 7 Software, Version V5.3 + SP3, Rev K5.3.3.0 gsdml-v2.0-wago-series750_753-20070115.xml (PROFINET GSD File) WAGO 758-500 5-Port Ethernet Switch WAGO PROFINET Node consisting of: WAGO 750-340 PROFINET Coupler 750-402 4Ch 24VDC Digital Input Module (4 Bits Digital Inputs) 750-504 4Ch 24VDC Digital Output Module (4 Bits Digital Outputs) 750-467 2Ch 0-10VDC Analog Input Module (2 Words Analog Inputs) 750-550 2Ch 0-10VDC Analog Output Module (2 Words Analog Outputs) 750-600 End Module

Solution 7 4 Solution This document assumes that you have an overall understanding of the Siemens S7 hardware and software. It focuses on the basics of configuring the WAGO 750-340 PROFINET Coupler in the STEP 7 HW-Configuration tool. After the hardware configuration is complete, the WAGO 750-340 is available for use as distributed I/O in a STEP 7 project. This procedure is divided into the following steps: Configure the S7 PLC in the STEP 7 HW-Configuration Install the WAGO 750-340 GSD file Configure the WAGO 750-340 in the STEP 7 HW-Configuration Assign a Device Name to the WAGO 750-340 in the STEP 7 HW- Configuration Download the hardware configuration to the S7 PLC Test the WAGO 750-340 in the ONLINE mode of the STEP 7 HW- Configuration

8 Solution 4.1 Configure the S7 PLC in the STEP 7 HW-Configuration In this section the Siemens CPU315F-2 PN/DP Processor/PROFINET Scanner is added to the STEP 7 HW-Configuration. The PROFINET scanner is assigned an IP address and a PROFINET subnet is created. Launch SIMATIC Manager and create a new project.

Solution 9 In the New Project dialog box enter the name of the project. Example: S7_PN_AppNote Click OK. The project name appears in the project organizer.

10 Solution Right-click on the project name and select Insert New Object > SIMATIC 300 Station from the menu list as shown below. The project organizer is displayed.

Solution 11 Right-click on SIMATIC 300(1) and select Open Object. The HW Config window appears. Select the menu command Insert > Insert Object... From the list select SIMATIC 300 > RACK-300 > Rail.

12 Solution An empty station grid is displayed. The components of the local PLC rack need to be added to the grid, which in this case includes a power supply and the CPU. Right-click on Slot 1 and select Insert Object... Then select the power supply for your system. Right-click on Slot 2 and select Insert Object. Then select the model and version of the CPU.

Solution 13 A Properties dialog box is displayed for defining the Ethernet interface. Enter the IP address and Subnet mask of the PROFINET Scanner. When this is complete, click New... Another Properties dialog box is displayed for defining a new subnet. Enter a name for the PROFINET network, such as ProfiNet1 and click OK. Click OK a second time to exit the Properties window.

14 Solution The S7 PLC and PROFINET scanner are now configured in the STEP 7 HW- Configuration. The SIMATIC Manager will display a network similar to the one shown below:

Solution 15 4.2 Install the WAGO 750-340 GSD File A GSD file (Generic Station Description), which is supplied by the device manufacturer, contains a description of the PROFINET device. A GSD file provides a simple way to import a device s profile into a PROFINET configuration tool, like the STEP 7 HW-Configuration tool. The current revision of the WAGO 750-340 GSD file is named gsdml-v2.0- wago-series750(753)-20060703.xml. This file can be obtained from the download area of the WAGO website (www.wago.com) or by contacting WAGO Technical Support. To stall the WAGO 750-340 GSD file in STEP 7 HW-Configuration, select the menu command Options > Install GSD file.

16 Solution The following dialog box appears. Click Browse and navigate to the folder where the WAGO 750-340 GSD file is stored. Select the GSD file in the list box and click Install. After successfully installing the WAGO 750-340 GSD file, its profile is available for the STEP 7 HW-Configuration tool.

Solution 17 4.3 Configure the WAGO 750-340 in the STEP 7 HW- Configuration In this section, the WAGO 750-340 PROFINET Coupler is added to the STEP 7 HW-Configuration. WAGO I/O modules are then added to the configuration in the order in which they are physically located in the node. Click on the PROFINET network. Then right-click on it to bring up the menu shown below. Select the menu command Insert Object

18 Solution From the menu, select Additional Field Device. A list of installed devices is displayed. Select the 750-340 V01.00.xx. The WAGO 750-340 is added to the network as shown below. Right-click on the WAGO node and select Object Properties.

Solution 19 A Properties dialog box is displayed. The default Device Name and Device Number are displayed for the WAGO 750-340. The STEP 7 HW- Configuration automatically generates these values from the device profile. These values can be change if desired. Click OK to continue. Note: All devices on an Ethernet subnet must have a unique Device Name. The Device Names must also satisfy DNS naming conventions. Note: The STEP 7 HW-Configuration automatically assigns an IP address to the WAGO 750-340. Starting with the IP address of the IO controller, STEP 7 HW-Configuration searches for the next available IP address.

20 Solution Next the STEP 7 HW-Configuration tool is used to assign the I/O modules in the WAGO 750-340 PROFINET node. All modules are entered in the order in which they are physically located in the node. Click on the WAGO node. The I/O grid for the WAGO 750-340 is displayed at the bottom of the screen. Right-click on slot 1 and select Insert Object...

Solution 21 Select the 750-340 > Digital Input Module > 75x-402 4DI(+4 BIT 1) Note: There are two parts that start with the 75x-402 part number. The 75x- 402 4DI (+4Bit 0) is used when 75x-402 module starts a new byte in the input process image. This module only uses the first 4 bits of the byte. If a second 75x-402 module is needed, the 75x-402* 4DI (-4Bit 0) part is used. This part serves as a placeholder and fills-in the last 4 bits of the existing byte. Right-click on slot 2 and select Insert Object... Then select the 750-340 > Digital Output Module > 75x-504 4DO(+4 Bit 0). Right-click on slot 3 and select Insert Object... Then select the 750-340 > Analog Input Module > 75x-467 2AI, 0-10V. Right-click on slot 4 and select Insert Object... Then select the 750-340 > Analog Output Module > 75x-550 2AO, 0-10V.

22 Solution When all the I/O modules are added, the grid should appear as below: The addresses of the I/O modules are automatically assigned and displayed in the grid. These addresses can now be use in the S7 project. Input Process Image Map Input Device 750-402 Channel 1 I 0.0 750-402 Channel 2 I 0.1 750-402 Channel 3 I 0.2 750-402 Channel 4 I 0.3 750-467 Channel 1 IW 256 750-467 Channel 1 IW 258 IEC-61131 Address Output Process Image Map Output Device 750-504 Channel 1 Q 0.0 750-504 Channel 2 Q 0.1 750-504 Channel 3 Q 0.2 750-504 Channel 4 Q 0.3 750-550 Channel 1 QW 256 750-550 Channel 1 QW 258 IEC-61131 Address Note: Only the modules that produce or consume data should be added to the I/O grid. Some modules, such as the 750-600 end module and some power feed modules, do not send or receive data. Modules such as these should not be included in the I/O grid.

Solution 23 4.4 Assign a Device Name to the WAGO 750-340 The Assign device name dialog box is used to assign a Device Name to a remote I/O device. This dialog box displays all devices available on the Ethernet subnet along with their IP address (if available) and their MAC address, as well as the device type determined online. In the STEP 7 HW-Configuration select the WAGO 750-340 node by clicking on it. Then select PLC >Ethernet > Assign Device Name from the menu.

24 Solution The device name for the selected WAGO 750-340 node is displayed in the Device name list box (in the example below the device name is also called WAGO 750-340 ). To assign this configuration to a physical device, select the physical device from the Available devices list, and click the Assign Name button. Click Close when complete.

Solution 25 4.5 Download the hardware configuration to the S7 PLC In this section the STEP 7 HW-Configuration tool is used to download the offline configuration to the S7 PLC. In the STEP 7 HW-Configuration window, select the menu command PLC > Download. The Select Target Module dialog box is displayed. Select the device type from the Target modules list and click OK.

26 Solution The Select Node Address dialog box is displayed. Changes can be made to the target station if required. Click OK to continue. A Download dialog box is displayed showing the progress of the download. When the download is complete, the dialog box disappears.

Solution 27 4.6 Testing the WAGO 750-340 in the ONLINE Mode The STEP 7 HW-Configuration can be used in ONLINE mode to test the IO configuration. To start ONLINE mode, select the menu command Open ONLINE. Select WAGO 750-340 node by clicking on it. Then right-click on module you want to monitor or control. For this example, right-click on slot 1, the WAGO 750-402, and select Monitor/Modify

28 Solution The Monitor/Modify dialog box displays the inputs of the 750-402 module in table format. Click on the Status Value button to refresh the screen. The digital input and output modules are displayed in binary format and analog modules are in word format.

Solution 29

WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 D-32385 Minden Hansastraße 27 D-32423 Minden Phone: 05 71/8 87 0 Telefax: 05 71/8 87 1 69 E-Mail: info@wago.com Internet: http://www.wago.com