Reduce data center PUE using Munters innovative cooling solutions

Size: px
Start display at page:

Download "Reduce data center PUE using Munters innovative cooling solutions"

Transcription

1 d a t a center applica t i o n guide Reduce data center PUE using Munters innovative cooling solutions

2 Reduce data center energy costs by up to 75% Traditional refrigeration cooling systems are an inefficient means of rejecting heat from modern data centers. With Munters Oasis Indirect Air-Side Economizer (IASE) and Wet-Bulb Economizer (WBE) products, the energy required to remove heat is significantly reduced. Munters systems use cooling/heat rejection strategies that achieve a balance of reliability and energy efficiency for data centers, some using as little as 20% of the cooling energy required by conventional cooling systems. In the last few years, several trends have emerged that have impacted the way that digital data are manipulated, stored and transmitted. There are three distinct trends: Tremendous increase in data transmitted, led by social networking, video, music, and voice transmission and cloud computing Ability of electronics to operate at higher temperatures Increase in IT equipment utilization by use of virtual computing which leads to greater power density per unit area of a data center These trends place a greater demand on data center cooling systems. However, the cooling process now occurs at higher inlet and outlet temperatures, resulting in the emergence of a new breed of cooling systems. Engineers have identified several new energy-efficient solutions to manage the thermal loads in data centers. Each strategy has pros and cons, but the biggest dilemma faced by engineers and clients is deciding which one to use. Munters simplifies this process by presenting the indirect air-side economizer, which has the potential to outperform current cooling strategies while offering some key system advantages. With over 35 years of experience with airto-air heat exchangers and evaporative cooling, Munters advanced cooling systems will provide the desired cooling results using significantly less energy than standard air conditioning. Munters offers custom system designs integrating DX, chilled water, indirect and direct evaporative and economizer cycles to meet the specific requirements of any facility. The indirect air-side economizer The indirect air-side economizer (IASE) 3 is a relatively new approach to data center heat rejection. It uses outdoor air to reject heat, with Current energy-efficient data center cooling options Air-side economizers (ASEs), where outdoor air is used for "free cooling" during favorable ambient conditions. ASE s complemented with direct evaporative cooling (DEC) for humidity control and operation over an extended envelope of ambient conditions, referred to as Wet-Bulb Economizers (WBEs) 1 Water-side economizers (WSEs), where cooling towers or fluid coolers are used in a variety of design configurations to reject some, or all of the heat from the data center in combination with, or without, chilled water or DX cooling 2 Combination air and water-side economizers (CAWEs) CAWEs complemented with DEC, referred to here as CAWE+D Liquid-cooled enclosures (LCEs), sometimes referred to as In-Row or In-Rack Cooling, where cool water produced from a combination of chillers and cooling towers, or refrigerant, is pumped to heat exchangers installed directly within the server racks the outdoor air never entering the process or white space. The Oasis IASE uses an air-to-air heat exchanger (HX) to transfer data center heat to a separate outdoor airstream ("scavenger air"). Figure 1 (page 3) shows details of one type of Munters Oasis IASE system that uses horizontal polymer-tube heat exchangers. With this design, outdoor scavenger air is drawn across the exterior of elliptical tubes, which are wetted by a recirculation water pump. The elliptical shape of the heat exchanger tubes maximizes the allowable surface area for heat rejection and is sufficiently elastic such that its subtle expansion and contractions, resulting from normal operation, aid in the shedding of residual solids that are a by-product of evaporation. With scavenger air flowing over the wet exterior tube surfaces, evaporative heat transfer efficiently cools the data center hot aisle air flowing through the inside of the tubes. Although only 45% to 51% effective when operating dry, when the outside of the polymertube HX is wetted it operates with 70% to 80% wet-bulb depression effectiveness (WBDE) as an indirect evaporative cooler. WBDE is a measure of the approach of the hot-aisle drybulb temperature to the outdoor air wet-bulb temperature. Using a 75% WBDE HX design, 100% of data center heat may be rejected solely using indirect evaporative cooling (IEC) if the following parameters exist: Ambient wet-bulb temperature is 66.2 F (19 C) or lower Hot aisle temperature (including recirculation fan heat) is F (38.6 C) The target cold aisle temperature is 75 F (23.9 C) 2 Data Center Application Guide

3 Figure 1: Oasis Indirect Evaporative Cooling System utilizing a polymer tube heat exchanger Scavenger Air Leaves System Exhaust/Scavenger Air Optional Condenser Coil Optional Compressor Vestibule Cooled Air is Ducted Back to Data Center for Heat Extraction Hot Aisle Return Air Scavenger Outside Air Optional Cooling Coil (DX or CHW) Cold Aisle Supply Air Hot Data Center Air Enters EPX Polymer Tube for Sensible Dry Cooling by the Evaporating Water Film on Tube Exterior Scavenger Air Flows Up and Around Outside of Tubes Having Extracted Heat from Air Flowing Inside Tubes Supply air temperature control Supply temperature is controlled on Oasis IASE systems by varying the scavenger airflow in combination with staging or modulating supplemental refrigeration as required. Scavenger fan motors are equipped with variable speed drives. When the ambient wet bulb is high, the scavenger fans run at 100% of design, to achieve maximum heat rejection. At cooler ambient conditions, the scavenger fans throttle back significantly, rejecting heat using a fraction of the power required at peak ambient wet bulb conditions. Supply fan speed control Supply fan motors on Oasis IASE units are equipped with Variable Speed Control such that the supply airflow from the units can closely match the airflow of the IT equipment fans. Too much air delivered into a contained rack system is wasteful, and too little air starves the IT fans, which can lead to hot spots. There are a variety of control algorithms currently being employed. Munters engineers work closely with the consulting engineers and customers to achieve the desired result. Side stream filtration A SSF system with MERV 13 filtration provides the necessary particulate removal in a more energy-efficient way compared to conventional air-handling designs. Figure 2 (page 6) For many data centers, the outdoor air (introduced by a separate makeup air system) is independently filtered with MERV 8 + MERV 13 filters. The removal of air filters within the Oasis IASE units relieves a burden of what is typically estimated at 1-inch wc (248.8 pa) of pressure drop from these heat rejection work horses. This results in a significant reduction in power consumption amounting to at least 1.65 kw/10,000 CFM (assumes fan static efficiency of 75% and motor efficiency of 95%). Since conventional air-side economizer units must utilize filtration (ASHRAE recommends MERV 8 + MERV 11 or 13 filters), the recirculating Munters Oasis IASE units installed at NV Energy in Las Vegas, Nevada air Oasis IASE heat rejection units consume less supply fan power than air-side economizer units because the air pressure drop through the polymer-tube HXs is typically less than 1-inch wc (248.8 pa). Data Center Application Guide 3

4 Worldwide effectiveness Other cities Percentage of annual hours in a typical year (TMY2) where IASE satisfies 100% of Data Cooling needs Percentage of Total Tonnage picked up by IEC during ASHRAE 0.4% WB Design Condition Seattle 99.1% 96.7% Los Angeles 92.8% 87.5% Boulder 99.3% 100.0% Mexico City 100.0% 100.0% Chicago 84.0% 70.1% Atlanta 65.7% 70.1% Toronto 90.2% 77.7% London 98.9% 94.6% Stockholm 99.7% 99.3% Rome 70.5% 65.0% Moscow 96.4% 90.0% Abu Dhabi 28.7% 43.5% Mumbai 11.2% 57.2% Shanghai 62.5% 54.5% Tokyo 73.6% 65.0% Salt Lake City 98.8% 96.4% Fort Worth 58.8% 67.5% Boston 86.5% 75.1% Brasilia 47.8% 85.0% Paris 95.8% 85.1% Berlin 97.2% 92.2% Barcelona 73.9% 70.2% Madrid 93.4% 84.8% Vienna 94.1% 89.8% Bejing 73.8% 65.0% Guangzhou 38.7% 57.2% Note TMY2: 100 F hot aisle, 75 F cold aisle Singapore 0.0% 59.8% Santiago 95.5% 92.0% São Paulo 57.3% 80.2% Johannesburg 98.0% 98.7% Sydney 76.8% 80.2% Auckland 92.8% 87.5% 4 Data Center Application Guide Data Center Application Guide 5

5 Makeup air and humidity control Humidity control within data centers is one of many concerns for design professionals. A dedicated outdoor air system (DOAS), that provides humidification and dehumidification as required, should be used in conjunction with Oasis IASE units, as indicated in Figure 2. Currently 0.25 air-changes-per-hour of ventilation air is recommended for data centers to prevent excessive build-up of VOCs and other pollutants that may be generated within the space. During cold, winter conditions, hotaisle air from the data center may be mixed with outdoor air, allowing for energy efficient adiabatic humidification. Using this method, no supplemental heat is required, since the heat for vaporization comes directly from the data center air. The preferred method of adiabatic humidification uses glass fiber wetted media and requires no special water treatment. Wetted media type humidifiers may be controlled by split-media staging or modulating face and bypass dampers around the evaporative media, as required to maintain room dew point at the lowest recommended level currently about 40 F (4.4 C). In humid climates, where ambient dewpoint frequently exceeds 65 F (18.3 C), it is recommended that the DOAS system include dehumidification capability. Dehumidification may be accomplished by inclusion of a DX or chilled water coil, or to achieve higher moisture removal efficiency, a waste heat reactivated desiccant or pre-cool air reheat system may be used. Dehumidification systems should be designed to deliver air at 45 F (7.2 C) dewpoint, or lower as required, such that room dewpoint may be controlled to 60 F (15.5 C) maximum using the minimum outdoor air delivered as the sole means for dehumidifying. Figure 2: Typical application of data center cooling and makeup air equipment. O/A MAKEUP AIR DEHUMIDIFICATION/ HUMIDIFICATION UNIT 0.25 ACH MIN OSA SCAVENGER OSA IN 100% RECIRCULATION AIR COOLING UNITS SFAN HX Q C C WINTER R/A SIDE-STREAM FILTRATION UNIT 6-10 ACH COLD AISLE SUPPLY HOT AISLE RETURN SERVER RACK 6 Data Center Application Guide

6 Benefits of Oasis indirect air-side economizer Filters may be eliminated from some or all of the heat rejection air-handing units (AHUs) because the data hall air is recirculated and cooled with the Oasis IASE systems without introducing outdoor air into the data center. Particulate removal may be accomplished by using a side-stream filtration unit, or filters may be included in a portion of the Oasis IASE units, such that the room air is filtered at a rate of perhaps 6 to 10 ACH, leading to reduced filter, maintenance, and fan power costs compared to installing filters on all of the heat rejection units, which often have air turnover rates in excess of 100 ACH. Reduced risk of outdoor air pollutants adversely affecting the IT equipment because no outdoor air is introduced into the space by the heat rejection units. Space humidity and pressure are not impacted, resulting in the potential to lower humidification costs and maintain more stable moisture levels in the data hall. Makeup air units, with MERV 8 and MERV 13 filters, equipped with dehumidification and humidification capability as required by the local climate, provide the recommended ventilation (0.25 ach has been recommended as the minimum) and humidity control. Humidification may be accomplished using direct evaporative media with heat from recirculated hot-aisle air. Decoupling the MUA function allows the Oasis IASE units to be optimized for one task: heat rejection. Unlike water-side and wet-bulb economizer systems, Oasis IASE systems may operate dry during cooler ambient conditions, resulting in lower annual water consumption and eliminating freeze concerns. During dry operation, Oasis IASE systems are able to achieve 100% heat rejection when outdoor air temperature is below 48.5 F (9.2 C) using HXs that are 50% effective, or 66.2 F (19 C), using HXs that are 75% effective (based on a hot aisle temperature of F (38.6 C), cooling to 75 F (23.9 C). Modulating mixed air dampers and relief fans/dampers are not required as part of the heat rejection cycle. Oasis IASE s require about one-third of the water flow rate of conventional water-side economizer systems, and operate with less pump head, resulting in significant annual pump power savings. When integrated with indirect evaporative cooling, refrigeration capacity may be significantly reduced on Oasis IASE systems in virtually all climates. Oasis IASE units have a rapid restart after power outage with little delay reaching full heat rejection potential. The Oasis IASE strategy is appli cable to data centers across the globe and is not limited for use in areas perceived to be cold or dry climates. The Oasis IASE strategy may be used even when cooler cold-aisle conditions are desired. The 100 F (37.8 C) hot-aisle and 75 F (23.9 C) cold-aisle conditions are solely a point of reference, since modern data centers are designed to similar or more aggressive conditions. Clearly, the maximum benefit of the Oasis IASE strategy is derived when implemented with hot- or cold-aisle containment, with warmer hot-aisle and warmer cold-aisle temperatures. 1 Scofield, M. and T. Weaver. Using Wet-Bulb Economizers, Data Center Cooling. ASHRAE Journal, August 2008: Yury, Y.L. Waterside and Airside Economizers, Design Considerations for Data Center Facilities. ASHRAE Transactions, Volume 116, Part 1, Dunnavant, K. Data Center Heat Rejection. ASHRAE Journal, March 2011: Data Center Application Guide 7

7 Munters locations Munters is a global leader in energy efficient air treatment solutions Using innovative technologies, our expert engineers create the perfect climate for customers in a wide range of industries, with the largest being food, pharmaceutical and data center sectors. Munters has been defining the future of air treatment since Today, manufacturing and sales are carried out in 30 countries by around 3,000 employees. Munters reports annual net sales in the region of SEK 4 billion and is owned by Nordic Capital Fund VII. For more information see Australia Munters Pty Limited, Phone , Fax , Austria via sales organization in Germany, Brazil Munters Brasil Industria e Comercio Ltda, Phone , Fax , China Munters Air Treatment Equipment (Beijing) Co., Ltd., Phone , Fax , Denmark via sales organization in Sweden, Finland Munters Oy, Phone , Fax , France Munters France S.A., Phone , Fax , Germany Munters Euroform GmbH, Phone , Fax , Indonesia Munters, Phone , Fax , Italy Munters Italy S.p.A., Phone , Fax , Japan Munters K.K., Phone , Fax , Kingdom of Saudi Arabia and Middle East Hawa Munters, c/o Hawa United Cooling Syst. Co. Ltd., Phone , Fax , Korea Munters Korea Co,. Ltd, Phone , Fax , Mexico Munters Mexico Phone , Fax , Norway via sales organization in Sweden, South Africa and Sub-Sahara Countries Munters (Pty) Ltd, Phone , Fax , Spain Munters Spain S.A., Phone , Fax , Sweden Munters Europe AB, Phone , Fax , Switzerland via sales organization in Germany, Thailand Munters (Thailand) Co. Ltd., Phone , Fax , United Kingdom Munters Ltd, Phone , Fax , USA Munters Corporation Fort Myers, Phone , Fax , Munters Corporation Mason, Phone , Fax , Export & other countries Munters, Phone , Fax Your closest distributor Munters Corporation Tel: (800) dhinfo@munters.com AG /14

Data Center Heat Rejection

Data Center Heat Rejection This article was published in ASHRAE Journal, March 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be

More information

Modular Data Center Cooling. Ultra High Efficiency. Oasis Optimum DCIE

Modular Data Center Cooling. Ultra High Efficiency. Oasis Optimum DCIE Modular Data Center Cooling Ultra High Efficiency Oasis Optimum DCIE Oasis Optimum Modular Cooling Compact, Economic, Greener, Ultra High Efficiency Munters Oasis Optimum DCIE data center cooling solution

More information

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some

More information

Alternate Cooling Solutions for Mission Critical Facilities Stuart Lawrence National Account Sales Engineer Munters Air Treatment

Alternate Cooling Solutions for Mission Critical Facilities Stuart Lawrence National Account Sales Engineer Munters Air Treatment Alternate Cooling Solutions for Mission Critical Facilities Stuart Lawrence National Account Sales Engineer Munters Air Treatment stuart.lawrence@munters.com 2103822646 Drivers of Alternative Approaches

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

OASIS PRODUCT GUIDE. Data Centre Cooling INDIRECT EVAPORATIVE COOLER. Data Centres. Telecoms. EPX technology. Class leading performance

OASIS PRODUCT GUIDE. Data Centre Cooling INDIRECT EVAPORATIVE COOLER. Data Centres. Telecoms. EPX technology. Class leading performance OASIS PRODUCT GUIDE Data Centres Telecoms EPX technology Class leading performance Fully configurable solutions INDIRECT EVAPORATIVE COOLER Data Centre Cooling 2 MUNTERS.COM/DATACENTRES Critical cooling

More information

Free Cooling for Data Centers

Free Cooling for Data Centers Free Cooling for Data Centers Release 1, September 2015 Contents 1. Abstract... 3 2. Introduction... 3 3. Data Center Temperatures and Free Cooling... 4 4. Direct Free Cooling... 4 5. Indirect Free Cooling...

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Using Wet-Bulb Economizers. Data Center Cooling

Using Wet-Bulb Economizers. Data Center Cooling The following article was published in ASHRAE Journal, August 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance

More information

White Paper #10. Energy Efficiency in Computer Data Centers

White Paper #10. Energy Efficiency in Computer Data Centers s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular

More information

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel. Climate solutions evaporative cooling, adiabatic humidification and programmable controllers energy saving solutions for data centers carel.com Data center air-conditioning Data center air-conditioning

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Award-Winning Innovation in Data Center Cooling Design

Award-Winning Innovation in Data Center Cooling Design Award-Winning Innovation in Data Center Cooling Design Oracle s Utah Compute Facility O R A C L E W H I T E P A P E R D E C E M B E R 2 0 1 4 Table of Contents Introduction 1 Overview 2 Innovation in Energy

More information

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010 White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence

More information

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015 Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed

More information

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes

More information

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Legacy Data Centres Upgrading the cooling capabilities What are the options? Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems

More information

Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager

Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager Data Centre Cooling Technologies 1 Jon Pettitt, EMEA DataCenter Business Development Manager Munters Group Key facts 3.000 Employees 30 Countries Turnover of 470 M HQ in Sweden Global DC Support 25+ Data

More information

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy

More information

Indirect Evaporative Cooling (IDEC) Unit for Data Centers

Indirect Evaporative Cooling (IDEC) Unit for Data Centers Indirect Evaporative Cooling (IDEC) Unit for Data Centers NORTEK AIR SOLUTIONS Cool3 IDEC UNIT INDIRECT EVAPORATIVE COOLING The new Nortek Air Solutions Cool 3 IDEC unit is a proven approach for highly

More information

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by

More information

Guide to Minimizing Compressor-based Cooling in Data Centers

Guide to Minimizing Compressor-based Cooling in Data Centers Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi

More information

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

The Data Center Dilemma - A Case Study

The Data Center Dilemma - A Case Study Second Place: Industrial Facilities or Processes, Existing The TCS data center makes use of white cabinets and reflective surfaces as one method to reduce power for its lights and cooling. Data Center

More information

Hospital Application Guide. Cost-effective climate control for hospitals

Hospital Application Guide. Cost-effective climate control for hospitals Hospital Application Guide Cost-effective climate control for hospitals Munters is the world leader in dehumidification Munters is the largest manufacturer of dehumidifiers in the world. Since developing

More information

STULZ Water-Side Economizer Solutions

STULZ Water-Side Economizer Solutions STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

SIMULATION OF RADIANT COOLING PERFORMANCE WITH

SIMULATION OF RADIANT COOLING PERFORMANCE WITH SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE

More information

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and

More information

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM

IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM THE GLOBAL DATA CENTRE MARKET The data centre air conditioning market is expected to grow with a CAGR (compound annual growth rate) of about 12% in the next

More information

CRITICAL COOLING FOR DATA CENTERS

CRITICAL COOLING FOR DATA CENTERS IDEA 100 th Annual Conference & Trade Show CRITICAL COOLING FOR DATA CENTERS Presented by Ron Johanning, PE, LEED AP Mission Critical Market Leader Agenda EPA Report Data Center Energy Trends IT Best Practice

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:

Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by: Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.

More information

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative

More information

Knowledge for optimal efficiency

Knowledge for optimal efficiency Engineering Onboard Climate Control Knowledge for optimal efficiency MARINE HVAC-R MARINE HVAC-R ADVANTAGES 2 KNOWLEDGE FOR OPTIMAL EFFICIENCY The BRONSWERK Advantage It s like the ideal day at sea when

More information

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems

More information

IT Cooling Solutions. DFC² Direct Free Cooling for Data Centres. Energy-efficient, reliable and available around the world

IT Cooling Solutions. DFC² Direct Free Cooling for Data Centres. Energy-efficient, reliable and available around the world IT Cooling Solutions DFC² Direct Free Cooling for Data Centres Energy-efficient, reliable and available around the world Worldwide Green Engineering with Direct Free Cooling from STULZ Forward thinking

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral

More information

IT Cooling Solutions. DFC² Direct Free Cooling for Data Centres. Energy-efficient, reliable and available around the world

IT Cooling Solutions. DFC² Direct Free Cooling for Data Centres. Energy-efficient, reliable and available around the world IT Cooling Solutions DFC² Direct Free Cooling for Data Centres Energy-efficient, reliable and available around the world Worldwide Green Engineering with Direct Free Cooling from STULZ Forward thinking

More information

AIR-SITE GROUP. White Paper. Green Equipment Room Practices

AIR-SITE GROUP. White Paper. Green Equipment Room Practices AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider

More information

Economizer Modes of Data Center Cooling Systems

Economizer Modes of Data Center Cooling Systems Economizer Modes of Data Center Cooling Systems White Paper 132 Revision 0 by John Niemann John Bean Victor Avelar > Executive summary In certain climates, some cooling systems can save over 70% in annual

More information

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1

85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1 Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio

More information

AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA CENTRES

AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA CENTRES AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA GLOBAL DATA CENTRE IP TRAFFIC WILL TRIPLE WITHIN 5 YEARS Global data centre IP traffic has set a constant growth path, with

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Optimization of Water - Cooled Chiller Cooling Tower Combinations Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator

More information

AERIS DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM

AERIS DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM THE GLOBAL DATA CENTRE MARKET The data centre air conditioning market is expected to grow with a CAGR (compound annual growth rate) of about 12% in the next

More information

Global Real Estate Outlook

Global Real Estate Outlook Global Real Estate Outlook August 2014 The Hierarchy of Economic Performance, 2014-2015 China Indonesia India Poland South Korea Turkey Australia Mexico United Kingdom Sweden United States Canada South

More information

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage

More information

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

The Effect of Data Centre Environment on IT Reliability & Energy Consumption

The Effect of Data Centre Environment on IT Reliability & Energy Consumption The Effect of Data Centre Environment on IT Reliability & Energy Consumption Steve Strutt EMEA Technical Work Group Member IBM The Green Grid EMEA Technical Forum 2011 Agenda History of IT environmental

More information

Data Centre Cooling Air Performance Metrics

Data Centre Cooling Air Performance Metrics Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

CASE STUDY: COOLERADO CORPORATION

CASE STUDY: COOLERADO CORPORATION CASE STUDY: COOLERADO CORPORATION Coolerado uses Weather Analytics climate data to demonstrate to clients the energy-efficiency of their air conditioners in places around the globe. 02 Overview Coolerado

More information

Datacenter Efficiency Program

Datacenter Efficiency Program Datacenter Efficiency Program Yuming Qiu, CLEAResult Anna Stieve, CLEAResult Michael Stachowiak, CLEAResult Abstract Worldwide, datacenter energy consumption is skyrocketing and datacenter energy efficiency

More information

NSIDC Data Center: Energy Reduction Strategies

NSIDC Data Center: Energy Reduction Strategies NSIDC Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful effort to significantly reduce

More information

Evaporative Cooling. Terminology. Date: February 28, 2012. Concepts

Evaporative Cooling. Terminology. Date: February 28, 2012. Concepts Evaporative Cooling Date: February 28, 2012 P R E S E N T E D B Y R O B E R T P A D G E T E 3 M S E N G I N E E R E D M E C H A N I C A L S Y S T E M S Concepts 1. Evaporation is a cooling process. Using

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic Introduction to HVAC Systems One of the Systems Series February 2012 TRG-TRC018-EN Introduction to HVAC Systems One of the Systems Series A publication of Trane Preface Introduction

More information

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Executive Summary Data center energy usage has risen dramatically over the past decade and

More information

Answers to Your Questions from the Webinar

Answers to Your Questions from the Webinar 2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

3/29/2012 INTRODUCTION HVAC BASICS

3/29/2012 INTRODUCTION HVAC BASICS INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

Small-Scale Solar Heating and Cooling Systems

Small-Scale Solar Heating and Cooling Systems Contact Austria: AEE INTEC (www.aee-intec.at) France: Tecsol (www.tecsol.fr) Germany: Fraunhofer ISE (www.ise.fraunhofer.de) Greece: CRES (www.cres.gr) Italy: EURAC (www.eurac.edu) University of Bergamo

More information

Green Data Center: Energy Reduction Strategies

Green Data Center: Energy Reduction Strategies Federal Energy ManagEment Program Green Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005 KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

CoolTeg Plus Chilled Water (CW) version: AC-TCW

CoolTeg Plus Chilled Water (CW) version: AC-TCW version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420

More information

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment

More information

News in Data Center Cooling

News in Data Center Cooling News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase

More information

Data Center Energy Profiler Questions Checklist

Data Center Energy Profiler Questions Checklist Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

How air conditioning works

How air conditioning works 1 How air conditioning works The essential ingredients in an air conditioning system are a fan to blow air around, a cold surface to cool and dehumidify the air, a warm surface and a source of water vapour.

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

Critical Infrastructure for the World s Leading Data Centers

Critical Infrastructure for the World s Leading Data Centers Critical Infrastructure for the World s Leading Data Centers 2 YOU MAY KNOW US BY OUR BRAND NAMES THE EXPERTISE OF MANY. THE POWER OF ONE. Nortek Air Solutions provides critical infrastructure for the

More information

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda

More information

White Paper: Free Cooling and the Efficiency of your Data Centre

White Paper: Free Cooling and the Efficiency of your Data Centre AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...

More information