In Row Cooling Options for High Density IT Applications
|
|
|
- Wilfred Randolf Tate
- 10 years ago
- Views:
Transcription
1 In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering
2 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions from which to select. In Rows come in multiple configurations adaptable to various space and aisle constraints. They can be mounted in the ceiling, over the racks, within the racks, or in the aisle. The two most common cooling media used inside the units are either refrigerant (R134a) or water; the user has a choice to use either type based on preference and comfort level. Overhead units are meant to handle sensible cooling only and hence no condensate is typically generated in the process. In fact, the internal controls monitor dew point closely and maintain refrigerant and coil temperatures above room dew point. Vertical aisle In Rows such as the RP by APC do have humidity control. Liebert makes a self contained unit that operates either on chilled water or glycol. The message is that these units come in various flavors and colors to satisfy the needs for your high density cooling deployment. In this whitepaper, we will review some common In Row coolers available from vendors that have been manufacturing this type of solution for the past 5 years. We will compare and evaluate several technical and operational parameters and rank them in terms of a three-tiered favorability matrix. While this list is not inclusive of every In Row cooler type available in the market, it provides the user a starting point from which to gather intelligent information about various unit makes and models. Refrigerant Based In Row Coolers A. Rack Overhead Liebert XDV An XDV system is a modular cooling solution that mounts directly on the top of the racks or alternatively, suspended above the racks. Each unit connects to a main supply and return header utilizing either rigid or flexible piping with quick connect fittings. One option is to stack the XDV s and install blanking panels between the openings, although this would add complexity and cost to the install. Rack Mounted XDV Sensible Cooling Only Available in 8.8 kw and 10 kw modules. Units mount on top of Racks. Planning for additional units is relatively easy. Connects via flexible piping with quick connect fittings
3 2 Will need coordination with overhead IT and power cabling Dual A-B Power cords for increased uptime. Two fans on each unit add to reliability. Dependent on the reliability of the XDC unit. Minimal maintenance required: 1. Cooling fins should be kept clean 2. Circulating fans are easily accessible from the front and require no lubrication. Involves copper headers and quick connects with valves, controls and wiring. Requires an XDC unit. Dimensions Hx Wx D 14"x 23"x 40" $$$ B. Row Mounted Liebert XDH An XDH system is a modular cooling solution that mounts in the row between racks or at the end of a row. Each unit connects to a main supply and return header utilizing either rigid or flexible piping with quick connects. Row Mounted XDH Sensible Cooling Only Available in 22 kw and 30 kw modules. Units are floor mounted in between racks or at the end of a row. Will require planning day-one for location of units. Connects via flexible piping with quick connect fittings. Floor mounted is easier to coordinate Dual A-B Power cords for increased uptime. Two pumped refrigerant circuits. Multiple fans for load shedding. LED sensors indicate status. Dependent on the reliability of the XDC unit.
4 3 Floor mounted units are easier to access for maintenance.. Minimal maintenance required: 1. cooling fins should be kept clean 2. circulating fans are easily accessible from the front and require no lubrication Involves copper headers and quick connects with valves, controls and wiring. Requires an XDC unit. $$$$ Dimensions Hx Wx D 78" x 12" x 42" C. Aisle Overhead Liebert XDO An XDO system is a modular cooling solution that mounts over the cold aisle with a Unistrut system. The unit pulls hot air from the two opposite inlets and a fan discharges the cold air down into the cold aisle. Each unit connects to a main supply and return header utilizing either rigid or flexible piping with quick connects. The user should note that the cooling value of this unit should really be analyzed as it could be disproportionally shared by two opposing racks in the cold isle. Aisle Overhead Mounted Sensible Cooling Only XDO Available in 17.2 kw and 20 kw modules. Units mount over cold aisles. Planning for additional units is relatively easy. Connects via flexible piping with quick connect fittings Will need coordination with overhead IT and power cabling. Mounting above the cold aisle May require additional lighting. Dual A-B Power cords for increased uptime. Dependent on the reliability of the XDC unit. Minimal maintenance required: 1. Cooling fins should be kept clean 2. Circulating fan is easily
5 4 accessible from the bottom of the module and requires no lubrication Involves copper headers and quick connects with valves, controls and wiring. Requires an XDC unit. $$$$ Dimensions Hx Wx D 22.5 x 72 x 24 D. Aisle Overhead APC OA The OA system is a modular cooling solution that mounts over the hot aisle utilizing a Unistrut system or APC s OA mounting frame. The unit pulls air from the hot aisle via two fans and discharges the cold air vertically where it is eventually drawn back into the front of the racks. Each unit connects to a main supply and return header utilizing rigid or flexible piping with quick connects. The headers connect to the RDU cooling distribution unit capable of providing 160 kw of cooling. Again, the user is reminded that the cooling value of this unit should be analyzed as it will be removing heat from the common hot aisle. The rank was elevated to Medium as the kw is slightly higher for this unit. Aisle Overhead Mounted OA Sensible Cooling Only Up to 27 kw (5 to 14 kw/rack densities) Units mount over hot aisles. Planning for additional units is relatively easy. Connects via flexible piping with quick connect fittings Will need coordination with overhead IT and power cabling. Mounting above the hot aisle may require additional lighting. Dual A-B Power cords for increased uptime. Dependent on the reliability of the RDU unit.
6 5 Minimal maintenance required: 1. Cooling fins should be kept clean 2. Circulating fan is easily accessible from the bottom of the module and requires no lubrication Involves copper headers and quick connects with valves, controls and wiring. Requires an RDU unit. Dimensions Hx Wx D 13.9 x 51.7 x 23.5 $$$$ E. Rear Door Heat Exchangers Liebert XDR An XDR system is a fixed cooling solution that mounts directly to the rear of the IT rack. Each unit connects to a main supply and return header utilizing rigid or flexible piping with quick connects. Door Mounted XDR Sensible Cooling Only 20.5 kw Units are passive fanless heat exchangers that replace the rear door of the IT rack. Relies on server fans to provide airflow through the unit. Connects via hard and flexible piping. Once installed however, the cooling capacity is fixed and can t be scaled down. Replaces IT rack rear door. The unit is passive, no moving parts to fail other than the quick coupling which is installed on all the XD class units. No moving parts to maintain. Scheduled cleaning of the coil fins. Involves copper headers and quick connects with valves, controls and wiring. Requires an XDC unit. $$$
7 6 Dimensions Hx Wx D 78.4 x 23.5 x 5.9 Only compatible with a 24 x 42 U Rack Water Based In Row Coolers A. Rack Mounted APC RC & RP 600 mm (24 ) The RP/RC600 system is a modular cooling solution that mounts in the row between racks. Each unit ties to a main supply and return chilled water header through rigid and flexible piping. Row Mounted RP600, RC600 Cooling w/ Option For Reheat and Humidity Control (RP Only) & Condensate Management (both units) Nominal 43 kw. Can go up to 70 kw. Units are floor mounted in between racks. Will require planning day-one for location of units. Connects via flexible piping. Floor mounted is easier to coordinate Dual A-B Power only on RC600. Multiple fans for variable load control. LED sensors indicate status. Floor mounted is easier to maintain. Minimal maintenance required: 1. Cooling fins should be kept clean 2. Circulating fans are easily accessible and require no lubrication Involves copper headers and quick connects with valves, controls and wiring. Dimensions Hx Wx D 78" x 24" x 42" $$$$$
8 7 B. Row Mounted APC RC300 An RC system is a modular cooling solution that mounts in the row between racks. Each unit ties to a main supply and return chilled water header through rigid or flexible piping. Row Mounted RC300 Sensible Cooling w/ Option For Condensate Management Nominal 18.2 kw. Can go up to 30 kw. Units are floor mounted in between racks. Will require planning day-one for location of units. Connects via flexible piping. Floor mounted is easier to coordinate Dual A-B Power cords for increased uptime. Multiple fans for variable load control. LED sensors indicate status. Floor mounted is easier to maintain. Minimal maintenance required: 1. Cooling fins should be kept clean 2. Circulating fans are easily accessible and require no lubrication Involves copper headers and quick connects with valves, controls and wiring. Dimensions Hx Wx D 78" x 12" x 42" $$$$
9 8 C. Rear Door Heat Exchangers (RDHx) Coolcentric Vette The system is a fixed cooling solution that mounts directly to the rear of the IT rack. Each unit ties to a main supply and return chilled water header through rigid and flexible piping with quick connects. RDHx Coolcentric Sensible Cooling Only 16 kw up to 35kW Units are passive fanless heat exchangers mounted on the rear door of the IT rack. Connects via hard and flexible piping. Once installed however, the cooling is cooling capacity is fixed and can t be scaled down. Door mounted. The unit is passive, no moving parts to fail No moving parts to maintain. Scheduled cleaning of the coil fins. Dimensions Hx Wx D Involves copper headers and quick connects with valves, controls and wiring. Requires a cooling distribution unit CDU. Compatible with a 42U x 24 rack but can be modified for a 30 wide rack. Standalone In Row Coolers A. Liebert CRV DX Standalone Cooling Unit A Liebert CRV is a standalone unit that connects directly to an outdoor condensing unit, drycooler, or chilled water. As such, it eliminates the need for the middle cooling distribution unit. It has state of the art scalable cooling and control capabilities and may be specified with integral humidification and reheat.
10 9 Liebert Air Cooled CRV Unit Full Cooling Capability using DX, Glycol, or Chilled Water Available in 20 kw and 35 kw Air Cooled modules The units are compact and fully contained with front and rear access. Digital Scroll compressors and variable speed fans within the unit enable variable cooling capacity from %. Each unit is piped separately to a condenser/ drycooler/cooling tower or chilled water source. Unit sits on the floor but requires a more extensive installation. Multiple fans and Compressors with full monitoring capability. The unit is fully contained with scroll compressors and EC fans (non chilled water unit). It may also be specified with options for built in reheat, humidification, and a condensate pump. Therefore the unit will have more components to maintain. This unit is piped similar to a standalone DX/Glycol/Chilled water CRAC unit. Dimensions Hx Wx D x 23.6 x 43.3 Conclusion There is no lack of choice when it comes to selecting an In Row cooling solution for high density applications. We have presented several products with a ranking matrix that can clarify the technical and operational impacts when selecting amongst the many brand names. While the list of products was limited to three manufacturers: Liebert, APC, and Coolcentric, additional products from Huntair, Stulz and Motiveair are being introduced and will most likely go through the same process to gain customer confidence and truly compete in the high density market. In TSS database of previous and ongoing projects, we have designed, installed, commissioned and maintained almost all the types mentioned in this paper. TSS can help you in your next high
11 10 density installation project from the conceptual selection process through design, construction, and facility maintenance of the completed project. About the Author Ramzi Y. Namek, PE, LEED AP BD+C; Director of Engineering, Total Site Solutions Mr. Namek is located out of the headquarter office of TSS in Columbia, Maryland and has over 17 years of experience in both Design and Project Management of mechanical systems for mission-critical, commercial, and government projects. He is skilled in HVAC, plumbing, and fire protection design, construction management, engineering economics, as well as energy analysis. With over ten publications in various leading industry journals, his current areas of interest are in data center energy efficiency, the cloud computing environment, and the dynamics of change in the data center business model. Mr. Namek was awarded his B.S. Degree in Mechanical Engineering from American University of Beirut and his M.S. Degree in Engineering Management from Virginia Tech. He is a board member in the ASHRAE National Capital Chapter.
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment
Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment The Intelligent Data Center Cooling Solution: Liebert CRV Trust the industry leader in Precision Cooling to deliver
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity
Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
Blade Server & Data Room Cooling Specialists
SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling
CoolTeg Plus Chilled Water (CW) version: AC-TCW
version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS
CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT
2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms
Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
STULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C
COOLS conditioned server - racks for direct installation into the room COOLSIDE box INVERTER R410A E C 2 COOLSIDE box GENERAL FEATURES COOLSIDE BOX is a split system consisting of an outdoor motocondensing
EHDC. Cooling system for Data Center and server cabinets.
EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1
WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
AIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Raised Floor Data Centers Prepared for the Future
Raised Floor Data Centers Prepared for the Future Raised Floors Protect My Investment by Providing a Foundation for Current and Future Technologies. Creating the Future Proof Data Center Environment The
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center
CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
Critical Infrastructure for the World s Leading Data Centers
Critical Infrastructure for the World s Leading Data Centers 2 YOU MAY KNOW US BY OUR BRAND NAMES THE EXPERTISE OF MANY. THE POWER OF ONE. Nortek Air Solutions provides critical infrastructure for the
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
News in Data Center Cooling
News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase
National Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
Unified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
Agenda. Who we are What we do How we serve the BPO Industry
Achieving Energy Efficiency in Data Centres Agenda Who we are What we do How we serve the BPO Industry Energy Efficiency for Data Centres Jardine Matheson Founded as a trading company in China in 1832,
Reference Guide: SmartDesign Approach: Common Data Center Challenges:
Smart Solutions Reference Guide Solutions For Business-Critical Continuity 1100kW Tier 3 With High Density Design Intelligent, Integrated Infrastructure for the Data Center Reference Guide: 1100kW Tier
Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy
Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Executive Summary Data center energy usage has risen dramatically over the past decade and
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Best Practices for Wire-free Environmental Monitoring in the Data Center
White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com [email protected] Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for
Data Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
Best Practices in HVAC Design/Retrofit
Best Practices in HVAC Design/Retrofit Little Server Room BIG $AVINGS Justin Lewis, P.E., LEED AP, DCEP Sr Energy Project Manager C:530.400.6042 O:530.754.4870 [email protected] 1 What s the problem here?
Liebert : The Right Cooling For IT Environments. Precision Cooling For Business-Critical Continuity
Liebert : The Right Cooling For IT Environments Precision Cooling For Business-Critical Continuity New Challenges To IT System Uptime Many IT professionals are finding that dedicated precision cooling
Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
University of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
Legacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 [email protected] www.chatsworth.com All products
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
White Paper Rack climate control in data centres
White Paper Rack climate control in data centres Contents Contents...2 List of illustrations... 3 Executive summary...4 Introduction...5 Objectives and requirements...6 Room climate control with the CRAC
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Cooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
Energy-efficient & scalable data center infrastructure design
Seminar am 30. September 2010 in Wetzlar Nachhaltigkeit durch UPI (Unified Physical Infrastructure) Vortrag von Stefan Fammler: Energieeffiziente Strategien im Rechenzentrum Energy-efficient & scalable
LEVEL 3 DATA CENTER ASSESSMENT
Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments
JAWAHARLAL NEHRU UNIVERSITY
School of Biotechnology JAWAHARLAL NEHRU UNIVERSITY New Delhi 110 067 Tender No. JNU/SBT/DBT-BUILDER/Data Centre/2015-16 Sealed Quotation for the establishment of a Data Centre for High-End Computational
Improving Data Center Efficiency with Rack or Row Cooling Devices:
Improving Data Center Efficiency with Rack or Row Cooling Devices: Results of Chill-Off 2 Comparative Testing Introduction In new data center designs, capacity provisioning for ever-higher power densities
Technical Systems. Helen Bedford
Technical Systems in Data Centres Helen Bedford Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre
European Code of Conduct for Data Centre. Presentation of the Awards 2016
European Code of Conduct for Data Centre Presentation of the Awards 2016 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment
Airflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
LIEBERT CORPORATION Air Products. Model Number Reference Guide. Revision: April 2004
LIEBERT CORPORATION Air Products Model Number erence Guide Revision: April 2004 MODEL NUMBER INDEX BEGINNING MODEL PRODUCT PAGE FD, UD Deluxe System 2 1 FH, FE, UH, UE Deluxe System 3 1 DH, DE, VH, VE,
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems
NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
Data Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
Tech Byte 27: Small Computer Room and IT Closet Cooling
Questions Answered in This Paper Sensible cooling capacity is the measuring stick for IT cooling capacity needs. What is the sensible cooling capacity of the comfort split system in comparison to the precision
Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA
Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale
Data Center Cooling Critical Facility & Infrastructure Optimization. Presented by. Greg Stover SVP NER Data Corporation
Data Center Cooling Critical Facility & Infrastructure Optimization Presented by Greg Stover SVP NER Data Corporation About NER Data Corporation Data Center Infrastructure Optimization NER has been a leading
AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
CRAC Precision climate control units for data centres
CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have
Energy Efficient Cooling Solutions for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Energy Efficient Cooling Solutions for Data Centers Introducing an Emerson Network Power tool for evaluating cooling system total cost
Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment
Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
EXAMPLE OF A DATA CENTRE BUILD
EXAMPLE OF A DATA CENTRE BUILD BT Harmondsworth Data Centre Hall 2 Upgrade Temperature Control have been involved in providing specialist to data centres for over 20 years, starting from providing specialist
5 Reasons. Environment Sensors are used in all Modern Data Centers
5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center
IPSIP M series-m Modular Data Center
IPSIP M series-m Modular Data Center IPSIP MODULAR TECHNOLOGIES. 1 With the rapid development of cloud computing and mobile Internet businesses, the growth of IT density and energy consumption are bringing
Innovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity
Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems A White Paper from the Experts in Business-Critical Continuity Executive Summary In enterprise data centers, designers face
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS