Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager

Size: px
Start display at page:

Download "Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager"

Transcription

1 Data Centre Cooling Technologies 1 Jon Pettitt, EMEA DataCenter Business Development Manager

2 Munters Group Key facts Employees 30 Countries Turnover of 470 M HQ in Sweden Global DC Support 25+ Data Centers 95 MW+ Cooling 455 Installed units Founded1955 Munters Your Perfect Climate 2

3 Global Manufacturing & Logistics Support Manufacturing plants Logistic & assembly hubs 16 Manufacturing Plants 5 Logistic & Assembly Hubs 53 Sales & Service Centres

4 A Corporate Culture of Technical Innovation and a History of Customer Service 2010 Acquired by Nordic Capital 2012 Acquire Proflute 2011 Acquire Kerulai China and Rotem 2008 Acquire TN Belgium 2007 Acquire Des Champs USA 1955 Munters Sweden bought UK/US CargoCaire 1946 Munters CargoCaire manufacture under licence 1960 Munters Worldwide 1997 on Swedish stock exchange Carl Munters ( ) Swedish inventor and entrepreneur A pioneer in desiccant rotor & evaporative cooling/humidification Applied for close to 1,000 patents Invented Desiccant rotor technology over 30 years ago

5 Munters Data Centre Installations to May 2013

6 Why Choose Munters? Stable Organisation year history - Group sales approx 430m. Financial Strength - Consistently profitable with strong backing from Nordic Capital & Rothschild. Commitment to the Data Centre Market - 600k invested in the Data Centre Test Facility in Dison. Proven Technology years of fault-free performance. Capacity for Large Projects - 15 manufacturing facilities worldwide, including 6 plants able to produce Data Centre cooling systems. Global Support - 53 Sales & Service Centres in over 30 countries After Sales Support Munters Service Engineers in Asia. Customer Service - Dedicated structure to support our Data Centre customers. Proven Track Record - 12 years experience in Data Centre Cooling, with over 85mW of cooling installed worldwide. 6

7 Some of our Customers

8 no. 8 Challenges in DC Development

9 Key Challenges & Drivers Impacting the Data Centre Industry Reliability/Uptime SLA s Contamination Energy Costs Carbon Emissions Modularity

10 Uptime & Reliability Tier 1: Tier 2: Tier 3: Tier 4: Non-redundant capacity components (single uplink and servers). Tier 1 + Redundant capacity components. Tier 1 + Tier 2 + Dual-powered equipment and multiple uplinks. Tier 1 + Tier 2 + Tier 3 + all components are fully fault-tolerant including uplinks, storage, chillers, HVAC systems, servers etc. Everything is dual-powered. The levels also describes the guaranteed availability of data from the hardware at a location: Tier 1: % availability. Tier 2: % availability. Tier 3: Tier 4: % availability. RELIABILITY is THE Critical Success Factor % availability.

11 Air Contamination

12 Air Contamination

13 Energy Efficiency and Carbon Footprint

14 Industry Future?? Future??? + + +

15 Sustainability Green Grid introducing new metrics to measure and help DC owners improve Sustainability with Data Centre s PUE = Power Usage Effectiveness CUE = Carbon Usage Effectiveness WUE = Water Usage Effectiveness

16 Infrastructure Power Supplies Data Centre size is often restricted by availability of power to site. By reducing cooling power consumption, more power becomes available for critical processes and server operations. Space Land cost Availability Planning Consents Water Availability Cost

17 ASHRAE Recommended & Allowable Envelopes A3 A4 A2 60% A1 15 o C dew point 5.5 o C dew point 18 o C 27 o C

18 no. 18 Cooling Technologies

19 no. 19 Indirect Evaporative Cooling

20 Indirect Air Side Economizer Using Polymer Tube HX Exhaust Outside 23 C 35 C

21 Three Modes of Operation Mode 1 Cold Ambient Operation:- DRY MODE Air to Air Heat exchanger only Mode 2 Warm Ambient Operation:- EVAP MODE Indirect Evaporative Cooling only Mode 3 Very Warm/Hot Ambient (above approx 22 C WB) Operation:- EVAP + DX MODE Indirect Evaporative Air Cooling only + DX Cooling circuit

22 Oasis IEC Video Oasis video runs here

23 Polymer Heat Exchanger 23

24 Polymer Heat Exchanger Flexible Polymer Tubes 2.44 meters length 75-80% approach to outdoor scavenger air wet bulb temp 55% dry heat recovery Scale Limiting design Corrosion Resistant Independently tested UL 900 Class II Flame retardant (UL94-V0) 24

25 Water Spray Operation Video of water running through the H/Ex runs here no. 27

26 Beneath the Heat Exchanger 26

27 Beneath the Heat Exchanger, in Wet Mode Scavenger Air

28 Legionella Risk Analysis The Risk Assessment of the OASIS unit confirms that the risks of causing growth and spread of Legionella bacteria are negligible. If the temperature is below 25 C, no risk of occurrence of Legionella in the system, which is the case most of the time. In the operating conditions for water above 25 C, the system is designed so that water flows continuously in the circuit so that there is no stagnation of water and no risk of emergence of bacteria. The Oasis IEC has an automatic emptying system that starts if installation is at standstill for agreed hours. Therefore no risk of proliferation of legionella in the water recovery pan.

29 OASIS TM IEC Range Oasis 100 Oasis 200 Oasis 300 < 100 kw < 200 kw < 310 kw m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h 1 block 1 block 2 prefab blocks 6.9 x 1.4 x 3.6 / 9.4 m x 2.6 x 3.6 / 17.8m x 3.94 x 3.6 / 27.2m Ton 6.6 Ton 8.8 Ton

30 30 Perimeter format Oasis 200

31 #5: Performance & Cost Comparisons no. 33 Section 5

32 Independent Performance Verification

33 Results of Independent Engineering Review Benefits of Oasis IEC Cooling over high efficiency free-cooling chillers: Lower capital costs Reduced Infrastructure 40% lower annual operating cost Low partial PUE Source: Cundall Product Engineering Review. Based on 1MW data centre (N+1)

34 Oasis Indirect Evaporative Cooler Energy savings vs Chillers

35 Oasis Indirect Evaporative Cooler Energy savings vs Chillers

36 Hours pa that Oasis IEC can provide 23 C without Mechanical Cooling Based on Hot Aisle return air temperature of 35DegC Hours run with EPX only Hours run with EPX and supplementary cooling Hours of operation per year

37 Hours pa that Oasis IEC can provide 27 C without Mechanical Cooling Based on Hot Aisle return air temperature of 39DegC Hours run with EPX only Hours run with EPX and supplementary cooling Hours of operation per year

38 no. 39 Existing Installations

39 Oasis Indirect Evaporative Air Cooler (IEAC)

40 Australia

41 Australia

42 Wenatchee, WA

43 T5 El Segundo, CA.

44 DCO2 Belgium 5 MW Winner Datacenter Dynamics leadership award 'Green Datacentre' 2011 & European Code of Conduct Award for new Data Centre 2011 With free cooling system: dust & pollution from surrounding farmland caused - Frequent replacement of filters - Required man power & frequent inspection - Caused pressure drop & increased fan power Solution: Munters Oasis Indirect Evaporative Cooler replaced full free cooling system

45 Sabey Intergate Quincy no. 46

46 Sabey Case Study Sabey video runs here 46

47 Data Centre Test Facility Wenatchee, WA

48 All units can be FATesting in our Data Center Test Facility Performance testing Leakage testing Controls simulations 48

49 Benefits Oasis IEC Systems Contamination Control Supply and outdoor airflow do not mix Corrosion Prevention: No added moisture/humidity to supply Usable for any kind of sweet water Rain water harvesting Eliminating DX cooling 100% IEC Cooling in some regions IEC efficiency can increase further As allowable supply air temperature to server inlet increases,

50 Thank you Questions? no. 52

Modular Data Center Cooling. Ultra High Efficiency. Oasis Optimum DCIE

Modular Data Center Cooling. Ultra High Efficiency. Oasis Optimum DCIE Modular Data Center Cooling Ultra High Efficiency Oasis Optimum DCIE Oasis Optimum Modular Cooling Compact, Economic, Greener, Ultra High Efficiency Munters Oasis Optimum DCIE data center cooling solution

More information

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by

More information

OASIS PRODUCT GUIDE. Data Centre Cooling INDIRECT EVAPORATIVE COOLER. Data Centres. Telecoms. EPX technology. Class leading performance

OASIS PRODUCT GUIDE. Data Centre Cooling INDIRECT EVAPORATIVE COOLER. Data Centres. Telecoms. EPX technology. Class leading performance OASIS PRODUCT GUIDE Data Centres Telecoms EPX technology Class leading performance Fully configurable solutions INDIRECT EVAPORATIVE COOLER Data Centre Cooling 2 MUNTERS.COM/DATACENTRES Critical cooling

More information

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy

More information

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

HVAC Infrastructure Retrofit Solutions

HVAC Infrastructure Retrofit Solutions Kyoto Cooling Lunch & Learn David Belleville, APA LLC March 9, 2015 Owners choose APA solutions to: Rely on our 30+ years of delivering engineered solutions; HVAC Infrastructure Retrofit Solutions Insure

More information

Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis

Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

Guideline for Water and Energy Considerations During Federal Data Center Consolidations

Guideline for Water and Energy Considerations During Federal Data Center Consolidations Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda

More information

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information

Indirect Evaporative Cooling (IDEC) Unit for Data Centers

Indirect Evaporative Cooling (IDEC) Unit for Data Centers Indirect Evaporative Cooling (IDEC) Unit for Data Centers NORTEK AIR SOLUTIONS Cool3 IDEC UNIT INDIRECT EVAPORATIVE COOLING The new Nortek Air Solutions Cool 3 IDEC unit is a proven approach for highly

More information

The Effect of Data Centre Environment on IT Reliability & Energy Consumption

The Effect of Data Centre Environment on IT Reliability & Energy Consumption The Effect of Data Centre Environment on IT Reliability & Energy Consumption Steve Strutt EMEA Technical Work Group Member IBM The Green Grid EMEA Technical Forum 2011 Agenda History of IT environmental

More information

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance

More information

TelecityGroup plc. Outstanding data centres. Expertise you can trust.

TelecityGroup plc. Outstanding data centres. Expertise you can trust. TelecityGroup plc Outstanding data centres. Expertise you can trust. ABOUT TELECITYGROUP 2 / About TelecityGroup TelecityGroup is Europe s leading provider of premium carrier-neutral data centres. Helsinki

More information

Dell s Next Generation Servers: Pushing the Limits of Data Center Cooling Cost Savings

Dell s Next Generation Servers: Pushing the Limits of Data Center Cooling Cost Savings Dell s Next Generation Servers: Pushing the Limits of Data Center Cooling Cost Savings This white paper explains how Dell s next generation of servers were developed to support fresh air cooling and overall

More information

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative

More information

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel. Climate solutions evaporative cooling, adiabatic humidification and programmable controllers energy saving solutions for data centers carel.com Data center air-conditioning Data center air-conditioning

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

FEAR Model - Review Cell Module Block

FEAR Model - Review Cell Module Block F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Legacy Data Centres Upgrading the cooling capabilities What are the options? Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems

More information

Data Center Heat Rejection

Data Center Heat Rejection This article was published in ASHRAE Journal, March 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be

More information

Alfa Laval Abatigo. Redefining adiabatic cooling

Alfa Laval Abatigo. Redefining adiabatic cooling Alfa Laval Abatigo Redefining adiabatic cooling Experience and expertise recognized throughout the world With decades of broad experience and practical expertise in heat transfer, Alfa Laval is today a

More information

Interested in conducting your own webinar? Email webinars@bnpmedia.com

Interested in conducting your own webinar? Email webinars@bnpmedia.com Interested in conducting your own webinar? Email webinars@bnpmedia.com Improving Efficiencies by Integrating Data Center Systems August 30 th, 2012 Audio Abstract Presenter Info Slides Handouts Group Chat

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Infrastructure & Cities Sector

Infrastructure & Cities Sector Technical Article Infrastructure & Cities Sector Building Technologies Division Zug (Switzerland), October 18, 2011 Saving Energy in a Data Center A Leap of Faith? New guidelines from ASHRAE (American

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

DATA CENTERS BEST IN CLASS

DATA CENTERS BEST IN CLASS Data Energy Audit Chameleon Data Center DATA CENTERS BEST IN CLASS... By Wouter Kok, MSc, Strategic Advisor Global Data Center Practice Deerns leads the way in making data centers greener, by reducing

More information

IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM

IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM THE GLOBAL DATA CENTRE MARKET The data centre air conditioning market is expected to grow with a CAGR (compound annual growth rate) of about 12% in the next

More information

Reduce data center PUE using Munters innovative cooling solutions

Reduce data center PUE using Munters innovative cooling solutions d a t a center applica t i o n guide Reduce data center PUE using Munters innovative cooling solutions Reduce data center energy costs by up to 75% Traditional refrigeration cooling systems are an inefficient

More information

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency NREL 1 National Renewable Energy Laboratory Presentation Road Map A Holistic Approach to Efficiency: Power, Packaging, Cooling, Integration

More information

Alternate Cooling Solutions for Mission Critical Facilities Stuart Lawrence National Account Sales Engineer Munters Air Treatment

Alternate Cooling Solutions for Mission Critical Facilities Stuart Lawrence National Account Sales Engineer Munters Air Treatment Alternate Cooling Solutions for Mission Critical Facilities Stuart Lawrence National Account Sales Engineer Munters Air Treatment stuart.lawrence@munters.com 2103822646 Drivers of Alternative Approaches

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore

Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational

More information

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An

More information

Free Cooling for Data Centers

Free Cooling for Data Centers Free Cooling for Data Centers Release 1, September 2015 Contents 1. Abstract... 3 2. Introduction... 3 3. Data Center Temperatures and Free Cooling... 4 4. Direct Free Cooling... 4 5. Indirect Free Cooling...

More information

Award-Winning Innovation in Data Center Cooling Design

Award-Winning Innovation in Data Center Cooling Design Award-Winning Innovation in Data Center Cooling Design Oracle s Utah Compute Facility O R A C L E W H I T E P A P E R D E C E M B E R 2 0 1 4 Table of Contents Introduction 1 Overview 2 Innovation in Energy

More information

Data Center Design and Energy Management

Data Center Design and Energy Management Agenda EasyStreet Online Services, Inc. Data Center Design and Energy Management Introduction to EasyStreet Speaker Bio EasyStreet Sustainability Data Center 1 (Retrofit completed May 2010) Data Center

More information

Data Center Facility Basics

Data Center Facility Basics Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire. http://rare-idc.herts.ac.

Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire. http://rare-idc.herts.ac. Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire http://rare-idc.herts.ac.uk Making Existing Server Rooms More Efficient Reduction and Re-use

More information

AERIS DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM

AERIS DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM THE GLOBAL DATA CENTRE MARKET The data centre air conditioning market is expected to grow with a CAGR (compound annual growth rate) of about 12% in the next

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Data Centers: Definitions, Concepts and Concerns

Data Centers: Definitions, Concepts and Concerns Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

Three Steps To Perfectly Green

Three Steps To Perfectly Green R E S E A R C H U N D E R W R I T E R W H I T E P A P E R LEAN, CLEAN & GREEN Deerns Consulting Engineers Three Steps To Perfectly Green By Wouter M. Kok, Manager, Cleanroom, Laboratory, and Data Center

More information

Take the complication out of cooling. Data center cooling equipment and service from Alfa Laval

Take the complication out of cooling. Data center cooling equipment and service from Alfa Laval Take the complication out of cooling Data center cooling equipment and service from Alfa Laval How to make cooling less complicated As data grows, so does the demand for new data centers with increased

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

NSIDC Data Center: Energy Reduction Strategies

NSIDC Data Center: Energy Reduction Strategies NSIDC Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful effort to significantly reduce

More information

Introduction to Datacenters & the Cloud

Introduction to Datacenters & the Cloud Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview

More information

Server room guide helps energy managers reduce server consumption

Server room guide helps energy managers reduce server consumption Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

Data Centre Cooling Air Performance Metrics

Data Centre Cooling Air Performance Metrics Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption

More information

Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings

Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings ASHRAE Conference, Denver Otto Van Geet, PE June 24, 2014 NREL/PR-6A40-58902 NREL is a national laboratory of the U.S. Department

More information

Green Data Center: Energy Reduction Strategies

Green Data Center: Energy Reduction Strategies Federal Energy ManagEment Program Green Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful

More information

White Paper: Free Cooling and the Efficiency of your Data Centre

White Paper: Free Cooling and the Efficiency of your Data Centre AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...

More information

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features

More information

Economizer Modes of Data Center Cooling Systems

Economizer Modes of Data Center Cooling Systems Economizer Modes of Data Center Cooling Systems White Paper 132 Revision 0 by John Niemann John Bean Victor Avelar > Executive summary In certain climates, some cooling systems can save over 70% in annual

More information

The Mission Critical Data Center Understand Complexity Improve Performance

The Mission Critical Data Center Understand Complexity Improve Performance The Mission Critical Data Center Understand Complexity Improve Performance Communications Technology Forum Fall 2013 Department / Presenter / Date 1 Rittal IT Solutions The State of the Data Center Market

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

INFO HTK. Hybrid dry cooler. The reference for hybrid dry cooling. 100 4,000 kw

INFO HTK. Hybrid dry cooler. The reference for hybrid dry cooling. 100 4,000 kw INFO HTK Hybrid dry cooler The reference for hybrid dry cooling 4, kw JAEGGI The Original Since 929, JAEGGI has been engaged in the development, production and sale of heat exchangers. Since 995, the company

More information

DATA CENTRE DESIGN AND

DATA CENTRE DESIGN AND SPUSC 2008 SOUTH PACIFIC USER SERVICES CONFERENCE DATA CENTRE DESIGN AND ENERGY INITIATIVES Presented by Jarrad Clift Electrical Engineer Greenstar Accredited Presentation Content Data Centres General

More information

Capgemini UK Infrastructure Outsourcing

Capgemini UK Infrastructure Outsourcing Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,

More information

Smarter Data Centers. Integrated Data Center Service Management

Smarter Data Centers. Integrated Data Center Service Management Smarter Data Centers Integrated Data Center Service Management Approx. 3.500 ton CO² is generated by: Diesel Car-6l /100 km 20.000 km Airplane 5 * Brussels-Barcelona Server, 1.5 A, 24*7*365*3.000 Kwhr

More information

DataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation.

DataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation. DataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation. Dr. Rainer Weidmann, DC Architecture & DC Innovation Dr. Rainer Weidmann, DC Architecture

More information

Screw Compressors ESM 30 132 Fixed Speed & VS 30 132 Variable Speed

Screw Compressors ESM 30 132 Fixed Speed & VS 30 132 Variable Speed Screw Compressors ESM 30 132 Fixed Speed & VS 30 132 Variable Speed Rely on GD to provide the perfect fit The perfect fit to maximise productivity The growing industrial demand for compressed air requires

More information

Modular Chiller Plants for data centers. Downtime isn t acceptable

Modular Chiller Plants for data centers. Downtime isn t acceptable Modular Chiller Plants for data centers Downtime isn t acceptable Reducing risk with Quick Start A direct solution to your most important challenge uptime. At Johnson Controls we protect our customers

More information

European Business Reliance Centres when Commodity serves Green IT

European Business Reliance Centres when Commodity serves Green IT European Business Reliance Centres when Commodity serves Green IT www.ebrc.com www.trusteddatacentre.com www.trustedcloudeurope.com www.trustedmanagedservices.com ebrc COMPANY PROFILE 5 datacenters = 17.000

More information

How to build your Data Center Digitice roadshow Vaasa 3.12.2015

How to build your Data Center Digitice roadshow Vaasa 3.12.2015 How to build your Data Center Digitice roadshow Vaasa 3.12.2015 Mikko Aho Sales Director 044 593 4698 1 A Strong Family The Friedhelm Loh Group a successful business 11.500 employees worldwide 78 int.

More information

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer

More information

Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:

Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by: Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2014

European Code of Conduct for Data Centre. Presentation of the Awards 2014 European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

Deep Dive Think Tank: Energy Costs and Strategies for Reduction

Deep Dive Think Tank: Energy Costs and Strategies for Reduction Deep Dive Think Tank: Energy Costs and Strategies for Reduction Andrew Donoghue European research manager, Datacenter Technologies 1 Discussion points Does energy cost really matter or does uptime still

More information

How to Build a Data Centre Cooling Budget. Ian Cathcart

How to Build a Data Centre Cooling Budget. Ian Cathcart How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information

ASHRAE Rocky Mountain Chapter. RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc.

ASHRAE Rocky Mountain Chapter. RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc. ASHRAE Rocky Mountain Chapter Evaporative Cooling RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc. April 19, 2013 1 Fundamentals Dry Bulb Temperature Wet Bulb Temperature

More information

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate:

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate: Questions to be responded to by the firm submitting the application Why do you think this project should receive an award? How does it demonstrate: innovation, quality, and professional excellence transparency

More information

HPC TCO: Cooling and Computer Room Efficiency

HPC TCO: Cooling and Computer Room Efficiency HPC TCO: Cooling and Computer Room Efficiency 1 Route Plan Motivation (Why do we care?) HPC Building Blocks: Compuer Hardware (What s inside my dataroom? What needs to be cooled?) HPC Building Blocks:

More information

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London. Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial

More information

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.

More information

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Equinix Telecity Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 se.info@telecity.com www.telecitygroup.se

More information

Greening Data Centers

Greening Data Centers Greening Data Centers Dallas Thornton SDSC Division Director, Cyberinfrastructure Services March 2, 2011 Data Centers Are Enormous Users of Power US Data Centers (TeraWatt Hours per Year) 125 US Televisions

More information

STULZ Water-Side Economizer Solutions

STULZ Water-Side Economizer Solutions STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014

More information

VISIT 2010 Fujitsu Forum Europe 0

VISIT 2010 Fujitsu Forum Europe 0 VISIT 2010 Fujitsu Forum Europe 0 Virtualization & Automation Room 13a Shaping tomorrow with you. Green Data Center Services Martin Provoost Director, Data Centers and Networks, Fujitsu UK & Ireland 14:00

More information

11 Top Tips for Energy-Efficient Data Center Design and Operation

11 Top Tips for Energy-Efficient Data Center Design and Operation 11 Top Tips for Energy-Efficient Data Center Design and Operation A High-Level How To Guide M e c h a n i c a l a n a l y s i s W h i t e P a p e r w w w. m e n t o r. c o m When is Data Center Thermal

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

The European Programme for Energy Efficiency in Data Centres: The Code of Conduct

The European Programme for Energy Efficiency in Data Centres: The Code of Conduct The European Programme for Energy Efficiency in Data Centres: The Code of Conduct Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 Why Data Centres? Continuing demand for

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200

More information