Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager
|
|
- Winifred Barker
- 8 years ago
- Views:
Transcription
1 Data Centre Cooling Technologies 1 Jon Pettitt, EMEA DataCenter Business Development Manager
2 Munters Group Key facts Employees 30 Countries Turnover of 470 M HQ in Sweden Global DC Support 25+ Data Centers 95 MW+ Cooling 455 Installed units Founded1955 Munters Your Perfect Climate 2
3 Global Manufacturing & Logistics Support Manufacturing plants Logistic & assembly hubs 16 Manufacturing Plants 5 Logistic & Assembly Hubs 53 Sales & Service Centres
4 A Corporate Culture of Technical Innovation and a History of Customer Service 2010 Acquired by Nordic Capital 2012 Acquire Proflute 2011 Acquire Kerulai China and Rotem 2008 Acquire TN Belgium 2007 Acquire Des Champs USA 1955 Munters Sweden bought UK/US CargoCaire 1946 Munters CargoCaire manufacture under licence 1960 Munters Worldwide 1997 on Swedish stock exchange Carl Munters ( ) Swedish inventor and entrepreneur A pioneer in desiccant rotor & evaporative cooling/humidification Applied for close to 1,000 patents Invented Desiccant rotor technology over 30 years ago
5 Munters Data Centre Installations to May 2013
6 Why Choose Munters? Stable Organisation year history - Group sales approx 430m. Financial Strength - Consistently profitable with strong backing from Nordic Capital & Rothschild. Commitment to the Data Centre Market - 600k invested in the Data Centre Test Facility in Dison. Proven Technology years of fault-free performance. Capacity for Large Projects - 15 manufacturing facilities worldwide, including 6 plants able to produce Data Centre cooling systems. Global Support - 53 Sales & Service Centres in over 30 countries After Sales Support Munters Service Engineers in Asia. Customer Service - Dedicated structure to support our Data Centre customers. Proven Track Record - 12 years experience in Data Centre Cooling, with over 85mW of cooling installed worldwide. 6
7 Some of our Customers
8 no. 8 Challenges in DC Development
9 Key Challenges & Drivers Impacting the Data Centre Industry Reliability/Uptime SLA s Contamination Energy Costs Carbon Emissions Modularity
10 Uptime & Reliability Tier 1: Tier 2: Tier 3: Tier 4: Non-redundant capacity components (single uplink and servers). Tier 1 + Redundant capacity components. Tier 1 + Tier 2 + Dual-powered equipment and multiple uplinks. Tier 1 + Tier 2 + Tier 3 + all components are fully fault-tolerant including uplinks, storage, chillers, HVAC systems, servers etc. Everything is dual-powered. The levels also describes the guaranteed availability of data from the hardware at a location: Tier 1: % availability. Tier 2: % availability. Tier 3: Tier 4: % availability. RELIABILITY is THE Critical Success Factor % availability.
11 Air Contamination
12 Air Contamination
13 Energy Efficiency and Carbon Footprint
14 Industry Future?? Future??? + + +
15 Sustainability Green Grid introducing new metrics to measure and help DC owners improve Sustainability with Data Centre s PUE = Power Usage Effectiveness CUE = Carbon Usage Effectiveness WUE = Water Usage Effectiveness
16 Infrastructure Power Supplies Data Centre size is often restricted by availability of power to site. By reducing cooling power consumption, more power becomes available for critical processes and server operations. Space Land cost Availability Planning Consents Water Availability Cost
17 ASHRAE Recommended & Allowable Envelopes A3 A4 A2 60% A1 15 o C dew point 5.5 o C dew point 18 o C 27 o C
18 no. 18 Cooling Technologies
19 no. 19 Indirect Evaporative Cooling
20 Indirect Air Side Economizer Using Polymer Tube HX Exhaust Outside 23 C 35 C
21 Three Modes of Operation Mode 1 Cold Ambient Operation:- DRY MODE Air to Air Heat exchanger only Mode 2 Warm Ambient Operation:- EVAP MODE Indirect Evaporative Cooling only Mode 3 Very Warm/Hot Ambient (above approx 22 C WB) Operation:- EVAP + DX MODE Indirect Evaporative Air Cooling only + DX Cooling circuit
22 Oasis IEC Video Oasis video runs here
23 Polymer Heat Exchanger 23
24 Polymer Heat Exchanger Flexible Polymer Tubes 2.44 meters length 75-80% approach to outdoor scavenger air wet bulb temp 55% dry heat recovery Scale Limiting design Corrosion Resistant Independently tested UL 900 Class II Flame retardant (UL94-V0) 24
25 Water Spray Operation Video of water running through the H/Ex runs here no. 27
26 Beneath the Heat Exchanger 26
27 Beneath the Heat Exchanger, in Wet Mode Scavenger Air
28 Legionella Risk Analysis The Risk Assessment of the OASIS unit confirms that the risks of causing growth and spread of Legionella bacteria are negligible. If the temperature is below 25 C, no risk of occurrence of Legionella in the system, which is the case most of the time. In the operating conditions for water above 25 C, the system is designed so that water flows continuously in the circuit so that there is no stagnation of water and no risk of emergence of bacteria. The Oasis IEC has an automatic emptying system that starts if installation is at standstill for agreed hours. Therefore no risk of proliferation of legionella in the water recovery pan.
29 OASIS TM IEC Range Oasis 100 Oasis 200 Oasis 300 < 100 kw < 200 kw < 310 kw m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h 1 block 1 block 2 prefab blocks 6.9 x 1.4 x 3.6 / 9.4 m x 2.6 x 3.6 / 17.8m x 3.94 x 3.6 / 27.2m Ton 6.6 Ton 8.8 Ton
30 30 Perimeter format Oasis 200
31 #5: Performance & Cost Comparisons no. 33 Section 5
32 Independent Performance Verification
33 Results of Independent Engineering Review Benefits of Oasis IEC Cooling over high efficiency free-cooling chillers: Lower capital costs Reduced Infrastructure 40% lower annual operating cost Low partial PUE Source: Cundall Product Engineering Review. Based on 1MW data centre (N+1)
34 Oasis Indirect Evaporative Cooler Energy savings vs Chillers
35 Oasis Indirect Evaporative Cooler Energy savings vs Chillers
36 Hours pa that Oasis IEC can provide 23 C without Mechanical Cooling Based on Hot Aisle return air temperature of 35DegC Hours run with EPX only Hours run with EPX and supplementary cooling Hours of operation per year
37 Hours pa that Oasis IEC can provide 27 C without Mechanical Cooling Based on Hot Aisle return air temperature of 39DegC Hours run with EPX only Hours run with EPX and supplementary cooling Hours of operation per year
38 no. 39 Existing Installations
39 Oasis Indirect Evaporative Air Cooler (IEAC)
40 Australia
41 Australia
42 Wenatchee, WA
43 T5 El Segundo, CA.
44 DCO2 Belgium 5 MW Winner Datacenter Dynamics leadership award 'Green Datacentre' 2011 & European Code of Conduct Award for new Data Centre 2011 With free cooling system: dust & pollution from surrounding farmland caused - Frequent replacement of filters - Required man power & frequent inspection - Caused pressure drop & increased fan power Solution: Munters Oasis Indirect Evaporative Cooler replaced full free cooling system
45 Sabey Intergate Quincy no. 46
46 Sabey Case Study Sabey video runs here 46
47 Data Centre Test Facility Wenatchee, WA
48 All units can be FATesting in our Data Center Test Facility Performance testing Leakage testing Controls simulations 48
49 Benefits Oasis IEC Systems Contamination Control Supply and outdoor airflow do not mix Corrosion Prevention: No added moisture/humidity to supply Usable for any kind of sweet water Rain water harvesting Eliminating DX cooling 100% IEC Cooling in some regions IEC efficiency can increase further As allowable supply air temperature to server inlet increases,
50 Thank you Questions? no. 52
Modular Data Center Cooling. Ultra High Efficiency. Oasis Optimum DCIE
Modular Data Center Cooling Ultra High Efficiency Oasis Optimum DCIE Oasis Optimum Modular Cooling Compact, Economic, Greener, Ultra High Efficiency Munters Oasis Optimum DCIE data center cooling solution
More informationExcool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling
Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by
More informationOASIS PRODUCT GUIDE. Data Centre Cooling INDIRECT EVAPORATIVE COOLER. Data Centres. Telecoms. EPX technology. Class leading performance
OASIS PRODUCT GUIDE Data Centres Telecoms EPX technology Class leading performance Fully configurable solutions INDIRECT EVAPORATIVE COOLER Data Centre Cooling 2 MUNTERS.COM/DATACENTRES Critical cooling
More informationHeat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
More informationMaximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
More informationDATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
More informationHVAC Infrastructure Retrofit Solutions
Kyoto Cooling Lunch & Learn David Belleville, APA LLC March 9, 2015 Owners choose APA solutions to: Rely on our 30+ years of delivering engineered solutions; HVAC Infrastructure Retrofit Solutions Insure
More informationMinimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com
More informationFree Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
More informationAIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
More informationGuideline for Water and Energy Considerations During Federal Data Center Consolidations
Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationEnergy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
More informationElements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
More informationIndirect Evaporative Cooling (IDEC) Unit for Data Centers
Indirect Evaporative Cooling (IDEC) Unit for Data Centers NORTEK AIR SOLUTIONS Cool3 IDEC UNIT INDIRECT EVAPORATIVE COOLING The new Nortek Air Solutions Cool 3 IDEC unit is a proven approach for highly
More informationThe Effect of Data Centre Environment on IT Reliability & Energy Consumption
The Effect of Data Centre Environment on IT Reliability & Energy Consumption Steve Strutt EMEA Technical Work Group Member IBM The Green Grid EMEA Technical Forum 2011 Agenda History of IT environmental
More informationData Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
More informationData Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
More informationPaul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA
Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale
More informationDataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
More informationEconomizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
More informationTelecityGroup plc. Outstanding data centres. Expertise you can trust.
TelecityGroup plc Outstanding data centres. Expertise you can trust. ABOUT TELECITYGROUP 2 / About TelecityGroup TelecityGroup is Europe s leading provider of premium carrier-neutral data centres. Helsinki
More informationDell s Next Generation Servers: Pushing the Limits of Data Center Cooling Cost Savings
Dell s Next Generation Servers: Pushing the Limits of Data Center Cooling Cost Savings This white paper explains how Dell s next generation of servers were developed to support fresh air cooling and overall
More informationLiebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit
Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative
More informationClimate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.
Climate solutions evaporative cooling, adiabatic humidification and programmable controllers energy saving solutions for data centers carel.com Data center air-conditioning Data center air-conditioning
More informationSpecialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
More informationFEAR Model - Review Cell Module Block
F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data
More informationDirect Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
More informationLegacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
More informationData Center Heat Rejection
This article was published in ASHRAE Journal, March 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be
More informationAlfa Laval Abatigo. Redefining adiabatic cooling
Alfa Laval Abatigo Redefining adiabatic cooling Experience and expertise recognized throughout the world With decades of broad experience and practical expertise in heat transfer, Alfa Laval is today a
More informationInterested in conducting your own webinar? Email webinars@bnpmedia.com
Interested in conducting your own webinar? Email webinars@bnpmedia.com Improving Efficiencies by Integrating Data Center Systems August 30 th, 2012 Audio Abstract Presenter Info Slides Handouts Group Chat
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationInfrastructure & Cities Sector
Technical Article Infrastructure & Cities Sector Building Technologies Division Zug (Switzerland), October 18, 2011 Saving Energy in a Data Center A Leap of Faith? New guidelines from ASHRAE (American
More informationDefining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
More informationDATA CENTERS BEST IN CLASS
Data Energy Audit Chameleon Data Center DATA CENTERS BEST IN CLASS... By Wouter Kok, MSc, Strategic Advisor Global Data Center Practice Deerns leads the way in making data centers greener, by reducing
More informationIEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM
DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM THE GLOBAL DATA CENTRE MARKET The data centre air conditioning market is expected to grow with a CAGR (compound annual growth rate) of about 12% in the next
More informationReduce data center PUE using Munters innovative cooling solutions
d a t a center applica t i o n guide Reduce data center PUE using Munters innovative cooling solutions Reduce data center energy costs by up to 75% Traditional refrigeration cooling systems are an inefficient
More informationBytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL
Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency NREL 1 National Renewable Energy Laboratory Presentation Road Map A Holistic Approach to Efficiency: Power, Packaging, Cooling, Integration
More informationAlternate Cooling Solutions for Mission Critical Facilities Stuart Lawrence National Account Sales Engineer Munters Air Treatment
Alternate Cooling Solutions for Mission Critical Facilities Stuart Lawrence National Account Sales Engineer Munters Air Treatment stuart.lawrence@munters.com 2103822646 Drivers of Alternative Approaches
More informationData Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
More informationData Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
More informationEnergy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling
Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An
More informationFree Cooling for Data Centers
Free Cooling for Data Centers Release 1, September 2015 Contents 1. Abstract... 3 2. Introduction... 3 3. Data Center Temperatures and Free Cooling... 4 4. Direct Free Cooling... 4 5. Indirect Free Cooling...
More informationAward-Winning Innovation in Data Center Cooling Design
Award-Winning Innovation in Data Center Cooling Design Oracle s Utah Compute Facility O R A C L E W H I T E P A P E R D E C E M B E R 2 0 1 4 Table of Contents Introduction 1 Overview 2 Innovation in Energy
More informationData Center Design and Energy Management
Agenda EasyStreet Online Services, Inc. Data Center Design and Energy Management Introduction to EasyStreet Speaker Bio EasyStreet Sustainability Data Center 1 (Retrofit completed May 2010) Data Center
More informationData Center Facility Basics
Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern
More informationDataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
More informationMaking Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire. http://rare-idc.herts.ac.
Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire http://rare-idc.herts.ac.uk Making Existing Server Rooms More Efficient Reduction and Re-use
More informationAERIS DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM
DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM THE GLOBAL DATA CENTRE MARKET The data centre air conditioning market is expected to grow with a CAGR (compound annual growth rate) of about 12% in the next
More informationAnalysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
More informationDealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges
More informationData Centers: Definitions, Concepts and Concerns
Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data
More informationUniversity of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
More informationThree Steps To Perfectly Green
R E S E A R C H U N D E R W R I T E R W H I T E P A P E R LEAN, CLEAN & GREEN Deerns Consulting Engineers Three Steps To Perfectly Green By Wouter M. Kok, Manager, Cleanroom, Laboratory, and Data Center
More informationTake the complication out of cooling. Data center cooling equipment and service from Alfa Laval
Take the complication out of cooling Data center cooling equipment and service from Alfa Laval How to make cooling less complicated As data grows, so does the demand for new data centers with increased
More informationChallenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,
More informationNSIDC Data Center: Energy Reduction Strategies
NSIDC Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful effort to significantly reduce
More informationIntroduction to Datacenters & the Cloud
Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview
More informationServer room guide helps energy managers reduce server consumption
Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,
More informationState of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
More informationData Centre Cooling Air Performance Metrics
Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption
More informationTrends in Data Center Design ASHRAE Leads the Way to Large Energy Savings
Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings ASHRAE Conference, Denver Otto Van Geet, PE June 24, 2014 NREL/PR-6A40-58902 NREL is a national laboratory of the U.S. Department
More informationGreen Data Center: Energy Reduction Strategies
Federal Energy ManagEment Program Green Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful
More informationWhite Paper: Free Cooling and the Efficiency of your Data Centre
AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...
More informationHow High Temperature Data Centers and Intel Technologies Decrease Operating Costs
Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features
More informationEconomizer Modes of Data Center Cooling Systems
Economizer Modes of Data Center Cooling Systems White Paper 132 Revision 0 by John Niemann John Bean Victor Avelar > Executive summary In certain climates, some cooling systems can save over 70% in annual
More informationThe Mission Critical Data Center Understand Complexity Improve Performance
The Mission Critical Data Center Understand Complexity Improve Performance Communications Technology Forum Fall 2013 Department / Presenter / Date 1 Rittal IT Solutions The State of the Data Center Market
More informationCase Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
More informationINFO HTK. Hybrid dry cooler. The reference for hybrid dry cooling. 100 4,000 kw
INFO HTK Hybrid dry cooler The reference for hybrid dry cooling 4, kw JAEGGI The Original Since 929, JAEGGI has been engaged in the development, production and sale of heat exchangers. Since 995, the company
More informationDATA CENTRE DESIGN AND
SPUSC 2008 SOUTH PACIFIC USER SERVICES CONFERENCE DATA CENTRE DESIGN AND ENERGY INITIATIVES Presented by Jarrad Clift Electrical Engineer Greenstar Accredited Presentation Content Data Centres General
More informationCapgemini UK Infrastructure Outsourcing
Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,
More informationSmarter Data Centers. Integrated Data Center Service Management
Smarter Data Centers Integrated Data Center Service Management Approx. 3.500 ton CO² is generated by: Diesel Car-6l /100 km 20.000 km Airplane 5 * Brussels-Barcelona Server, 1.5 A, 24*7*365*3.000 Kwhr
More informationDataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation.
DataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation. Dr. Rainer Weidmann, DC Architecture & DC Innovation Dr. Rainer Weidmann, DC Architecture
More informationScrew Compressors ESM 30 132 Fixed Speed & VS 30 132 Variable Speed
Screw Compressors ESM 30 132 Fixed Speed & VS 30 132 Variable Speed Rely on GD to provide the perfect fit The perfect fit to maximise productivity The growing industrial demand for compressed air requires
More informationModular Chiller Plants for data centers. Downtime isn t acceptable
Modular Chiller Plants for data centers Downtime isn t acceptable Reducing risk with Quick Start A direct solution to your most important challenge uptime. At Johnson Controls we protect our customers
More informationEuropean Business Reliance Centres when Commodity serves Green IT
European Business Reliance Centres when Commodity serves Green IT www.ebrc.com www.trusteddatacentre.com www.trustedcloudeurope.com www.trustedmanagedservices.com ebrc COMPANY PROFILE 5 datacenters = 17.000
More informationHow to build your Data Center Digitice roadshow Vaasa 3.12.2015
How to build your Data Center Digitice roadshow Vaasa 3.12.2015 Mikko Aho Sales Director 044 593 4698 1 A Strong Family The Friedhelm Loh Group a successful business 11.500 employees worldwide 78 int.
More informationHow Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
More informationSelf-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.
More informationGreen Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationEuropean Code of Conduct for Data Centre. Presentation of the Awards 2014
European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
More informationOverview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
More informationDeep Dive Think Tank: Energy Costs and Strategies for Reduction
Deep Dive Think Tank: Energy Costs and Strategies for Reduction Andrew Donoghue European research manager, Datacenter Technologies 1 Discussion points Does energy cost really matter or does uptime still
More informationHow to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
More informationASHRAE Rocky Mountain Chapter. RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc.
ASHRAE Rocky Mountain Chapter Evaporative Cooling RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc. April 19, 2013 1 Fundamentals Dry Bulb Temperature Wet Bulb Temperature
More informationQuestions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate:
Questions to be responded to by the firm submitting the application Why do you think this project should receive an award? How does it demonstrate: innovation, quality, and professional excellence transparency
More informationHPC TCO: Cooling and Computer Room Efficiency
HPC TCO: Cooling and Computer Room Efficiency 1 Route Plan Motivation (Why do we care?) HPC Building Blocks: Compuer Hardware (What s inside my dataroom? What needs to be cooled?) HPC Building Blocks:
More informationEnergy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.
Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial
More informationGREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
More informationData Centre Stockholm II, Sweden Flexible, advanced and efficient by design.
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Equinix Telecity Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 se.info@telecity.com www.telecitygroup.se
More informationGreening Data Centers
Greening Data Centers Dallas Thornton SDSC Division Director, Cyberinfrastructure Services March 2, 2011 Data Centers Are Enormous Users of Power US Data Centers (TeraWatt Hours per Year) 125 US Televisions
More informationSTULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
More informationVISIT 2010 Fujitsu Forum Europe 0
VISIT 2010 Fujitsu Forum Europe 0 Virtualization & Automation Room 13a Shaping tomorrow with you. Green Data Center Services Martin Provoost Director, Data Centers and Networks, Fujitsu UK & Ireland 14:00
More information11 Top Tips for Energy-Efficient Data Center Design and Operation
11 Top Tips for Energy-Efficient Data Center Design and Operation A High-Level How To Guide M e c h a n i c a l a n a l y s i s W h i t e P a p e r w w w. m e n t o r. c o m When is Data Center Thermal
More informationImproving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
More informationEnvironmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
More informationThe European Programme for Energy Efficiency in Data Centres: The Code of Conduct
The European Programme for Energy Efficiency in Data Centres: The Code of Conduct Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 Why Data Centres? Continuing demand for
More informationCooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
More information