1 - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008
2 Contents ABSTRACT WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM ENERGY USE OF DATA CENTRE AIR CONDITIONING SYSTEMS REDUCTION OF ENERGY USE OF DATA CENTRE AIR CONDITIONING SYSTEMS THE AIR CONDITIONING SYSTEM WITH DFC DYNAMIC FREE COOLING HOW DOES IT INCREASE EFFICIENCY... 5 A. DYNAMIC WATER TEMPERATURE CONTROL... 5 B. FREE COOLING STANDBY MANAGEMENT... 7 C. INDIRECT FREE COOLING... 8 D. DYNAMIC COMPONENT CONTROL... 8 E. OPTIMISED CASING DESIGN... 9 F. DUAL 2-WAY VALVE SYSTEM DYNAMIC FREE COOLING HOW MUCH CAN BE SAVED DYNAMIC FREE COOLING WHAT DOES IT COST AND WHAT IS THE PAYBACK PERIOD Stulz - All rights reserved Dynamic Free Cooling Rel.2 Page 2 of 10
3 Abstract Increasing energy costs and limited resources of available electricity are driving the data centre industry to the use of energy efficient technical equipment. Dynamic Free Cooling is a control concept for data centre s air conditioning systems combining Hybrid Indirect Free Cooling Precision Air Conditioning Units, fan speed controlled drycooler and speed controlled central pumps to a highly efficient precision cooling system. All system components are centrally controlled to minimise overall energy consumption depending on the ambient temperature and the room load conditions. 1. Why do I need an Energy Efficient Cooling System There are two major reasons to use an Energy Efficient Precision Cooling System for your Data Centre. The first reason is saving operating cost during the lifetime of the data centre. In today s data centre 40% of the entire data centre power input is consumed by the cooling equipment. In worst cases it reaches up to 60%. Secondly, electrical power is becoming a scarce resource and it should be used to maximise the use of the servers and not be wasted unnecessarily on powering cooling equipment. Apart from reducing costs and more efficient power management there is always an argument for green data centres with low carbon footprints using energy efficient cooling systems. 2. Energy use of Data Centre Air Conditioning Systems Data centres need air conditioning systems to remove the heat generated by the servers and other heat sources and the air conditioning systems need to be reliable and available 24/7 with built in standby redundancy. Temperature, humidity and air cleanliness have to be supplied to within the IT equipment manufacturer s specifications. There are various air conditioning systems available but all of them require significant electrical power to run the fans, compressors and pumps. Fans in the CRAC units within the room circulate the conditioned air to transfer heat from the IT equipment to the CRAC units Stulz - All rights reserved Dynamic Free Cooling Rel.2 Page 3 of 10
4 Refrigerant compressors absorb the heat directly in a direct expansion (DX) air, water or glycol system or indirectly in a chiller where chilled water is used as a secondary refrigerant. The refrigerant compressor is the largest user of electricity in the air conditioning systems. Other components that use power are the chilled water or glycol circulating pumps and condenser, drycooler or cooling tower fans that are located outside the building where heat is ultimately rejected to atmosphere. 3. Reduction of energy use of Data Centre Air Conditioning Systems Data centre air conditioning systems are usually oversized by design for further growth, redundancy and a safety factor. The additional air conditioning plant can be used to reduce overall energy. Standby units can be used to share the airflow to all units. This leads to huge amount of power savings. By doing so, heat exchanger surface of the standby units is in use as well which increases the efficiency of the total system. Logically, the mechanical refrigeration in the air conditioning system is only required when the outside ambient temperature is higher than the internal temperature of the data centre. If the ambient temperature is low, there is no need for the refrigeration compressor to operate and the room s heat can easily be transferred directly to a water/glycol solution and pumped outside the building where the heat will be transferred from the water/glycol directly to the ambient air. Ethylene glycol is added to the water to prevent the drycooler freezing in winter. The temperature of the glycol has a major influence on the efficiency of the Air Conditioning System. The higher the glycol temperature, the lower the CRAC unit s cooling capacity, but as a positive the number of hours per year where the system runs in free cooling mode increases dramatically. These circumstances can easily be used to the advantage of reducing air conditioning running costs, and is used by the DFC system Stulz - All rights reserved Dynamic Free Cooling Rel.2 Page 4 of 10
5 4. The Air Conditioning System with DFC The system described in this article consists of hybrid CRAC units located in the data centre, drycoolers located outside the building and pumps that circulate the glycol in a closed hydraulic circuit between the CRAC units and the drycooler. The hybrid CRAC units consist of speed controlled EC fans for air circulation in the data centre, closed refrigerant circuit with scroll compressors and an air-to-glycol heat exchanger for free cooling operation. The drycooler consists of a glycol-to-air heat exchanger coil with variable speed EC fans for circulating ambient air through the heat exchanger coil. The central inverter driven variable speed pump circulates the glycol between the CRAC unit and the drycooler and out of the data centre. All components involved in the air conditioning process are controlled by the microprocessor in the CRAC units with outside ambient air sensors and return air sensors in the air intake of the CRAC units. Figure 1: Free Cooling Figure 2: Compressor Cooling 5. Dynamic Free Cooling How does it increase efficiency There are various elements that make the Dynamic Free Cooling what it is and as efficient as it is. The most important elements are described here: a. Dynamic Water Temperature Control Standard indirect freecooling systems operate with fixed water or glycol temperatures for regular compressor operating mode of say 35 C at high ambient temperatures and about 7 C in free cooling mode at low ambient temperatures Stulz - All rights reserved Dynamic Free Cooling Rel.2 Page 5 of 10
6 The period of usable free cooling is very limited as the number of hours per year when the ambient air is say 3 C or lower and cold enough to produce glycol of 7 C is few. By means of DFC the glycol temperature is not fixed but fully dynamic depending on the requirements of the system. Why? It must be understood, that this system operates like a chilled water system in free cooling mode. The cooling capacity of chilled water systems depends on the water temperature, the higher the water temperature, the lower the cooling capacity. It sounds negative at this point but this behavior is used by the DFC control as a benefit. A data centre operating at full load requires in free cooling a water temperature of say 10.5 C. This 10.5 C water can be produced by the external drycooler with ambient temperatures of up to 7 C. The same data centre operating at part load of 60% also only requires 60% cooling capacity. The air conditioning system in free cooling mode can produce this 60% cooling capacity already at a much higher glycol temperature of 16 C and this glycol temperature can be achieved with an ambient temperature of 14 C. What does this mean for the period of free cooling per year: In London, 32% = 2,800h per year are below 7 C while 74% = 6,500h per year are below 14 C (Figure 3). This means, there are additional 3,700 hours or 154 days per year usable for freecooling. Traditional systems operate already in mix mode or even full compressor operation at this outdoor temperature. % of hours per year below x C 100% 95% 90% 85% 80% 75% 70% 65% 60% 55% 50% 45% 40% 35% 30% 25% 20% 15% 10% 5% 0% UK - London C -2 C -1 C 0 C 1 C 2 C 3 C 4 C 5 C 6 C 7 C 8 C 9 C 10 C 11 C 12 C 13 C 14 C 15 C 16 C 17 C 18 C 19 C 20 C 21 C 22 C 23 C 24 C 25 C 26 C 27 C 28 C 29 C 30 C Outdoor Temperature Figure 3: London, hours below x C per year 2008 Stulz - All rights reserved Dynamic Free Cooling Rel.2 Page 6 of 10
7 b. Free Cooling Standby Management Most data centres are designed with standby redundancy to cater for CRAC unit maintenance or failure. To save energy the standby units are designed to be sequenced off as they are not needed to handle the cooling load. By means of DFC the CRAC units operate in freecooling mode in a new, different way. The use of high efficiency EC fans allows automatic control of fan speed. Fan laws dictate that air volume is directly proportional to fan speed and that fan power is a cube of the fan speed (Figure 4). Therefore, by running the stand-by CRAC units at reduced speed (air volume) the overall fan power consumption is drastically reduced. It is more energy efficient to run all units including the standby CRAC units at lower speed than to shut off or sequence off the standby unit(s). This technique also provides a more even and predictable air distribution throughout the raised floor. DFC controls the CRAC units in free cooling mode in this new way and huge savings on fan power are realised. Should a DFC controlled CRAC unit be switched off the remaining units ramp up their fan speed automatically to ensure full air circulation. 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% Airflow Absorbed Power 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 1/2 Airflow Airflow 1/8 Absorbed Power Absorbed Power Figure 4: Standby Management and Cube Law 2008 Stulz - All rights reserved Dynamic Free Cooling Rel.2 Page 7 of 10
8 c. Indirect Free Cooling Dynamic Free Cooling is an indirect freecooling system. Indirect free cooling (Figure 5) uses glycol as heat transfer medium between the data centre air and ambient air at low ambient air temperatures and there is no need to introduce ambient air directly into the data centre and therefore preserving the data centres vapour seal. A very small amount of fresh air is required in the data centre to meet the local code regulations for ventilation standards. Direct freecooling systems (Figure 6) use ambient air which is must be preconditioned and pre-filtered before entering the room. Ambient air quality and conditions normally forbid the use of direct free cooling. Induced smoke can activate fire suppression systems. Dirty air requires a high degree of filtration and very regular (expensive) filter maintenance programme. Low specific moisture levels in winter require huge amount of expensive pre-humidification. Figure 5: Indirect Free Cooling Figure 6: Direct Free Cooling d. Dynamic Component Control There are four major components in the air conditioning system using energy, the compressor in the CRAC units, the fans in the CRAC units, the central pump and the fans on the drycooler outside the building. Dynamic Free Cooling controls these components depending on the room load conditions. The microprocessor controller analysis the ambient air temperature and the difference between actual and design room temperature to optimize the CRAC units components to reduce energy consumption but still maintain room conditions. The main focus is to minimise the running time of the compressors, the component using the most energy Stulz - All rights reserved Dynamic Free Cooling Rel.2 Page 8 of 10
9 Next priority is to control the remaining components as there are CRAC unit fans, drycooler fans and the central pump such that the total absorbed power is at its minimum. e. Optimised Casing Design The CRAC units used for the DFC system are optimised for high efficiency. The airflow pattern and internal components are designed to minimise air resistance. The casing itself is enlarged compared with units without freecooling for the same reason. These design measures reduce the fan power by up to 40%. f. Dual 2-Way Valve System The hydraulic system is designed with the use of two 2-way valves in a way that the glycol quantity circulating in the system is absorbing the largest possible amount of heat in the CRAC unit, either in freecooling, mix or compressor cooling mode. The glycol quantity circulating the system is reduced and the required pump power is minimised. 6. Dynamic Free Cooling How much can be saved By use of Dynamic Free Cooling savings up to 60% can be reached. The savings depend on several points. The geographical location (annual temperature profile), the comparison system, the standby quantity, the design room temperature and the percentage of actual IT equipment cooling load installed compared with the peak design. Calculation software to compare different systems taking into consideration all the above variables is helpful for a selection. Manual calculations are complex but possible and usually take several days for one comparison only Stulz - All rights reserved Dynamic Free Cooling Rel.2 Page 9 of 10
10 +60% -58% Figure 7: Example, 120kW Data Centre, London 7. Dynamic Free Cooling What does it cost and what is the payback period The capital cost for a Dynamic Free Cooling system compared with a basic air cooled system can be up to 50% more. However, the savings of operating cost are huge; typically the payback period is from less than 1 year up to 3 years. About the Author: Benjamin Petschke is Head of Product Management and Sales Support. After studying physics he joined Stulz in 1996 as R&D engineer. In 1997 he changed to the sales department and worked in different positions. Benjamin Petschke is specialised in data center design regarding air conditioning, energy saving and acoustic issues. About Stulz GmbH: Founded in 1947 in Germany, Stulz has specialized in areas requiring technological expertise and entrepreneurial flexibility. The family owned company looks back at more than 30 years of experience in precision air conditioning for data centres. Being a true global player Stulz is present today in over 100 countries worldwide with production sites in Germany, USA, Italy, China and India Stulz - All rights reserved Dynamic Free Cooling Rel.2 Page 10 of 10
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
News in Data Center Cooling
News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
Free Cooling for Data Centers
Free Cooling for Data Centers Release 1, September 2015 Contents 1. Abstract... 3 2. Introduction... 3 3. Data Center Temperatures and Free Cooling... 4 4. Direct Free Cooling... 4 5. Indirect Free Cooling...
European Code of Conduct for Data Centre. Presentation of the Awards 2014
European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
National Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
STULZ View On DataCenter Cooling
STULZ View On DataCenter Cooling Stulz Was Founded In Hamburg (Germany) In 1947 And Has 5 Production Sites And 14 Subsidiaries In 14 Countries. We Are Represented By Partners In Over 110 Countries. Stulz
Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA
Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale
Drives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.
Climate solutions evaporative cooling, adiabatic humidification and programmable controllers energy saving solutions for data centers carel.com Data center air-conditioning Data center air-conditioning
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
IT Cooling Solutions. DFC² Direct Free Cooling for Data Centres. Energy-efficient, reliable and available around the world
IT Cooling Solutions DFC² Direct Free Cooling for Data Centres Energy-efficient, reliable and available around the world Worldwide Green Engineering with Direct Free Cooling from STULZ Forward thinking
Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)
Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
AIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
IT Cooling Solutions. DFC² Direct Free Cooling for Data Centres. Energy-efficient, reliable and available around the world
IT Cooling Solutions DFC² Direct Free Cooling for Data Centres Energy-efficient, reliable and available around the world Worldwide Green Engineering with Direct Free Cooling from STULZ Forward thinking
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling
Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by
Legacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
60-150kW. For more information on Airedale visit www.barbourproductsearch.info SmartCool. 0-150kW. > SmartCool. www.airedale.com
60-150kW 0-150kW > Next generation precision air conditioning Typical applications > Data centres and computer rooms > Telecommunications and ISP facilities > Clean rooms > Switching stations > Laboratories
Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new
Data Center Ultra-Efficient chilled water system optimization White paper File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new Data Center - Ultra-Efficient white paper 3 abstract The primary
STULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
White Paper Rack climate control in data centres
White Paper Rack climate control in data centres Contents Contents...2 List of illustrations... 3 Executive summary...4 Introduction...5 Objectives and requirements...6 Room climate control with the CRAC
An Introduction to Cold Aisle Containment Systems in the Data Centre
An Introduction to Cold Aisle Containment Systems in the Data Centre White Paper October 2010 By Zac Potts MEng Mechanical Engineer Sudlows October 2010 An Introduction to Cold Aisle Containment Systems
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units
CoolTeg Plus Chilled Water (CW) version: AC-TCW
version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420
The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity
Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings
DataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes
Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,
In Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
Drives and motors. A guide to using variable-speed drives and motors in data centres
Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers
Example Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
European Code of Conduct for Data Centre. Presentation of the Awards 2016
European Code of Conduct for Data Centre Presentation of the Awards 2016 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
Technical Systems. Helen Bedford
Technical Systems in Data Centres Helen Bedford Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre
How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners
How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners White Paper #56 Revision 2 Executive Summary Today's technology rooms require precise, stable environments in order for
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA CENTRES
AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA GLOBAL DATA CENTRE IP TRAFFIC WILL TRIPLE WITHIN 5 YEARS Global data centre IP traffic has set a constant growth path, with
CRAC Precision climate control units for data centres
CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
Why Do I Need Precision Air Conditioning?
Why Do I Need Precision Air Conditioning? Executive Summary Today's technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Printing and Publishing Energy Savings Guide
Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems
Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may
Chilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling
How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling Abstract Data center managers are increasingly in search of methods and technologies for
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
White Paper #10. Energy Efficiency in Computer Data Centers
s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular
System solution for data centres
1 System solution for data centres Energy-efficient air conditioning with ServeLine Cooling IT infrastructure, high availability, low energy costs and communication with DCIM systems all in one from your
INFO HTK. Hybrid dry cooler. The reference for hybrid dry cooling. 100 4,000 kw
INFO HTK Hybrid dry cooler The reference for hybrid dry cooling 4, kw JAEGGI The Original Since 929, JAEGGI has been engaged in the development, production and sale of heat exchangers. Since 995, the company
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat
AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
Variable-Speed Fan Retrofits for Computer-Room Air Conditioners
Variable-Speed Fan Retrofits for Computer-Room Air Conditioners Prepared for the U.S. Department of Energy Federal Energy Management Program Technology Case Study Bulletin By Lawrence Berkeley National
Data Centre. Flexible, high efficiency cooling solutions. www.airedale.com CONDITIONING CONDENSING UNITS CONTROLS SERVICE TRAINING
Sector Data Centre Data Centre Flexible, high efficiency cooling solutions IT COOLING PRISION AIR CONDITIONING CHILLERS CONDENSERS & CONDENSING UNITS www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools
Heat Recovery Dehumidification (HRD) system Designed for municipal swimming pools A dehumidification and ventilation system with dynamic heat pump heat recovery to swimming pool water and air ENVIRONMENTAL
HEATING, VENTILATION & AIR CONDITIONING
HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating
Data Centres A complete solution to noise control and acoustic packages
Data Centres A complete solution to noise control and acoustic packages Introduction World class noise control. Expertise you can trust. IAC Acoustics is world-renowned for providing cost effective solutions
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
Excool Data Centre Cooling Product Comparison Report
Excool Data Centre Cooling Product Comparison Report Desktop Study Job No: 1003780 Date: October 2011 Cundall Johnston and Partners LLP Saffron House 6-10 Kirby Street London EC1N 8TS tel 020 7438 1600
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.
MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating
How to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Innovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
Eni Green Data Center - Specification
Eni Green Data Center - Specification Green IT Adopting the principles of sustainable development is one of the key missions in the field of information technology today. 2% of the world s CO2 emissions
Daikin Altherma. hybrid heat pump. The natural combination
Daikin Altherma hybrid heat pump The natural combination Why choose Daikin? As an industry leader, Daikin combines broad experience, technical innovation and responsive customer service to help you meet
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
Cooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
The natural ombination
The natural ombination DAikin Altherma Hybrid heat pump system The future is now The new hybrid system Heat pump solution for gas boiler replacement market Daikin Altherma hybrid combines heat pump technology
ASTACEA4 Inspect complex/central air conditioning systems
Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air
CONTROL STRATEGIES FOR HVAC SYSTEMS
CONROL SRAEGIES FOR HVAC SYSEMS ZBIGNIEW POPIOLEK Department of Heating, Ventilation and Dust Removal echnology Silesian University of echnology, Poland 1 Definition of control: to apply a regulating influence
Data Centre. Flexible, high efficiency cooling solutions. www.airedale.com CONDITIONING CONDENSING UNITS CONTROLS SERVICE TRAINING
Sector Data Centre Data Centre Flexible, high efficiency cooling solutions IT COOLING PRISION AIR CONDITIONING CHILLERS CONDENSERS & CONDENSING UNITS www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY
Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit
Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative
I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility
Economizer Modes of Data Center Cooling Systems
Economizer Modes of Data Center Cooling Systems White Paper 132 Revision 0 by John Niemann John Bean Victor Avelar > Executive summary In certain climates, some cooling systems can save over 70% in annual