Hospital Application Guide. Cost-effective climate control for hospitals
|
|
|
- Ralph Cook
- 9 years ago
- Views:
Transcription
1 Hospital Application Guide Cost-effective climate control for hospitals
2 Munters is the world leader in dehumidification Munters is the largest manufacturer of dehumidifiers in the world. Since developing the first desiccant dehumidifier in the late 1930 s, Munters has continued to innovate in the fields of dehumidification and energy recovery. Our long history and extensive expertise in dehumidification makes us the premier choice for your dehumidification needs. Controlling humidity in hospitals is obviously important, but the fear of mold and bacteria is not what is truly driving the requirement for dehumidification equipment. Surgeons are demanding cooler, drier operating room conditions. Hospital administration has prioritized indoor environmental conditions not just for the safety of the patient, but also to improve the efficiency and quality of work life for the surgeon. Many times surgeon discomfort is obvious. The multiple layers of clothing, face masks, hair covers, and protective gloves are uncomfortable as they trap in body heat and exacerbate perspiration. The key is to select the most efficient climate control technologies to eliminate wasted expense impacting operating costs. Given the current climate of product and/or service liability in the health care industry, and the close tolerance for indoor conditions specified by surgical equipment manufacturers, hospitals have to invest periodically in upgrades to existing HVAC systems or acquiring new systems altogether. Munters, The Humidity Expert Our extensive knowledge and experience makes us the premier choice for your dehumidification needs. Hospital Application Guide 1
3 Efficient ventilation solutions for hospitals Hospital engineers are challenged with the daunting task of employing HVAC systems that provide the proper amount of fresh outside air, filtration, air changes, and temperature and humidity control. The proper selection and sizing of dehumidification equipment is critical for the HVAC system efficiency and basic hospital operation Dry Bulb Temperature F Figure 1: Hospital design conditions 90% 80% 70% 60% 50% 40% Operating Rooms 60 F, 50% RH 20% 10% Outside Air 83 F, 133 gr/lb, 80% RH Common Areas 75 F, 50% RH Humidity Ratio Grains of Moisture per Pound of Dry Air (gr/lb) operations that require cooler space conditions need substantially drier supplied air in order to maintain 50% space relative humidity. Common areas are generally maintained at 75 F and 50% RH, which equates to a 55 F dewpoint. Operating rooms are often maintained at 60 F and also must be kept at 50% RH, but this equates to a 41 F dewpoint. This exact relationship represents the difficulty in designing HVAC equipment to maintain cooler operating room conditions. Both set points equate to 50% relative humidity, but the cooler set point requires substantially drier air. 1. General comfort is significantly higher with RH maintained below 60%. 2. Perspiration issues are minimized with RH maintained below 60%. 3. Mold, mildew and fungi all feed on moisture. 4. Higher relative humidity increases the likelihood that condensation and fogging will occur on magnifying lenses and polished metal working apparatus. Condensation prevention In hospital environments, it is critical that condensation be prevented. Computers, electrical machines and lighting all create high cooling loads. In order to offset these loads, cold air is conveyed throughout the building to maintain space temperature set-points. Ductwork, distribution grills and any adjacent surfaces will be cooler than air temperature set-point and will be areas of condensation formation if the temperature of the surface is below the space dew point. Ventilation air represents the largest potential for introducing unwanted moisture into a space. For example, in Greensboro, North Carolina, each 1000 CFM of fresh air represents 7.1 gallons per hour of water relative to space setpoint of 60 F / 50% RH. Conventional equipment that heats and cools air can remove some of this moisture if the cooling load is high enough. TMY weather bin data indicates 3623 total hours in Greensboro, NC where the ambient dewpoint is above 55 F. The ambient temperature is below 75 F 2,418 of these hours. 66.7% of the dehumidification season is cool and wet simultaneously. During these times, conventional equipment will be off, or cycling on and off. This is the reason why the use of thermostat controlled conventional equipment commonly results in a building with high relative humidity, condensation and mold issues. A simple solution for maintaining accurate humidity levels in the building is to control dewpoint in addition to controlling temperature. By utilizing dewpoint control the indoor environmental conditions will be more manageable. 2 Hospital Application Guide
4 OA pre-conditioning design guidelines: 1. Positively dehumidify all makeup air to required dew point. 2. Account for internal latent load. People load, open water and infiltration all represent internal sources of moisture. Dehumidification equipment must supply air with a lower dewpoint than the desired space dewpoint to support these internal loads- similar to cooling equipment that must support loads from solar gain, lighting motors, by delivering air cooler than the space temperature. 3. Reheat is required to prevent over-cooling the space. This is especially critical for operating room applications (considering the conventional method for achieving 40 F dewpoint is to over cool the air to 40 F). Reheat location can differ based on the hospitals needs and/or to prevent duct condensation, but applying reheat at the site of the AHU restricts the individual control of conditions in surgical suites. Low-temp chiller approach The low-temp chiller approach for dehumidifying operating rooms is to mix ventilation air with return air and then cool the entire air stream to 40 F. Since 40 F supply air can not be achieved utilizing typical chilled water, this is generally a two step process. The first stage uses normal chilled water; for example, 42 F that cools partially toward the 40 F air temperature goal. The final stage utilizes a lower temperature chilled water/brine mixture to achieve the necessary 40 F air. Because this air is too cold, reheat is applied as needed at each zone to maintain temperature set-point. To simplify this approach, designs often use a one stage approach where the entire dehumidification process is accomplished with one large coil served with 35 F water/brine mixture. Challenges with this approach are: 1. A low temperature chiller has 35 F 42 F Low Temp 45 F 52 F Chiller a 20% first cost premium Chiller Plant compared to an equivalent tonnage standard chiller. Supply Air 40 F 36.5 gr/lb 55 F 2. The KW/Ton is approximately 22% 64 gr/lb higher for a low temperature chiller vs. an equivalent tonnage standard chiller. Reheat Boxes 57 F LAT F is the lowest dew point that can reasonably be achieved without the risk of freezing the chilled water coil. All of the air must be cooled to this dew point to achieve Suite 1 Suite 2 Suite 3 the desired space humidity and substantial sensible cooling must Figure 2: Low-temp chiller approach be consumed before any moisture is condensed. 4. Substantial reheat energy is required to prevent over-cooling of served areas. Return Air 8,000 cfm 60 F, 40gr/lb 5. Either a separate chiller is required or the whole chilled water system needs to be low temperature type. 6. Conveying cold saturated air from the main air handler to reheat boxes will challenge insulation to prevent condensation on duct exteriors. 7. Any apparatus, such as filters, will create condensate down stream of the chilled water coil. Saturated air moving across any pressure loss device will condense F water/brine mixture requires better piping insulation package in order to prevent condensation F water/brine mixture has a higher probability of leaking at connection areas. 10. The air handler system for the low-temp chilled water approach should include construction that limits through metal from the inside to outside. If mounted inside or outside, the air handler surrounding dewpoint will often be higher than 40 F, and any through metal area will sweat profusely. Air handler door frames, wall panels and through connections should include a thermal break. This construction is not conventional and will be more expensive compared to a typical air handler. Dehum Cooling Coil Stage 2 Dehum Cooling Coil Stage 1 Heating Coil (Winter) Mixed Air 68 F 71gr/lb Suite 4 Outside Air 4,000 cfm 83 F, 133 gr/lb Microbiological Growth Many bacteria flourish in humid air. According to a study done by Pennsylvania State University, the bacteria responsible for Legionnaire s disease (Legionella pneumophila) survive best at a Relative Humidity of 65%. At 35% RH, the bacterium dies quite rapidly. Many viruses also thrive in high humidity. The Polio virus not only survives, but multiplies when air is above 80% RH. Fungi and dust mites also thrive in humid building materials, which can lead to musty odors and respiratory problems associated with sick building syndrome. The high humidity in ductwork downstream for cooling coils is, unfortunately, an ideal environment for these organisms. (Below): Bacteria growth caused by saturated duct conditions will be significantly minimized with a desiccant air handling system. Hospital Application Guide 3
5 Dry Air Reactivation Air Figure 3: Desiccant wheel illustration Desiccant dehumidifiers Wet Air Pre-Cooled Outside Air Desiccant dehumidifiers utilize a desiccant wheel to provide dehumidification of the supply air. The operation of a desiccant wheel is based on the principal of sorption. Sorption is the adsorption or the absorption process by which desiccant removes water vapor directly from air. Most commonly, desiccant is embedded within a rotary bed (rotor or wheel). The wheel is split into two sectors; the supply air stream and reactivation air stream are continuously rotated in order to provide the dehumidification process. Once the wheel absorbs moisture, the moisture must be driven off of the wheel during a "reactivation process." The desiccant wheel rotates into a secondary air stream (reactivation air) where water vapor is transferred to heated air, and exhausted. Reactivation temperature can range from 110 F to over 300 F depending on application. Generally, the drier the air requirements, the warmer the reactivation air must be. As supply air is dried through the desiccant, it is simultaneously heated. For example, 55 F saturated air (64 gr/lb) entering will leave at 97 F and 29 gr/lb. Rotor speed is generally eight revolutions per hour. Most of the heat associated with the drying process is converted latent energy. Desiccant approach Desiccant technology is widely viewed as the most viable method to generate air lower than a 45 F dewpoint. In fact, for applications requiring dewpoints below 35 F, desiccant dehumidification is the most reliable and modern approach utilized. Since hospital applications require cooler temperatures and lower dewpoints, desiccant technology is an optimal method to achieve operating room conditions and helps reduce the cost of equipment investment. Note the following: 1. The cost to operate a desiccant approach will be approximately 40% less then the low temp chiller approach. 2. Desiccant pre-cooling and final post cooling requirements are achieved using standard temperature chilled water. The added cost for a special low temperature chiller is removed. The inefficiency associated with a low temperature chiller is also removed. 3. Since desiccant dehumidification can easily achieve dewpoints lower than Desiccant Dehumidification Approach Figure 4: Desiccant dehumidification approach 40 F, only a portion of the total supply air only needs to be dehumidified. This allows for greater system design flexibility. In this example, only the outside air requirements are dehumidified. All the work associated with sensibly cooling the supply air to dewpoint is removed from the equation. 4. Cooling fluid is warmer reducing the chance for pipe condensation. 5. Cooling fluid does not require brine mixture, removing the added propensity for leaks, and removing the cost of maintaining correct fluid chemistry. 6. Supply air is not over-cooled dramatically reducing the reheat energy required at each zone. 7. Conveyed air is not cold and saturated, which reduces chance for duct condensation, and condensation across pressure loss apparatus within the supply duct. Supply Air Reheat Boxes 57 F LAT Post-Cooling Coil (Sensible Only) 42 F 52 F Heating Coil (Winter) Chiller Plant 57 F Mixed Air 36.5 gr/lb 70 F 97 F 36.5 gr/lb 29 gr/lb Conclusion The medical industry is advancing at a quick pace, and so are the dehumidification technologies. It is critical that design engineers identify the required space temperature and dewpoint conditions to determine what dehumidification equipment will meet the needs of the hospital. When choosing the equipment, in addition to precise space condition control, engineers should also consider methods to improve the total operation of the hospital. With increased utility costs, design engineers are opting for more reliable and energy efficient dehumidification options. Dehumidification of surgical suites is achievable with many technologies, but with the growing demand for colder and drier operating rooms, selecting the proper equipment is more important than ever. Choose equipment wisely, it is not only important for the hospitals bottom lineyour life may depend on it. Suite 1 Suite 2 Suite 3 Desiccant Wheel 42 F 52 F 55 F 64 gr/lb Suite 4 Pre-Cooling Coil Outside Air 4,000 cfm 83 F, 133 gr/lb Return Air 8,000 cfm 60 F, 40 gr/lb 4 Hospital Application Guide
6 Munters is a global leader in energy efficient air treatment solutions. Munters manufactures engineered products that can economically control humidity and temperature, provide energy recovery, and/or utilize direct or indirect evaporative cooling for comfort, process and environmental protection. With permanent or temporary solutions, Munters offers a wide variety of options to meet specific climate, application and budget requirements. Munters has net sales approaching $1 billion USD with more than 20 manufacturing facilities across the globe and sales offices in over 30 countries. Munters employs approximately 4,300 people worldwide. For more information see Munters Corporation Tel: (800) [email protected] AG /09
By Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air Trevor Wende Vice President, Marketing Advantix Systems, Inc. 0 Humidity: The Hidden Cost Driver Conventional A/C process Start
Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!
Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air 0 Optimal Air Quality: Critical to Hotels Provides comfortable environment for guests no overcooling Protects building, carpets
Moisture Control. It s The Dew Point. Stupid! Its not the humidity.
Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA [email protected] 805 687-3175 Matching great technology to market need! Topics SHR
Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems
APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage
Dehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Pool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
ENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Chilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
Innovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
Molds and mildew are fungi that grow
Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
What is LEED? Why pursue LEED accreditation? How does LEED accomplish these goals? Sustainable sites Water efficiency Energy and Atmosphere
Green AAON for What is LEED? Sustainability and green have recently become terms used within the building industry (and others) to refer to a construction project that has low environmental impact, or
Bring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015
Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
Indoor Air Quality FILL YOUR HOME WITH AIR THAT IS AS CLEAN AS IT IS COMFORTABLE. READ ONLY
Indoor Air Quality FILL YOUR HOME WITH AIR THAT IS AS CLEAN AS IT IS COMFORTABLE. QUALITY AIR STARTS HERE. AccuExchange Energy Recovery Ventilator Improve your home s indoor environment by exchanging stale
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates
Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb
Dedicated Outdoor Air Systems (D.O.A.S.)
Commercial and Industrial Climate Control Systems Dedicated Outdoor Air Systems (D.O.A.S.) AMDOAS-1 What is it? Why use one? What are my options? Selection considerations Design steps What is it? A separate
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
Matching the Sensible Heat Ratio of Air Conditioning Equipment with the Building Load SHR
Matching the Sensible Heat Ratio of Air Conditioning Equipment with the Building Load SHR Final Report to: Airxchange November 12, 2003 Report prepared by: TIAX LLC Reference D5186 Notice: This report
Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools
Heat Recovery Dehumidification (HRD) system Designed for municipal swimming pools A dehumidification and ventilation system with dynamic heat pump heat recovery to swimming pool water and air ENVIRONMENTAL
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
Biological Contamination in the HVAC System
Biological Contamination in the HVAC System by Chin S. Yang, Ph.D. P & K Microbiology Services, Inc. Cherry Hill, New Jersey The heating, ventilating, and air-conditioning system (HVAC) in a building is
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system
*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.
Dow Chemical is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members.
Ventilation Solutions Fresh Air Solutions for Ductless Heating & Cooling. fantech
Ventilation Solutions Fresh Air Solutions for Ductless Heating & Cooling 2 Ductless Ventilation & Fresh Air Solutions We can fill your home with healthy, fresh air Indoor Air Pollution is real, and it
Whole House Dehumidification for Occupant Comfort and Energy Savings
Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
Mold Alert... Operation Manual P0270
Mold Alert... Operation Manual P0270 introduction Congratulations on your purchase of the P0270 Mold Alert! Mold is as old as the Earth and it s everywhere. Under the right set of conditions, it can actually
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem
Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
Temperature and Humidity
Temperature and Humidity Overview Water vapor is a very important gas in the atmosphere and can influence many things like condensation and the formation of clouds and rain, as well as how hot or cold
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects
4.02.08 updated Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects Moisture Removal Systems www.groundheaters.com www.wackerneuson.com Controlling moisture
Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects
Makeup Air For Exhaust Systems In Tight Houses Tony Jellen Engineering Projects PA Housing & Land Development Conference February 23, 2012 Effects of Kitchen Ventilation on Residential Dwellings Anthony
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
Energy Efficiency in Industrial HVAC Systems
Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Preliminary Final Proposal
1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient
Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the
Refrigeration and Air Conditioning Prof M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 38 Air Conditioning Systems Welcome back in the last lecture
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE <[email protected]
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE
Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
To provide good indoor air quality
Conditioning Ventilation Air for Improved Performance and Air Quality The practice of using a mixing chamber for mixing outdoor and return in a single system should be replaced by a technique with two
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
IT S NOT THE HEAT, IT S THE HUMIDITY.
IT S NOT THE HEAT, IT S THE HUMIDITY. Before the invention of air conditioning, if you wanted to control indoor humidity you d just open a window or door. Unfortunately, that was a moot exercise if it
newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer
engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems
Answers to Your Questions from the Webinar
2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in
Humidification Strategies for Data Centers and Network Rooms
Humidification Strategies for Data Centers and Network Rooms By Tony Evans White Paper #58 Revision 1 Executive Summary The control of humidity in Information Technology environments is essential to achieving
Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
Air Conditioning Clinic
Air Conditioning Clinic Introduction to HVAC Systems One of the Systems Series February 2012 TRG-TRC018-EN Introduction to HVAC Systems One of the Systems Series A publication of Trane Preface Introduction
How air conditioning works
1 How air conditioning works The essential ingredients in an air conditioning system are a fan to blow air around, a cold surface to cool and dehumidify the air, a warm surface and a source of water vapour.
Knowledge for optimal efficiency
Engineering Onboard Climate Control Knowledge for optimal efficiency MARINE HVAC-R MARINE HVAC-R ADVANTAGES 2 KNOWLEDGE FOR OPTIMAL EFFICIENCY The BRONSWERK Advantage It s like the ideal day at sea when
Role of Economizers in Dedicated Outdoor Air Systems
Introduction: Role of Economizers in Dedicated Outdoor Air Systems A question that frequently arises when a dedicated outdoor air system (DOAS) (Mumma, 2001) is discussed, particularly when the parallel
White Paper #10. Energy Efficiency in Computer Data Centers
s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular
Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010
Air Water Vapor Mixtures: Psychrometrics Leon R. Glicksman c 1996, 2010 Introduction To establish proper comfort conditions within a building space, the designer must consider the air temperature and the
HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.
Reducing Building HVAC Costs of site rec By Stephen J. Pargeter Building owners are caught between two powerful forces the need to lower energy costs and the need to meet or exceed outdoor air ventilation
Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Design Options for HVAC Distribution Systems
Design Options for HVAC Distribution Systems Course No: M06-017 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877)
The HVAC Process: Changing the Properties of Air
The HVAC Process: Changing the Properties of Air Alexander Delli Paoli, Jr. ABSTRACT This discussion addresses the physical properties of air and water vapor mixtures. The components of the heating, ventilation,
HEATING, VENTILATION & AIR CONDITIONING
HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating
Home inspectors are not mold inspectors, however they do inspect for defects that
CONDENSATION IN THE WALLS Home inspectors are not mold inspectors, however they do inspect for defects that can result in mold. Mold grows in wet or damp environments. Defects that result in a wet or damp
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
Humidity, Condensation, Clouds, and Fog. Water in the Atmosphere
Humidity, Condensation, Clouds, and Fog or Water in the Atmosphere The Hydrologic Cycle Where the Water Exists on Earth Evaporation From the Oceans and Land The Source of Water Vapor for the Atmosphere
Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
Humid Air. Water vapor in air. Trace Glasses 1% Argon (A) Water vapor (H 2
Humid Air Water vapor in air Oxygen 21% Trace Glasses 1% Argon (A) Water vapor (H 2 O) Carbon dioxide (CO 2 ) Neon (Ne) Helium (He) Krypton (Kr) Hydrogen (H) Ozone (O 3 ) Nitrogen 78% Humid Air Water vapor
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
Absolute and relative humidity Precise and comfort air-conditioning
Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013
The Fundamentals of HVAC: What Shapes the Storage Environment Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013 Introduction Presenter Jeremy Linden, Preservation
Basic Mold Prevention
Basic Mold Prevention Mold is a form of fungi and a part of nature. Just as other plants produce seeds to reproduce themselves, mold produces tiny spores to reproduce itself. These spores are floating
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent
Residential HVAC System Sizing
Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: [email protected] SUMMARY Heating, ventilating and air-conditioning (HVAC)
Principles of Rice Drying How does rice dry?
Principles of Rice Drying James F. Thompson June 30, 1998 How does rice dry? Rice gains or loses moisture based on its moisture and the humidity of the air around it. If the humidity is low, high moisture
Wet Bulb Temperature and Its Impact on Building Performance
Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?
Drives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
Building Re-Tuning Training Guide: AHU Heating and Cooling Control
Building Re-Tuning Training Guide: AHU Heating and Cooling Control Summary The purpose of the air-handling unit (AHU) heating and cooling control guide is to show, through examples of good and bad operations,
HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget
A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable