DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers
|
|
|
- Stephany McDaniel
- 10 years ago
- Views:
Transcription
1 DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and Facility Managers Building Cooling Systems Building Technologies Operations and Maintenance Operating Engineers/Building Technicians Building Cooling Systems Operations and Maintenance Expected Results for Those Completing this Training Develop plans for and implement processes to control temperature and air volume in high- intensity data centers based on new ASHRAE TC 9.9 information. ASHRAE TC 9.9 Guidelines and General Energy Efficiency in Data Center Resources To learn more about data center energy efficiency, check these resources. FEMP: Data Center Energy Efficiency Page 1
2 ASHRAE Technical Committee Thermal Guidelines for Data Processing Environments Expanded Data Center Classes and Usage Guidance data- center/it_it/static/pdf/ashrae_1.pdf FEMP Training for Data Centers Labs, Data Centers, and High- Tech Facilities First Thursday Seminar: There are multiple opportunities for you to view the Data Center Profiler (DCPro) Tool Training Webinar. Check for dates and times. Glossary of Lighting Technology Terms ACAE - Air Conditioning Airflow Efficiency, the amount of heat removed per standard cubic foot of airflow per minute. AHU - Air Handling Unit. Air Mixing - The unintended mixing of cold and hot air. Airside Economizer - A device consisting of fans, ducting and a control which utilizes outside air directly to cool the data center when environmental conditions allow. Air is typically filtered, brought into existing distribution system and then exhausted back to the atmosphere. Aisle - The open space between rows of racks. Best- practice dictates racks should be arranged with consistent orientation of front and back to create cold' and hot' aisles. ASHRAE - American Society of Heating, Refrigerating and Air- Conditioning Engineers founded in 1894, is a building technology society with more than 50,000 members worldwide. The Society and its members focus on building systems, energy efficiency, indoor air quality and sustainability within the industry. Through research, standards writing, publishing and continuing education, ASHRAE shapes tomorrow s built environment today. Blanking Panel - A device mounted in unused U spaces in a rack that restricts recirculation airflow, also called blanking or filler plates. Page 2
3 BMS - Building Management System, synonymous with BAS, AMS and other computer- based control systems installed in buildings to control and monitor the building s mechanical and electrical equipment. Bypass Airflow - Conditioned air that does not reach computer equipment. With fixed speed fans (common in DX equipment), some bypass air is inevitable and without containment, some bypass air is prudent. Unintended bypass air can occur by escaping through cable cut- outs, holes under cabinets, misplaced perforated tiles or holes in the computer room perimeter walls. CAC - Cold Aisle Containment system that directs cooled air from air conditioning equipment to the inlet side of racks in a highly efficient manner. CADE - Corporate Average Data Center Efficiency. Conditioned Air - Air controlled in terms of temperature, humidity, and particles per thousand. CFD - Computational Fluid Dynamics, a numerical analysis technique commonly used in the analysis of airflow in data centers. Chilled beams - Units which, by natural convection from a finned heat exchanger, cool the air in a room. Chiller - A unit consisting of a compressor, a condensing section and an expansion section. The condensing and expansion sections nearly always have water or glycol as the heat transfer agent to the rest of the system; primary water/glycol on the condensing side and secondary water on the expansion side. Class A1 - Used to classify IT Equipment that is suitable for deployment within a data center with tightly controlled environmental parameters (dew point, temperature, and relative humidity) and mission critical operations; types of products typically designed for this environment are enterprise servers and storage products. Class A2 - Used to classify IT Equipment that is suitable for deployment within an information technology space or office or lab environment with some control of environmental parameters (dew point, temperature, and relative humidity); types of products typically designed for this environment are volume servers, storage products, personal computers, and workstations. Class A3/A4 - Used to classify IT Equipment that is suitable for deployment within an information technology space or office or lab environment with some control of environmental parameters (dew point, temperature, and relative humidity); types of products typically designed for this environment are volume servers, storage products, personal computers, and workstations. Page 3
4 Class B - Used to classify IT Equipment that is suitable for deployment within an office, home, or transportable environment with minimal control of environmental parameters (temperature only); types of products typically designed for this environment are personal computers, workstations, laptops, and printers. Class C - Used to classify IT Equipment that is suitable for deployment within a point- of- sale or light industrial or factory environment with weather protection, sufficient winter heating and ventilation; types of products typically designed for this environment are point- of- sale equipment, ruggedized controllers, or computers and PDAs. Close- Coupled Cooling - Cooling technology that is installed adjacent to server racks, minimizing the path that air must flow from the cooling unit through the IT equipment and back to the cooling unit. Cold Aisle - An aisle where rack fronts face into the aisle. Supply (cold) airflow is directed into this aisle so that it can then more readily enter the fronts of the racks. Cold Spot - An area where ambient air temperature is below desired levels. Typically caused by ineffective airflow management necessitating a temperature set point lower than that which would be required with proper airflow management. Constant Air Volume (CAV) Systems - the temperature of the air supplied to the building can vary, but the air flow rate is kept constant. Cooling panels - Cold water flows through an aluminum plate, which transfers heat from the air to the cold water. The panel cools the warm room air and also cools the room s surfaces by low- temperature radiation. Cooling Tower - A device which cools water via the direct evaporation of some of the water. Water is pumped into the top of the cooling tower and allowed to run down over the fill, typically pads or strips into a sump at the bottom of the cooling tower. Air is drawn in from the sides over the fill by fans in the top of the tower, evaporating some of the water, which cools the remaining water. The temperature of the water in the sump is controlled by varying the speed of the fans. The water in the sump is then used to cool the condensing section of a chiller or to cool the secondary loop directly via a heat exchanger (see water side economizer). CRAC - Computer room air conditioner (pronounced crack), which uses refrigerant and a compressor. Cooling of the air in the data center is accomplished by airflow over the evaporation coils where the refrigerant is being "directly expanded" (see DX). CRAH - Computer Room Air Handler (pronounced craw) which uses chilled water passing through a heat exchanger to cool air flowing over the heat exchanger. Page 4
5 Critical Load - Computer equipment whose uptime is non- interruptible, typically supported by a UPS. CSI - Cold Supply Infiltration index, quantifies the amount of hot air mixing with cold inlet air prior to entering the rack. Cutout - An open area in a raised floor that allows airflow or cable feeds. DCie - Data Center Infrastructure Efficiency Dead Band - A control technique which prevents oscillation or unnecessary cycling of a controlled variable. In data center cooling, it typically applies to the action of the CRAC or CRAH relative to the set point. A certain amount of dead band around the set point prevents unnecessary cycling of the compressor or chilled water valve. Delta T - The difference in temperature across a device. Examples include the temperature difference between the inlet and outlet of piece of IT equipment or between the inlet and outlet of a cooling unit (CRAC or CRAH). Delta T, airflow and thermal dissipation are related: thermal dissipation = airflow x delta T x specific heat of air. Dewpoint - The temperature at which air reaches water vapor saturation. Dewpoint is constant for a specific amount of water in a specific amount of air while relative humidity varies with temperature. The latest ASHRAE TC 9.9 Thermal Guidelines for data center environmental conditions includes an upper limit for humidity based on dewpoint. D/H - Dehumidifying/Humidifying. Dry- Bulb Temperature - The temperature of the air measured using a dry- bulb thermometer such that evaporative cooling has no effect. Typically taken in conjunction with a wet- bulb reading which does include the evaporative cooling effect in order to determine relative humidity. Dry Cooler - A liquid- to- air heat exchanger that is a radiator over which air is blown via fans. Typically used as the heat rejection device for water or glycol cooled condensers, may also be used as the heat rejection device for liquid cooled coils in an AHU under proper environmental conditions. DX - An abbreviation for direct expansion. This refers to the use of refrigerant directly expanded into evaporation coils in the supply air. EMCS - Energy Monitoring and Control System ERE - Energy Reuse Effectiveness. ERE is defined as the ratio of the total energy to run the data center facility minus the reuse energy to the total energy drawn by all IT equipment. Page 5
6 Free Cooling - Used in connection with all- air cooling systems, when the cooling requirement can be met solely without the use of compressors or mechanical refrigeration. Also used to describe the process of utilizing the colder outside air to cool a building instead of operating an air conditioning unit. HAC - Hot Aisle Containment, system that segregates and channels heated air from the outlet side of racks directly back to air conditioning equipment in a manner that prevents and air mixing with the supply air to the data center. Heat Exchanger - A device used to transfer heat energy from one medium to another. Common uses of heat exchangers are water to air heat exchangers in air handling units, water to water (plate and frame or shell and tube) heat exchangers in water side economizers, etc. Hot Aisle - An aisle where rack backs face into the aisle. Heated exhaust air from the equipment in the racks enters this aisle and is then directed to the CRAC or CRAH return vents. HPDC - High- Performance Data Center, a data center with above average kw loading, typically greater than 10kW/rack. Hot Spot - An area, typically related to a rack or set of racks, where ambient air temperature is above acceptable levels. Typically caused by poor airflow management (insufficient cool air supply or an excess of recirculation). In- Row Cooling - Cooling technology installed between racks in a row that draws warm air from the hot aisle and delivers cool air to the cold aisle, minimizing the path of the air (see close coupled cooling). Inlet Air - The air entering the equipment. For air conditioning equipment this is the heated air returning to be cooled, also called return air. For IT equipment (e.g. servers) this is the cooled air entering the equipment. Latent Cooling - Latent cooling is the process of lowering the temperature of air below its dew point to reduce its moisture content. In a typical HVAC application, latent cooling occurs when air is moved across a cold surface, like a cooling coil. In order for latent cooling to occur, the temperature of this cold surface must be lower than the dew point of the air. As the air is moved across this cold surface, its temperature drops until moisture condenses on the cold surface, lowering the moisture content of the air. This is known as latent cooling. Once air reaches a temperature that results in condensation, both sensible and latent cooling will occur simultaneously.. Latent Cooling Capacity - Cooling capacity related to wet bulb temperature and objects that produce condensation. Page 6
7 Liquid Cooling - A general term used to refer to cooling technology that uses a liquid as the heat transport medium. In data centers, the two prevalent forms of heat evacuation are liquid (chilled water) and refrigerant (DX). Load - The demand placed on a system, typically used to describe the electrical demand on the electrical supply system or the cooling demand on the cooling system. Units are power such as kw, BTU/hr, Tons, etc. MAH - Makeup Air Handler, an air handler that conditions and delivers outside air into an occupied space. Make- Up Air - The conditioned air delivered by a MAU or MAH. MAU - Makeup Air Unit, synonymous with MAH. MERV - Minimum Efficiency Reporting Value, ASHRAE 52.2, for air filtration measured in particulate size. Nominal Cooling Capacity - The total cooling capacity of air conditioning equipment, includes both latent cooling and sensible cooling capacities. OEM - Original equipment manufacturer Overcooling - A situation where air is cooled below optimum levels. Typically used in reference to rack inlet temperatures. PDU - Power Distribution Unit, this typically refers to one of two pieces of equipment in the power delivery chain. One is the combination transformer/breaker panel that is often used between a UPS supplying voltage higher than that used by the IT equipment and the cabinets. The other is the smaller "power strip" like device that is used inside the rack to distribute power to the IT equipment. Pressure Differential - The difference in pressure between two locations in the data center. Air flows from higher pressure areas to lower pressure areas. Often times, the pressure differential between the under- floor plenum and the above- floor space is controlled by varying the speed of the fans supplying air to the under- floor plenum. This allows the addition of vented floor tiles to occur without affecting the air delivered to existing vented floor tiles so that additional IT load may be placed on the floor without disturbing the tuning of the existing floor. Plenum - A receiving chamber for air used to direct air flow. Primary Loop - Refers to the water loop which cools the condenser side of a chiller. This loop is cooled by dry coolers or cooling towers. Page 7
8 PU - Packaged Unit, an air handler that is a complete device shipped ready for use rather than a custom device that is assembled on- site from components. PUE - Power Usage Effectiveness, a measure of data center efficiency calculated by dividing the total data center energy consumption by the energy consumption of the IT computing equipment. Rack - Device for holding IT equipment, also called a cabinet when its architecture is enclosed. RAH - Recirculation Air Handler, a device that circulates air but does not cool the air. RCI - Rack Cooling Index. RCI measures how effectively equipment racks are cooled according to equipment intake temperature guidelines established by ASHRAE/NEBS Raised Floor - Metal flooring on stanchions that creates a plenum for airflow and / or cabling, synonymous with RMF. Recirculation - Air which exits IT equipment and then re- enters either the same IT equipment or another piece of IT equipment without being cooled and therefore increases the burden on the cooling equipment. Typically the result of poor airflow management (e.g. missing blanking panels, gaps in rows, no containment, poor row architecture, insufficient air supply, etc.). Return Air - The heated air returning to air conditioning equipment. Rh - Relative Humidity. RMF - Raised Metal Floor, an alternate term for the more commonly used term raised floor'. RPM - Revolutions per Minute, a unit of angular velocity. RPP - Remote Power Panel. RTI - Return Temperature Index. RTI evaluates the energy performance of the air management system. RTU - Rooftop Unit, an air handler designed for outdoor use mounted on a rooftop. SCFM - Standard Cubic Feet per Minute, the volumetric flow rate of a gas corrected to standardized conditions of temperature, pressure and relative humidity. SCADA- Supervisory Control and Data Acquisition Secondary Loop - Refers to the water which is used to cool the heat exchangers in AHUs and is cooled via the expansion unit in a chiller. Page 8
9 Sensible Cooling - The action of lowering the dry bulb temperature of air without condensation taking place. Set Point - In a control system, this is the value against which the variable that is being controlled is compared. Temperature and humidity set points are common in the cooling system for a data center. Short Cycling - Chilled airflow returning to cooling units without passing through IT equipment, also referred to as bypass. Standby Power - standby power as the power consumed by a product when in the lowest power consuming mode. This typically occurs when the product is switched to "off" or not performing its primary purpose. Sub- Floor - The open area underneath a raised computer floor, also called a sub- floor plenum. Supply Air - The cooled airflow emitted from air conditioning equipment. Total Annual Energy - is calculated as the weighted sum of the annual energy consumption for all energy types serving the data center at the data center boundary. TCO - Total cost of ownership (capital cost + operating cost over a finite period of time) Thin Provisioning - Thin Provisioning, in a shared storage environment, is a method for optimizing utilization of available storage. It relies on on- demand allocation of blocks of data versus the traditional method of allocating all the blocks up front. This methodology eliminates almost all whitespace which helps avoid the poor utilization rates, often as low as 10%, that occur in the traditional storage allocation method where large pools of storage capacity are allocated to individual servers but remain unused (not written to). This traditional model is often called "fat" or "thick" provisioning. UPS - Uninterruptible Power Supply, a device placed in series with the supply of power from the utility which contains internal energy storage such that the supply of power from the UPS is continuous even when the primary supply of power (typically the utility) is removed. While battery- based energy storage is the most common, flywheel- based energy storage is gaining in popularity due to the reduced maintenance cost. The duration of time that the UPS runs using its internal energy source is typically short and intended to span the gap between the primary source of power is removed and either returned or replaced by the secondary source of power (typically an emergency generator). Velocity - A speed of airflow expressed in Feet Per Minute (FPM). Page 9
10 VFD - Variable Frequency Drive, a device which supplies AC power of varying frequency, typically used to control the speed of induction motors. In the data center, it is common to vary the speed of fans, pumps, and chillers. Volumetric Air Flow - The volume and speed of air being transported; expressed in Cubic Feet per Minute. Waterside Economizer - A system which uses a source other than a chiller to cool the secondary loop water used by the AHUs. This typically consists of either a dry cooler or cooling tower, piping, valves and in the case of a cooling tower, it also includes a heat exchanger since the secondary loop water is treated completely differently than the primary loop water and is typically much "better" water. Wet- Bulb Temperature - The temperature of the air measured using a wet- bulb thermometer, that is, the temperature to which a wet surface can be cooled by evaporation. This temperature is affected by both the dry bulb temperature and the dew point of the air. Dryer air has a lower wet bulb temperature. This is a design constraint when utilizing cooling towers or evaporative pads in the cooling process. Wg - Inches of water column, a unit of pressure based on the height of a column of water supported by the pressure differential between the top and bottom of the column. 1 inch wg =.036 psi. WPSF - Watts per Square Foot, a unit of power density. In a data center this is a bulk term that refers to the total load in a raised floor space divided by the total area of that raised floor space. This is a design parameter for total capacity of the cooling and power systems and is used in conjunction with point load (the amount of load in a small space such as a rack). Page 10
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
STULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
Cooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
Unified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
Data Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
White Paper #10. Energy Efficiency in Computer Data Centers
s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
> Executive summary. Explanation of Cooling and Air Conditioning Terminology for IT Professionals. White Paper 11 Revision 2. Contents.
Explanation of Cooling and Air Conditioning Terminology for IT Professionals White Paper 11 Revision 2 by Tony Evans Click on a section to jump to it > Executive summary As power densities continue to
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
Data Centre Cooling Air Performance Metrics
Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. [email protected] Abstract Data centre energy consumption
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
How to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
Data Center Power Consumption
Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT
DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources ALEXANDRU SERBAN, VICTOR CHIRIAC, FLOREA CHIRIAC, GABRIEL NASTASE Building Services
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling
White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that
How To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
How To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
Reducing the Annual Cost of a Telecommunications Data Center
Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility
BICSInews. plus. july/august 2012. + Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment.
BICSInews m a g a z i n e july/august 2012 Volume 33, Number 4 plus + Industrial-grade Infrastructure and Equipment + I Say Bonding, You Say Grounding + Data Center Containment & design deployment The
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Humidification Strategies for Data Centers and Network Rooms
Humidification Strategies for Data Centers and Network Rooms By Tony Evans White Paper #58 Revision 1 Executive Summary The control of humidity in Information Technology environments is essential to achieving
University of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
Chilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
Stanford University Server/Telecom Rooms Design Guide
Stanford University Server/Telecom Rooms Design Guide CONTENTS 1.0 How to Use this Guide...3 1.1 Document Organization...3 2.0 Summary Form and Sample Options Matrix...3 3.0 Options Matrix...7 4.0 Recommended
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Driving Data Center Efficiency Through the Adoption of Best Practices
Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary
Data Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation
Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation Version 1.0 - November, 2011 Incorporating Data Center-Specific Sustainability Measures into
Data Center Environments
Data Center Environments ASHRAE s Evolving Thermal Guidelines By Robin A. Steinbrecher, Member ASHRAE; and Roger Schmidt, Ph.D., Member ASHRAE Over the last decade, data centers housing large numbers of
QUALITATIVE ANALYSIS OF COOLING ARCHITECTURES FOR DATA CENTERS
WHITE PAPER #30 QUALITATIVE ANALYSIS OF COOLING ARCHITECTURES FOR DATA CENTERS EDITOR: Bob Blough, Emerson Network Power CONTRIBUTORS: John Bean, APC by Schneider Electric Robb Jones, Chatsworth Products
In Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods
Air Conditioning Clinic
Air Conditioning Clinic Introduction to HVAC Systems One of the Systems Series February 2012 TRG-TRC018-EN Introduction to HVAC Systems One of the Systems Series A publication of Trane Preface Introduction
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Measure Server delta- T using AUDIT- BUDDY
Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because
How To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland
AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Enclosure and Airflow Management Solution
Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...
Best Practices. for the EU Code of Conduct on Data Centres. Version 1.0.0 First Release Release Public
Best Practices for the EU Code of Conduct on Data Centres Version 1.0.0 First Release Release Public 1 Introduction This document is a companion to the EU Code of Conduct on Data Centres v0.9. This document
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
EHDC. Cooling system for Data Center and server cabinets.
EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
A Comparative Study of Various High Density Data Center Cooling Technologies. A Thesis Presented. Kwok Wu. The Graduate School
A Comparative Study of Various High Density Data Center Cooling Technologies A Thesis Presented by Kwok Wu to The Graduate School in Partial Fulfillment of the Requirements for the Degree of Master of
Great Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Wright Line Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant Currently 60 percent of the cool air that