Legacy Data Centres Upgrading the cooling capabilities What are the options?
|
|
- Marion McKinney
- 8 years ago
- Views:
Transcription
1 Legacy Data Centres Upgrading the cooling capabilities What are the options?
2 Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems & Comparison Common Requirements Weatherite s Cooling Solutions Summary Q & A s
3 So, What is a typical Legacy Data Centre? High density data centre / Hosting facility In-house medium sized facility Server Room Electronic equipment, positioned in racks which, as a result of their function, generate waste heat that needs to be removed in order to ensure continual, safe operation. Switch Room Communications Room Broom Cupboard!!!!
4 Weatherite Group-July 11 / Issue1. All Rights Reserved
5 CRAC Cooling Computer Room Computer Room Data Centre with reactive controls Air Conditioning Full Air Conditioning Inc. Cooling, Heating, Humidification, Dehumidification, Reactive Control Cooling AHU s & filters with Proactive controls
6 DEW POINT TEMPERATURE - C ENTHALPY - KJ PER KILOGRAM OF DRY AIR Computer Room Environmental Requirements With Dublin Weather Data WET BULB TEMPERATURE - C PSYCHROMETRIC CHART Normal Temperature SI Units 84 METERS BAROMETRIC PRESSURE:.315 kpa Weather Data Location: DUBLIN, ALL REGIONS, IRELAND Weather Hours 36 to 1 72 to 37 8 to to 9 18 to to to to to ENTHALPY - KJ PER KILOGRAM OF DRY AIR SATURATION TEMPERATURE - C % 8% 7% 6% 5% 4% 3% % 15 % RELATIVE HUMIDITY 25% 15% 8% RELATIVE HUMIDITY 6% 4% 2% Chart by: HANDS DOWN SOFTWARE, DRY BULB TEMPERATURE - C
7 DEW POINT TEMPERATURE - C ENTHALPY - KJ PER KILOGRAM OF DRY AIR ASHRAE - Data Centre Recommended Environmental Envelope WET BULB TEMPERATURE - C PSYCHROMETRIC CHART Normal Temperature SI Units 84 METERS BAROMETRIC PRESSURE:.315 kpa Weather Data Location: DUBLIN, ALL REGIONS, IRELAND Weather Hours 36 to 1 72 to 37 8 to to 9 18 to to to to to ENTHALPY - KJ PER KILOGRAM OF DRY AIR SATURATION TEMPERATURE - C % 8% 7% 6% 5% 4% 3% % 15 % RELATIVE HUMIDITY 25% 15% 8% RELATIVE HUMIDITY 6% 4% 2% Chart by: HANDS DOWN SOFTWARE, DRY BULB TEMPERATURE - C
8 DEW POINT TEMPERATURE - C ENTHALPY - KJ PER KILOGRAM OF DRY AIR ASHRAE - Data Centre Allowable Environmental Envelopes WET BULB TEMPERATURE - C PSYCHROMETRIC CHART Normal Temperature SI Units 84 METERS BAROMETRIC PRESSURE:.315 kpa Weather Data Location: DUBLIN, ALL REGIONS, IRELAND Weather Hours 36 to 1 72 to 37 8 to to 9 18 to to to to to ENTHALPY - KJ PER KILOGRAM OF DRY AIR SATURATION TEMPERATURE - C % 8% 7% 6% 5% 4% 3% % 15 % RELATIVE HUMIDITY 25% 15% 8% RELATIVE HUMIDITY 6% 4% 2% Chart by: HANDS DOWN SOFTWARE, DRY BULB TEMPERATURE - C
9 Available Cooling Systems Traditional Used Systems Chilled Water CRAC units with Centralised Chillers Refrigerant CRAC units with remote condensers Additional Optional System Direct fresh air with DX top-up / % back-up Direct Adiabatic Indirect Adiabatic Indirect Adiabatic with top-up cooling In-Row Cooling Each of these systems will have real and perceived advantages and disadvantages.
10 CW CRACS with remote chiller RA 22C / SA 12C CW CRACS with remote chiller with free cooling - RA 22C / SA 12C DX CRACS with remote condensers RA 22C / SA 12C CW CRACS with remote chiller with free cooling - RA 27C / SA 17C FA / DX with Free Cooling RA 22C / SA 12C FA / DX with Free Cooling RA 27C / SA 17C Indirect Adiabatic RA 37C / SA 27C FA / DX with Free Cooling RA 37C / SA 27C Direct Adiabatic RA 37C / SA 27C Cooling System Comparison for kw load kwh / kg of CO2 4, 35, 3, 25,, 15,, 5, - Annual Energy Use (kwh) Annual CO2 Emissions (kg of CO2) Annual Energy Cost ( ) 9% Saving 4, 35, 3, 25,, 15,, 5, -
11 Common Requirements - Considerations Operation - always on Split power supplies Mains Engine UPS Reliability Multiple Circuits Fresh Air / DX Multiple DX circuits Adiabatic Energy Efficiency EC Fans Fresh Air / DX Adiabatic Multiple controls
12 Common Requirements Considerations, cont. Ease of maintenance Front service access In- service-replacement of components N+1 Space Availability Internal External Re-location Air Distribution Raised Floor Flooded Room Cold Aisle Hot Aisle
13 Common Requirements Considerations, cont. Future Planning Growth plans Relocating Out sourcing Controls Strategy Return Air Reactive Control Supply Air Proactive Control Controls Integration BMS integration Statistics Monitoring Alarms
14 What Weatherite can offer? 43 years history of providing HVAC solutions Over 35 years experience cooling IT environments. Made to measure cooling solutions (no one size fits all!!) A range of designs - to facilitate each specific application, all offering the opportunity to reduce your operation PUE. Design and manufacture all our cooling equipment in-house Project report with recommendations, plus optional assistance with commissioning & maintenance services. Over, cooling units installed across UK & Ireland
15 Weatherite s Cooling Solutions Conventional Systems Direct Replacement - CRAC Chilled Water Units & Chillers
16 Weatherite s Cooling Solutions Alternative Efficient Systems Direct Fresh Air / DX FreTec Direct Fresh Air / DX - FreTec Plus
17 Weatherite s Cooling Solutions Adiabatic Systems Direct Adiabatic 15kW to 6kW In-direct Adiabatic 6kW to 35kW
18 Weatherite s Cooling Solutions High Capacity Systems In-Row DX Condensers Chilled Water Chillers Adiabatic Fully Package Systems Roof Top Plant External Plant Rooms Air Containment Cold Aisle Containment Hot Aisle Containment
19 Summary Space Conditions have changed More energy efficient options available No need to go for Like for Like Bespoke Options available to maximise cooling Running cost savings of up to 9% Potential short payback period Weatherite can assist in all aspects of the cooling design
20 Weatherite Group Feb 15. All Rights Reserved Some of Weatherite Group s Customers
21 Questions & Answers
22 Look forward to meeting you on STAND 319 Pat Gillan - Data Centre Sales Manager pgillan@weatheritegroup.com mobile: +44 () Brian Taylor Business Development Manager (All Weatherite Group products & services) btaylor@weatheritegroup.com Mobile: +44 ()
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
More informationDATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
More informationAnalysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
More informationAIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
More informationLiebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit
Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative
More informationCRITICAL COOLING FOR DATA CENTERS
IDEA 100 th Annual Conference & Trade Show CRITICAL COOLING FOR DATA CENTERS Presented by Ron Johanning, PE, LEED AP Mission Critical Market Leader Agenda EPA Report Data Center Energy Trends IT Best Practice
More informationEXAMPLE OF A DATA CENTRE BUILD
EXAMPLE OF A DATA CENTRE BUILD BT Harmondsworth Data Centre Hall 2 Upgrade Temperature Control have been involved in providing specialist to data centres for over 20 years, starting from providing specialist
More informationUniversity of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
More informationData Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
More informationI-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility
More informationEuropean Code of Conduct for Data Centre. Presentation of the Awards 2014
European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
More informationFree Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationHeat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
More informationHow to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling
How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling Abstract Data center managers are increasingly in search of methods and technologies for
More informationMinimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com
More informationWhite Paper #10. Energy Efficiency in Computer Data Centers
s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular
More informationEnergy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.
Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial
More informationMaximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
More informationExcool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling
Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by
More informationData Centre Cooling Air Performance Metrics
Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption
More informationEuropean Code of Conduct for Data Centre. Presentation of the Awards 2013
European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started
More informationTop 5 Trends in Data Center Energy Efficiency
Top 5 Trends in Data Center Energy Efficiency By Todd Boucher, Principal Leading Edge Design Group 603.632.4507 @ledesigngroup Copyright 2012 Leading Edge Design Group www.ledesigngroup.com 1 In 2007,
More informationState of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
More informationDefining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
More informationGuide to Minimizing Compressor-based Cooling in Data Centers
Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi
More informationAERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA CENTRES
AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA GLOBAL DATA CENTRE IP TRAFFIC WILL TRIPLE WITHIN 5 YEARS Global data centre IP traffic has set a constant growth path, with
More informationPaul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA
Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale
More informationCapgemini UK Infrastructure Outsourcing
Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationEnergy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
More informationImproving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
More informationWhite Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
More informationEnvironmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
More informationHow to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
More informationI-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 4, Lancaster University, 2 nd July 2014
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 4, Lancaster University, 2 nd July 2014 Background Data centres estimated to use 2-3% of total electricity consumption in the UK and generate
More informationElements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
More informationSTULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
More informationTechnical Systems. Helen Bedford
Technical Systems in Data Centres Helen Bedford Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre
More informationEconomizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
More informationData Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationICT and the Green Data Centre
ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by
More informationBy Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
More informationFree Cooling for Data Centers
Free Cooling for Data Centers Release 1, September 2015 Contents 1. Abstract... 3 2. Introduction... 3 3. Data Center Temperatures and Free Cooling... 4 4. Direct Free Cooling... 4 5. Indirect Free Cooling...
More informationCIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How
CIBSE ASHRAE Group Data Centre Energy Efficiency: Who, What, Why, When, Where & How Presenters Don Beaty PE, FASHRAE Founder, President & Managing Director DLB Associates Consulting Engineers Paul Finch
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationExcool Data Centre Cooling Product Comparison Report
Excool Data Centre Cooling Product Comparison Report Desktop Study Job No: 1003780 Date: October 2011 Cundall Johnston and Partners LLP Saffron House 6-10 Kirby Street London EC1N 8TS tel 020 7438 1600
More informationSpeaker: John Peterson Time: April 4, 2014, 9:45-10:45 a.m. Venue: Crystal 1-2. Data Center Design and Commissioning
Speaker: John Peterson Time: April 4, 2014, 9:45-10:45 a.m. Venue: Crystal 1-2 Data Center Design and Commissioning High enterprise relevancy for addressing space, power, and cooling, as well as costs
More informationHow To Test A Theory Of Power Supply
A CASE STUDY ON: THE EFFECTS OF HIGHER OPERATING TEMPERATURES ON DATA CENTER EFFICIENCY Victor Garcia Director of Facilities Brocade October 24, 2012 Jeff Stein, PE Principal Taylor Engineering 2010 Brocade
More informationEnergy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling
Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An
More informationDrives and motors. A guide to using variable-speed drives and motors in data centres
Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers
More informationDrives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)
Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to
More informationHVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
More informationImprove competiveness of IDC and enterprise data centers with DCIM
Improve competiveness of IDC and enterprise data centers with DCIM This paper studies the implementation of modern DCIM systems for data centers to improve operational competitiveness with ATEN's DCIM
More informationFEAR Model - Review Cell Module Block
F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data
More informationNSIDC Data Center: Energy Reduction Strategies
NSIDC Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful effort to significantly reduce
More informationData Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
More informationWhite Paper: Free Cooling and the Efficiency of your Data Centre
AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...
More informationIn Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
More informationInternational Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
More informationCANNON T4 MINI / MICRO DATA CENTRE SYSTEMS
CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly
More informationGreen Data Center: Energy Reduction Strategies
Federal Energy ManagEment Program Green Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful
More informationAdvanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
More informationGreening Data Centers
Greening Data Centers Dallas Thornton SDSC Division Director, Cyberinfrastructure Services March 2, 2011 Data Centers Are Enormous Users of Power US Data Centers (TeraWatt Hours per Year) 125 US Televisions
More informationOverview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
More informationEHDC. Cooling system for Data Center and server cabinets.
EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment
More informationClimate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.
Climate solutions evaporative cooling, adiabatic humidification and programmable controllers energy saving solutions for data centers carel.com Data center air-conditioning Data center air-conditioning
More informationControl of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project
Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify
More informationLiquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
More informationManaging Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
More informationStanford University Server/Telecom Rooms Design Guide
Stanford University Server/Telecom Rooms Design Guide CONTENTS 1.0 How to Use this Guide...3 1.1 Document Organization...3 2.0 Summary Form and Sample Options Matrix...3 3.0 Options Matrix...7 4.0 Recommended
More informationCase Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
More informationTHE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University
THE PSYCHROMETRIC CHART: Theory and Application Perry Peralta NC State University PSYCHROMETRIC CHART Identify parts of the chart Determine moist air properties Use chart to analyze processes involving
More informationBlade Server & Data Room Cooling Specialists
SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling
More informationData Centre. Flexible, high efficiency cooling solutions. www.airedale.com CONDITIONING CONDENSING UNITS CONTROLS SERVICE TRAINING
Sector Data Centre Data Centre Flexible, high efficiency cooling solutions IT COOLING PRISION AIR CONDITIONING CHILLERS CONDENSERS & CONDENSING UNITS www.airedale.com BRITISH MANUFACTURER ENERGY EFFICIENCY
More informationFederal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
More informationDatacentre Capability March 2015
Callaghan Engineering Consul-ng Engineers Project Managers Datacentre Capability March 2015 Callaghan Engineering Multi-discipline engineering & project management company Established in 1990 Offices in
More informationGreen Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
More informationEngineers Ireland Cost of Data Centre Operation/Ownership. 14 th March, 2013 Robert Bath Digital Realty
Engineers Ireland Cost of Data Centre Operation/Ownership 14 th March, 2013 Robert Bath Digital Realty Total Cost of Operation (TCO) Rental TCO - 10 Year Lease Term Power Cooling Connectivity Costs 26%
More informationData Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
More informationSubtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland
Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC
More informationIntroduction to Datacenters & the Cloud
Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview
More informationBCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
More informationInfrastructure & Cities Sector
Technical Article Infrastructure & Cities Sector Building Technologies Division Zug (Switzerland), October 18, 2011 Saving Energy in a Data Center A Leap of Faith? New guidelines from ASHRAE (American
More informationReducing Data Center Loads for a Large-Scale, Net Zero Office Building
rsed Energy Efficiency & Renewable Energy FEDERAL ENERGY MANAGEMENT PROGRAM Reducing Data Center Loads for a Large-Scale, Net Zero Office Building Energy Efficiency & Renewable Energy Executive summary
More informationMeasuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
More informationHPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.)
HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) Felipe Visbal / March 27, 2013 HPPR Data Center Technologies Team Services Data Centers: Thermal Assessments
More informationImproving Sustainability in Campus Data Centers Click To Edit Master Title Style
Improving Sustainability in Campus Data Centers Click To Edit Master Title Style March 31, 2015 12:10-1:00 PM ET Agenda Welcome and Better Buildings Overview Michigan State University Partnering with the
More informationHow To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
More informationControlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015
Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed
More informationGUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
More informationGreen Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range
More informationBest Practice Guide for Data Centres - a UH Perspective Steve Bowes-Phipps, Data Centres Manager University of Hertfordshire
Best Practice Guide for Data Centres - a UH Perspective Steve Bowes-Phipps, Data Centres Manager University of Hertfordshire http://rare idc.herts.ac.uk Best Practice Guide for Data Centres RARE-IDC Overview
More informationDataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
More informationAward-Winning Innovation in Data Center Cooling Design
Award-Winning Innovation in Data Center Cooling Design Oracle s Utah Compute Facility O R A C L E W H I T E P A P E R D E C E M B E R 2 0 1 4 Table of Contents Introduction 1 Overview 2 Innovation in Energy
More informationCRAC Precision climate control units for data centres
CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have
More informationNews in Data Center Cooling
News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase
More informationNational Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
More information