Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015
|
|
|
- Ashley Lindsey
- 9 years ago
- Views:
Transcription
1 Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology
2 Background: HVAC systems are often designed to supply a constant discharge air temperature from an air handling system to maintain comfort in the space. Some HVAC systems, especially those that have strict space humidity requirements, should be controlled for a constant discharge air dew point temperature (or maximum discharge air dew point) in addition to controlling to a set discharge dry bulb temperature. Wrap-around heat pipe systems, especially controllable wrap-around heat pipe systems, can be an effective tool to help meet these strict space humidity requirements. Wrap-around heat pipe systems are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil. The upstream precool heat pipe shifts the excess sensible cooling capacity off the cooling coil while the downstream heat pipe provides reheat. Wrap-around heat pipes are passive devices that are driven by the difference in thermal energy between the entering hot air and the cold air leaving the cooling coil. This thermal energy affects a phase change of the refrigerant in the tubes which drives the flow of refrigerant between the two heat pipe sections. As warm air enters the precool heat pipe, refrigerant changes phase from liquid to vapor extracting heat from the air stream thus lowering the air temperature. Refrigerant then flows naturally to the reheat section where it condenses and releases the energy it absorbed from the precool section to the airstream in the form of sensible heat. The Challenge: HVAC systems with strict space humidity requirements typically need to provide air with a dew point that is lower than the dry bulb temperature. Operating rooms and many other applications fall under this category. For this article, let s consider another example:
3 A space with chilled beams is being served by a dedicated outdoor air system (DOAS). A typical DOAS unit uses an air-to-air heat exchanger to transfer energy between the supply and exhaust air streams, followed by a preheat coil, a cooling coil and supply fan(s). The chilled beams in this example require 55 degree air (the supply air dry bulb set point, SASP) with a maximum dew point of 48 degrees (the supply air dew point set point, SADP). In the typical DOAS system, the chilled water coil will cool the air down to the SADP (48 degrees) to remove the necessary moisture. However, reheat is then required to bring the dry bulb temperature up to 55 degrees, as 48 degrees is too cold for the space. By introducing a wraparound heat pipe, the heat pipe can be selected to help precool the incoming air, relieving sensible load from the cooling coil, then reheat the air from 48 degrees to 55 degrees, which is exactly what the space requires. Since the wrap-around heat pipe system is a passive device, there is no means to control the amount of reheat applied to the supply air stream. The heat pipe can only reheat with as much energy as is extracted from the air on the precool side. Therefore, if a heat pipe system is selected for a hot day, the heat pipe will underperform on a cool day when the entering heat energy is lower and supply colder air than is needed to the space. If a heat pipe system is selected for a cool day, the heat pipe will overperform on a hot day when the entering heat energy is higher, and supply warmer air than is needed to the space. The Solution: Enter the controllable wrap-around heat pipe. By installing solenoid valves on the refrigerant circuits of the wrap-around heat pipe, the building management system (BMS) can control the amount of refrigerant flow in individual circuits between the precool and reheat heat pipes, and thus effectively control the amount of reheat being applied to the airstream. In our example, if we select the heat pipe to supply 55 dry bulb/48 dew point air with a 65 degree entering air temperature, for any entering air temperature above 65 degrees, the BMS will stage the solenoid valves closed to prevent overheating of the discharge air. What about other entering outdoor
4 air/humidity scenarios? How would the system be controlled then? The following psychrometric charts portray all possible air condition scenarios and explain how each should most effectively be handled. Note: The air-to-air heat exchanger is assumed to transfer total enthalpy for ease of illustration; however the same principles could be applied to a sensible-only energy recovery device. OADP: Entering outdoor air dew point temperature OAT: Entering outdoor air dry bulb temperature SADP: Supply air dew point set point SASP: Supply air dry bulb set point RAT: Return air dry bulb temperature from the space to the DOAS 1. Cold and dry (OAT < SADP): This is normal heating mode, and the air-to-air heat exchanger and hot water coil will work to reach the supply air dry bulb set point temperature. The heat pipe will do nothing under these conditions.
5 2. Cool and dry (OAT < SASP and OAT > SADP and OADP < SADP): This case is for when the outdoor air temperature is between the supply air dew point and dry bulb temperatures, and the air is sufficiently dry to not require dehumidification. As in case 1, the air-to-air heat exchanger and hot water coil will work to reach the supply air dry bulb set point temperature. The heat pipe will do nothing under these conditions.
6 3. Warm and dry (OAT < RAT and OAT > SASP and OADP < SADP): This case sees the outdoor air temperature between the supply air set point and the return air temperature. Because the dew point is sufficiently low, dehumidification is not required, the heat pipe and air-toair heat exchanger can be turned off, and the cooling coil brings the entering air down to the supply air set point.
7 4. Cool to warm, but humid (OAT< RAT and OAT > SADP and OADP > SADP): The outdoor air temperature is between the return air temperature and the supply air dew point set point, but contrary to cases 2 and 3, the entering dew point temperature is sufficiently high to require dehumidification. In this scenario, cooling mode is enabled, but the air-to-air heat exchanger operates to bring the entering air temperature as close as possible to the return air temperature to maximize reheat effectiveness. Though this increases the cooling load, the additional reheat savings will outweigh that additional cooling penalty. The cooling coil will work to cool/dehumidify, and the heat pipe can be staged to meet the supply air dry bulb set point.
8 5. Hot and dry (If OAT > RAT and OADP < SADP): The outdoor air temperature is greater than the return air temperature, but because the outdoor air dew point is below the supply air dew point set point, dehumidification is not required. Cooling mode is enabled and the airto-air heat exchanger precools outdoor air. The heat pipe can be staged off and the cooling coil is used to cool down the air to the supply air dry bulb set point.
9 6. Hot and humid (If OAT > RAT and OADP > SADP): This scenario is for a typical summer day, when full cooling mode is enabled. The air-to-air heat exchanger precools outdoor air and the heat pipe/cooling coil work to cool/dehumidify/reheat supply air. Stage heat pipe solenoid valves closed as required to maintain supply air dry bulb set point. Conclusions: With proper application and control of wrap-around heat pipe systems, the example illustrated can be expanded to nearly any system with strict space humidity requirements. Even more common systems where humidity requirements aren t as strict can be accomplished the same way by simply raising the dew point line that separates Cases from Cases Although the example did not include mention of humidification requirements, the system can be used in conjunction with a humidification system to effectively raise the humidity in the airstream and space as required. Furthermore, it is worth noting that the larger the outdoor air (ventilation) requirement for the particular air handling system, the more effective the controllable wrap-around heat pipe system will be, as less return air means less opportunity to condition the air by mixing.
10 About Flow Tech, Inc.: Flow Tech, Inc. s mission is to provide the highest quality and most energy-efficient HVAC systems and products that directly affect how buildings operate. Serving the commercial, healthcare, education, research, pharmaceutical, and water and wastewater markets, we strive to maintain the utmost professional and educated team offering sales, support and on-call, 24/7 service. We are a full-service heating, ventilating and air conditioning (HVAC) equipment manufacturer s representative celebrating over 25 years of business and serving CT, Western Massachusetts and counties in New York. We pride ourselves in offering: The premier source of new VFD applications, retrofits and servicing all brands of existing VFDs The finest critical airflow control solution in the market providing a safe and energy efficient environment for the occupants to work. The highest quality custom built air handlers providing a dependable means for building owners to provide conditioned air to occupants. Multiple technologies of heat recovery allowing owners to run their buildings at peak efficiencies. A service department that is educated and experienced and provides a level of service that goes above and beyond customer expectations Our product lines include ABB variable frequency drives, Air Enterprises, Air Monitor Corporation, Aircuity, Heat Pipe Technology, M.K. Plastics, Phoenix Controls, Steril-Aire, TAMCO, Thermowheel, ToxAlert, Twin City Fans and VAW. Learn more at About Heat Pipe Technology: HEAT PIPE TECHNOLOGY, INC. (HPT) is the innovation leader in energy recovery and dehumidification systems for commercial applications around the globe. Employing the very latest in passive heat transfer technology, HPT designs and supplies the core systems to the world's leading commercial air handling equipment manufacturers. Heat Pipe Technology, Inc. is recognized worldwide for our innovation and expertise. Our heat pipes are made right here in Tampa, Florida; they save energy and dramatically reduce heating and cooling costs. With a network of more than 70 representatives and licensees in North and South America, Europe, The Middle East, Asia, and Australia, HPT is a true global operator. Learn more at
By Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
Moisture Control. It s The Dew Point. Stupid! Its not the humidity.
Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA [email protected] 805 687-3175 Matching great technology to market need! Topics SHR
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Pool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems
APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Answers to Your Questions from the Webinar
2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates
Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
How To Get A Passive House
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2015 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Product
newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer
engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems
Dedicated Outdoor Air-Dual Wheel System Control Requirements
4428 Dedicated Outdoor Air-Dual Wheel System Control Requirements Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE ABSTRACT The central thrust of this paper is to develop a clear understanding of the performance
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
Legacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
How To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
Hospital Application Guide. Cost-effective climate control for hospitals
Hospital Application Guide Cost-effective climate control for hospitals Munters is the world leader in dehumidification Munters is the largest manufacturer of dehumidifiers in the world. Since developing
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
Preliminary Final Proposal
1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system
Refrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the
Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!
Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air
The HVAC Process: Changing the Properties of Air
The HVAC Process: Changing the Properties of Air Alexander Delli Paoli, Jr. ABSTRACT This discussion addresses the physical properties of air and water vapor mixtures. The components of the heating, ventilation,
Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
To provide good indoor air quality
Conditioning Ventilation Air for Improved Performance and Air Quality The practice of using a mixing chamber for mixing outdoor and return in a single system should be replaced by a technique with two
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE <[email protected]
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is
White Paper #10. Energy Efficiency in Computer Data Centers
s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
Example Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center [email protected] 402-559- 5301 402-630-
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
What is LEED? Why pursue LEED accreditation? How does LEED accomplish these goals? Sustainable sites Water efficiency Energy and Atmosphere
Green AAON for What is LEED? Sustainability and green have recently become terms used within the building industry (and others) to refer to a construction project that has low environmental impact, or
Building Re-Tuning Training Guide: AHU Heating and Cooling Control
Building Re-Tuning Training Guide: AHU Heating and Cooling Control Summary The purpose of the air-handling unit (AHU) heating and cooling control guide is to show, through examples of good and bad operations,
Mechanical Rooftop Custom Capabilities
Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
How To Control Humidity With A Humidifier
Control of ventilation and air conditioning plants Building Technologies s Contents.Temperature control in air treatment systems 2. Humidity controls 3. Recirculated air mixing. Internal heat sources 6.2
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
Innovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
USER S GUIDE For all Packaged Systems (Air Conditioners and Heat Pumps)
USER S GUIDE For all Packaged Systems (Air Conditioners and Heat Pumps) WA & WL - Series Air Conditioners WH & SH - Series Air Source Heat Pumps IH - Series Air Source Heat Pumps DATE: 02-21-12 QA - Series
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0.
Psychrometrics Psychrometric Chart Relative Humidities RH% 49.4 100% 80% 0.030 Enthalpies 70% H btu/lb 46.5 0.028 85 Not to Scale 0.026 Humidity Numbers and Values 43.7 60% Ratios are approximate 0.024
Using Time-of-Day Scheduling To Save Energy
The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.
Bring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
Air Conditioning Clinic
Air Conditioning Clinic Introduction to HVAC Systems One of the Systems Series February 2012 TRG-TRC018-EN Introduction to HVAC Systems One of the Systems Series A publication of Trane Preface Introduction
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem
Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment
AT-01-7-3 Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment Kurt M. Shank Student Member ASHRAE Stanley A.
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air 0 Optimal Air Quality: Critical to Hotels Provides comfortable environment for guests no overcooling Protects building, carpets
> Executive summary. Explanation of Cooling and Air Conditioning Terminology for IT Professionals. White Paper 11 Revision 2. Contents.
Explanation of Cooling and Air Conditioning Terminology for IT Professionals White Paper 11 Revision 2 by Tony Evans Click on a section to jump to it > Executive summary As power densities continue to
In Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
How Ground/Water Source Heat Pumps Work
How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy
Product Data Bulletin
Product Data Bulletin Adjustable Frequency Drives and HVAC Systems An Application Guide September, 1994 Raleigh, NC, U.S.A. INTRODUCTION All buildings pose the same problem: how to heat or cool the air
Printing and Publishing Energy Savings Guide
Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand
Dehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *
Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
Role of Economizers in Dedicated Outdoor Air Systems
Introduction: Role of Economizers in Dedicated Outdoor Air Systems A question that frequently arises when a dedicated outdoor air system (DOAS) (Mumma, 2001) is discussed, particularly when the parallel
THE PSYCHROMETRIC CHART AND ITS USE
Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader
Infrastructure & Cities Sector
Technical Article Infrastructure & Cities Sector Building Technologies Division Zug (Switzerland), October 18, 2011 Saving Energy in a Data Center A Leap of Faith? New guidelines from ASHRAE (American
Guide to Minimizing Compressor-based Cooling in Data Centers
Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi
CASE STUDY: COOLERADO CORPORATION
CASE STUDY: COOLERADO CORPORATION Coolerado uses Weather Analytics climate data to demonstrate to clients the energy-efficiency of their air conditioners in places around the globe. 02 Overview Coolerado
How To Use A Water Source Heat Pump
Geothermal Energy Using Water-Source Heat Pumps By VIRSTAR Corporation Geothermal Expertise Since 1978 All information contained herein is the exclusive property of VIRSTAR Corporation, all rights reserved.
Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the
Refrigeration and Air Conditioning Prof M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 38 Air Conditioning Systems Welcome back in the last lecture
Humid Air. Water vapor in air. Trace Glasses 1% Argon (A) Water vapor (H 2
Humid Air Water vapor in air Oxygen 21% Trace Glasses 1% Argon (A) Water vapor (H 2 O) Carbon dioxide (CO 2 ) Neon (Ne) Helium (He) Krypton (Kr) Hydrogen (H) Ozone (O 3 ) Nitrogen 78% Humid Air Water vapor
2008 ASHRAE Environmental Guidelines for Datacom Equipment -Expanding the Recommended Environmental Envelope-
2008 ASHRAE Environmental Guidelines for Datacom Equipment -Expanding the Recommended Environmental Envelope- Overview: The current recommended environmental envelope for IT Equipment is listed in Table
Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.
Climate solutions evaporative cooling, adiabatic humidification and programmable controllers energy saving solutions for data centers carel.com Data center air-conditioning Data center air-conditioning
Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013
The Fundamentals of HVAC: What Shapes the Storage Environment Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013 Introduction Presenter Jeremy Linden, Preservation
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent
J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design
Copyright 24, American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 79 Tullie Circle NE, Atlanta, GA. 3329. Reprinted by permission from the September 24 Issue of ASHRAE Journal
Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit
Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative
saving energy in comfort Factsheet Recair Enthalpy
saving energy in comfort Factsheet Recair Enthalpy Introduction Enthalpy Exchanger The enthalpy exchanger is able to transfer both sensible heat and latent heat (moisture) from the cooled to the heated
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
Humidification Strategies for Data Centers and Network Rooms
Humidification Strategies for Data Centers and Network Rooms By Tony Evans White Paper #58 Revision 1 Executive Summary The control of humidity in Information Technology environments is essential to achieving
SIMULATION OF RADIANT COOLING PERFORMANCE WITH
SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,