Environmental Data Center Management and Monitoring
|
|
|
- Bruce Cox
- 10 years ago
- Views:
Transcription
1 2013 Raritan Inc.
2 Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor Page 6 Contact Closure Page 6 Webcam Page 7 Management Software Page 7 The Benefits Of New Technology, Solutions And Tools Page 8 About Raritan Page 8 Raritan.com Page 2
3 Introduction When data center managers think of environmental management and monitoring they typically think of temperature sensors, and perhaps humidity sensors but, where should they be placed? Though temperature sensors remain the most prevalent sensors, there are many sensors which can be usefully deployed in a data center. There are sensors for determining whether a cabinet door is open, the difference in pressure between two locations, the rate of airflow, and the presence of water. There are even sensors for tracking IT assets. This white paper will review some of the sensors which are useful in a data center. There was a time, not long ago, when data center managers relied on the room thermostat to indicate the ambient temperature of a data center. They would set the temperature in the mid-60s F to ensure adequate cooling. Now, most data center managers know that such an ambient temperature is unnecessarily cold and wasteful of energy. A room thermostat only indicates the temperature at the thermostat s location, typically an interior wall. It is far more useful to know the temperature at the cool air inlets of IT devices. Being able to see plots of temperatures from multiple sensors can identify hot spots and areas of overcooling. Sensor Design Considerations Architecture Sensors can be deployed as a separate overlay network or as part of an existing network. Deploying sensors as a separate overlay network requires a controller with its own network connections. The extra hardware and work to deploy network drops, which can cost $300 to $500 per drop, make an overlay approach to sensors expensive. If sensors are deployed as plug-and-play options to rack PDUs there is no need for a separate controller which reduces cost. The data is communicated to energy management software via the Ethernet or Wi-Fi network used to control and monitor the rack PDUs. A Web-based GUI allows data center managers to report and plot sensor values in real time or over a period of time. With plug-and-play sensors no dedicated network needs to be established which eliminates the work and cost of cable installation. Thresholds and alerts One of the many benefits of sensors is an end user being able to set thresholds and alerts. For example, a temperature sensor can be set to send an alert if the temperature rises to a level where it might damage sensitive IT equipment. It can also be set to send an alert if the temperature falls below a threshold to ensure that energy isn t being wasted by overcooling the data center. It may even be necessary to set different thresholds for different locations. For example, the thresholds for the sensors on the cool air inlet side would be set lower than the sensors on the hot air exhaust side. In general, higher levels of accuracy are preferred but the importance of accuracy varies depending on what is being metered and monitored. Energy usage, measured in kwh, should be accurate to +/- 1% to support billing or reporting. For humidity, accuracy is less critical though data center managers should ensure that relative humidity (RH) guidelines are followed. Raritan.com Page 3
4 Types of sensors There are analog and digital sensors. One isn t necessarily better than the other, it depends on the application and the nature of the deployment. Analog sensors tend to be smaller and therefore more easily deployed. Digital sensors can be more accurate but are often physically larger making some deployments awkward. The form factor of a sensor can have big implications for how it is used. For example, temperature sensors at the cool air inlets of IT devices require small sensors that can be easily and unobtrusively mounted to the front of a rack. Temperature and Humidity Sensors Every Watt of power consumed by IT equipment is turned into a Watt of heat. As the power consumed at the rack has dramatically increased due to high-density racks so too has the heat generated by IT equipment. Properly placing temperature sensors on a rack means temperatures can be plotted to ensure that IT devices don t overheat and that energy isn t being wasted by overcooling. Plotting individual sensors allows data center managers to identify hot spots requiring additional cooling or changes in the airflow or air pressure of the system to ensure adequate cooling is reaching all the locations where it is needed. One of the most important organizations for data centers when it comes to heat and cooling is the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). They publish recommended IT equipment rack positions for temperature sensors. Specifically, sensors should be placed at the bottom, middle and top on the cool air inlet side. Recommended IT Equipment Rack Positions for Temperature Sensors Monitor Points Rack with 2 Servers Rack with 19 Servers Source: Thermal Guidelines for Data Processing Environments, 2ed 2009 ASHRAE Raritan.com Page 4
5 ASHRAE also publishes recommended ranges for temperature (65 F to 80 F, 18 C to 27 C) and relative humidity (20% to 80%). The upper end of the ASHRAE temperature range, 80 F, is approximately the point at which an IT device s fan turns on. Since both cooling infrastructure and internal fans consume power, the most efficient way to operate a data center is for the cool air at the device air inlet to be close to 80 F. Obviously, temperature sensors at the rack are an excellent way for a data center manager to improve efficiency. One of the best ways to understand the relationship between temperature and humidity is to look at a psychrometric chart. The bottom of the chart is dry bulb temperature meaning air containing no moisture. The scale on the right of the chart is the amount of moisture in pounds contained in a pound of dry air. The curves running through the chart are the relative humidity (RH) from 0% to 100%. The temperature scale along the 100% RH curve is the wet bulb temperature. Environmental envelopes pertaining to air entering the IT equipment R ASHRAE PSYCHROMETRIC CHART NO.1 NORMAL TEMPERATURE BAROMETRIC PRESSURE: INCHES OF MERCURY Copyright 1992 AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING ENGINEERS, INC. SEA LEVEL R 80 80% 60% 40% Generally accepted telecom practice for Central Offices (lower RH limit not defined in NEBS) Existing Recommended Class 1 & 2 Operating Environment Allowable Class 1 Operating Environment (for reference only) 35 WET BULB TEMPERATURE - ( F) - SLANTED DEW POINT TEMPERATURE - ( F) - HORIZONTAL HUMIDITY RATIO - POUNDS MOISTURE PER POUND DRY AIR New Class 1 & 2 Recommended Operating Environment DRY BULB TEMPERATURE - F Source: Thermal Guidelines for Data Processing Environments, 2ed 2009 ASHRAE 100% RH is the maximum amount of moisture the air can contain. Beyond this point, the dew point (DP), the excess moisture condenses into droplets. The height of the chart increases from left to right. This is because colder air can hold less moisture than warmer air. If you fill a glass with ice water on a warm summer day condensation forms on the glass. This is because the air at the surface of the glass has cooled from say 75 F down to just above freezing at the surface of the glass. If the 75 F air had a RH of 50% that would be pounds of moisture per pound of air. But, at 32 F air saturates (100% RH) at pounds of moisture per pound of air. The excess moisture ( ) becomes the condensation on the glass. Raritan.com Page 5
6 Data centers using airside economizers need to think about adding humidification because the cool outside air, say 40 F and 50% RH which is approximately pounds of moisture, comes into the data center and is then warmed by IT equipment to say 80 F pounds of moisture at 80 F is less than 15% RH which is below the ASHRAE recommendation of at least 20% RH to minimize electrostatic discharge. Airflow Sensor The area under a computer room s raised floor is quite often used as a plenum for chilled air. However, this space can become cluttered with networking and power cables which can restrict the flow of cooling air. Often, when new power or network cables are run under the floor the old cables are left in place. Over time these obstructions build up and can seriously restrict air flow. Perforated tiles allow the chilled air from the raised floor plenum to flow up to cool IT devices. Not only can this airflow be blocked by obstructions within the plenum but perforated tiles are available with various size holes. A cooling problem might be solved by changing to a tile with larger or smaller holes. It is important to monitor the chilled airflow but it can also be important to monitor the hot air return airflow. Differential Air Pressure Sensor In fluid dynamics, Bernoulli s principle states that for a fluid flow, an increase in the speed of the fluid occurs simultaneously with a decrease in pressure or a decrease in the fluid s potential energy. If you think about a shower curtain, before the shower is turned on the shower curtain hangs straight down. But when you turn on the shower the fluid inside the shower (air, steam and water) is moving faster than the fluid outside the shower (air) so the shower curtain is drawn into the shower because the pressure inside the shower has decreased. For hot aisle / cold aisle deployments using variable speed fans to conserve energy, the difference in the flow of air between the two aisles can potentially cause less rigid partitions such as plastic curtains to be drawn into one of the aisles creating air leaks. A differential air pressure sensor set up to alert when thresholds are crossed can help identify if there are pressure differences that might lead to partition leaks and inefficiencies. A chimney above a high-density / high-heat rack, and therefore high air pressure in the restricted volume of a chimney, might tend to leak hot air into a neighboring chimney above a low-density / low-heat rack and therefore low pressure. A differential air pressure sensor can indicate if such a condition exists. Water Sensor Water sensors can be used under racks to detect leaks. There are individual sensors and rope or cable sensors. A rope sensor can be laid under a row of racks and detect water anywhere along its length. A rope sensor can also be wrapped around pipes to detect leaks. Contact Closure Contact closure sensors can be set to be normally open or normally closed. They are often connected to third-party sensors and send an alert when the third-party sensor is triggered. For example, a contact closure sensor could be connected to a third-party smoke detection sensor and send an alert when smoke is detected. Or a contact closure sensor could trigger a webcam to take a picture when a cabinet door is opened. Raritan.com Page 6
7 Webcam A webcam itself can be considered a sensor in that it monitors a data center by providing images. These can be still images as was mentioned in the example above in the contact closure section or video can be streamed such as in a surveillance application. Management Software All these data points provided by sensors need to be managed. Environmental sensors can play a key role in partial or complete data center infrastructure management (DCIM) solutions. Sensors can provide important inputs for establishing a baseline of initial conditions, identifying problem areas such as hot spots or water leaks and tracking and reporting improvements and savings. For example, trend reports showing increasing data center temperatures over time can be added to information on reduced cooling energy consumption and cost in a corporate social responsibility (CSR) report. Or data center managers can confirm that proper operating conditions have been maintained and they are in compliance with corporate, vendor or utility guidelines and requirements. Psychrometric Chart (operational view of temperature and humidity sensors in data center) Source: Raritan Power IQ energy management software Sensors are particularly useful as part of a capacity planning process. Do you have adequate cooling where it is needed? Energy management software that can plot temperature sensor data on a psychrometric chart as described earlier gives data center managers a view as to what is happening where. Are some racks in hot spots? Do some areas of the data center require humidification? Careful planning is required when changing cooling infrastructure. There can be unintuitive consequences. For example, putting in additional air conditioning units might actually make existing hot spots worse or create new ones if the units disrupt airflow patterns. Raritan.com Page 7
8 The Benefits Of New Technology, Solutions And Tools A data center, whether a room or an entire building, is all about what is happening at the rack. The right environment monitoring and metering at the rack can lead to some nifty data center improvements right sizing the data center and just-in-time expansions to save on capital expenses; improved energy efficiency, IT productivity and utility; and better integration with cloud computing. The right way to look at a data center is not as a number of different IT devices and supporting infrastructure such as cooling and power distribution. Instead, look at a data center as a system. Each of the components has an impact on the other components. For example, replacing 1U pizza box servers with blade servers can significantly increase the amount of power consumed, and the amount of heat that must be removed from a rack. Bringing in DCIM software data points from several different types of sensors lets data center managers see their total operation as a whole yet with the ability to drill deeply into specific details. An environment management and monitoring program using one or more of the sensors described in this white paper is a good step towards really understanding a data center. Use technology, solutions and tools to make intelligent use of all your IT resources including IT assets, power, cooling, networks and, of course, people. About Raritan Raritan is a proven innovator of power management, infrastructure management, KVM and serial solutions for data centers of all sizes. In more than 50,000 locations worldwide, Raritan s award-winning hardware and software solutions including intelligent rack PDUs; energy management software; DCIM software solutions to effectively manage data center capacity, assets and change; KVM-over-IP and Serial-over-IP access products provide IT and facility directors, managers and administrators with the control they need to increase power management efficiency, improve data center productivity and enhance branch office operations. Based in Somerset, NJ, Raritan has offices worldwide serving customers in 76 countries. Visit us at Raritan.com or follow us on the Raritan blog. Raritan is an active member of the Green Grid, Climate Savers Computing Initiative and the Leadership in Energy and Environmental Design associations. The company was recognized by the EPA for its contribution to the agency s data center initiative Raritan Inc. All rights reserved. Raritan and Know more. Manage smarter. are registered trademarks or trademarks of Raritan Inc. or its wholly-owned subsidiaries. All others are registered trademarks or trademarks of their respective owners. Raritan.com Page V1170 8
5 Reasons. Environment Sensors are used in all Modern Data Centers
5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center
DCIM Data Center Infrastructure Monitoring
DCIM Data Center Infrastructure Monitoring ServersCheck offers a flexible, modular and affordable DCIM solution. It is based on our range of IP & SNMP hardware environmental sensors and management software.
How To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
EO 13514 and Smart Federal Government Data Center Management
1 Overview In fiscal year 2009, the U.S. government used an astounding 1,095.7 trillion BTUs of energy. This total included everything from keeping the lights on at the Lincoln Memorial to maintaining
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
How To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
Management and Wireless in the Data Center
SOLUTIONS BRIEF Management and Wireless in the Data Center High Performance Wireless Networks Management and Wireless in the Data Center Worldwide demand for new and more powerful IT-based applications,
Best Practices for Wire-free Environmental Monitoring in the Data Center
White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com [email protected] Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for
White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
Measure Server delta- T using AUDIT- BUDDY
Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
Data Centre Cooling Air Performance Metrics
Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. [email protected] Abstract Data centre energy consumption
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning 2009, Raritan Inc. Overview Corporate America is more dependent than ever on computing
Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers
C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
2008 ASHRAE Environmental Guidelines for Datacom Equipment -Expanding the Recommended Environmental Envelope-
2008 ASHRAE Environmental Guidelines for Datacom Equipment -Expanding the Recommended Environmental Envelope- Overview: The current recommended environmental envelope for IT Equipment is listed in Table
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
Data Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
Driving Data Center Efficiency Through the Adoption of Best Practices
Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary
Data Center Equipment Power Trends
Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data
Sensor Monitoring and Remote Technologies 9 Voyager St, Linbro Park, Johannesburg Tel: +27 11 608 4270 ; www.batessecuredata.co.
Sensor Monitoring and Remote Technologies 9 Voyager St, Linbro Park, Johannesburg Tel: +27 11 608 4270 ; www.batessecuredata.co.za 1 Environment Monitoring in computer rooms, data centres and other facilities
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT
DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Data Center Power Distribution and Capacity Planning:
Data Center Power Distribution and Capacity Planning: Understanding what you know and don t know about power usage in your data center 2009, Raritan Inc. About This Series Raritan, a leading provider of
How To Find A Sweet Spot Operating Temperature For A Data Center
Data Center Operating Temperature: The Sweet Spot A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Power Management. Raritan Description. http://www.raritan.com/products/power-management/
Raritan Description Raritan is a proven innovator of power management, infrastructure management, KVM and serial solutions for data centers of all sizes. In more than 50,000 locations worldwide, our hardware
Top 5 Trends in Data Center Energy Efficiency
Top 5 Trends in Data Center Energy Efficiency By Todd Boucher, Principal Leading Edge Design Group 603.632.4507 @ledesigngroup Copyright 2012 Leading Edge Design Group www.ledesigngroup.com 1 In 2007,
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Using CFD for optimal thermal management and cooling design in data centers
www.siemens.com/datacenters Using CFD for optimal thermal management and cooling design in data centers Introduction As the power density of IT equipment within a rack increases and energy costs rise,
Prediction Is Better Than Cure CFD Simulation For Data Center Operation.
Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.
Legacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
Data Center Power Consumption
Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling
Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems
NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
Cooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
The Effect of Data Centre Environment on IT Reliability & Energy Consumption
The Effect of Data Centre Environment on IT Reliability & Energy Consumption Steve Strutt EMEA Technical Work Group Member IBM The Green Grid EMEA Technical Forum 2011 Agenda History of IT environmental
Server Room Thermal Assessment
PREPARED FOR CUSTOMER Server Room Thermal Assessment Analysis of Server Room COMMERCIAL IN CONFIDENCE MAY 2011 Contents 1 Document Information... 3 2 Executive Summary... 4 2.1 Recommendation Summary...
Improving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures
Reducing the Annual Cost of a Telecommunications Data Center
Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities
Rack Blanking Panels To Fill or Not to Fill
Rack Blanking Panels To Fill or Not to Fill A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss Joyce F. Ruff Learn more at Dell.com/PowerEdge/Rack THIS WHITE PAPER IS FOR INFORMATIONAL
EO 13514 and Smart Federal Government Data Center Management
EO 13514 and Smart Federal Government Data Center Management 2011 Raritan Inc. Overview In fiscal year 2009, the U.S. government used an astounding 1,095.7 trillion BTUs of energy. This total included
Enclosure and Airflow Management Solution
Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...
DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers
DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ 2011 Raritan Inc. Overview Data center managers are faced with increasingly challenging demands: supplying additional computing
Center Thermal Management Can Live Together
Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots
Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential
TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com
AIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 [email protected] www.chatsworth.com All products
Improving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures
DataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360
Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy
THE PSYCHROMETRIC CHART AND ITS USE
Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader
Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Wright Line Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant Currently 60 percent of the cool air that
Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling
Saving energy in the Brookhaven National Laboratory Computing Center: Cold aisle containment implementation and computational fluid dynamics modeling Student Intern Earth and Environmental Engineering,
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
BRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT
Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
Alcatel-Lucent Modular Cooling Solution
T E C H N O L O G Y W H I T E P A P E R Alcatel-Lucent Modular Cooling Solution Redundancy test results for pumped, two-phase modular cooling system Current heat exchange methods for cooling data centers
Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs
WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level
BICSInews. plus. july/august 2012. + Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment.
BICSInews m a g a z i n e july/august 2012 Volume 33, Number 4 plus + Industrial-grade Infrastructure and Equipment + I Say Bonding, You Say Grounding + Data Center Containment & design deployment The
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
An Introduction to Cold Aisle Containment Systems in the Data Centre
An Introduction to Cold Aisle Containment Systems in the Data Centre White Paper October 2010 By Zac Potts MEng Mechanical Engineer Sudlows October 2010 An Introduction to Cold Aisle Containment Systems
White Paper: Free Cooling and the Efficiency of your Data Centre
AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200