Elements of Energy Efficiency in Data Centre Cooling Architecture

Size: px
Start display at page:

Download "Elements of Energy Efficiency in Data Centre Cooling Architecture"

Transcription

1 Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total Employees 600 Mio Plastics Technology A/C Technology Total A/C Technology Manufacturer and Distributor of Air Conditioning Products, Systems Engineering, Service and Object Management. STULZ GmbH, Germany (P) STULZ Pty Ltd., Australia STULZ-ATS (Shanghai), China (P) STULZ France S.A.R.L., France STULZ UK Ltd., Great Britain STULZ CHSPL Pvt. Ltd., India (P) STULZ SpA, Italy (P) STULZ Groep B.V., Netherlands STULZ Ltd., New Zealand STULZ Polska Sp. z o.o., Poland STULZ España S.A., Spain STULZ-ATS Inc., USA (P) (P): Production Site Plastics Technology Development and Production of Technical Plastic Components for automotive industry. MONTAPLAST GmbH, Germany MONTAPLAST of North America, Inc. MONTAPLAST Automotive System (SIP) Co.,LTD Energy Efficient Data Center Cooling 2 1

2 STULZ International Production Sites»STULZ»Air Technology Systems,»Frederick/MD, USA»STULZ S.p.A.»Valeggio sul Mincio(VR),»Italy»STULZ GmbH»Hamburg, Germany»STULZ»Air Technology Systems»(Shanghai), China»STULZ CHSPL (India)»Pvt. Ltd., India Energy Efficient Data Center Cooling 3 Headquarter Find STULZ... Germany Production Sites Germany Italy USA India and its qualified and professional partners worldwide. China Energy Efficient Data Center Cooling 4 2

3 Why Energy Efficient Cooling? Energy Efficient Data Center Cooling 5 Source: Lawrence Berkeley National Lab; Data centre energy benchmark case studies Energy Efficient Data Center Cooling 6 3

4 Energy Flow through the Data Centre Energy Efficient Data Center Cooling 7 again: Why energy efficient cooling? Save operating cost throughout the data centre's lifetime Get more IT capacity out of your data centre at a given available power by reducing power use of secondary physical infrastructure Energy Efficient Data Center Cooling 8 4

5 Elements influencing the Efficiency The Rack The Raised Floor The CRAC unit The Room Forced Air Cooling InRow Cooling Dynamic Free Cooling Energy Efficient Data Center Cooling 9 Elements influencing the Data Centre Cooling Efficiency Free Cooling Air Distribution Refrigerant Charge Filter Status Installed Options Ambient Conditions (Location) Room Temperature Room Humidity Raised Floor Height Perforated Tile Quantity Redundancy Level Pump Technology Pipe Sizing Refrigerant Dimensions Fan Technology Drycooler Size Filter Surface Water Temperatures Part Load Behaviour Heat Exchanger Surface Perforated Tile Opening Factor Leakage Airflow Rate Energy Efficient Data Center Cooling 10 5

6 Elements influencing the Efficiency The Rack The Raised Floor The CRAC unit The Room Forced Air Cooling InRow Cooling Dynamic Free Cooling Energy Efficient Data Center Cooling 11 Blanking plates in the rack separation of cold and hot aisle in the rack Source: HP informs: How to Meet 24 by Forever Demands of Your Data Center Prevent internal hot air recirculation by sealing the front of cabinets with blanking plates, including empty areas in the equipment mounting surface, between the mounting rails, and the edges of the cabinets (if necessary). Energy Efficient Data Center Cooling 12 6

7 Elements influencing the Efficiency The Rack The Raised Floor The CRAC unit The Room Forced Air Cooling InRow Cooling Dynamic Free Cooling Energy Efficient Data Center Cooling 13 Raised floor for decades of cables??? Energy Efficient Data Center Cooling 14 7

8 Raised floor For supply air (and cables/pipes) Energy Efficient Data Center Cooling 15 Leakage Airflow - to be avoided Energy Efficient Data Center Cooling 16 8

9 Air Cooling A matter of Raised Floor Design - Free raised floor height - the more, the better - Leakage Airflow - close all unwanted openings - Cabling or Air - if used for both, define space for each - Tile open area and number of tiles - less is more Energy Efficient Data Center Cooling 17 Elements influencing the Efficiency The Rack The Raised Floor The CRAC unit The Room Forced Air Cooling InRow Cooling Dynamic Free Cooling Energy Efficient Data Center Cooling 18 9

10 System Selection Major Influence on CAPEX and OPEX A G GE CW ACW GCW CW2 : Direct expansion - air cooled : Direct expansion - water cooled : Direct expansion - water cooled AND freecooling (Standard version) : Chilled water : Dualfluid - Direct expansion - aircooled and chilled water : Dualfluid - Direct expansion - watercooled and chilled water : Dual chilled water Energy Efficient Data Center Cooling 19 Influence of the fan technology on the power consumption Annual energy costs fan only [8.500m³/h at 350Pa] Energy costs [Euro/Year] % -28% -10% Centrifugal Plug fan STULZ EC fan Energy cost savings with EC fan compared to ordinary fans Energy Efficient Data Center Cooling 20 10

11 Design of the CRAC unit: Build in Energy Efficiency Low power consumption by means of State of the art fan technology EC-Fans Low Air Resistance Heat Exchanger Low Air Resistance Filter with increased surface Enlarged Casing Free of charge reheat with optional refrigerant reheat Control of external Ultrasonic Humidifier...but an acceptable footprint is still achieved! Energy Efficient Data Center Cooling 21 Stand-by Managment Sample: 3x ASD1500CW At 24 C/50% with 7/12 C water incl. 1/3 standby capacity Standby Airflow: 2x m³/h Fan absorbed power: 2x 8,0 = 16,0 kw Lpa,2m = 2x 59,7dBA = 62,7dBA Airflow: 3x m³/h Fan absorbed power: 3x 2,3 = 6,9 kw Lpa,2m = 3x 50,8dBA = 55,6dBA 2x 112,1 = 224,2 kw net sensible 3x 75,1 = 225,3 kw net sensible Benefits: + Considerable energy savings + Reduced noise levels => Energy savings: 9,1 kw x 8760h x 0,13 = ,13 /kwh => Noise reduction: -7,1 dba Energy Efficient Data Center Cooling 22 11

12 Elements influencing the Efficiency The Rack The Raised Floor The CRAC unit The Room Forced Air Cooling InRow Cooling Dynamic Free Cooling Energy Efficient Data Center Cooling 23 Room Efficiency Best Room Efficiency will be reached, if each m³ of cold air leaving the CRAC unit, passing the data centre and reaching the return air of the CRAC unit, takes only once the design amount of heat from the IT equipment. Means: No leakage airflow, no recirculating air, no bypass air. Energy Efficient Data Center Cooling 24 12

13 How much Air Volume? Low air volume Right air volume High air volume Source: Intel Energy Efficient Data Center Cooling 25 How to guide the Air through the Room. Energy Efficient Data Center Cooling 26 13

14 Air Cooling A matter of a Defined Air Path (1/3) Cold Supply Air: Directly into the Room Warm Return Air: Through the Room Part of the raised floor must be closed (hot aisle) Increase of cooling capacity/efficiency due to better defined air path Still risk of air short circuit (top of Racks, end of rows) Usable in combination with non-19 -stand alone equipment 1 tile/rack, 600cfm/tile, 120cfm/kW => 5kW/rack can be removed SOURCE: ASHRAE - Datacom Equipment Power Trends and Cooling Applications Energy Efficient Data Center Cooling 27 Air Cooling A matter of a Defined Air Path (2/3) Cold Supply Air: Directly into the Room Warm Return Air: Through duct and false ceiling Whole raised floor can be used for perforated tiles No need for front to front layout Increased cold air supply to the room / rack front area possible Usable in combination with non-19 -stand alone equipment 2 tile/rack, 600cfm/tile, 120cfm/kW => 10kW/rack can be removed SOURCE: ASHRAE - Datacom Equipment Power Trends and Cooling Applications Energy Efficient Data Center Cooling 28 14

15 Air Cooling A matter of a Defined Air Path (3/3) Cold Supply Air: Directly into the Rack Warm Return Air: Through duct and false ceiling No need for perforated tiles No need for front to front layout Usable in combination with non-19 -stand alone equipment High Delta T Cooling (20 C) with Blade Servers poss ible e.g. 2000cfm/rack, 100cfm/kW => 20kW/rack can be removed SOURCE: ASHRAE - Datacom Equipment Power Trends and Cooling Applications Energy Efficient Data Center Cooling 29 Elements influencing the Efficiency The Rack The Raised Floor The CRAC unit The Room Forced Air Cooling InRow Cooling Dynamic Free Cooling Energy Efficient Data Center Cooling 30 15

16 Air Cooling A matter of a Defined Air Path Air Distribution Unit ADU» Conditioned Room Air Is: Pulled in from underneath raised floor Delivered from bottom to top of rack by dual fans Drawn in by the IT equipment» Provides Cooler Air to the Rack Provides better cooling for IT equipment reducing heat related failures. Extends the life of equipment in the rack Energy Efficient Data Center Cooling 31 Air Cooling A matter of a Defined Air Path Air Removal Unit ARU» Hot air scavenging systems Collect hot air at the point of generation Route directly to CRAC Snap-on retrofit 2,000 CFM airflow Variable speed: as needed Dual Path Power and N+1 Flexible, Movable Hard floor or raised floor» Applications Rack density needs to increase» Limit: 12.5 kw per rack for servers Up to 23 kw per rack for blades Energy Efficient Data Center Cooling 32 16

17 Air Cooling A matter of a Defined Air Path Energy Efficient Data Center Cooling 33 Air Cooling A matter of a Defined Air Path Energy Efficient Data Center Cooling 34 17

18 Elements influencing the Efficiency The Rack The Raised Floor The CRAC unit The Room Forced Air Cooling InRow Cooling Dynamic Free Cooling Energy Efficient Data Center Cooling 35 APC InRow Cooling System IT Racks Cooling Front View Energy Efficient Data Center Cooling 36 18

19 »InRow Cooling APC InRow Cooling System Close coupled heat source and heat removal Raised floor not required for air distribution Energy Efficient Data Center Cooling 37 APC InRow Cooling with Hot Aisle Containment System (HACS) Energy Efficient Data Center Cooling 38 19

20 APC InRow Cooling with Hot Aisle Containment System (HACS) Energy Efficient Data Center Cooling 39 Secure Chilled Water Supply Chiller mounted indoors Condenser / Drycooler CyberAir Air Conditioning Unit CyberCool CSI Indoor Chiller Energy Efficient Data Center Cooling 40 20

21 Secure Chilled Water Supply Chiller mounted outdoors CyberCool CSO Chiller mounted outside CyberAir Air Conditioning Unit CyberCool CPI System Transfer / Pump Station Energy Efficient Data Center Cooling 41 Secure Chilled Water Supply for existing Chilled Water Sources CyberCool CPI System Transfer / Pump Station Energy Efficient Data Center Cooling 42 21

22 Elements influencing the Efficiency The Rack The Raised Floor The CRAC unit The Room Forced Air Cooling InRow Cooling Dynamic Free Cooling Energy Efficient Data Center Cooling 43 CyberAir with DFC lowers TCO TCO Total Cost of Ownership Amortisation CyberAir 2 Extra Investment CyberAir 2 Basic Investment Ordinary Climate Control Running Time Lower Opex Higher Capex Energy Efficient Data Center Cooling 44 22

23 Hybrid Climate Control System»Automatic selection of energy efficient cooling mode depending on outdoor temperature and thermal load»compressor operation or Free Cooling in four modes»electronic Expansion Valve: increased COP compressor cooling in MIX mode»dynamic component control ( pump, fan unit, expansion valve, fan dry cooler and water valves)»dynamic water temperature in order to get the maximum energy saving Energy Consumption FC Free Cooling EFC Extended Free Cooling High efficient MIX mode Compressor & Free Cooling DX Compressor Cooling Energy Efficient Data Center Cooling 45 Regions for Free Cooling Energy Efficient Data Center Cooling 46 23

24 System Design The Location / The Temperature Profile MIX & Free Cooling Compressor Energy Efficient Data Center Cooling 47 System Design 1 Use of Dynamic Free Cooling System CapEx: +75% OpEx: -30% 10year savings: 814 k Energy Efficient Data Center Cooling 48 24

25 Annual Operating Hours Percentage per Mode Energy Efficient Data Center Cooling 49 Various possibilities to analyse/optimise Energy Efficient Data Center Cooling 50 25

26 System Design 2 Chilled Water w/o and w/ Free Cooling CapEx: +11% OpEx: -3.3% 10year savings: 103 k Energy Efficient Data Center Cooling 51 System Design 3 Chilled Water Temperature UP CapEx: -6% (!!) OpEx: -29% 10year savings: k Energy Efficient Data Center Cooling 52 26

27 System Design 3 Chilled Water Temperature UP Energy Efficient Data Center Cooling 53 System Design 4 without vs. with Standby Management CapEx: +0% OpEx: -10% 10year savings: 110 k Energy Efficient Data Center Cooling 54 27

28 System Design 4 without vs. with Standby Management Energy Efficient Data Center Cooling 55 Return Air temperature Room temperature Return Air 24 C I M P O R T A N T!!! 21 C Return Air Room Depending on heat load the return air temp. is at least 2-3K higher than room temperature Supply Air 16 C Energy Efficient Data Center Cooling 56 28

29 System Design 5 Influence of Return Air Temperature CapEx: -<1% OpEx: -39% 10year savings: k Energy Efficient Data Center Cooling 57 System Design 5 Influence of Return Air Temperature Energy Efficient Data Center Cooling 58 29

30 ...thank you for your attention Energy Efficient Data Center Cooling 59 30

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

News in Data Center Cooling

News in Data Center Cooling News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Free Cooling for Data Centers

Free Cooling for Data Centers Free Cooling for Data Centers Release 1, September 2015 Contents 1. Abstract... 3 2. Introduction... 3 3. Data Center Temperatures and Free Cooling... 4 4. Direct Free Cooling... 4 5. Indirect Free Cooling...

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

IT Cooling Solutions. DFC² Direct Free Cooling for Data Centres. Energy-efficient, reliable and available around the world

IT Cooling Solutions. DFC² Direct Free Cooling for Data Centres. Energy-efficient, reliable and available around the world IT Cooling Solutions DFC² Direct Free Cooling for Data Centres Energy-efficient, reliable and available around the world Worldwide Green Engineering with Direct Free Cooling from STULZ Forward thinking

More information

IT Cooling Solutions. DFC² Direct Free Cooling for Data Centres. Energy-efficient, reliable and available around the world

IT Cooling Solutions. DFC² Direct Free Cooling for Data Centres. Energy-efficient, reliable and available around the world IT Cooling Solutions DFC² Direct Free Cooling for Data Centres Energy-efficient, reliable and available around the world Worldwide Green Engineering with Direct Free Cooling from STULZ Forward thinking

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

STULZ Water-Side Economizer Solutions

STULZ Water-Side Economizer Solutions STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2014

European Code of Conduct for Data Centre. Presentation of the Awards 2014 European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

STULZ View On DataCenter Cooling

STULZ View On DataCenter Cooling STULZ View On DataCenter Cooling Stulz Was Founded In Hamburg (Germany) In 1947 And Has 5 Production Sites And 14 Subsidiaries In 14 Countries. We Are Represented By Partners In Over 110 Countries. Stulz

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Data Centre Cooling: Don't Waste Money on the Wrong Solution

Data Centre Cooling: Don't Waste Money on the Wrong Solution Data Centre Cooling: Don't Waste Money on the Wrong Solution Stulz IT Cooling Production Sites STULZ GmbH Hamburg, Germany STULZ S.p.A., Valeggio sul Mincio (VR), Italy STULZ Air Technology Systems, Frederick/MD,

More information

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010 White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence

More information

CoolTeg Plus Chilled Water (CW) version: AC-TCW

CoolTeg Plus Chilled Water (CW) version: AC-TCW version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420

More information

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.

More information

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION 1/16 Contents: 1. Introduction: the increasing importance of energy efficiency 1.1 Power consumers in the data

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

How to Build a Data Centre Cooling Budget. Ian Cathcart

How to Build a Data Centre Cooling Budget. Ian Cathcart How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options

More information

How to Meet 24 by Forever Cooling Demands of your Data Center

How to Meet 24 by Forever Cooling Demands of your Data Center W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Data Center Equipment Power Trends

Data Center Equipment Power Trends Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data

More information

White Paper Rack climate control in data centres

White Paper Rack climate control in data centres White Paper Rack climate control in data centres Contents Contents...2 List of illustrations... 3 Executive summary...4 Introduction...5 Objectives and requirements...6 Room climate control with the CRAC

More information

National Grid Your Partner in Energy Solutions

National Grid Your Partner in Energy Solutions National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National

More information

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

Data Center Energy Profiler Questions Checklist

Data Center Energy Profiler Questions Checklist Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some

More information

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Blade Server & Data Room Cooling Specialists

Blade Server & Data Room Cooling Specialists SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack

More information

BICSInews. plus. july/august 2012. + Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment.

BICSInews. plus. july/august 2012. + Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment. BICSInews m a g a z i n e july/august 2012 Volume 33, Number 4 plus + Industrial-grade Infrastructure and Equipment + I Say Bonding, You Say Grounding + Data Center Containment & design deployment The

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

EHDC. Cooling system for Data Center and server cabinets.

EHDC. Cooling system for Data Center and server cabinets. EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

Data Center Temperature Rise During a Cooling System Outage

Data Center Temperature Rise During a Cooling System Outage Data Center Temperature Rise During a Cooling System Outage White Paper 179 Revision 1 By Paul Lin Simon Zhang Jim VanGilder > Executive summary The data center architecture and its IT load significantly

More information

Technical Systems. Helen Bedford

Technical Systems. Helen Bedford Technical Systems in Data Centres Helen Bedford Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre

More information

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Legacy Data Centres Upgrading the cooling capabilities What are the options? Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

Precise, Reliable and Innovative Air Conditioning for Information and Communication Technology

Precise, Reliable and Innovative Air Conditioning for Information and Communication Technology STULZ the natural choice Precise, Reliable and Innovative Air Conditioning for Information and Communication Technology 2 Perfect Air Conditioning for Secure ICT Technology Innovative blade constructions,

More information

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however

More information

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Energy Impact of Increased Server Inlet Temperature

Energy Impact of Increased Server Inlet Temperature Energy Impact of Increased Server Inlet Temperature By: David Moss, Dell, Inc. John H. Bean, Jr., APC White Paper #138 Executive Summary The quest for efficiency improvement raises questions regarding

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

Data Center Temperature Rise During a Cooling System Outage

Data Center Temperature Rise During a Cooling System Outage Data Center Temperature Rise During a Cooling System Outage White Paper 179 Revision 0 By Paul Lin Simon Zhang Jim VanGilder > Executive summary The data center architecture and its IT load significantly

More information

AIR-SITE GROUP. White Paper. Green Equipment Room Practices

AIR-SITE GROUP. White Paper. Green Equipment Room Practices AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider

More information

Benefits of Cold Aisle Containment During Cooling Failure

Benefits of Cold Aisle Containment During Cooling Failure Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200

More information

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

Rittal Liquid Cooling Series

Rittal Liquid Cooling Series Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de

More information

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Executive Summary Data center energy usage has risen dramatically over the past decade and

More information

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

Enclosure and Airflow Management Solution

Enclosure and Airflow Management Solution Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...

More information

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An

More information

Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package

Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package Munther Salim, Ph.D. Yury Lui, PE, CEM, LEED AP eyp mission critical facilities, 200 west adams street, suite 2750, Chicago, il 60606

More information

Energy Efficiency Best Practice Guide Data Centre and IT Facilities

Energy Efficiency Best Practice Guide Data Centre and IT Facilities 2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits

More information

DataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation.

DataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation. DataCenter 2020. Data Center Management and Efficiency at Its Best. OpenFlow/SDN in Data Centers for Energy Conservation. Dr. Rainer Weidmann, DC Architecture & DC Innovation Dr. Rainer Weidmann, DC Architecture

More information

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings

More information

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel. Climate solutions evaporative cooling, adiabatic humidification and programmable controllers energy saving solutions for data centers carel.com Data center air-conditioning Data center air-conditioning

More information

Webinar: Precision Cooling in Data Centres and other applications 24 June 2014

Webinar: Precision Cooling in Data Centres and other applications 24 June 2014 Webinar: Precision Cooling in Data Centres and other applications 24 June 2014 Jeremy Towler - Senior Manager Energy & Smart Technologies David Garwood Researcher Air-conditioning solutions Helen Bedford

More information

White Paper #10. Energy Efficiency in Computer Data Centers

White Paper #10. Energy Efficiency in Computer Data Centers s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore

Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational

More information

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London. Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry

More information