Free Cooling for Data Centers
|
|
|
- Loreen Dorsey
- 10 years ago
- Views:
Transcription
1 Free Cooling for Data Centers Release 1, September 2015
2 Contents 1. Abstract Introduction Data Center Temperatures and Free Cooling Direct Free Cooling Indirect Free Cooling Single-stage Indirect Free Cooling Two-stage Indirect Free Cooling Two-stage Indirect Free Cooling: CRAC with dry cooler Two-stage Indirect Free Cooling: CRAH with chiller Adiabatic Assistance Adiabatic Assistance with Direct Free Cooling Systems Adiabatic Assistance with Indirect Free Cooling Systems Techniques of Adiabatic Cooling Use of Adiabatic Assistance Other Free Cooling Systems Summary
3 1. Abstract This white paper provides an overview of free cooling for data centers. It consists of a general description of free cooling and an explanation of different available free cooling solutions, as well as their strengths and weaknesses. The term free cooling is equivalent to the term economizer that is nowadays predominantly used in the North American region. 2. Introduction What is free cooling? Is free cooling really free of charge as implied? Free cooling for data centers generally refers to the removal of heat, created by IT equipment in the data center by means of cold outdoor air and therefore without the use of refrigeration compressors. In any case, air needs to be moved to remove the heat, which means that fans must be in operation. Indirect free cooling systems use both, fans and pumps, but no energy-intensive refrigeration compressors. Free cooling therefore means to remove heat from the data center with the minimum amount of energy required to operate fans and pumps. This amount of energy required to cool the data center (or to remove the heat) is much lower compared with systems without free cooling where refrigeration compressors are required for heat removal. 3
4 3. Data Center Temperatures and Free Cooling There are various measurable temperatures present in a data center e.g. supply air, return air, room air, cold aisle, server inlet temperature and so on. When talking about data center temperature, it is important to be clear which temperature you are most concerned with. Server inlet temperature and server exit temperature are well known to have a significant effect on the efficiency of any cooling system. The server inlet temperature is similar to the supply air temperature of the cooling equipment (assuming minimal losses). The server exit temperature is similar to the return air temperature of the cooling equipment, considering a properly designed airflow through the data center without air recirculation, bypass air or significant leakages (see STULZ white paper on this topic for a detailed discussion). The higher the server inlet temperature, the more efficient the cooling system can become and the more free cooling hours per year can be realized. Twenty years ago, the CRAC (packaged Computer Room Air Conditioner) return air temperature was the main control parameter and was set to C (72-75 F). This resulted in unnecessarily low supply air temperatures in a range of 12 C (54 F). Today, the best practices are very different. In a modern data center, the supply air temperature is the main control parameter. It is typically set between 18 C and 27 C (64 F and 81 F) as recommended by ASHRAE TC9.9 (2011 Thermal Guidelines for Data Processing Environments). This has resulted in return air temperatures to the cooling equipment of C ( F). As you can see, the overall temperature levels in data centers has been increased by around 10 C (18 F). 4. Direct Free Cooling On the most basic level, direct free cooling could be described as follows: open a window, blow cold air from outside through the data center, pick up the heat, transport it back outside, done! Physically speaking, that s exactly what happens. However, the process of moving the air requires energy. Unfortunately, in real life things are not that simple. Outdoor air is not always in a condition that the IT equipment is comfortable with. Sometimes it s hot and sometimes cold, sometimes it s very humid and sometimes very dry. What s more, outdoor air is not always 4
5 Figure 1: Direct Free Cooling Direct Free Cooling STRENGTHS Highest theoretical efficiency of any free cooling system WEAKNESSES Depends on outdoor air quality Significant air filtration is required High maintenance requirements Measures for humidification and dehumidification required Huge indoor space requirements for ductwork Security issues to consider Limited to locations with colder climates Client service level agreements with humidity tolerances to be agreed 100% mechanical cooling backup required clean. The outdoor air is often full of particles which can be very hostile to modern IT equipment. So, direct free cooling should only be used where the negative properties of the outdoor air can be controlled by financially acceptable measures. Before the outdoor air is allowed access to the data center, it must be filtered a process that can be expensive. If the outdoor air is too cold, a certain proportion of warm air from the data center must be mixed in with the cold air to supply controlled, tempered air to the IT equipment. The airflow concept and the control system in the data center must be designed to ensure this. If the outdoor air is too warm, additional mechanical cooling will be required. Therefore, in locations with very high average annual temperatures, direct free cooling may not be a feasible option. 5
6 Air humidity is yet another challenge. Although they are only machines, servers really don t like excessively dry or excessively humid air. Methods to humidify or dehumidify the air can also be very expensive and complex. The amount of cooling that can be transported by outdoor air is much less than can be transported by traditional means using chilled water or refrigerant pipes. This means that large ductwork systems are required in addition to large openings in the building fabric to bring in the outdoor air plus an equally large ductwork system and fabric openings for the exhaust air. The openings and ductwork brings a security risk to the data center that has to be considered. So as we can see, the main advantages are put into perspective if expensive additional measures are necessary due to conditions at the site in question. 5. Indirect Free Cooling With indirect free cooling, the window stays shut. The outdoor air, with all its contaminating particulates, can t get into the data center and remains outside. The weaknesses of direct free cooling mentioned above do not apply with indirect free cooling. Unfortunately, indirect free cooling is theoretically less efficient than direct free cooling, as at least one heat transfer must always take place between the air in the data center and the outdoor air. At least one heat exchanger is required, and that means a loss of efficiency Single-stage Indirect Free Cooling Single-stage Indirect Free Cooling systems transfer heat using an air/air heat exchanger. Figure 2: Indirect Free Cooling with air/air plate heat exchanger 6
7 The air in the data center is circulated and conveyed through the inside section of the air/ air heat exchanger without making direct contact or mixing with the outdoor air. Likewise, the outdoor air is ducted through the outdoor air section of the air/air heat exchanger and then ducted back outdoor the data center. This air/air heat exchanger can either be a cubic formed box, typically a plate heat exchanger with fixed positions, or a large, slow rotating heat exchanger thermal wheel. Figure 3: Indirect Free Cooling with heat exchanger thermal wheel Single-stage Indirect Free Cooling STRENGTHS Very high efficiency Independent from outdoor air quality Independent from outdoor air humidity WEAKNESSES Very high indoor footprint required. 4 to 6 times more than two-stage systems require. 100% mechanical cooling backup required Security issues to consider Additional equipment for humidification and dehumidification required 7
8 5.2. Two-stage Indirect Free Cooling Two-stage Indirect Free Cooling systems have a considerably smaller footprint than their single-stage counterparts, but are somewhat less efficient as they function with two heat transfers. In the first heat exchanger, the heat from the air in the data center is transferred to a liquid, normally glycol. This is then pumped to the outside in relatively small pipes, where heat from the data center is rejected to the outdoor air via a second heat exchanger. Again, we lose some efficiency through this second heat transfer. Here, the mechanical cooling unit is an integral part of the system, and is only used to supplement the free cooling at high outdoor air temperatures. If the outdoor air is very hot, all cooling will take place mechanically. There are generally two different Two-stage Indirect Free Cooling systems available; one consists of a CRAC (packaged Computer Room Air Conditioner) and dry cooler or cooling tower, the other of a CRAH (chilled water Computer Room Air Handler) and chiller Two-stage Indirect Free Cooling: CRAC with dry cooler In this type of system, a CRAC is located in the data center and is equipped with an additional free cooling heat exchanger. The CRACs are connected via water pipes with the dry cooler that is located outside the building. During cold periods, the dry cooler supplies cold water to the CRAC. At this time it operates in free cooling mode with the compressor off. When outdoor air temperatures are high, the water temperature supplied from the dry cooler is not cold enough for free cooling and the CRAC must use mechanical cooling to make up the difference. In between, at moderate outdoor air temperatures, the system works in mixed mode; in addition to free cooling, the mechanical cooling works to top-up cooling when required. The advantage of this system is that the mixed mode already starts at relatively high outdoor air temperatures. As soon as the dry cooler can produce water with a temperature below the return air temperature in the data center, the mixed mode starts and the compressor operating time can be reduced. Depending on the sizing of the dry cooler mixed mode takes place when the outdoor air temperature is approximately 5 C (9 F) below the return air temperature in the data center. Full free cooling can then start at relatively high (moderate) outdoor air temperatures when the dry cooler can produce a water temperature which is sufficient to run the CRAC in full free cooling mode. Modern Two-stage Indirect Free Cooling Systems, such as STULZ s Dynamic Free Cooling System (see separate STULZ white paper), work with a dynamic water temperature between CRAC and dry cooler. This leads to a dynamic adaptation and increase in free cooling hours to the part load behavior in the data center. The lower the load, the higher the water temperature, the more free cooling hours will be achieved. The coolant water is normally mixed with glycol acting as an anti-freeze to protect the dry cooler when the outdoor air temperature is below freezing. 8
9 Figure 4: Indirect Free Cooling with CRAC and dry cooler Two-stage Indirect Free Cooling by CRAC and dry cooler STRENGHTS High efficiency Independent from outdoor air quality Independent from outdoor air humidity 100% mechanical cooling backup included Tried and tested system WEAKNESSES Unknown, so far 9
10 Two-stage Indirect Free Cooling: CRAH with chiller The second typical Two-stage Indirect Free Cooling system consists of CRAHs and a chiller with free cooling heat exchanger. This can either be an air cooled chiller with integral built-in free cooling heat exchanger or a water cooled chiller connected to a dry cooler or cooling tower. The chilled water temperature from the chiller to the CRAH is relatively low, and when the outdoor air temperature is below the chilled water temperature, the chiller can activate mixed mode free cooling and reduce the chiller s compressor run time. If the outdoor air temperature is significantly lower than the chilled water temperature, then 100% free cooling can be achieved. Due to relatively low chilled water temperatures with this type of indirect free cooling system, it is less efficient than the above system (5.2.1.) with packaged CRAC units. The chilled water is normally mixed with glycol acting as an anti-freeze to protect the chiller s free cooling coil or dry cooler when the outdoor air temperature is below freezing. This system can usually be found in large applications with a large number of CRAH s connected to chillers in the megawatt range. Figure 5: Indirect Free Cooling with CRAH and chiller Two-stage Indirect Free Cooling by CRAH and chiller STRENGTHS Good efficiency Independent from outdoor air quality Independent from outdoor air humidity 100% mechanical cooling backup included Simple tried and tested system WEAKNESSES Full free cooling and mixed operation starts at relatively low outdoor air temperatures 10
11 6. Adiabatic Assistance There is a physical principle that can further increase the efficiency of free cooling systems, whether they are direct, single-stage indirect or two-stage indirect. Air contains a certain amount of water. The amount of water that is contained in air is limited. This amount depends on the air temperature and barometric pressure. The amount of water content in relation to what is maximally possible is expressed in the metric relative humidity. If air has a relative humidity of 50% or 70%, this air can absorb more water (up to 100% RH). As water absorbs into the air, an adiabatic process takes place; this means the temperature of the air will decrease (desired effect) while the energy content of the air remains unchanged. The physics behind this process is not important for this publication; however, the benefit of a reduction in the air temperature and increase in free cooling are of great importance. Adiabatic Assistance STRENGTHS Increase in efficiency of the data center free cooling systems Wider outdoor air temperature range (wet bulb approach) for free cooling Particularly suited for dry desert climates (if water is available WEAKNESSES Not suited for humid tropical climates Requires large amounts of fresh water Assessing Legionella risk, control & monitoring responsibilities May be maintenance intensive Regional restrictions on safe fresh water handling Large water storage required if uninterrupted water supply is a concern How can it be used to increase efficiency of data center free cooling systems? 11
12 6.1. Adiabatic Assistance with Direct Free Cooling Systems By using adiabatic assistance in direct free cooling systems the air that enters the data center will be cooled before entering the data center if it is too warm. This is by far a more efficient alternative to mechanical cooling. However, by doing so, the humidity of the air is increased and there are usually limits for the humidity levels of the air in the data center. This means that this is a great idea in theory, but its use is limited in practice Adiabatic Assistance with Indirect Free Cooling Systems Indirect free cooling and adiabatic assistance is more conducive for the data center, as the adiabatically assisted outdoor air never enters the data center. In Single-stage Indirect Free Cooling systems, adiabatic assistance will reduce the temperature of the outdoor air entering the air/air heat exchanger and therefore extend the amount of free cooling and reduce the amount of mechanical cooling required to satisfy the supply air temperature to the IT equipment. In Two-stage Indirect Free Cooling systems, the warm outdoor air can be cooled by adiabatic assistance before entering the dry cooler to either increase the hours of usable free cooling or to extend the mixed mode at the upper limit to reduce the use of mechanical cooling. Note: When designing a Two-stage Indirect Free Cooling system with adiabatic assistance from the initial stage, there is a risk associated with reducing the size of the dry cooler to save capital expenses with a smaller dry cooler with adiabatic assistance. With a smaller dry cooler in dry operation, the amount of full free cooling hours and mixed mode free cooling hours per year will be reduced. More importantly, should there be an interruption in the water supply in summer when the outdoor air temperature is hot the smaller dry cooler would not have the capacity to reject the heat from the CRAC units causing them to shut down on safety pressure switches. This means that in systems like these the dry cooler should be sized based on dry cooling mode without the use of adiabatic assistance Techniques of Adiabatic Cooling There are different possibilities for evaporative (or adiabatic) cooling. Water may be evaporated by means of an ultrasonic humidifier which produces very small water drops, or using spray systems or systems where the air is drawn through water-moistened pads. The water-moistened pad system is very popular in combination with dry coolers and, though the system is easy to handle, it also represents a permanent resistance in the airflow, which increases the fan power consumption, even when adiabatic cooling is not required. Spray systems are commonly used in cooling towers and ultrasonic humidifiers can be found in some air handlers for adiabatic assistance. 12
13 FREIE KÜHLUNG FÜR RECHENZENTREN 6.4. Use of Adiabatic Assistance The benefits of adiabatic assistance are best realized in dry climate areas, but they are now used almost anywhere where a small benefit can be achieved. The water itself is not free of charge and the equipment to evaporate the water may be expensive, not to mention the cost of operating the equipment. Handling water, in particular recycled sprayed water, involves a statutory requirement to provide a detailed risk assessment to prevent Legionella (Legionnaires disease) with sterilization control and ongoing monitoring. A high level of maintenance may also be required, so the use of adiabatic assistance must be evaluated carefully. 7. Other Free Cooling Systems In the above chapters, we have described the most popular systems and principles of free cooling. There are several variants available that make use of pre-existing equipment. We will pick out the most popular variant here: This is a system consisting of dual chilled water units. In this example, we will consider a CRAH with two independent circuits: one circuit is connected to a chiller plant without free cooling, and the other circuit is connected to a dry cooler or a cooling tower. The existing chiller plant is used for operation when outdoor air temperatures do not allow free cooling and, as soon as outdoor air temperatures are moderate or low, the second circuit will start to run the dual circuit CRAH in free cooling mode or mixed mode. Special control logics are required. 8. Summary As shown in this white paper, there are several methods for reducing the PUE and the energy bill of a data center by means of free cooling. No system is perfect, and all systems described here have some limitations; some have regional advantages, others may offer advantages due to the size of the data center. Adiabatic assistance is useful but may not be used everywhere and not under all circumstances. It is important to evaluate what kind of free cooling is best suited to the application on a case by case basis. 13
14 ACKNOWLEDGMENTS I would like to thank the following people for their input, reviews and comments on this paper during the review phases: John Jakovcevic, Derek Siveter, Erik Wever, Dave Meadows, Aaron Sabino and Phillip Diffley. ABOUT THE AUTHOR Benjamin Petschke was born in 1969 in Germany. After studying physics he joined STULZ in 1996 and, since then has been working in the R&D, Export and Marketing division in various positions. With 18+ years experience in the data center cooling industry, Benjamin specializes in data center cooling design, energy saving and acoustic issues. He works closely with the Joint Research Centre of the European Commission for the Code of Conduct on Data Centres, Best Practice section, and recently with the German DKE on the development of the DIN EN 50600, Information technology Data Centre facilities and infrastructures. Benjamin has written white papers on subjects like Best Practice for Data Centre Cooling and Indirect Free Cooling with Dynamic Control Logic. ABOUT STULZ GMBH Since it was founded in 1947, STULZ has evolved into one of the world s leading system suppliers for air-conditioning technology. STULZ manufactures precision air-conditioning units, chillers, air handlers and high density cooling solutions. Since 1974, the group has seen continual international expansion of its air conditioning technology business, specializing in A/C for data centers and telecommunications installations. STULZ employs 2,200 workers in Germany and maintains seventeen international subsidiaries (in France, Italy, Great Britain, Belgium, the Netherlands, New Zealand, Mexico, Brazil, Austria, Poland, Spain, Singapore, China, India, South Africa, Australia and the USA). The company also works with sales and service partners in over 130 other countries and therefore boasts an international network of air-conditioning specialists. It has production plants in Germany, Italy, the USA, China and India. 14
15 STULZ GmbH Holsteiner Chaussee Hamburg Subsidiaries AUSTRALIA STULZ AUSTRALIA PTY. LTD. FRANCE STULZ FRANCE S. A. R. L. NEW ZEALAND STULZ NEW ZEALAND LTD. AUSTRIA STULZ AUSTRIA GmbH UK STULZ U. K. LTD. POLAND STULZ POLSKA SP. Z O.O. [email protected] BELGIUM STULZ BELGIUM BVBA [email protected] ITALY STULZ S.p.A. [email protected] SINGAPORE STULZ SINGAPORE PTE LTD. [email protected] BRASIL STULZ Brasil Ar Condicionado Ltda. [email protected] CHINA STULZ AIR TECHNOLOGY AND SERVICES SHANGHAI CO., LTD. [email protected] SPAIN STULZ ESPAÑA S.A. [email protected] INDIA STULZ-CHSPL (INDIA) PVT. LTD. [email protected] MEXICO STULZ México S.A. de C.V. [email protected] NETHERLANDS STULZ GROEP B. V. [email protected] USA STULZ AIR TECHNOLOGY SYSTEMS (SATS), INC. [email protected] SOUTH AFRICA STULZ SOUTH AFRICA PTY. LTD. [email protected]
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
State of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
The Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
White Paper #10. Energy Efficiency in Computer Data Centers
s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
IT Cooling Solutions. DFC² Direct Free Cooling for Data Centres. Energy-efficient, reliable and available around the world
IT Cooling Solutions DFC² Direct Free Cooling for Data Centres Energy-efficient, reliable and available around the world Worldwide Green Engineering with Direct Free Cooling from STULZ Forward thinking
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
Legacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
Guide to Minimizing Compressor-based Cooling in Data Centers
Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi
IT Cooling Solutions. DFC² Direct Free Cooling for Data Centres. Energy-efficient, reliable and available around the world
IT Cooling Solutions DFC² Direct Free Cooling for Data Centres Energy-efficient, reliable and available around the world Worldwide Green Engineering with Direct Free Cooling from STULZ Forward thinking
Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
Data Centre Cooling Air Performance Metrics
Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. [email protected] Abstract Data centre energy consumption
Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.
Climate solutions evaporative cooling, adiabatic humidification and programmable controllers energy saving solutions for data centers carel.com Data center air-conditioning Data center air-conditioning
STULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
Technical Systems. Helen Bedford
Technical Systems in Data Centres Helen Bedford Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Economizer Modes of Data Center Cooling Systems
Economizer Modes of Data Center Cooling Systems White Paper 132 Revision 0 by John Niemann John Bean Victor Avelar > Executive summary In certain climates, some cooling systems can save over 70% in annual
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
How To Get A Passive House
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2015 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Product
> Executive summary. Explanation of Cooling and Air Conditioning Terminology for IT Professionals. White Paper 11 Revision 2. Contents.
Explanation of Cooling and Air Conditioning Terminology for IT Professionals White Paper 11 Revision 2 by Tony Evans Click on a section to jump to it > Executive summary As power densities continue to
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling
Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An
THERMAL CLIMATE IN A DATA CENTER
Polina Krapivnitckaia T662KA THERMAL CLIMATE IN A DATA CENTER Bachelor s Thesis Building Services Engineering December 2013 DESCRIPTION Date of the bachelor's thesis 04.12.2013 Author(s) Polina Krapivnitckaia
DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers
DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and
OASIS PRODUCT GUIDE. Data Centre Cooling INDIRECT EVAPORATIVE COOLER. Data Centres. Telecoms. EPX technology. Class leading performance
OASIS PRODUCT GUIDE Data Centres Telecoms EPX technology Class leading performance Fully configurable solutions INDIRECT EVAPORATIVE COOLER Data Centre Cooling 2 MUNTERS.COM/DATACENTRES Critical cooling
How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners
How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners White Paper #56 Revision 2 Executive Summary Today's technology rooms require precise, stable environments in order for
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
Data Centre Cooling: Don't Waste Money on the Wrong Solution
Data Centre Cooling: Don't Waste Money on the Wrong Solution Stulz IT Cooling Production Sites STULZ GmbH Hamburg, Germany STULZ S.p.A., Valeggio sul Mincio (VR), Italy STULZ Air Technology Systems, Frederick/MD,
STULZ View On DataCenter Cooling
STULZ View On DataCenter Cooling Stulz Was Founded In Hamburg (Germany) In 1947 And Has 5 Production Sites And 14 Subsidiaries In 14 Countries. We Are Represented By Partners In Over 110 Countries. Stulz
Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit
Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative
AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA CENTRES
AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA GLOBAL DATA CENTRE IP TRAFFIC WILL TRIPLE WITHIN 5 YEARS Global data centre IP traffic has set a constant growth path, with
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
Reduce data center PUE using Munters innovative cooling solutions
d a t a center applica t i o n guide Reduce data center PUE using Munters innovative cooling solutions Reduce data center energy costs by up to 75% Traditional refrigeration cooling systems are an inefficient
IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM
DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM THE GLOBAL DATA CENTRE MARKET The data centre air conditioning market is expected to grow with a CAGR (compound annual growth rate) of about 12% in the next
IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling
White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that
INFO HTK. Hybrid dry cooler. The reference for hybrid dry cooling. 100 4,000 kw
INFO HTK Hybrid dry cooler The reference for hybrid dry cooling 4, kw JAEGGI The Original Since 929, JAEGGI has been engaged in the development, production and sale of heat exchangers. Since 995, the company
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Modular Data Center Cooling. Ultra High Efficiency. Oasis Optimum DCIE
Modular Data Center Cooling Ultra High Efficiency Oasis Optimum DCIE Oasis Optimum Modular Cooling Compact, Economic, Greener, Ultra High Efficiency Munters Oasis Optimum DCIE data center cooling solution
DataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
AIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
Chiller-less Facilities: They May Be Closer Than You Think
Chiller-less Facilities: They May Be Closer Than You Think A Dell Technical White Paper Learn more at Dell.com/PowerEdge/Rack David Moss Jon Fitch Paul Artman THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES
HVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
ASTACEA4 Inspect complex/central air conditioning systems
Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air
Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy
Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Executive Summary Data center energy usage has risen dramatically over the past decade and
Humidification Strategies for Data Centers and Network Rooms
Humidification Strategies for Data Centers and Network Rooms By Tony Evans White Paper #58 Revision 1 Executive Summary The control of humidity in Information Technology environments is essential to achieving
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
Alfa Laval Abatigo. Redefining adiabatic cooling
Alfa Laval Abatigo Redefining adiabatic cooling Experience and expertise recognized throughout the world With decades of broad experience and practical expertise in heat transfer, Alfa Laval is today a
University of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
White Paper: Free Cooling and the Efficiency of your Data Centre
AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
AERIS DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM
DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM THE GLOBAL DATA CENTRE MARKET The data centre air conditioning market is expected to grow with a CAGR (compound annual growth rate) of about 12% in the next
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)
Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat
Guidelines with preventive maintenance schedule. Value up guidelines
Guidelines with preventive maintenance schedule Value up guidelines Note: Cleaning period depends on environment, atmosphere, and operating time, etc. Dust or cigarette tar has adhered to the unit, but
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
CoolTeg Plus Chilled Water (CW) version: AC-TCW
version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
Top 5 Trends in Data Center Energy Efficiency
Top 5 Trends in Data Center Energy Efficiency By Todd Boucher, Principal Leading Edge Design Group 603.632.4507 @ledesigngroup Copyright 2012 Leading Edge Design Group www.ledesigngroup.com 1 In 2007,
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
Precise, Reliable and Innovative Air Conditioning for Information and Communication Technology
STULZ the natural choice Precise, Reliable and Innovative Air Conditioning for Information and Communication Technology 2 Perfect Air Conditioning for Secure ICT Technology Innovative blade constructions,
Air Conditioning Clinic
Air Conditioning Clinic Introduction to HVAC Systems One of the Systems Series February 2012 TRG-TRC018-EN Introduction to HVAC Systems One of the Systems Series A publication of Trane Preface Introduction
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
Air-Conditioning Buying Guide
Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence
Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager
Data Centre Cooling Technologies 1 Jon Pettitt, EMEA DataCenter Business Development Manager Munters Group Key facts 3.000 Employees 30 Countries Turnover of 470 M HQ in Sweden Global DC Support 25+ Data
Pool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE
PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
The Data Center Dilemma - A Case Study
Second Place: Industrial Facilities or Processes, Existing The TCS data center makes use of white cabinets and reflective surfaces as one method to reduce power for its lights and cooling. Data Center
products 22 º C Ventilation Air Conditioning Refrigeration Energy & Cost Saving Products Inside PROVIDED BY HEINEN & HOPMAN
products > Energy & Cost Saving Products OUTSIDE 35 C HUMIDITY 90% 22 º C Inside PROVIDED BY HEINEN & HOPMAN Heating Ventilation Air Conditioning Refrigeration HVAC energy & COST SAVING POSSIBILITIES A
Energy Saving Fact Sheet Air Conditioning
Energy Saving Fact Sheet Air Conditioning Get your air conditioning into better shape Everyone wants air conditioning. But don t let your existing system, or one that you re considering installing, burn
Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
USER S GUIDE For all Packaged Systems (Air Conditioners and Heat Pumps)
USER S GUIDE For all Packaged Systems (Air Conditioners and Heat Pumps) WA & WL - Series Air Conditioners WH & SH - Series Air Source Heat Pumps IH - Series Air Source Heat Pumps DATE: 02-21-12 QA - Series
Why Do I Need Precision Air Conditioning?
Why Do I Need Precision Air Conditioning? Executive Summary Today's technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
White Paper Rack climate control in data centres
White Paper Rack climate control in data centres Contents Contents...2 List of illustrations... 3 Executive summary...4 Introduction...5 Objectives and requirements...6 Room climate control with the CRAC
News in Data Center Cooling
News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase
Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
Drives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration