Powering the Data Center - Distributed 48Vdc is an Effective Choice. Dan McMenamin President Dan McMenamin and Associates, Inc.
|
|
|
- Kathryn Shields
- 10 years ago
- Views:
Transcription
1 Powering the Data Center - Distributed 48Vdc is an Effective Choice Dan McMenamin President Dan McMenamin and Associates, Inc. INTRODUCTION Effective management takes creativity. The engineer, as both manager and steward of his company s resources is called upon to deliver world-class service and reliability, usually on a compressed timeline, funded from a parsimonious budget such that every Dollar, Euro or Pound is wrung from the fingers of a soulless bean-counter screeching first cost from his or her iron cubicle. Accomplishing the engineer s job in the pressure cooker world of Information Technology (IT.) takes a creative person with the guts to think, design and manage outside the box. While the centralized, decentralized architecture pendulum has swung back and forth in telecom for quite awhile now, the decentralized concept is somewhat foreign to data centers. Similarly, while 48V data centers have gained traction, the concept of distributed 48V power to data center systems hasn t seen a lot of press but offers significant advantages over centralized systems. One way to look at distributed 48Vdc power is a microgrid or series of microgrids bringing modularity and cost containment to the task of supplying energy to the Routers, Servers and other inner-workings that comprise the I.T. world. This paper will explore the many conditions and parameters where distributed low voltage dc makes solid engineering sense in the I.T. environment. Failure Impact As the demand decreases for wireline telephony and dramatically increases for wireless, the need for power availability is greater than ever. Wireline central offices are limited to a given territorial radius by the loop length of subscriber cable pairs. In the digital world of wireless telephony, that restriction went away. Therefore, where a wireline central office might have served 50,000 or even 90,000 telephone customers, a wireless Mobile Switching Center (MSC) easily can handle the traffic for a half-million lines or more. Therefore, the impact of power problems looms large in the industry. Figure 1. a comparative view of the impact of power failure in telephone facilities 9 1
2 With the advent of highly specialized wireless data services, carriers had to increase the bandwidth of their network between data providers and cell towers and from the cell site to the customer handset. The traditional T-1 line was far too limited in capacity and thus, the Internet protocol (I.P.) Ethernet based systems came into prominence. Much wireless telephone traffic now passes through what essentially are central offices filled with data center type systems. Some operating companies call such facilities, Network Equipment Centers (NEC) in order to differentiate them from traditional data centers because very different fire protection standards apply to them. Traditional data centers are governed by NFPA 75 2, whereas telecommunications facilities greater than 1,500 square feet (139.4 square meters) are governed by NFPA AC UPS Protected power for most data centers is provided by a centralized ac Uninterruptible Power Supply (UPS) as shown in Figure 2, or a parallel redundant ac UPS arrangement such as is shown in Figure 3. One advantage of using transformer equipped Power Distribution Units (PDU) is that for both 208 and 480 volt UPS systems, any common mode electrical noise induced into the cabling between the UPS and the PDU is consumed in the delta primary winding of the transformer where its energy simply becomes a trivial heat source. For 480 volt UPS systems there is the added advantage of using smaller conductors to the PDU and then stepping down to 208/120 to feed single and three phase loads. The redundant arrangement in Figure 2 utilizes what s called either a paralleling cabinet or a system control cabinet to couple the output from two or more UPS modules to Power Distributing Units (PDU) s and provide both a static switched bypass source or a manually switched maintenance bypass. Figure 2. Block diagram of a traditional double-conversion non redundant ac UPS system These configurations have been around since the earliest days of the data center business and they comprise the power scheme for most data centers around the world although the actual operating voltages vary from country to country. 9 2
3 In the 1990 s as Information Technology (IT) equipment began making inroads into the dc powered world of telecommunications central offices, a bit of stress and controversy came with them. At the time, virtually all IT equipment was powered by ac and the telecom network was powered by a rather bulletproof 48 Volt dc rail. While the applications and features to be gained with the addition of IT network elements were a superb value, powering the units was less so. The telecom industry has long used inverters for ac powered items, but doing so adds cost; and to some extent reduces reliability by adding system complexity and points of failure. Some telephone companies began pushing their IT suppliers for 48 Volt powered versions of their products and before long, companies like Cisco and others responded accordingly. Figure 3. Block diagram of a traditional double-conversion redundant ac UPS system Sometime in 1998, a meeting was held in Stockholm among the Technical Subgroup on Telecommunications Energy Systems of the Power Electronics Society of the Institute for Electrical and Electronics Engineers. The product of that meeting was a White Paper titled -48VDC Computer Equipment Topology An Emerging Technology. 1 The intent of the paper was a call to the industry to provide IT solutions for use in the telecommunications network that would efficiently continue operation during an ac mains failure of four (4) to eight (8) hours and that the 48 volt bus was the most effective power source for such an operation. The paper cited a number of case studies as well as providing a model that showed a traditional telecommunications 48 volt plant as having some twenty times improved availability over that of ac UPS. In essence, the paper reignited the hard fought War of the Currents, waged in the late 1800 s between Thomas Edison and his former employee Nikola Tesla, who, at the time worked for George Westinghouse. 9 3
4 As IT systems and subsystems made greater penetration into telecommunications network infrastructure, some operating companies began to plan entire data centers powered by 48 Volts with a handful of marginal ac powered systems fed from centralized power room inverters or point of use inverter units. The advantages of a 48 Volt data center were many including the facts that one didn t have to balance phase load across the Wye (Secondary) windings of PDU transformers or use electricians to add minor circuits. One disadvantage is that the deployment of large scale, energy-dense IT systems produced heat loads that drove companies to use access floors as a cooling air plenum. Plenum floors require plenum-rated cables, and while various companies manufacture communications and data cabling for such applications, no one makes a dc power cable suitable for deployment in an air plenum. Further, the cabling volume was so large that it wouldn t easily fit into traditional conduits and wiring troughs would be so large as to obstruct the flow of fire suppression gasses used in clean-agent systems. Another disadvantage is the commodity and installation cost of large copper cables needed to overcome voltage drop between a centralized power room and the systems to be operated. Distributed 48 volt deployments have seen limited use, however, the size, weight and occasional leakage problems associated with lead acid batteries has served to deter most telco engineers from such an arrangement. Such is true even of Valve Regulated Lead Acid (VRLA) cells even though they have about a 20% improved power density than Vented (formerly called Flooded) cells. The improved density comes from two factors: a. there are thinner plates resulting in more power at reduced life; and b. less electrolyte is used in the cell construction. Emerging battery technologies promise densities significantly higher than their lead acid counterparts. Lithium-ion and sodium-nickel cells may have the potential to make a distributed architecture more efficacious for the central office or data center environment simply because they occupy less floor space. There are few, if any, data centers that operate as a single complex of servers, routers and related equipment. Generally, there are communities of systems and subsystems sharing a conditioned space with a centralized or decentralized source of protected power. Figure 4. Rows of UPS fed Power Distributing Units (gray cabinets) feeding power to rows of IT equipment (Black cabinets) 9 4
5 Wireless telecom facilities, for example, house groups of systems serving voic storage, small message (text) processing and storage and various other systems such as home location registers, message registers etc., that interconnect with each other but there is no particular requirement for a single power source. If a voice mail system was depowered that would be an inconvenience but not drastically curtail telecommunications services. Indeed, many central offices, mobile service centers and the like, designed under fire protection standards prescribed by NFPA 76, are arranged for selective zone depowering. Using this protection scheme, fire departments are able to remove power to certain equipment areas without depowering other areas of the building. The intent of such an arrangement is to minimize the impact of a depowering on the vital telecommunications network. Such an arrangement is quite different from the kill everything, Emergency Power Off (EPO) used in an IT world. Figure 5. Equipment aisles identified with color coded reflective decals for zoned emergency power disconnect Because most server equipment has dual A/B power supplies sized for N+N redundancy at the shelf level or individual server, the architecture lends itself to pairs of distributed -48 volt dc plants. Following the zoned disconnect scheme that has found favor with fire departments across the nation, equipment communities might be arranged similar to that shown in Figure 6 with the A dc plant feeding the A sides of all equipment and the B dc plant feeding all the B sides. 9 5
6 With this level of redundancy, yet another fire service tool and equipment reliability initiative could be built into the network relatively inexpensively. Under zoned disconnect plans, fire service responders locate a bay that is emitting smoke and they note what color floor decals surround the problematic bay or cabinet. Then, they follow color coded floor decals to the dc power room and then to the distribution fuse or circuit breaker bay(s) feeding that color zone. Then, the fire service simply pulls those fuses or trips those circuit breakers to kill power to that zone. With all other equipment zones intact, power-wise, the impact on telecommunications services may be minimized. Quite possibly, the impairment will be severe but at least minimized as opposed to a total power-down. If A/B pairs of distributed architecture plants fed individual equipment zones, then buttons protected against accidental operation could be placed at the equipment room door to facilitate depowering that zone in a manner that offers high reliability to the network by giving the option to shut down only the A plant or the B plant in a given zone, and both only if need be. For example, a fire service responds to smoke alarms in an equipment room, a Class C (electrical) fire, and they detect smoke coming from a cabinet in the blue equipment zone. They then would visit a nest of shutdown buttons near the door and operate the shutdown for blue zone A plant. At this point they d wait a minute or so and see if the smoke had significantly diminished. If the smoke has diminished no further disconnection is necessary. Servers would remain in service fed by the remaining power plant. If the smoke did not diminish, then the fire department would operate the blue zone B plant switch, fully depowering that zone. If the fire was in the dc power bay itself and power off had not resolved the problem, then the traditional floor decals would show the path to kill all ac power and generator power in the facility, placing the remaining equipment groups on battery but still in service. Figure 6. Equipment aisles identified with color coded reflective decals for zoned emergency power disconnect 9 6
7 Figure 7. A zoned power disconnect arrangement for facilities with distributed dc (6 zones are shown in this example). What would the power off circuit look like at the distributed dc bay? Output contactors are not new, nor are shunt trips for main feeder circuit breakers as might feed rectifiers. One issue is that many codes require that power off circuits be tested periodically. If all dc equipment was A/B fed and properly administered, depowering either dc plant should be a non-issue. Of course, errors in A/B assignment where both sides of a server or other subsystem were fed by either plant would evidence themselves pretty quickly as those equipments would fail. Another approach might be to include a bypass switch around the power off contactor similar to what s shown in Figure 7. Because distributed dc plants would be fairly small, incorporating a molded case bypass switch with auxiliary contacts wouldn t be very expensive. The auxiliary contacts would operate an indicator Light Emitting Diode (LED) and perhaps a piezoelectric buzzer to alert that the plant disconnect was in a bypass mode. The test plan would be to close the bypass switch for the plant under test and note the LED and annunciator operating. Next, operate the remote power off button for that plant and note that the contactor had opened and the rectifiers depowered. Upon restoring the power off button, the contactor should reengage and at that point the bypass switch should be returned to the open position and the ac power main breaker reset. The rectifiers would restart and the test therefore is completed to satisfy the code without ever dropping the load. 9 7
8 Figure 8. A zoned power disconnect arrangement with a bypass feature for system tests Because a distributed dc architecture would be close to the equipment it serves the wiring becomes small enough to fit within standard flexible steel conduits eliminating the problem caused by the industry unavailability of plenum rated dc power cable. Figure 9. End view sketch of rows showing -48 volt feeding cabinets via flexible conduits. The Battery The engineering choice of a battery plays a critical role in the design of any dc system whether centralized or distributed. The battery, for all practical purposes is like a parachute for the load; and is what saves your bacon. The more reliable and the more capacity the battery (or the parachute) has, the slower and gentler you hit the ground. When designing for an A/B fed dual-plant arrangement the battery reserve calculation becomes complicated because battery reserve time is not a linear load function. As will be explained further, doubling the load does not simply halve the battery reserve time. Also, there are a number of A/B arrangements in telecom and data systems and therefore the design engineer must understand in order to know what will be the load profile with which he or she is working. 9 8
9 Referring to Figure 10, some A/D systems utilize two 48 volt inputs which pass through two 48/5 volt converters which in turn flow through forward biased diodes so that each feed and dc/dc converter carries exactly half the load of the circuit. In the event that either feed or dc/dc converter fails, the remaining feeder sees a load doubling. The forward-biased diodes often are referred to as ORing diodes because both or one input can carry the load. The diode serves to isolate the inputs so that a fault on the A side doesn t impinge on the B side. Other A/B arrangements have dual inputs and dual loads, such as processors, and both processors run in parallel. If one input fails that processor fails and the remaining one keeps operating. In this case, the load would not double as each side runs independently. Figure 10. depicts two A/B input systems that have very different load profiles. These issues are critical to battery design. Figure 11 shows an excerpt from the battery discharge chart for several C&F vented lead acid cells commonly used in telecommunications service. Taking a discharge load of approximately 150 Amperes per string (159 on the chart) on a battery comprised of 1680 Ampere Hour cells, the battery would discharge down to a telco typical minimum volts per cell in 10 hours. If that load was to double to 300 amperes as would be the case in diode-oring A/B feeds, the battery reserve time would be 4 hours. It s a common error for people to assume that doubling the load on a 10 hour battery would provide a 5 hour reserve time but it s clear from the discharge chart that such is not the case. This is not a battery vendor-specific issue, but one common to batteries in general. Figure 11. a battery discharge chart showing the impact of load doubling on reserve time 9 9
10 Accordingly, it is critical that the engineer designing the battery determine the load profile so as to understand exactly how much load will be presented to the battery and under what circumstances so that the proper capacity is designed into the system. Otherwise, the design may fall well short of expectations. Returning to the parachute metaphor, such a miscalculation would be like putting a 250 pound person under a canopy designed for a 150 pound person and his or her ride is likely to end badly. Cost? Because of sales volumes, generally, smaller dc plants are more cost competitive than large dc plants intended for central offices. And they are cheaper to ship and install. Together with the reduced cost of copper resulting from such an arrangement, such deployments would offer large savings and even larger gains in overall system flexibility and reliability. The significantly reduced size of sodium-nickel batteries and lithium-ion cells made available through Electric Vehicle (EV) research, would make such deployments sensible for the equipment room. Both of these technologies behave well in the benign environment of an equipment room. Their cost, while significantly higher than lead acid, would be offset by the per square foot cost of building construction or addition. Conclusions Is a distributed -48 volt dc system the answer to each and every data center? Probably not, yet there is every reason to believe that for many data centers and in particular, in avoiding building additions to existing data centers, that the 48 volt option offers engineers the opportunity to win the tug of war between cost and reliability. Those who win that game remain competitive. References V DC Computer Equipment Topology - an Emerging Technology J. Åkerlund, B. Lindemark, D. McMenamin, S. Muroyama, J. Parsons, J. Poulin, C. Riddleberger, K. Yotsumoto, INTELEC 98, San Francisco, California USA 2. NFPA 75 Standard for the Protection of Information Technology Equipment. National Fire Protection Association, Quincy MA 3. NFPA 76 Standard for the Fire Protection of Information of Telecommunications Facilities. National Fire Protection Association, Quincy MA 9 10
Qualitative Analysis of Power Distribution Configurations for Data Centers
Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,
Dan McMenamin Dan McMenamin & Associates, Inc. [email protected]
What Does A Telco Need for 400 VDC To Find A Place In The Central Office 400 Volts: Even though the technology isn t quite here yet, it s not just for data centers anymore Dan McMenamin Dan McMenamin &
Understanding Emergency Power Off (EPO)
Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single
Inverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
BATTERY AND SUBSYSTEM ELEMENTS OF A HVDC SYSTEM FOR THE TELECOMMUNICATIONS AND DATA NETWORKS. FIRST, DO NO HARM.
BATTERY AND SUBSYSTEM ELEMENTS OF A HVDC SYSTEM FOR THE TELECOMMUNICATIONS AND DATA NETWORKS. FIRST, DO NO HARM. Dan McMenamin William Cantor, P.E. Phillip Zakielarz Thomas Flores Dan McMenamin and Test
AC vs DC for Data Centers and Network Rooms
AC vs DC for Data Centers and Network Rooms White Paper #63 Revision 1 Executive Summary The use of DC power distribution as an alternative to AC in data centers and network rooms is uncommon. The considerations
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
Data Center Infrastructure & Managed Services Outline
Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Power Management of Cell Sites
International Refereed Journal of Engineering and Science (IRJES) ISSN (Online) 2319-183X, (Print) 2319-1821 Volume 2, Issue 9 (September 2013), PP.41-45 Power Management of Cell Sites K.Santhosh Kumar
Mixing Sodium and Lead Battery Technologies in Telecom Applications
Mixing Sodium and Lead Battery Technologies in Telecom Applications Paul Smith Shanon Kolasienski Technical Marketing Manager Application Engineer GE Critical Power GE Energy Storage Plano, TX 75074 Schenectady,
Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks
Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks White Paper Anil K. Trehan, Vice President, Energy Solutions CommScope, Inc. May 28, 2013 Contents
DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES
DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES Edward P. Rafter, P. E. Principal Tier IV Consulting Group Lee s Summit, Missouri 64064 INTRODUCTION There are concerns among owners
100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G
100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
Three-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
OPERATIONS MANUAL DATA CENTER COLOCATION
Section I: Introduction and Service Description. OPERATIONS MANUAL DATA CENTER COLOCATION Company means MCI Communications Services, Inc., d/b/a Verizon Business Services, or any affiliated entity designated
Server Technology Inc.
Server Technology Inc. Efficiency Gains with 480V/277V Power at the Cabinet Level White Paper STI-100-012 2011-May-2 Headquarters Server Technology, Inc. 1040 Sandhill Drive Reno, NV 89521 United States
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Data Center Management
Data Center Management How Cisco IT Operates, Manages, and Protects Its Data Center A Cisco on Cisco Case Study: Inside Cisco IT 1 Overview The Cisco IT Operations Data Center on the San Jose, California
Power Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
Self Monitoring Power Supply (BPSM)
LIFETIME REPLACEMENT WARRANTY Self Monitoring Power Supply (BPSM) Application - When interfacing with a fire alarm system where the system s auxiliary relay cannot handle the full current potential of
UPS Applications and VRLA Battery Sizing
TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the
Data Center Commissioning: What you need to know
Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,
IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS
IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS Executive Summary IT managers who are used to implementing power protection for IT network or data
Power Management Module 2. Installation
Power Management Module 2 30 300 kva Installation Table of Contents Safety... 1 Safety Instructions... 1 Certification Standards Three Phase... 1 Product Safety... 2 Special Precautions... 2 System Description...
Thyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
singapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Singapore. We can colocate standard rack-mountable servers or other
SiteRanger tm. Power quality / site monitoring. Comm/net Systems, Inc.
SiteRanger tm Comprehensive Broadband/ Enterprise site monitoring device for Headend s, Hub Sites. Power quality / site monitoring Focus on power system infrastructure Retrofit legacy devices for remote
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Energy Efficient High-tech Buildings
Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory [email protected] Acknowledgements California
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
APC 3Phase Power Distribution
APC 3Phase Power Distribution North American 3 Phase Business Development Team All content in this presentation is protected 2008 American Power Conversion Corporation Objectives Understand the entire
DC Power Solutions Overview. DC Power Solutions for EVERY Network Application.
DC Power Solutions Overview DC Power Solutions for EVERY Network Application. DC Power Solutions for Every Network Application Eaton recognizes the challenges that are unique to different customers applications.
PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where
PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where the power generated by the solar panel (panels) runs an
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
Specification Requirements DBL 700MX and 1000MX Series UPS
Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
AN-3 SEVEN KEY CONSIDERATIONS BEFORE YOU START YOUR SLIC OR FXS PHONE LINE INTERFACE DESIGN
AN-3 SEVEN KEY CONSIDERATIONS BEFORE YOU START YOUR SLIC OR FXS PHONE LINE INTERFACE DESIGN By Joe Randolph Introduction The conventional 2-wire analog phone line that telephone companies provide to residential
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
DISTRIBUTED REDUNDANCY:
DISTRIBUTED REDUNDANCY: MAXIMUM AVAILABILITY AT MINIMAL COST A White Paper by: Liebert Corporation As the need for greater system availability intensifies across virtually every industry from global banking
A Comparison of AC and DC Power Distribution in the Data Center Transcript
A Comparison of AC and DC Power Distribution in the Data Center Transcript Slide 1 Welcome to the Data Center University course on the A Comparison of AC and DC Power Distribution in the Data Center. Slide
Colocation. Introduction. Structure of the service. Service Description
Introduction IP-Only provides colocation services for customers with very high reliability and availability requirements. In combination with its transmission and IP services, IP-Only offers space in high-security
QuickSpecs. Overview. HP Power Distribution Rack. HP Power Distribution Rack. DA - 12859 North America Version 5 August 22, 2008 Page 1
Overview It's getting harder to manage a data center efficiently, with rising utility bills and ever-increasing demands due to processor power and server density increases. Growing user requests mean heavier
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial MODEL NUMBER: SMARTINT3000VS Highlights 3kVA / 3000VA / 2250W line interactive tower UPS system 230V
30-120 3 Phase Modular Finally the benefits of Modular ups are for all
MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1
Intelligent Power Distribution in the Data Center
Rack Power Intelligent Power Distribution in the Data Center Agenda Data Centre Power UPS Power Distribution Rack Mount PDU s UPS Power problems Configuration Capacity Power Distribution Types of Distribution
AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
Constant Voltage Charger Selection for VRLA Batteries
TECHNICAL BULLETIN 41-2129 Constant Voltage Charger Selection for VRLA Batteries Please Note: The information in this technical bulletin was developed for C&D Dynasty 12 Volt VRLA products. While much
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System
Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Cory David Smith, Project Manager, ECOM Engineering Inc., and David Lawrence Smith, Principal, ECOM Engineering
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
Paralleling Switchgear
Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL
Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy.
Match Uninterruptible Power Supply 500-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com
SECTION 13850 DETECTION AND ALARM
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring
Model #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V
SmartPro VS Tower UPS System Intelligent, line-interactive power management system Model #: SMART2200VS 2200VA / 2.2kVA line interactive tower UPS Maintains 120V nominal output over an input range of 79
APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.
USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS Abstract This application note describes the necessary procedure to use a standard Pacific Power Source Model
DATA CENTRE DATA CENTRE MAY 2015
DATA CENTRE DATA CENTRE MAY 2015 CONCERTHOUSE MUSIC Concerthouse Music Data Centre services are located in the Equinix Internet Business Exchange (IBX ) Centre at Mascot. This IBX offers the highest level
UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES
UNINTERRUPTIBLE POWER SUPPLIES 9900A >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES 9900A The 9900A UPS system uses the most advanced IGBT in both the converter and inverter with Digital Signal Processor (DSP)
Working definitions of terms: Commercial vs. Industrial UPS Systems:
The Essential Differences Between Commercial & Industrial UPS Systems Page 1 of 8 Working definitions of terms: Commercial vs. Industrial UPS Systems: On-Line, Uninterruptible Power Systems (abbreviated:
South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime
South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in August 2002,
AETNA FIRE ALARM SERVICE CO., INC.
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the inspection or test. It shall be permitted to modify this form as needed
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL
ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142
Data Center Presentation
Data Center Presentation The NetSource Datacenter. Agenda General Layout of Data Center Policies and Procedures Designed to Latest Standards High Performance High Reliability High Security Design Details
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING
HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING There are several ways to wire multiple batteries to achieve the correct battery voltage or capacity for a particular DC
Process and Motor Controls in Central and Remote Buildings: PlantWeb Center, the Intelligent Remote Building
Apr-07 Page 1 This paper introduces the PlantWeb Center and the use of Intelligent Motor Control. Emerson Process Management 1996 2007 All rights reserved. DeltaV, the DeltaV design, SureService, the SureService
conventional system operation
conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than
san francisco//usa data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in San Francisco, USA. We can colocate standard rack-mountable servers
Evaluating the Opportunity for DC Power in the Data Center
A White Paper from the Experts in Business-Critical Continuity Evaluating the Opportunity for Power in the Data Center by Mark Murrill and B.J. Sonnenberg, Emerson Network Power Summary With data center
MPR-Systems. Mini Power Racks 1200 W - 8100 W
LUCAS-BENNING World Class Power Solutions With compliments Helmut Singer Elektronik www.helmut-singer.de [email protected] fon +49 241 155 315 fax +49 241 152 066 Feldchen 16-24 D-52070 Aachen Germany
Contractors Guide Central Inverter System Installation
Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
IntraVUE Diagnostics. Device Failure
IntraVUE provides a method to record and capture the issues that occur in the Ethernet networks being used for automation applications. Automation networks are susceptible to subtle disturbances due to
AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)
AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:
Building a Tier 4 Data Center on a Tier 1 Budget
Building a Tier 4 Data Center on a Tier 1 Budget A Walk Through of TIA-942 Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc. March 27, 2008 BICSI South Central Region Meeting Denver, CO TIA-942