Building a Tier 4 Data Center on a Tier 1 Budget

Size: px
Start display at page:

Download "Building a Tier 4 Data Center on a Tier 1 Budget"

Transcription

1 Building a Tier 4 Data Center on a Tier 1 Budget A Walk Through of TIA-942 Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc. March 27, 2008 BICSI South Central Region Meeting Denver, CO

2 TIA-942 History - Timeline 1960 s and 1970 s - Data centers limited to finance, telecommunications, and government sectors companies come together in NYC Forum for users and owners of data centers to share information Continues to develop into various groups and associations

3 TIA-942 History Moving Forward 1993 Site Uptime Network formed by The Uptime Institute, Inc. Network of member companies sharing information and collaborating to find solutions.

4 TIA-942 History Tiers Several systems developed to classify data centers with respect to architecture, electrical, mechanical, and telecommunications. Systems tended to be complex for nontechnical management. The Uptime Institute s four-tier system provides simple means to understand data center investments.

5 TIA-942 History A Beginning In April 2005, ANSI/TIA approves ANSI/TIA-942 Telecommunication Infrastructure Standard for Data Centers Based on four-tier system of The Uptime Institute

6 TIA Overview Spaces within a data center Architectural design elements of data center spaces MEP design elements Cabling and pathways

7 What s in your data center?

8 A Data Center - More than a computer room Computer room

9 A Data Center - More than a computer room Computer room Computer room TR

10 A Data Center - More than a computer room Computer room Computer room TR Operations center

11 A Data Center - More than a computer room Computer room Computer room TR Operations center Support staff offices

12 Data Center - More than a computer room Computer room Computer room TR Operations center Support staff offices Entrance facilities

13 A Data Center - More than a computer room Computer room Computer room TR Operations center Support staff offices Entrance facilities Loading docks, storage, burn-in rooms

14 A Data Center - More than a computer room Computer room Computer room TR Operations center Support staff offices Entrance facilities Loading docks, storage, burn-in rooms Secured yards generators & fuel

15 A Data Center - More than a computer room Computer room Computer room TR Operations center Support staff offices Entrance facilities Loading docks, storage, burn-in rooms Mechanical and electrical spaces

16 Data Center Spaces Entrance Rooms & Access Providers Main Distribution Area & edge devices Horizontal Distribution Areas Telecommunications Room Racks & Cabinets

17 Topologies within Data Center Typical Single Entrance Room One or more TRs Several Horizontal Distribution Areas

18 Topologies within Data Center Minimized Single Main Distribution Area Entrance facility Telecommunications room Horizontal distribution within data center

19 Topologies within Data Center Divergent Multiple Entrance Rooms One or more TRs Multiple Horizontal Distribution Areas with redundant backbone cabling

20 Architectural Elements Size Equipment: electrical and mechanical Ceiling heights Treatments Lighting Doors Floor loading

21 Data Center Cabling

22 Cabling Elements Service provider cables Backbone cables Horizontal cables Zone distribution

23 Cabling Elements ANSI/TIA/EIA-568-B.2 still applies!

24 Cabling Elements Data center can be a building Backbones within data center Centralized optical fiber cabling Horizontal cable reduced Redundancy

25 Generators UPS and batteries Bonding and grounding Power & environmental monitoring Emergency-poweroff (EPO) Power Elements

26 Mechanical Elements Cooling operations Environmental parameters Fire suppression

27 Redundancy - the start of Tiering Entrance pathways - OSP Access provider services Entrance facilities Main distribution areas (with care) Backbone cabling Horizontal cabling Mechanical and electrical systems

28 Concurrent Maintainability Systems can be maintained, upgraded, and tested without impacting normal operations.

29 Fault Tolerant System can handle any unplanned failure or planned outage without impacting normal operations including loads on support systems.

30 Tier 1 - N A starting point Need - Just enough

31 Architectural Plain box Tier 1 - N

32 Tier 1 - N Cabling/Equipment Single feeder pathway for access provider Single entrance room Single-path distribution No redundancy

33 Power Tier 1 - N Single power feeder UPS - single module or non-redundant modules Generator optional PDU s may be used

34 Mechanical Tier 1 - N Single cooling source Multiple cooling units to need immediate need Generator power, if available

35 Tier 1 - N Need - Just enough Failure of single unit or disruption for maintenance will disrupt operations

36 Tier 1

37 Tier 2 - N+1 The start of redundancy Need plus one

38 Architectural Tier 2 - N+1 Physical protection against disruption, natural and man-made Environmental conditioning improvements Loading dock

39 Tier 2 - N+1 Cabling/Equipment Two feeder pathways for access provider Single entrance room Redundant backbone cables within data center Critical equipment with redundant components

40 Power Tier 2 - N+1 Single power feeders with ATS UPS - redundant UPS modules (N+1) Generator sized as N Redundant PDU s, preferably from separate UPS systems Dual power cords for all equipment Grounding Infrastructure

41 Mechanical Tier 2 - N+1 Multiple units plus redundant unit Single piping pathways Generator power Air supplied via raised floor

42 Tier 2 - N+1 Need plus one Single pathway for systems Maintenance of critical power will disrupt operations Less susceptible to disruption from the failure of single unit

43 Tier 1 Tier 2

44 Tier 3-2N Doubling up Two complete systems for each needed: One active set of systems One standby set of systems

45 Architectural Tier 3-2N Specific protections against most disruption Physical separate of redundant systems Security checkpoints, access controls, and fences Site access improvements EMI protection 2 or more loading docks

46 Tier 3-2N Cabling/Equipment Two access providers or two points-ofpresence Redundant backbone cables & pathways within data center Hot, standby spare for all critical equipment

47 Power Tier 3-2N A mix of N+1 and 2N Dual utility feeders, one active & one inactive N+1 redundancy at all component levels Redundant power to mechanical systems Generator sized for equipment and mechanicals plus 1 Any component can be isolated Power monitoring

48 Mechanical Tier 3-2N Fully redundant cooling units Dual path piping system Redundant power Environmental monitoring

49 Tier 3-2N One active, one standby Redundant pathways, each able to carry full load Planned outages of systems without disruption to service Unplanned failure of one system without disruption to service Susceptible to disruption in failure/maintenance mode

50 Tier 1 Tier 2 Tier 3

51 Tier 4-2(N+1) Two of everything, all the time Two complete systems for each needed: Two active sets of systems Each set is N+1

52 Architectural Tier 4-2(N+1) Specific protections against all disruption Secured equipment yard

53 Tier 4-2(N+1) Cabling/Equipment Secondary distribution area for redundant routers & switches Secondary area isolated from main area for all systems Armored cables or conduit pathways Dual power supplies for electronic equipment

54 Power Tier 4-2(N+1) Utility feeder from two different substations Both feeders are active Primary and reserve UPS systems Generator sized for building load plus 1

55 Mechanical Tier 4-2(N+1) Alternative water storage for evaporative cooling systems

56 Tier 4-2(N+1) Two active, each able to carry full load Planned outages of systems without disruption to service Unplanned failures without disruption to service Redundant pathways, Very limited susceptibility to service disruptions

57 Tier 1 Tier 2 Tier 3 Tier 4

58 Tier Data Center Costs Annual Outage* Construction Cost 1 N 28.8 hrs $450 / sq. ft. 2 N hrs $600 / sq. ft. 3 2N 1.6 hrs $900 / sq. ft. 4 2(N+1) 0.8 hrs $1,100 / sq. ft. * Outage times based on actual field data by The Uptime Institute, Inc.

59 Growth, a planned cost? Right-sizing the initial design Not too big, not too small Total Cost of Ownership Realistic planning for growth

60 Word of caution There is no almost.

61 It is only a standard.

62 A different approach to tiering A compromise - Application tiering

63 A different approach to tiering A compromise - Application tiering Dual site data center and redundancy

64 A different approach to tiering A compromise - Application tiering Dual site data center and redundancy =?

65 Question Can you build a Tier 4 data center on a Tier 1 budget?

66 Well sort of? Answer

67 Concluding remarks TIA-942 provides an excellent basis of design, not a blueprint for design. Designers must educate owners. Designers must consider creative solutions = 4, but 1$ + 1$ 1$

68 Questions? Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc.

How To Write An Infrastructural Standard For Data Center Infrastructure

How To Write An Infrastructural Standard For Data Center Infrastructure Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers

More information

Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM

Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM Data Center Management Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM A physical place that houses a computer network's most critical systems, including back-up power supplies, air conditioning, and

More information

BICSI 002 / TIA 942 / Uptime

BICSI 002 / TIA 942 / Uptime BICSI 002 / TIA 942 / Uptime Which Data Center Standard Should I Follow Phil Isaak, PE, P.Eng., RCDD, DCDC President, Master Instructor Isaak Technologies Inc. Standards Who are these People Standards

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group

Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group The data center industry has experienced several evolutions over the past 20 years. One principal change has been the development of the

More information

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers

More information

plantemoran.com {Data center. } Design standards

plantemoran.com {Data center. } Design standards plantemoran.com {Data center. } Design standards IT systems have become critical for the day-to-day operations of today s organizations. {Data center.} Design standards IT systems are critical for the

More information

Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc jew@j-and-m.com

Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc jew@j-and-m.com Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc jew@j-and-m.com J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942

More information

OPERATOR - FACILITY ADDRESS - DATE

OPERATOR - FACILITY ADDRESS - DATE . Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.

More information

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center

More information

The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements

The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements Edward P Rafter, P.E. CxAP Tier IV Consulting Group Synopsis The data center industry has experienced

More information

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center

More information

Telecommunications Infrastructure Standard for Data Centers. 802.3 Tutorial

Telecommunications Infrastructure Standard for Data Centers. 802.3 Tutorial Telecommunications Infrastructure Standard for Data Centers 802.3 Tutorial Prepared by: Jonathan Jew - J&M Consultants and Chris DiMinico - MC Communications - Co-chairs TR42.1.1 TR42: Data Center Standard

More information

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Jonathan Jew jew@j-and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center working group Co-chair BICSI data centers standards

More information

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Opportunities in Automating Infrastructure Why Automation in Data Center? Tiers, compartments and complexity Work

More information

Data Center Designs and Hospital Operations

Data Center Designs and Hospital Operations Data Center Designs and Hospital Operations Designing for Data Center Availability and the Effect on Daily Operations Joe Harris, PE, RCDD Senior Engineer, AECOM Data Centers and Hospitals June 10, 2015

More information

BICSI NxtGEN & Global Data Center Standards Update

BICSI NxtGEN & Global Data Center Standards Update BICSI NxtGEN & Global Data Center Standards Update Bob Faber, RCDD/NTS Siemon Global Accounts Manager Chair NEMA High Performance Wire & Cable Chair BICSI Standards Committee Vice Chair BICSI TI&M Committee

More information

Data Center Cabling Design Trends

Data Center Cabling Design Trends Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:

More information

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,

More information

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus. DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure

More information

Data Center Commissioning: What you need to know

Data Center Commissioning: What you need to know Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,

More information

DDesign collaboration between the owner/operator. Good things happen when the design team organizes around a plan. BY KEITH LANE

DDesign collaboration between the owner/operator. Good things happen when the design team organizes around a plan. BY KEITH LANE Good things happen when the design team organizes around a plan. BY KEITH LANE Keith Lane has over 20 years of experience in the design and implementation of mission-critical facilities. He is a professional

More information

Subject: County of Los Angeles Data Center Space Requirement

Subject: County of Los Angeles Data Center Space Requirement Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,

More information

Data Center Presentation

Data Center Presentation Data Center Presentation The NetSource Datacenter. Agenda General Layout of Data Center Policies and Procedures Designed to Latest Standards High Performance High Reliability High Security Design Details

More information

Data Center Design Considerations

Data Center Design Considerations Data Center Design Considerations Chris DiMinico MC Communications cdiminico@ieee.org Contributors: Jonathan Jew, President, J&M Consultants (Telecommunication Engineering Firm) Co-chair TR42.1.1, Data

More information

Data Center Colocation Build vs. Buy

Data Center Colocation Build vs. Buy Data Center Colocation Build vs. Buy Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for

More information

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G 100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the

More information

TIA-942: Data Center Standards

TIA-942: Data Center Standards plantemoran.com TIA-942: Data Center Standards Sri Chalasani Merit 2010 Conference May 25, 2010 Objectives What are concerns in the data center? Data center standards & best Practices Data Center Definition

More information

AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)

AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:

More information

A Quick Primer on Data Center Tier Classifications

A Quick Primer on Data Center Tier Classifications A Quick Primer on Data Center Tier Classifications What You Should Know Before Starting a Data Center Project White Paper Abstract Data center facility projects are often driven by the Uptime Institute

More information

How To Visit An Internet Data Center

How To Visit An Internet Data Center AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina

More information

The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.

The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade

More information

Keyword: TIA 942, Tier level, Nuclear Data Center. Introduction

Keyword: TIA 942, Tier level, Nuclear Data Center. Introduction Nuclear Data Center International Standard Towards TSO Initiative Raja Murzaferi Raja Moktar, Mohd Fauzi Haris, Siti Nurbahyah Hamdan, Saaidi Ismail,Radhiah Jamaluddin, Nursuliza Samsudin. IT Center, Technical

More information

Designing Fault-Tolerant Power Infrastructure

Designing Fault-Tolerant Power Infrastructure Designing Fault-Tolerant Power Infrastructure System Analysis and New Standards Enable Maximization of Operating Dependability for Data Centers & Other Mission Critical Facilities J.F. Christin (Author)

More information

Building a data center. C R Srinivasan Tata Communications

Building a data center. C R Srinivasan Tata Communications Building a data center C R Srinivasan Tata Communications Introduction Data Center as defined by TIA 942 A building or a portion of a building whose primary function is to house a computer room and its

More information

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA

More information

Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s"

Data Centre Issues supported in TIA-942 : Telecommunications Infrastructure for Data Centre s Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s" Data centre Standard EN50173-5 : "Telecommunications Infrastructure for Data Centre s Due, 2006 Gary Highton,

More information

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org

So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org So you want to build a data centre? Who do you contact? How do you work out what

More information

Attracting Data Centers to Your Market

Attracting Data Centers to Your Market Attracting Data Centers to Your Market A Presentation for: Presented by: Wendy McArthur, CB Richard Ellis OVERVIEW Introduction Qualify Requirement Site Selection Cost Marketing CB Richard Ellis Page 2

More information

Data Center Site Infrastructure Tier Standard: Topology

Data Center Site Infrastructure Tier Standard: Topology U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2009-2012 by Uptime Institute, LLC 20 West

More information

Zone Distribution in the Data Center

Zone Distribution in the Data Center Zone Distribution in the Data Center By Jennifer Cline, RCDD As data centers face the continued need to expand and grow, the fundamental concerns and needs remain constant. Key concerns of the data cabling

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Introduction to Datacenters & the Cloud

Introduction to Datacenters & the Cloud Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview

More information

Tier Standards. Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI. Consultant EMEA

Tier Standards. Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI. Consultant EMEA Tier Standards Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI Consultant EMEA Uptime Institute Unbiased and vendor neutral Global thought leadership for the data center industry Founded 1993 Standards and

More information

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier

More information

19 Site Location, Design and Attributes. Site Location, Design and Attributes

19 Site Location, Design and Attributes. Site Location, Design and Attributes 1 Site Location, Design and Attributes The Primary Data Center shall be physically located on Oahu, Hawaii. 2 Site Location, Design and Attributes The Primary Data Center shall be located at least 1 mile

More information

Considerations for choosing top-of-rack in today's fat-tree switch fabric configurations

Considerations for choosing top-of-rack in today's fat-tree switch fabric configurations From the April, 2014 Issue of Cabling Installation & Maintenance Magazine Considerations for choosing top-of-rack in today's fat-tree switch fabric configurations Pros and cons exist for each configuration,

More information

Experience Matters...

Experience Matters... Experience Matters... Travelport Data Center offers confidence and space to meet your demanding IT needs Transwestern presents the Travelport Data Center in Denver, Colorado totaling 267,000 SF with 121,600

More information

Data Centre Barrie, Ontario

Data Centre Barrie, Ontario COGECO DATA SERVICES DATA CENTRE Data Centre Barrie, Ontario Cogeco Data Services offers flexible, secure, connected and fully managed ICT solutions at its Flagship Data Centre in Barrie, Ontario Data

More information

Hosting Infrastructure. Overview and Benefits of Hosting Infrastructure

Hosting Infrastructure. Overview and Benefits of Hosting Infrastructure Hosting Infrastructure Overview and Benefits of Hosting Infrastructure Data Centre definition In it's simplest form, a data centre is a facility that houses IT equipment Servers, and networking kit. The

More information

COMMODITIZING THE DATA CENTER MARKET

COMMODITIZING THE DATA CENTER MARKET COMMODITIZING THE DATA CENTER MARKET Site Summary The building at 1360 Kifer Road has approximately 94,500 SF of server and support space and is currently divided into two independent data center areas.

More information

Intelligent Cable Management Systems

Intelligent Cable Management Systems Intelligent Cable Management Systems Bringing Practical Application Karen Pearson - Leviton Why Cable Management Matters Performance Cooling and air-handling Maintenance ANSI/TIA 569* Telecommunication

More information

How To Determine Data Center Reliability

How To Determine Data Center Reliability DATA CENTER INDUSTRY WHITE PAPER Data Center Services End-To-End Reliability Published by: Isaak Technologies, Inc. TABLE OF CONTENTS 1. Overview... 1 2. Reliability Classifications... 2 Reliability Class-0...

More information

Guidelines for Specifying Data Center Criticality / Tier Levels

Guidelines for Specifying Data Center Criticality / Tier Levels Guidelines for Specifying Data Center Criticality / Tier Levels By Victor Avelar White Paper #122 Executive Summary A framework for benchmarking a future data center s operational performance is essential

More information

Data Center Overview Document

Data Center Overview Document Overview NetSource is a Chicago area (Naperville) hosting company that owns and operates its own world class datacenter. The initial datacenter buildout was put into operation in 2007 and expanded in 2013.

More information

Tier Classification of Data Centres. Eric Maddison Senior Consultant, The Uptime Institute

Tier Classification of Data Centres. Eric Maddison Senior Consultant, The Uptime Institute Tier Classification of Data Centres Eric Maddison Senior Consultant, The Uptime Institute Uptime Institute Unbiased and vendor neutral Global thought leadership for the data center industry Founded 1993

More information

Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942 Chris DiMinico cdiminico@ieee.org MC Communications Data Center Standards ANSI/TIA-942 Telecommunications Infrastructure Standard

More information

Energy Efficiency in the Data Center

Energy Efficiency in the Data Center Energy Efficiency in the Data Center Maria Sansigre and Jaume Salom Energy Efficieny Area Thermal Energy and Building Performance Group Technical Report: IREC-TR-00001 Title: Energy Efficiency in the Data

More information

How To Write A Data Center Specification

How To Write A Data Center Specification Guidelines for Specifying Data Center Criticality / Tier Levels White Paper 122 Revision 2 by Victor Avelar > Executive summary A framework for benchmarking a future data center s operational performance

More information

Building Telecommunications Infrastructure Requirements

Building Telecommunications Infrastructure Requirements Building Telecommunications Infrastructure Requirements This page identifies specific requirements for the design of telecommunications infrastructure for buildings at Clemson University. (Revised October,

More information

Data center outages impact, causes, costs, and how to mitigate

Data center outages impact, causes, costs, and how to mitigate Data center outages impact, causes, costs, and how to mitigate Data centers sometimes fail. You can build in safeguards and fail safe mechanisms and redundancy through backup systems but like all engineered

More information

AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx)

AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx) AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx) Site Biography Market Area: Dallas and Fort Worth Areas of Texas Location: Allen, Tx 75013 Address: 900 Ventura Drive CLLI, POP, NPA/NXX

More information

South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime

South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in

More information

BICSI Data Center Standard. Presented by: Stephen Banks, RCDD CDCDP

BICSI Data Center Standard. Presented by: Stephen Banks, RCDD CDCDP BICSI Data Center Standard Presented by: Stephen Banks, RCDD CDCDP BICSI Data Center Standard BICSI 002, Data Center Design and Implementation Best Practices Used in conjunction with other standards ANSI/TIA-942

More information

Data Center Infrastructure & Managed Services Outline

Data Center Infrastructure & Managed Services Outline Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists

More information

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS Customer Handout Date Aug 2, 2010 Version 1.0 File Name Customer Requirements At Power Substations Document Id Outside Plant Engineering 1 Table Of Contents 1.0

More information

Data Centre Reliability and Redundancy. What do they mean and are you are getting what you need?

Data Centre Reliability and Redundancy. What do they mean and are you are getting what you need? Data Centre Reliability and Redundancy What do they mean and are you are getting what you need? What's the message? Why consider Reliability and Redundancy? How do you know what Reliability and/or Redundancy

More information

Data Centre Design ready for your future

Data Centre Design ready for your future Data Centre Design ready for your future Introduction to Data Centres What is a Data Centre? The definition of a Data Centre according to TIA-942 is a building or portion of a building whose primary function

More information

Academic and Technology Resources

Academic and Technology Resources Academic and Technology Resources 140 VISION INTRODUCTION Technology should effectively support pedagogy and multiple learning modalitites to facilitate the teaching and learning process. technology resources

More information

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company Data Centre Cabling 20 August 2015 Stefan Naude RCDD The SIEMON Company Agenda 1. Data Centre Standards 2. The Need for Speed 3. Copper in the Data Centre 4. Fibre in the Data Centre 5. Top of Rack vs

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, P.E., John H. Seader, P.E., and Kenneth G. Brill Widely accepted within the uninterruptible industry, The Uptime Institute s Tier Performance Standards are an objective basis for

More information

ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER

ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect Introduction The primary

More information

Data Center Site Infrastructure Tier Standard: Topology

Data Center Site Infrastructure Tier Standard: Topology U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2010 by Uptime Institute, LLC 20 West 37th

More information

How to Meet 24 by Forever Cooling Demands of your Data Center

How to Meet 24 by Forever Cooling Demands of your Data Center W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the

More information

X-tier Data Facility. Prepared by X-tier SAE Corporation

X-tier Data Facility. Prepared by X-tier SAE Corporation X-tier Data Facility Company Profile X-tier Corporation X-tier is based in Leawood, Kansas. X-tier provides business agnostic, security hardened, custom and turnkey Cloudbased software systems, services,

More information

C24 - Inside the Data Center Andrew J. Luca

C24 - Inside the Data Center Andrew J. Luca C24 - Inside the Data Center Andrew J. Luca Inside the Data Center What an auditor needs to know Course Objectives Understand the looks and feel of a data center Know what to look for and what questions

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Calculating Total Power Requirements for Data Centers

Calculating Total Power Requirements for Data Centers Calculating Total Power Requirements for Data Centers By Richard Sawyer White Paper #3 Executive Summary Part of data center planning and design is to align the power and cooling requirements of the IT

More information

OCDC. OMNIconnect Data Centre.

OCDC. OMNIconnect Data Centre. OCDC. OMNIconnect Data Centre. The OCDC OCDC Sales and Enquiries. 1300 662 457 enquiries@omniconnect.com.au OCDC Location. 14 Elite Way Carrum Downs Victoria Australia Company Overview. OMNIconnect Pty

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, P.E., John H. Seader, P.E., and Kenneth G. Brill Widely accepted within the uninterruptible industry, The Uptime Institute s Tier Performance Standards are an objective basis for

More information

Sovereign. The made to measure data centre

Sovereign. The made to measure data centre Sovereign D ATA C O N N E C T The made to measure data centre Prime Location Within touching distance of everything that s important. 2 Your Customer-Centric Data Centre For the vast majority of organisations

More information

AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA)

AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA) AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA) Site Biography Market Area: Washington, DC Area Location: Ashburn, VA 20147-6011 Address: All deliveries should be sent to

More information

Increasing Energ y Efficiency In Data Centers

Increasing Energ y Efficiency In Data Centers The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Upgrading the PRS datacentres: space requirement. S. S. Mathur, GM-IT, CRIS

Upgrading the PRS datacentres: space requirement. S. S. Mathur, GM-IT, CRIS Upgrading the PRS datacentres: space requirement S. S. Mathur, GM-IT, CRIS PRS / UTS scenario: then and now Year 2000 PRS: 600 locations UTS: 0 locations Year 2008 PRS 1600 locations E-ticketing Passengers

More information

Certified TIA-942 Tier IV Data Center

Certified TIA-942 Tier IV Data Center Certified TIA-942 Tier IV Data Center Beltsville, MD AiNET 11710 Montgomery Road Beltsville, MD 20705 USA www.ai.net Data Center Standard TIA-942 Developed by Telecommunications Industry Association Leading,

More information

White Paper. Optimizing the SAN Fiber Optic Physical Layer in Your Data Center

White Paper. Optimizing the SAN Fiber Optic Physical Layer in Your Data Center White Paper October 2012 Optimizing the SAN Fiber Optic Physical Layer in Your Data Center Deploying a structured cabling system for the SAN provides measurable results and long term value, whether you

More information

TIA STANDARD. Telecommunications Infrastructure Standard for Data Centers TIA-942 TELECOMMUNICATIONS INDUSTRY ASSOCIATION

TIA STANDARD. Telecommunications Infrastructure Standard for Data Centers TIA-942 TELECOMMUNICATIONS INDUSTRY ASSOCIATION TIA STANDARD ANSI/TIA-942-2005 Approved: April 12, 2005 Telecommunications Infrastructure Standard for Data Centers TIA-942 April 2005 TELECOMMUNICATIONS INDUSTRY ASSOCIATION Representing the telecommunications

More information

PROJECT REQUEST REPORT UNIVERSITY OF WASHINGTON DATA CENTER

PROJECT REQUEST REPORT UNIVERSITY OF WASHINGTON DATA CENTER UNIVERSITY OF WASHINGTON OFFICE OF THE VICE PROVOST PLANNING AND BUDGETING Capital and Space Planning PROJECT REQUEST REPORT UNIVERSITY OF WASHINGTON DATA CENTER JULY 31, 2006 University of Washington

More information

Consulting Engineering Outsourcing

Consulting Engineering Outsourcing Consulting Engineering Outsourcing Opportunities, challenges and strategies 5.º Fórum Lusófono das Comunicações Maputo, 24 de Abril de 2014 Maksen 2014 Consulting Engineering Outsourcing AGENDA 01. Data

More information

NORTHERN VIRGINIA ONE (NoVa) DATA CENTER OVERVIEW

NORTHERN VIRGINIA ONE (NoVa) DATA CENTER OVERVIEW VAZATA 9651 Hornbaker Road Manassas, VA 20109 VAZATA.COM VAZATA's NoVa One data center located at 9651 Hornbaker Road in Manassas, Virginia is engineered from the ground up to deliver highly reliable and

More information

RAGINGWIRE. THE WORLD S MOST TECHNOLOGICALLY ADVANCED DATA CENTERS!

RAGINGWIRE. THE WORLD S MOST TECHNOLOGICALLY ADVANCED DATA CENTERS! RAGINGWIRE. THE WORLD S MOST TECHNOLOGICALLY ADVANCED DATA CENTERS! RagingWire designs, builds, and operates mission-critical, high density data centers. With nearly one million square feet of multi-tenant

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

Assessment of Existing Data Centers for Critical Facilities Round Table Group

Assessment of Existing Data Centers for Critical Facilities Round Table Group Assessment of Existing Data Centers for Critical Facilities Round Table Group Chuck Shalley, P.E. Consulting Electrical Engineers BACKGROUND INFORMATION ASSIGNMENT Data Center Criteria Type Raised Floor

More information

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. 1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking

More information

Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport

Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport Welcome Zenium Istanbul One provides 12,000 square metres of high specification technical space across three purpose-built data centers. It is Turkey s first wholesale data center offering; the data halls

More information

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging

More information

Modern Data Centers: Creating a New Value Proposition

Modern Data Centers: Creating a New Value Proposition Modern Data Centers: Creating a New Value Proposition América Latina 2008 Inter-secretarial Commission for the Development of Electronic Government Mexico City 24 May 2013 Data Center Consolidation Consolidating

More information