LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification
|
|
|
- Denis Parrish
- 10 years ago
- Views:
Transcription
1 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA KVA General Specification This specification describes the features and design of the LTR Series Uninterruptible Power System. The system is designed and manufactured to assure maximum reliability, serviceability and performance. The system is a line interactive UPS incorporating a microprocessor controlled PWM inverter, high speed transfer devices, constant voltage regulating transformer, battery charger and energy storage battery platform to facilitate complete protection for critical electronic equipment applications. The UPS as specified herein provides complete immunity from line disturbances and power interruptions with no loss of or disruption in AC output power. The system s constant voltage output transformer regenerates the output waveform during all phases of operation, thus maintaining a regulated, clean power source for the intended load. A self-diagnostic monitoring system continuously advises of system status and battery condition. 2.0 UPS Ratings Model Rating Model Rating LTR VA / 500 Watts LTR VA / 1000 Watts LTR VA / 600 Watts LTR VA / 1200 Watts LTR VA / 700 Watts LTR VA / 1300 Watts LTR VA / 850 Watts LTR VA / 1500 Watts 3.0 Standards The system is designed in accordance with applicable portions of the following codes and standards: 3.1 American National Standards Institute (ANSI C57.110). 3.2 Institute of Electrical and Electronic Engineers (IEEE ) and (C ). 3.3 National Electric Code (NEC) (NFPA 70). 3.4 National Electrical Manufacturers Association (NEMA PE-1, 2003) and (IEC ). 3.5 Underwriters Laboratories (UL 1778). 3.6 Federal Communications Commission (FCC Part 15, Sec. J, Class A). 3.7 Listed UL Standard UL 1778, and cul C22.2, No M Input Specifications 4.1 Input Voltage: 208, 240 or 120 VAC at 60Hz. 4.2 Input Voltage Operating Range: +10% to -15% at full load without battery usage. 4.3 Input Voltage Extended Range: The unit incorporates the use of Fuzzy Ranging in conjunction with load percentage to extend the input range up to +10% to -40% without battery usage. 4.4 Frequency Range: 57.5 Hz to 62.5 Hz. 4.5 Power Factor: Self correcting to > Input Harmonics: < 5% THD. 4.7 Transient / Spike Attenuation: 3000:1. Page 1 of 5
2 5.0 Output Specifications 5.1 Output Voltage: 240/120, 208/120 or 120 VAC. 5.2 Output Waveform: Sinusoidal, regenerated, with maximum 3% harmonic distortion, any single harmonic. 5.3 Crest Factor: 3.0 : K Factor: 30 or better. 5.5 Harmonic Attenuation: Reflected load generated harmonics are attenuated 23dB at the input. 5.6 Line Regulation: Typically better than +/-3%. 5.7 Load Regulation: Typically better than +/-3%. 6.0 Battery Specifications 6.1 Battery time: Based on full KW load. 6.2 Battery Type: Sealed, maintenance free. 6.3 Battery Charger: 2 Amp, 3 stage, filtered 0.1%, temperature compensated (internal batteries only). 6.4 Recharge Time: Typically 10 times discharge time to full charge. 6.5 Bus Voltage: 24 VDC, float 2.27 VPC, final 1.75 VPC. 6.6 Projected Life: 5 years service. 7.0 Performance Specifications 7.1 Normal Operation: The load is supplied with regenerated, filtered and regulated utility power derived from the output constant voltage regulating transformer. When public utility AC power is present, the battery charger maintains a ripple free float charge on the batteries. 7.2 Uninterrupted Emergency Operation: Upon failure or unacceptable deviation of the public utility AC power, energy will be supplied by the battery, converted to AC through the PWM inverter, regenerated, filtered and regulated through the system s constant voltage regulating output transformer, and will continue to supply power to the load without interruption, loss or disturbance. When utility power is restored, the system reverts to normal operation without interruption, loss or disturbance. 7.3 Automatic Restart: In the case of a public utility power outage that exceeds the battery time requirement, the output of the system will de-energize to protect the battery system, but will automatically restart once commercial AC power returns. When the public utility power returns, recharging of the batteries commences immediately. 7.4 Hot Start (DC): The UPS is capable of being started from battery power when no AC power is present. This feature can be enabled or disabled through the RS232 interface. 7.5 Overload Capability: 125% for ten minutes. 7.6 Surge Capability: 150% of rated output without need of static bypass. 7.7 Frequency Stability: Hz. 7.8 Isolation: NEC article b, complies with this standard that specifies a separately derived power source. Page 2 of 5
3 7.9 Inner Winding Capacitance: 0.01 pf (primary to secondary coupling) Common Mode Noise Attenuation: 120 db (10 6 : 1 ground noise attenuation) Transverse Mode Noise Attenuation: 70 db (3160 : 1 line noise attenuation) Leakage Current to Ground: < 300µA 7.13 Reactive Power Correction: Load at.6 PF corrected to > 0.95 at input (automatically correcting) Expandability: Available with LTR700 Models (expandable to LTR850), LTR1200 Models (expandable to LTR1600) and LTR1800 Models (expandable to LTR2100) Efficiency, BTU/HR Emitted, Weight, Cabinet Sizes: Model Efficiency BTU/HR Weight Dimensions W x D x H LTR700 85% lb. 19 x 20 x 8.75 LTR850 85% lb. 19 x 20 x 8.75 LTR % lb. 19 x 20 x 8.75 LTR % lb. 19 x 20 x 8.75 LTR % lb. 19 x 20 x 8.75 LTR % lb. 19 x 20 x 8.75 LTR % lb. 19 x 20 x 8.75 LTR % lb. 19 x 20 x 8.75 Note: Weight includes minimum internal batteries. 8.0 Display Monitor and Diagnostics 8.1 Display Panel Front mounted, sealed, alphanumeric LED panel. Displays input voltage, output voltage, % load, and % battery as selected using display select push button. System display panel includes automatic visual status indicators for system on, system on battery, low battery and general alarm. Includes audible alarm for system on battery, low battery and general alarm condition(s). 8.2 General Alarm Conditions (Contact Closure) Communications port for access to general alarm conditions and electrical measurements. General alarm conditions include: loss of AC input power, low battery warning, frequency fault, check battery, shorted SCR, low battery shutdown, low output voltage, high output voltage, system overload and system over temperature warning. 8.3 Electrical Measurements (RS232) Communications port for access to general alarm conditions and electrical measurements. Electrical measurements include: AC input voltage, AC output voltage, output amps, % load, output watts, output VA, power factor, input line frequency, and number of power outages recorded from last clear function and number of overloads recorded from last clear function. 8.4 Battery Replacement Testing The system includes provisions for determining battery life and scheduled battery replacement. 9.0 Communications Interface 9.1 Status / Alarm open collector transistor interface is provided for use with optional remote annunciator panel, or automatic message dialer. Inverter on, utility AC power failure (system using battery power), low battery warning, and general alarm signals are included. 9.2 Status / Alarm open collector transistor ratings: 40 VDC maximum, 300mA for use with optional remote annunciator panel or automatic message dialer or for use with customer s remote indicator /- 10 VDC, 1 ma power supply and potential free contact closure REPO input included for use with customer s remote emergency power off push button. Page 3 of 5
4 9.4 RS232 communication port included for customer s remote computer terminal display of all monitored criteria Environmental 10.1 Operating Temperature: 0 C (32 F) to 40 C (105 F) Storage Temperature: -20 C to 50 C Relative Humidity: 95% non-condensed Elevation: 5,000 feet, 1500 meters without de-rating Reliability 11.1 Total System MTBF: 100,000 hours Transformer MTBF: 200,000 hours MTTR: Less than one hour Standard Equipment 12.1 Input plug with 6 detachable input line cord Keyed power on/off switch Main printed circuit control board (single PC board design) Constant voltage regulating output transformer Standard internal battery NEMA 5-20R2 duplex output receptacles, quantity of three (3); or for Canadian installations, NEMA 5-15R2, quantity of three (3) Copper conductor construction throughout entire system Local display monitor / diagnostics panel Communications port (RS232) Functional rack mountable style enclosure Optional Equipment 13.1 Internal and/or external battery options for extended back up time External battery options available in rack-mountable enclosures or in free-standing cabinets supplied on lockable casters Locking type input plug for 240, 208 or 120 VAC with 6 detachable input line cord Optional output NEMA receptacles for 240, 208 or 120 VAC. Consult factory for available configurations Hardwired input and output connections External wall-mounted make before break bypass switch for 120 VAC input / output hardwired models. Page 4 of 5
5 13.7 Automatic message dialer used in conjunction with system alarm conditions for system on emergency battery power, low battery warning, and general alarm Remote annunciator panel used in conjunction with system alarm conditions for system on emergency battery power, low battery warning, and general alarm Software package for automatic, unattended, graceful shutdown of computer systems in the event of an extended outage and limited battery time remaining, plus remote monitoring and notification of electrical parameters and alarm conditions Network device SNMP / Ethernet TCP/IP adapter Network device SNMP / MODBUS TCP / Ethernet TCP/IP adapter Network device SNMP / MODBUS TCP & RS485 / Ethernet TCP/IP adapter Warranty 14.1 All systems are guaranteed to be free from defects in material and workmanship for a period 1 year following shipment from the factory Batteries are warranted with a 1 year full replacement warranty, and an additional 3 year pro-rated warranty with the applicable optional maintenance contract Optional, extended warranty and maintenance contracts available. Page 5 of 5
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power
APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
Uninterruptible Power Supply
96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features
TOSHIBA G9000 80/100/160/225 kva
CORPORATE OFFICE 13131 WEST LITTLE YORK ROAD HOUSTON, TX 77041 PHONE: (713) 466-0277 (800) 231-1412 FACSIMILE: (713) 896-5226 TOSHIBA G9000 80/100/160/225 kva GUIDE SPECIFICATION THREE PHASE UNINTERRUPTIBLE
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications Model #: SU3000RTXL3U 3000VA online 3U rack / tower UPS Enhanced serial communications
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
PowerGem Pro Uninterruptible Power Supply
Uninterruptible Power Supply User-friendly Intelligent Ultra reliable Range The Most Intelligent On-Line Double Conversion Power Protection System The range achieves higher reliability and greater immunity
Galleon 6-10K Online UPS. Voltronic Power Technology Corporation
Galleon 6-10K Online UPS Voltronic Power Technology Corporation Features Galleon online UPS series delivers optimal power quality, provides superior power management, resolves utility power protection
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of
UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES
UNINTERRUPTIBLE POWER SUPPLIES 9900A >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES 9900A The 9900A UPS system uses the most advanced IGBT in both the converter and inverter with Digital Signal Processor (DSP)
BC Pro UPS System Standby UPS System
BC Pro UPS System Standby UPS System Model #: BCPRO1400 1400VA standby, tower UPS system Offers battery derived AC output during blackouts and brownouts starting at 99V 6 protected AC outlets (NEMA 5-15R)
Specification Requirements DBL 700MX and 1000MX Series UPS
Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without
Always On UPS Systems Inc., #100-150 Campion Road, Kelowna, BC Canada V1X 7S8
Door Mount UPS (Patent Pending) Shelf Mount UPS (Patent Pending) DESCRIPTION: The Always On NDM (door mount) and NSM (shelf mount) Series UPS s are dual conversion online UPS systems provided in slim,
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V APC Smart-UPS, 670 Watts / 1000 VA,Input 230V / Output 230V, Interface Port DB-9 RS-232, SmartSlot, USB Includes: CD with software, Smart UPS signalling
MAJORSINE Power Inverter
MAJORSINE Power Inverter Product Features: 24, 48, 130 V 1 KVA/800 Watts Output 2 KVA/1600 Watts Output 100-120 VAC Range 208-240 VAC Range Standard 19 /23, Pure Sine Wave Output High Low EMI/RFI Emissions
Model #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V
SmartPro VS Tower UPS System Intelligent, line-interactive power management system Model #: SMART2200VS 2200VA / 2.2kVA line interactive tower UPS Maintains 120V nominal output over an input range of 79
SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial
SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMART500RT1U Description Tripp Lite's SMART500RT1U intelligent, line-interactive rack/tower uninterruptible
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial MODEL NUMBER: SMARTINT3000VS Highlights 3kVA / 3000VA / 2250W line interactive tower UPS system 230V
Model #: SMART2200CRMXL
Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: [email protected] Model #: SMART2200CRMXL SmartPro Compact Rackmount UPS System - Precision Protection for
3U, 2200 VA Audio/Video Pure Sine Wave UPS System
3U, 2200 VA Audio/Video Pure Sine Wave UPS System MODEL NUMBER: HTR22-3U Description Tripp Lite's HTR22-3U Pure Sine Wave 2200VA/1600W on-line, double-conversion UPS system prevents media data loss, equipment
AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass
AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass APC AIS 3000, 12 kw / 15 kva,input 208V 3PH / Output 120V, 208V, 208V 3PH, Interface Port DB-9 RS-232,
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port
OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port MODEL NUMBER: OMNIVS1500 Highlights 1500VA / 1.5kVA tower 120V line-interactive UPS Corrects brownouts and overvoltages from 75 to 147V
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial MODEL NUMBER: SMART2200RM2U Highlights 2.2kVA / 2200VA / 1920W line interactive 2U
Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system
Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system Model #: SMART500RT1U 500VA line interactive 1U rack/tower UPS 7 outlets with 1 switchable load bank Simultaneous
Thyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
TECHNICAL SPECIFICATIONS FOR 1.5 KVA ONLINE UPS
Capacity Technology Inverter Technology Noise Level Operating Temperature Humidity Harmonic Distortion Total DC bus voltage Battery recharge time (After Complete discharge) to 100% charge Crest Factor
SECTION 16260 STATIC UNINTERRUPTIBLE POWER SUPPLY SYSTEM
1 0 1 0 1 SECTION 0 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Uninterruptible power supply (UPS) system. B. Related Sections include but are not necessarily limited to: 1. Owner s - Bidding
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
Single Phase, (3 to 20KVA) & (3 to 15 KW) Harsh Environment Outdoor Application NEMA 3R Cabinet
TECHNICAL SPECIFICATIONS for Single Phase, (3 to 20KVA) & (3 to 15 KW) Harsh Environment Outdoor Application NEMA 3R Cabinet Harsh Environment UPS (HE-UPS) 10/06/05 1. SCOPE A. The UPS shall be a solid-state
LAP ENERGIA PARA DATACENTERS
LAP ENERGIA PARA DATACENTERS Latin American Power. CABA, Argentina. 2 UPS INDOOR Latin American Power. CABA, Argentina. ALI ELITE SERIES Line Interactive UPS Tower/19 Rack Mount Versions 19 Rack Mount
SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial
SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial MODEL NUMBER: SMART1500SLT Highlights 1.5kVA / 1500VA line interactive tower UPS; Sine wave output
Audio/Video AVR Series UPS - Intelligent Automatic Voltage Regulated Power Management System
Audio/Video AVR Series UPS - Intelligent Automatic Voltage Regulated Power Management System MODEL NUMBER: HTR05-1U Description Tripp Lite's HTR05-1U AVR Series intelligent, Automatic Voltage Regulated
User Manual 1K/2K/3K Online UPS
User Manual 1K/2K/3K Online UPS Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4. Operation...
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial
SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SMART1000RM1U Description Tripp Lite SMART1000RM1U 1000VA / 1kVA / 800 watt line interactive,
30-120 3 Phase Modular Finally the benefits of Modular ups are for all
MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion
Liebert GXT3 Reliable On-Line UPS Protection In A Compact 2U Package 700VA -3000VA
Liebert GXT3 Reliable On-Line UPS Protection In A Compact 2U Package 700VA -3000VA Liebert GXT3 is a full feature UPS providing reliable protection for IT network equipment and data centers. It is a true
Internet Office UPS System Standby UPS for PCs, workstations and more
Internet Office UPS System Standby UPS for PCs, workstations and more Model #: INTERNETOFFICE500 500VA standby tower UPS system Offers battery-derived AC output during blackouts and brownouts starting
USER MANUAL Online UPS 1K/2K/3K Rack
USER MANUAL EN Online UPS 1K/2K/3K Rack Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3. Installation 2 1-4. Operation 2
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS, Sine
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P
Technical Data Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P Topic Page 1609-P Specifications 2 1609-P Approximate Dimensions and Shipping Weights 3 Additional Resources
TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial
TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SM1000RM1UTAA Description Tripp Lite SM1000RM1UTAA 1000VA / 1kVA / 800 watt line
UltraLITE. Centralized Emergency Lighting Inverters MODEL ELU
1.5 kw 14 kw SINGLE PHASE UltraLITE MODEL ELU Centralized Emergency Lighting Inverters True no-break system, with regulated output and transient voltage protection for LED lighting, electronic ballasts,
Internet Office 500VA Tower Standby 120V UPS with USB port
Internet Office 500VA Tower Standby 120V UPS with USB port MODEL NUMBER: INTERNETOFFICE500 Highlights 500VA tower 120V standby UPS Maintains AC output during power failures 3 UPS battery supported outlets,
USER MANUAL Online UPS 1K/2K/3K
USER MANUAL EN Online UPS 1K/2K/3K Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning 2 1.1. Transportation 2 1.2. Preparation 2 1.3. Installation 2 1.4. Operation 2 1.5.
Back-UPS 650 VA 120 V with AVR (BX650CI-LM)
Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit
Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE
Local Area Networks (LAN) Servers Data centers Internet centers (ISP/ASP/POP) Industrial PLCs EPOS (Electronic Point of Sale) Systems Emergency devices (lights/alarms) Electro-medical devices Telecommunication
EKOS Cart. Instructions for Use
EKOS Cart Instructions for Use EKOS Corporation 11911 North Creek Parkway South Bothell, WA 98011 USA (425) 415-3100 (tel) (425) 415-3102 (fax) [email protected] (e-mail) - 1-4913-002 REV E Intended Use
SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial
SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMX1000RT2U Highlights 1kVA / 1000VA / 900W line-interactive 2U rack/tower UPS, Sine
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS,
Internet Office 750VA Ultra-compact Standby 120V UPS with USB port
Internet Office 750VA Ultra-compact Standby 120V UPS with USB port MODEL NUMBER: INTERNET750U Highlights 750VA ultra-compact 120V standby UPS Maintains AC output during power failures 6 UPS battery supported
Online UPS. PowerWalker VFI 1000R/1U
Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.
APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 1000VA, 2000VA & 3000VA Smart-UPS RC 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 1000VA, 2000VA & 3000VA Smart-UPS RC 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
PC Personal 120V 600VA 375W Standby UPS with Pure Sine Wave Output, Tower, 6 Outlets
PC Personal 120V 600VA 375W Standby UPS with Pure Sine Wave Output, Tower, 6 Outlets MODEL NUMBER: BC600SINE Highlights 600VA tower 120V standby UPS with SINE WAVE output Maintains AC output during power
Power Quality. Uninterruptible Power Supply
Quality Uninterruptible Supply In the electrical system environment, power disturbances will occur. These can be caused by faults on the distribution system, the operation of nearby equipment, lightning
SmartPro 230V 750VA 500W Line-Interactive Sine Wave UPS, SNMP, Webcard, Tower, USB, DB9 Serial
SmartPro 230V 750VA 500W Line-Interactive Sine Wave UPS, SNMP, Webcard, Tower, USB, DB9 Serial MODEL NUMBER: SMX750SLT Highlights 750VA line interactive tower UPS; Sine wave output 220/230/240V nominal
User s Manual AURORA 1.2K/2.2K
User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable
RoHS APPROVAL SHEET. ituner 12V/6.6A SERIES NO. (E17) EA10953A. ( ) Edac Power Electronics (Suzhou) Co., Ltd. 59 No.59, Chang Sheng Road, Sheng Pu,
APPROVAL SHEET CUSTOMER ituner CUSTOMER P/N DESCRIPTION EDAC MODEL 12V/6.6A SERIES NO. (E17) EA10953A DATE 2010-06-22 REVISION 0 APPROVED DESIGN PREPARE RoHS CONCLUSION APPROVED CONDITON CUSTOMER S APP
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
on-line LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTERS internet centers (isp/asp/pop) industrial plcs industrial applications
ZP110 on-line UPS 1, 2, 3, 6, 10kVA single/single phase LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTERS internet centers (isp/asp/pop) industrial plcs Emergency Devices (Lights/Alarms) Electro-Medical Devices
Product Snapshot. Powerware 9140 Uninterruptible Power System. Superior de-centralized power protection for medium- and high-density rack environments
Powerware 9140 Uninterruptible Power System Product Focus Superior de-centralized power protection for medium- and high-density rack environments Product Snapshot Power Rating: Nominal Input Voltage: Nominal
CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING
PART 1-GENERAL 1.01 DESCRIPTION A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width modulated (PWM) inverter designed for use on a standard NEMA
DC UPS. RTB.e 50-1000 A. IMB.e/ITB.e 5-200 kva. E2001.e/E3001.e 5-200 kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.
Oil & Gas Energy Catalogue DC UPS RTB.e 50-1000 A 3 phase rectifier battery chargers voltage: 400 Vac, 3-phase, 50/60 Hz voltage: 24/48/110/220 Vdc RMB.e/RCB.e 50-100-150 A 1 and 3 phase compact rectifier
LIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro. UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase.
LIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro online UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase LOCAL AREA NETWORKS (LAN) INTERNET CENTERS (ISP/ASP/POP) ELECTRO-MEDICAL
NRG. Intelligent Engine Start Battery Charger. The Smart Choice for Mission-Critical Engine Starting
NRG Intelligent Engine Start Battery Charger The Smart Choice for Mission-Critical Engine Starting Fast, accurate, mission-critical charging gives best starting reliability 4-rate, temperature-compensated
JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410
The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a
QuickSpecs. HP R/T3000 G2 Uninterruptible Power System (UPS) Overview
Overview The industry leading packs up to 3000 watts into a space saving 2U design. Proven Digital Signal Processor (DSP) double conversion system provides clean, reliable power protection in an energy
Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy.
Match Uninterruptible Power Supply 500-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com
NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL
NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL [email protected] / www.tuncmatik.com Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3.
User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply
User Manual English APC Smart-UPS SC 1000/1500 VA 110/120/230 Vac 2U Tower/Rack-Mount Uninterruptible Power Supply 990-1851C, 10/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed
APC. DIN Rail Control Panel Mounting Uninterruptible Power Supply. Catalog
APC DIN Rail Control Panel Mounting Uninterruptible Power Supply Catalog 2014 Contents Introduction, description... 4 Specifications...5 References....6 Dimensions...7 Wiring diagrams....8 Product reference
User Manual. English. APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC. Tower Uninterruptible Power Supply
User Manual English APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC Tower Uninterruptible Power Supply 990-1587A 12/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent
For protection from laptops to high availability facilities - and everything in between - APC is a partner you can count on
Home Sign In View Cart Order Status Search Solutions Products and Services Support Your Business Company Data Center Server Rooms Solutions for Small-Medium Data Center Large Data Centers Cloud & Co-location
Intelligent Power Distribution in the Data Center
Rack Power Intelligent Power Distribution in the Data Center Agenda Data Centre Power UPS Power Distribution Rack Mount PDU s UPS Power problems Configuration Capacity Power Distribution Types of Distribution
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface
TLE Series UPS 225-1500 kw for best-in-class multi-mode operating efficiency
TLE Series UPS 225-1500 kw for best-in-class multi-mode operating efficiency Ensuring Uptime for Critical Processes Mission-critical processes need a power system that is cleaner and more reliable than
HP R/T3000 G2 Uninterruptible Power System (UPS) Overview
Overview The industry leading packs up to 3000 watts into a space saving 2U design. Proven Digital Signal Processor (DSP) double conversion system provides clean, reliable power protection in an energy
R5000 Uninterruptible Power System (UPS) Overview
Overview The innovative Minimally Switched Technology used in the HP R5000 UPS improves the performance over traditional line-interactive UPS designs while reducing the cost, weight, and size of traditional
Back-UPS Pro 1300/1500 Installation and Operation
Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Your Inspirations. Our Innovations. UNINTERRUPTIBLE POWER SUPPLY (UPS) Protecting Your Data CATALOGUE Revision 0 Table of Contents Table of Contents About Us - Company Profile Online UPS Professional
ekil 3 KGK tecrübesi olmayan herhangi bir ki i tarafından çalı tırılabilir.
ekil 3 KGK tecrübesi olmayan herhangi bir kii tarafından çalıtırılabilir. üçııı ıı ç ıöç ö çö ııı ç çıı çı ııııı ıüıçıııçııı ç ıç ö çı ııç ıı Akü Modu Akü düük Aırı yük Arıza Bypas modu 4 saniyede
How To Upgrade An Hp Power Distribution Rack To A Power Distribution Unit
Overview Power protection in the data center is critical to maintain up time, and the increased densities in data centers is driving the need for uninterruptible power with increased power density, power
Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS
+ Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,
F2400 FOM II Series Fiber Optic Modem Technical Manual
F2400 FOM II Series Fiber Optic Modem Technical Manual T1 Revision B Copyright April 2003 VERSITRON, Inc. 83 Albe Drive / Suite C Newark, DE 19702 www.versitron.com A030430283T PROPRIETARY DATA All data
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
IBM 11000VA LCD 5U Rack Uninterruptible Power Supply IBM System x at-a-glance guide
IBM 11000VA LCD 5U Rack Uninterruptible Power Supply IBM System x at-a-glance guide The IBM 11000VA LCD 5U Rack uninterruptible power supply (UPS) optimizes for both efficiency and performance, providing
UPS Applications and VRLA Battery Sizing
TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the
RIELLO ELETTRONICA. Master HP
RIELLO ELETTRONICA Master HP LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTRES TELECOM- MUNICATIONS DEVICES E-BUSINESS (Servers Farms, ISP/ASP/POP) INDUSTRIAL PROCESSES INDUSTRIAL PLCS ELECTRO- MEDICAL DEVICES
SG Series UPS 10-150 kva. high efficiency systems
SG Series UPS 10-150 kva high efficiency systems Touching all Areas of the Energy Industry With more than 100,000 employees in over 100 countries, GE s diverse portfolio of products and services is helping
USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018
USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and
Specification CyberWave UPS Ver 1.05 02/01/00
GUIDEFORM SPECIFICATION FOR CyberWave UPS Systems 10-112 kva SINGLE-PHASE OUTPUT The attached specification is intended for use by consulting engineers to provide bidding specifications for products with
R5000 Uninterruptible Power System (UPS) Overview
Overview The innovative Minimally Switched Technology used in the HP R5000 UPS improves the performance over traditional lineinteractive UPS designs while reducing the cost, weight, and size of traditional
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information