Power Plant Electrical Distribution Systems
|
|
|
- Antony Ramsey
- 10 years ago
- Views:
Transcription
1 PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA Phone: Fax: An Approved Continuing Education Provider
2 Power Plant Electrical Distribution Systems Gary W Castleberry, PE Course Description This one hour course provides an introduction to the design of electrical distribution systems found in electrical power generation plants. The type of equipment utilized in the electrical distribution systems is discussed in terms of its design, function, role and backup capabilities. A short quiz follows the end of the course material. Learning Objectives Upon completion of this course one should be able to understand the role of the following equipment in a power plant distribution system: Main electrical generator, isolated phase bus duct, step-up transformer, station auxiliary transformer, non-segregated phase bus duct, station startup transformer, medium voltage switchgear, secondary unit substations, and motor control centers. Along with the role of each type of equipment, one should understand how the equipment is utilized to provide reliable power to the station. Introduction Modern power plants have an extensive electrical distribution system to provide reliable power to all of the support equipment in the power plant. The utility operating the power plant is in the business of generating electrical power twenty four hours a day, seven days a week. Since electrical power can not be economically stored the plants must be online to produce power when the electrical demand is present. In this regard, the power plants must be highly reliable. Backup power sources within the plant must be ready to supply needed power within moments. This course will provide an overview of these systems and the relationships between the different systems. Course Content Large electrical generation power plants (power stations) today come in all varieties. Some of the plants utilize fossil fuels such as coal, oil and natural gas to fire boilers as tall as a twenty five story building. The boilers produce the massive amounts of steam necessary to spin large turbines connected to electrical generators. Nuclear plants produce the same large amounts of steam but use a nuclear reactor as the source of heat. Regardless of the type of plant, Gary W. Castleberry Page 2 of 16
3 the stations auxiliary components require substantial electrical distribution systems to provide reliable power. In the fossil plant these components include large circulating water pumps that provide cooling water to the turbine condenser, large fans that move the combustion air through the boiler and feedwater pumps that circulate the water through the boiler. Nuclear plants have similar circulating water pumps and feedwater pumps. In addition, the nuclear plants have emergency equipment that supports safe operation of the reactor. Both nuclear and fossil plants have large battery banks that provide backup DC power to the plant controls. These batteries are kept charged by large battery chargers. The designs of the electrical distribution systems are quite similar from plant to plant. Even the nuclear plants systems are somewhat similar although they have much more redundancy built into the designs. The reason the plant designs are generally the same is because utilities have perfected these plant design over the last century and continue to use what is a proven approach. When the nuclear plants came along in the 1960s and 70s, the existing proven electrical designs were simply modified slightly and used in the nuclear plant designs. The following one-line diagram shows a typical power plant electrical distribution system. Gary W. Castleberry Page 3 of 16
4 The one-line diagram shows a simplified arrangement of the primary electrical components. A more detailed discussion of each component follows this narrative. Starting at the upper left corner of the diagram, a circle symbol with a Y in the center represents the plant main electrical generator. The output of the generator is connected to the isolated phase bus duct shown as a green line. The isolated phase bus duct connects the output of the main generator to two other components: the step-up transformer and the station auxiliary transformer. The Step-up Transformer increases the generator voltage from 22,000 Volts or 22KV (Kilo-volts) to the transmission voltage of 500KV in this example. The transmission voltage varies from utility to utility and from plant to plant and is really a function of the transmission design that already exists (i.e. if a plant is built near an existing transmission line of a certain voltage, typically that will be the voltage chosen for the step-up transformer). The Unit Auxiliary Transformer is the power transformer that provides power to the station s auxiliaries during normal operation. This transformer is connected directly to the Main Generator and as such will provide the cheapest power for the station use since any power from the transmission lines has losses associated with it due to the line losses and transformer losses from whatever step-up transformer provided that power. This Unit Auxiliary Transformer (UAT) is a three winding transformer having one primary winding rated 22KV and two Gary W. Castleberry Page 4 of 16
5 secondary windings rated 6.9KV and 4.2KV. This allows the transformer to power two different voltage level buses in the plant. The UAT s secondary windings are connected to the Non-segregated Phase Bus Duct or (Non-seg Bus). This bus work conveys the power to the different medium voltage switchgears located in the plant. In this plant design there are two sets of switchgear buses rated at 6.9KV and 4160V. Each 6.9KV bus (shown in black) can be energized from the Unit Auxiliary Transformer. The same is true for the 4160V switchgear. There is another transformer shown in the drawing. The Start-up Transformer is energized from an incoming transmission line rated at 230KV. This transformer is also a three winding transformer and can feed all four of the switchgear lineups. This transformer is used to power the plant equipment while starting the unit up from cold conditions (i.e. no fire in the boiler). All plants utilize a numbering scheme for their switchgear and circuit breakers. The scheme utilized here is as follows: The first digit of the number refers to the voltage level of the bus. A 1 is for 6.9KV, a 2 is for 4160V, and a 3 is for 480V. The second character of the numbering scheme is a letter, either A or B and stands for which bus you are connected to, of the two buses at that voltage. A breaker with the characters 2B would be on the B bus of the 4160V switchgear. The next character in the designator is simply the breaker number. Notice that similar functioning breakers are usually assigned the same breaker numbers. Breaker 1A-1 and 1B-1 are both the incoming supply breakers from the Unit Aux Transformer and Breakers 1A-2 and 1B-2 are the incoming supply breakers from the Startup Transformer. The remainder of the one-line diagram reflects the low voltage system which is operated at 480V. This system is supplied by breakers from the 4160V bus and the voltage is stepped down to 480V by the 4160V/480V transformers shown on the drawing as SUS Transformer (Secondary Unit Substation). The electrical distribution system shown on the one-line diagram is typical for most plants for the configuration as shown. The number of switchgear buses will vary along with the voltages. The reasons for this will become more clear as the text continues with the detailed system descriptions. 1. Main Generator The generator produces the electrical power the utility is in business to produce and sell. The three primary components of the generator are the rotor, exciter, and stator. Gary W. Castleberry Page 5 of 16
6 Rotor: The rotor on the main generator is composed of a steel shaft to which a field winding has been added. This shaft connects to the main turbine shaft and rotates at the same rotational speed as the turbine. The field winding is located in slots machined into the rotor. When DC current is passed through the field windings, the rotor forms an electromagnet with North and South poles. The resultant magnetic flux rotates through the coils of the armature (in the stator) inducing a voltage. The number of North and South poles depends upon the machine design. Some rotors have two pole designs (a single North pole and South pole) while others have a four pole design (two North and two South poles). The rotor has a fan mounted on each end of the shaft. This fan is used to force gas into the generator for cooling. The gas used is hydrogen due to its heat transfer capability. Exciter: The exciter provides the DC current which is provided to the field windings. The exciter output can be varied to control the armature voltage. This is done by varying the amount of DC current to the field windings and thus varying the power of the rotor field; thus, the amount of voltage induced in the armature windings (stator) is changed. The exciter is typically a self-excited AC generator mounted on the same shaft as the rotor and turbine. Its output is rectified through a series of power diodes providing a DC current for the rotor field windings. Depending on the manufacturer, the exciter either uses collector rings and brushes to pass the DC current to the rotor (General Electric machines). Westinghouse generators use a brushless exciter system. Stator: The Stator has two primary parts: the stator core and the armature windings. The core is constructed out of donut shaped laminated iron alloy sheets that have slots around the inner circumference. The stator core has a dual purpose of supporting the armature windings and concentrating the magnetic flux around the conductors of the armature. The armature windings for the generator are located in the stator core slots. The induced voltage from the rotating field produces current in the conductors. This current is large in magnitude creating significant heating due to I 2 R losses (the heat produced in a conductor is equal to the current times itself times the resistance of the conductor). In order to remove this heat the conductors are hollow and cooled with either hydrogen gas or water depending upon the machine design. Gary W. Castleberry Page 6 of 16
7 Utilities generate three phase power so there are three armature windings in the machine producing three voltages which are 120 degrees apart in phase. The armature leads exit the generator at the bottom and pass through cubicles with potential transformers (PT) and current transformers (CT) for metering and protective relays In addition, the generator neutral is brought out of the machine into a separate cubicle. In the neutral grounding cubicle the grounding equipment and protective relays are located. There are a variety of ways to ground a generator neutral. In this example a ground transformer and resister are used. The purpose of the grounding equipment is to provide a means for monitoring the current in the neutral with protective relays. From the PT and CT cubicle the generator output connects to the Isolated Phase Bus Duct. 2. Isolated Phase Bus Duct Isolated Phase Bus Duct (Iso-Phase) is used to connect the high voltage and high current output of the generator to transformers that either transform the voltage higher for the transmission of the power over the utility transmission grid or steps the voltage down for use in the station. The picture below shows a section of Iso-Phase Bus where it is connects to an auxiliary transformer. Gary W. Castleberry Page 7 of 16
8 The sketch below shows a cross section of this equipment. The Isolated Phase Bus Duct is comprised of large aluminum tubes approximately 18 inches in diameter. The tubes form a protective enclosure to house the actual energized bus bar which is mounted on insulators. Each Gary W. Castleberry Page 8 of 16
9 phase of the three phase system is isolated from the other two phases. This isolation minimizes the possibility of a short circuit (fault) involving all three phases. The bus bars are constructed out of a tubular material that is usually aluminum. The shape may be a square tube as shown or a round tube shape. The isolated bus duct and supporting structure is custom designed for each installation. The inner and outer tubes have field welded connections with expansion joints that allow for the thermal expansion and contraction of both the conductors and housing tubes. Large ampacity bus ducts have cooling systems that circulate cooling air through the tubes to remove heat from the I 2 R losses. 3. Step-up transformer The Step-up transformer transforms the voltage from the generator to a higher voltage necessary for the transmission of the generator s power over the utility s electric grid (transmission network). These large power transformers come in two basic configurations: Single three phase transformer or three single phase individual transformers. The photo below shows one of the three single phase transformers at a generating station. Gary W. Castleberry Page 9 of 16
10 Utilities were forced to use single phase transformers for step-up transformer applications as the size of the generators grew. Manufacturers of transformers were limited by the size of a transformer that could be shipped by the railroads. Once this limit was reached, single phase transformers were the only economically option for increase the size of transformer. As the practice grew, utilities grasped the benefit of this configuration because a spare single phase transformer provided economically backup protection for a transformer failure. Gary W. Castleberry Page 10 of 16
11 4. Station Startup Transformer The Station Startup Transformer is a power transformer used to connect the power station to the transmission system so that power is available for the plant equipment when the plant is being started. Power plants are routinely brought down for servicing of major pieces of equipment or when the demand for power is low such as in the spring and fall. This transformer provides the so called Startup power. The Start-up transformer is also used when the plant is being shutdown to power the station equipment that operates regardless of whether the plant is producing power. Finally, the Start-up transformer is used when ever the Station Auxiliary Transformer is un-available such as planned maintenance or repair. Power plants usually have a transmission substation close to the plant. Here several transmission lines, sometimes at different voltages, come together and a line will be brought to the plant startup transformer for startup power. The transformer shown in the one-line diagram is a three winding transformer. The purpose of the three windings is discussed in the next article on Unit Auxiliary Transformers. The photo below shows a typical startup transformer. Gary W. Castleberry Page 11 of 16
12 5. Station or Unit Auxiliary Transformer The Station Auxiliary Transformer is connected to the generator output by a tap off of the Isolated Phase Bus Duct. The high voltage winding of the transformer is designed to match the generator output voltage which is 22,000 Volts or 22KV in this example. This particular transformer is shown as a three winding transformer. It has a primary winding and two separate secondary windings at different voltages. This allows the station to have two different voltage levels one at 6900 Volts or 6.9kV and the other at 4160 Volts or 4.16KV. The higher voltage afforded by the 6.9KV windings allows for the use of similar higher voltage motors for large pumps or fans. The higher voltage motors offer several advantage over 4.16KV motors such as higher starting torques and lower full load currents. This transformer and the station startup transformer have to be specified and connected in a configuration so that the output voltages will be in phase. The bus voltages need to be in phase so that live bus transfers can be facilitated. This is accomplished by the internal connections of the transformer phases, as specified, as either delta or wye connected. This will assure that the incoming voltage from the transmission line is in phase with the voltage from the generator (after being transformed by the auxiliary transformer). The Unit Auxiliary Transformer is the normal power source for the station equipment when the plant is operating. Once the generator is brought on line and is connected to the transmission grid, the station loads can be transferred from the Start-up transformer. This would normally be done by closing the feed breakers from the Auxiliary Transformer (the 1A-1 and!b- 1 Breakers on the A 6.9KV Bus) while the feed breakers from the Start-up Transformer (Breakers 1A-2 and 1B-2 in this example) are still closed. The two transformers are now operating in parallel. As soon as the Auxiliary feed breakers are closed the plant operators open the feed breakers from the Start-Up Transformer as parallel operation of the transformers is not a desired operating mode. This is because having two transformers connected to the switchgear provides two sources of fault current should a short circuit occur in the switchgear or downstream of the switchgear. The resulting total fault current may exceed the switchgear s short circuit rating and a catastrophic failure of the switchgear could occur. 6. Non-segregated Phase Bus Duct Non-segregated Phase Bus Duct (Non-seg Bus) is typically used to connect the station auxiliary transformers low voltage windings to the Gary W. Castleberry Page 12 of 16
13 station switchgear. Some stations use parallel runs of cable or more isolated phase bus duct in lieu of Non-seg Bus; however, the author s experience has been with Non-seg bus designs. The drawing below shows a cross section of Non-segregated Bus Duct. Non-seg bus duct is comprised of copper bus bars which are insulated (shown here with a blue insulation) and held in place with a support system made of fiberglass or some other non-conducting material. All three bus bars are surrounded by a grounded metal enclosure. Non-seg bus is custom designed for each installation. It is built in sections at the factory and bolted together in the plant. Insulating boots cover the bolted bus bars. The enclosure on each section is flanged so that each enclosure section can be bolted together. Once installed and tested, nonsegregated bus duct is a highly reliable component providing years of service with little maintenance required. 7. Medium Voltage Switchgear The 6.9KV and 4.16KV Buses shown in the one-line diagram represent the plant medium voltage switchgear. Switchgear refers to a line-up of equipment to house circuit breakers, protective relays and control wiring. The switchgear is completely enclosed in a metal structure that prevents individuals from coming in contact with the lethal voltages within this equipment. Switchgear is made up of a series of cubicles which are bolted together in a row. Each cubicle contains a rear section where the bus bars are located, a lower compartment where the circuit breaker resides, and an Gary W. Castleberry Page 13 of 16
14 upper compartment where the protective relays and breaker control wiring is located. Typically, the incoming or feed breakers are located on the ends of the switchgear line-up. As shown on the one-line diagram the pairs of switchgear can be connected together via tie breakers (one 6.9KV Bus A and B these are breakers 1A-6 and 1B-3). These breakers are normally open; however, in the event of a problem with the non-segregated bus duct or incoming feed breaker, the tie breakers can be closed and both buses energized on the same feed breaker. Each circuit breaker is mounted on a rack and the breaker is rolled or jacked into various positions such as all the way in which is the connected or in-service position, partially withdrawn which is the test position, and fully withdrawn which is the disconnected position. While in the test position, the circuit breaker can be operated but it is not connected to the live bus bars. This allows functional tests to be performed on the breaker. Each cubicle contains protective relays in the top portion. The type of relay varies depending upon the breaker application. Typically, each breaker will have as a minimum some type of over-current relay and ground fault relay. 8. Secondary Unit Substations Secondary Unit Substations (SUSs) are essentially a repeat of the configuration of the station auxiliary transformer and the Medium Voltage Switchgear but at a lower voltage. Breakers from one of the plant switchgear will feed a transformer (in the one-line diagram the feed breakers is the 2A-3 breaker on the 2A 4160 Volt Bus) that will reduce the voltage to 480 Volts. This transformer is an integral part of a line-up of 480 Volt Switchgear. Sometimes the Unit Substations are designed with a transformer at each end of the switchgear. These are referred to as double ended secondary unit substations. The configuration shown in the one-line above is single ended substations with tie breakers which provides essentially the same reliability as a double ended substation. Secondary Unit Substations are used to feed the large majority of components in a power plant by further distributing power to load centers, motor control centers, and battery chargers. In addition, medium range motors 200 to 300 horsepower are fed by individual 480 V SUS circuit breakers. 9. Motor Control Centers Gary W. Castleberry Page 14 of 16
15 Based upon shear numbers of components fed, Motor Control Centers feed to most components in the power plant. These include motor operators for valves, small to medium motors, lighting panels, receptacle power panels to name a few. Motor control centers are comprised of vertical sections of cubicles or buckets. Each bucket contains a molded case circuit breaker, motor starter, control transformer, control fuses and wiring. In the rear of the MCC buckets, vertical bus bars distribute power to the different buckets. The vertical sections of buckets are bolted together to form the MCC. Below is a picture of an outdoor Motor Control Center. Motor Control Centers are located throughout the power plant and are placed near groups of loads for convenience. Outdoor MCCs are located in an additional enclosure for weather protection. A door opens to reveal each vertical section as shown in the photo above. Glossary of Terms CT Current Transformer An instrument transformer that provides a fractional current value proportional to the current it is monitoring. Exciter - The exciter provides the DC current which is provided to the field windings of the generator. Gary W. Castleberry Page 15 of 16
16 Grounding Systems several different techniques of construction all related to personnel safety and the proper functioning of protective devices. Isolated Phase Bus Duct Bus bars on insulators, surround by a metal tube, that connect the output of the station generator to the step-up transformer low voltage bushing. Main Generator- Machine composed of the rotor, stator, and exciter that produces electricity by rotating a magnetic field through an armature winding. Medium Voltage Switchgear Motor Control Centers Modular electrical panels housing the breakers and controls for numerous motors. Non-seg Bus see Non-segregated Phase Bus Duct Non-segregated Phase Bus Duct equipment designed to conduct large amounts of current through insulated bus bars surrounded by a grounded metal enclosure PT Potential Transformer An instrument transformer that provides a fractional voltage value proportional to the voltage it is monitoring. Station or Unit Auxiliary Transformer the power transformer connected to the main generator output-used when the plant is operating Station Startup Transformer the power transformer connected to outside source of power used when the plant is starting up from cold conditions Secondary Unit Substations Low voltage switchgear with integral step down transformers Step-up transformer the transformer(s) that is connected to the generator output and transforms the voltage to transmission voltage levels SUT Start-up Transformer- the power transformer connected to outside source of power used when the plant is starting up from cold conditions UAT Unit Auxiliary Transformer - the power transformer connected to the main generator output-used when the plant is operating Conclusions This course has provided an overview of the major electrical distribution equipment in an electric generating power plant. The role of the generator, main transformers, medium voltage, and low voltage switchgear was explained. Although each power plant is different in its design, they are surprisingly very similar in their electrical distribution systems. Hopefully, this course has provided a sense of the magnitude of the scope in providing electricity to the consumer every day of the year. Gary W. Castleberry Page 16 of 16
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
DIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
Understanding the Alternator
http://www.autoshop101.com THIS AUTOMOTIVE SERIES ON ALTERNATORS HAS BEEN DEVELOPED BY KEVIN R. SULLIVAN PROFESSOR OF AUTOMOTIVE TECHNOLOGY AT SKYLINE COLLEGE SAN BRUNO, CALIFORNIA ALL RIGHTS RESERVED
The following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1
Basics of Electricity
Basics of Electricity Generator Theory PJM State & Member Training Dept. PJM 2014 8/6/2013 Objectives The student will be able to: Describe the process of electromagnetic induction Identify the major components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
Current Transformers Ratio / Polarity / Types
CT1 Current Ratio / Polarity / Types Application Current (CT s) are instrument transformers that are used to supply a reduced value of current to meters, protective relays, and other instruments. CT s
Module 1. Introduction. Version 2 EE IIT, Kharagpur
Module 1 Introduction Lesson 2 Generation, Transmission and Distribution of Electric Power an Overview Contents 2 Generation, transmission and distribution of electric power 2 2.1 Goals of the lesson...
DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.
DC Generators DC generators are widely used to produce a DC voltage. The amount of voltage produced depends on a variety of factors. EO 1.5 LIST the three conditions necessary to induce a voltage into
Siemens STEP 2000 Course Basics of Electrical Products
Siemens STEP 2000 Course Basics of Electrical Products It's easy to get in STEP! Download any course. Hint: Make sure you download all parts for each course and the test answer form. Complete each chapter
ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
Chen. Vibration Motor. Application note
Vibration Motor Application note Yangyi Chen April 4 th, 2013 1 Table of Contents Pages Executive Summary ---------------------------------------------------------------------------------------- 1 1. Table
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet
ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before
Welcome to Linear Controls Quarterly Training
Welcome to Linear Controls Quarterly Training Introduction to Power Generation Objectives Supply attendees with basic knowledge of power generators and voltage regulators and provide the fundamentals of
Electrical Systems - IQAN Digital Control System. IQAN Control System Components... 5.1.3
Section 5.1 Electrical Systems - IQAN Digital Control System IQAN Control System Components........................... 5.1.3 IQAN Operational Description: At Machine Startup.....................................
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings
Three-phase AC circuits
Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
Inverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
Three-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
Fusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Primary Electric Distribution for Industrial Plants
PDH Course E242 Primary Electric Distribution for Industrial Plants Adolph A. Biss, P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)
UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system
Principles and Working of DC and AC machines
BITS Pilani Dubai Campus Principles and Working of DC and AC machines Dr Jagadish Nayak Constructional features BITS Pilani Dubai Campus DC Generator A generator consists of a stationary portion called
Sample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
ELECTRICAL ENGINEERING Vol. III - Induction Motor and Self-Excited Induction Generator - Tze-Fun Chan
INDUCTION MOTOR AND SELFEXCITED INDUCTION GENERATOR TzeFun Chan The Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong, China Keywords: threephase induction motor, singlephase induction motor,
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.
Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional
Generic PCSR Sub-chapter 15.4 : Electrical Equipment
Form10/00 Document ID : GA91-9101-0101-15004 Document Number : EE-GDA-C284 Revision Number : A Generic Design Assessment Generic PCSR Sub-chapter 15.4 : Electrical Equipment Hitachi-GE Nuclear Energy,
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
Switchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS
UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS Automobile Electrical Structure 3.1 Introduction Objectives 3.2 Ignition System 3.3 Requirement of an Ignition System 3.4 Types of Ignition 3.4.1 Battery or Coil Ignition
RENEWABLE ENERGY SUBSTATIONS SOLAR PHOTOVOLTAIC AND WIND POWER. tgood.com. Energy. Fast.
RENEWABLE ENERGY SUBSTATIONS SOLAR PHOTOVOLTAIC AND WIND POWER tgood.com Energy. Fast. TGOOD is a world leading manufacturer of prefabricated renewable energy substations PRODUCT CONCEPT ENVIRONMENTAL
This is a Master s degree level apprenticeship which includes academic learning combined workplace learning and training.
Power Engineer Degree Apprenticeship The UK s energy sector is integral to the prosperity and stability of the UK economy as a whole, delivering an absolutely fundamental service for all its citizens.
The electrical energy produced at the gen
300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5
101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer
101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module
STUDY GUIDE: ELECTRICITY AND MAGNETISM
319 S. Naperville Road Wheaton, IL 60187 www.questionsgalore.net Phone: (630) 580-5735 E-Mail: [email protected] Fax: (630) 580-5765 STUDY GUIDE: ELECTRICITY AND MAGNETISM An atom is made of three
Cable/Conduit Conversion
Cable/Conduit Conversion Busway can be used in many applications where cable and conduit are more commonly used. The question arises, Why use busway instead of conventional cable and conduit? Benefits
Permanent Magnetic Generator Construction Manual
Permanent Magnetic Generator Construction Manual http://hojomotor.com Our Team Doing an On-site Assembly in Peru http://hojomotor.com Section 1) Introduction This manual describes how to build a 'permanent
Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP
Grid Interconnection & Contract Development Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Submittal Instructions Prior to submitting your application and
IRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
1. The diagram below represents magnetic lines of force within a region of space.
1. The diagram below represents magnetic lines of force within a region of space. 4. In which diagram below is the magnetic flux density at point P greatest? (1) (3) (2) (4) The magnetic field is strongest
Single-Phase AC Synchronous Generator
ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.
OVERCURRENT & EARTH FAULT RELAYS Objective: To study the protection of equipment and system by relays in conjunction with switchgear. Theory: The function of a relay is to detect abnormal conditions in
HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING
HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING There are several ways to wire multiple batteries to achieve the correct battery voltage or capacity for a particular DC
ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat -
Doc. : 08C00031_e Date : 10.02.2009 Page : 1 / 9 ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric - (Preliminary) Doc. : 08C00031_e
Lab 8: DC generators: shunt, series, and compounded.
Lab 8: DC generators: shunt, series, and compounded. Objective: to study the properties of DC generators under no-load and full-load conditions; to learn how to connect these generators; to obtain their
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
Powerformer chosen for Swedish combined heat and power plant
Powerformer chosen for Swedish combined heat and power plant Powerformer, a radically new type of generator developed by ABB, has been chosen for a combined heat and power plant in Eskilstuna, Sweden.
understanding medium frequency induction melting furnace and its components
understanding medium frequency induction melting furnace and its components 9 Spruce Street, Jersey City, NJ 07306 USA [email protected] INDUCTION MELTING FURNACE AND ITS COMPONENTS The purpose
CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR
47 CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR 4.1 INTRODUCTION This chapter deals with the design of 24 slots 8 poles, 48 slots 16 poles and 60 slots 16 poles brushless dc
EVANS ENTErprises, Inc.
EVANS ENTErprises, Inc. Since 1954 THE LEADER IN ELECTRO-MECHANICAL SALES, SERVICE AND INTERGRATION Our Mission Our purpose at Evans Enterprises is to serve customers by providing increased value of product
Unit 33 Three-Phase Motors
Unit 33 Three-Phase Motors Objectives: Discuss the operation of wound rotor motors. Discuss the operation of selsyn motors. Discuss the operation of synchronous motors. Determine the direction of rotation
DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR
1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
Emirates Aluminium starts up World s first fully integrated power distribution system from ABB
Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s
Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow
ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations
ELECTRODYNAMICS 05 AUGUST 2014
ELECTRODYNAMICS 05 AUGUST 2014 In this lesson we: Lesson Description Discuss the motor effect Discuss how generators and motors work. Summary The Motor Effect In order to realise the motor effect, the
Understanding Generator Ripple Waveforms
Understanding Generator Ripple Waveforms 2 Understanding Generator Ripple Waveforms Chapter Page Preliminary Information and Setup 3 Generator Theory 6 Generator Ripple Theory 15 Factors that Influence
The stable way. Synchronous condenser solutions. siemens.com/energy/facts
The stable way Synchronous condenser solutions siemens.com/energy/facts Bringing grids in line with new requirements Global climate change poses new challenges for power generation and transmission. Innovative
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6
Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of
PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP
PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection
HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.
*ADVANCED ELECTRIC GENERATOR & CONTROL FOR HIGH SPEED MICRO/MINI TURBINE BASED POWER SYSTEMS
*ADVANCED ELECTRIC GENERATOR & CONTROL FOR HIGH SPEED MICRO/MINI TURBINE BASED POWER SYSTEMS Jay Vaidya, President Electrodynamics Associates, Inc. 409 Eastbridge Drive, Oviedo, FL 32765 and Earl Gregory,
Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
A S Y N C H R O N O U S M O T O R S
ASYNCHRONOUS M O T O R S S E R I E S INDAR ASYNCHRONOUS MOTORS S E R I E S WHO WE ARE Indar Electric s trajectory is endorsed by the construction of thousands of motors for the different industrial sectors.
Chapter 22: Electric motors and electromagnetic induction
Chapter 22: Electric motors and electromagnetic induction The motor effect movement from electricity When a current is passed through a wire placed in a magnetic field a force is produced which acts on
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
NATIONAL CERTIFICATE (VOCATIONAL)
NATIONAL CERTIFICATE (VOCATIONAL) SUBJECT GUIDELINES ELECTRICAL PRINCIPLES AND PRACTICE NQF Level 4 September 2007 ELECTRICAL PRINCIPLES AND PRACTICE LEVEL 4 CONTENTS INTRODUCTION 1 DURATION AND TUITION
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING INDEX 1. Introduction 3 2. Objectives 3 3. Employment Opportunity 4 4. Course Structure 4 5. Entry Qualification 4 6. List
3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C
41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers
COMPUTER AIDED ELECTRICAL DRAWING (CAED) 10EE65
COMPUTER AIDED ELECTRICAL DRAWING (CAED) EE Winding Diagrams: (i) DC Winding diagrams (ii) AC Winding Diagrams Terminologies used in winding diagrams: Conductor: An individual piece of wire placed in the
This section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
Induction Motor Theory
PDHonline Course E176 (3 PDH) Induction Motor Theory Instructor: Jerry R. Bednarczyk, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
AC Motor Speed. n s = synchronous speed (in RPM), f = frequency (in Hz), and p = the number of poles
AC Induction Motors Simplest and most rugged electric motor Consists of wound stator and rotor assembly AC in the primary member (stator) induces current in the secondary member (rotor) Combined electromagnetic
261000 Medium Voltage Electrical Distribution
Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This
Electrical Engineering
Electrical Engineering Trust our people. R eady is a professional engineering firm with highlyqualified electrical and controls personnel focused on providing solutions to meet your specific needs. Ready
ABB Dedicated Products, Systems and Services for the Power Generation Industry
ABB Dedicated Products, Systems and Services for the Power Generation Industry ABB Now, More Than Ever, your Dependable and Focused Power Generation Partner It is estimated that the North American demand
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
Rotary Phase Converters
FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON
PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront
