Evaluating the Opportunity for DC Power in the Data Center
|
|
|
- Julius Fowler
- 9 years ago
- Views:
Transcription
1 A White Paper from the Experts in Business-Critical Continuity Evaluating the Opportunity for Power in the Data Center by Mark Murrill and B.J. Sonnenberg, Emerson Network Power
2 Summary With data center managers struggling to increase efficiency while maintaining or improving availability, every system in the data center is being evaluated in terms of its impact on these two critical requirements. The power system has proven to be one of the more difficult systems to optimize because efficiency and availability are often in conflict; the most efficient approach to critical power is rarely the most reliable. One solution to power system optimization that deserves serious consideration is power. Since utility AC power must ultimately be converted to for use by IT system components and because stored energy systems (batteries, flywheel, etc.) provide power for backup, a power architecture requires fewer total conversions from grid to chip, creating the opportunity to reduce costs and increase efficiency. A data center-optimized, row-based power protection system is now available to help data center operators take advantage of that opportunity. This system, combined with the availability of 48V -powered IT equipment from major manufacturers, makes power an ideal solution for small and midsize data centers seeking to optimize efficiency, reliability and scalability. Other applications include high-density equipment rows with a consistent footprint and pod-based data centers. As the leading provider of AC and power systems, Emerson Network Power is uniquely positioned to help organizations evaluate the suitability of power and determine whether a row-based infrastructure is appropriate for a given application. 2
3 Introduction The first decade of the twenty-first century was one of incredible growth and change for data centers. The demand for computing and storage capacity exploded, and many IT organizations struggled to deploy servers fast enough to meet the needs of their businesses. At the same time, the trend to consolidate data centers and centralize computing resources resulted in fewer opportunities for planned downtime while also increasing the cost of unplanned outages. Data center operators were able to meet the demand for increased compute capacity by deploying more powerful servers often in the same physical space as the servers being displaced creating a dramatic rise in data center power consumption and density. Between 2004 and 2009, power and heat density became top concerns among data center managers as they struggled to adapt to a 400 to 1,000 percent increase in rack density. The dramatic increase in data center energy consumption created both financial and environmental challenges. Energy costs, which once had been relatively inconsequential to overall IT management, became more significant as the rise in consumption was exacerbated by a steady and in some years significant increase in the cost of electricity. In addition, increased awareness of the role that power generation plays in atmospheric carbon dioxide levels prompted the U.S. EPA to investigate large energy consumers such as data centers. In 2007 the EPA presented a report to the U.S. Congress that included recommendations for reducing data center energy consumption. The industry responded with a new focus on energy efficiency and began implementing server virtualization, higherefficiency server power supplies, and new approaches to cooling. Yet, while significant progress has been made in some areas, the critical power system has yet to be fully optimized. While individual components have been improved, the overall system complexity is high, which can create inefficiency and add operational risk. Faced with the choice of increasing system efficiency or adding risk, many continue to choose proven approaches that deliver high availability but do not deliver the highest efficiency. However, a close examination of the available options reveals that, in many cases, efficiency can be improved without sacrificing overall availability. Established Data Center Power Distribution Options Traditional AC power distribution systems in North America bring 480V AC power into a UPS, where it is converted to to charge batteries, and then inverted back to AC. The power is then stepped down to 208V within the distribution system () for delivery to the IT equipment. The power supplies in the IT equipment convert the power back to and step it down to lower voltages that are consumed by processors, memory and storage [Figure 1]. Double Conversion UPS 480V AC 480V AC 208V AC Rectifier AC 12V Transformer Figure Typical 480V 480V AC to 208V AC to AC 208V data center AC data power center system power configuration. system configuration. 3 Double Conversion UPS
4 In recent years, manufacturers have increased component efficiencies and developed new operating modes, such as the eco-mode available on some UPS systems, to improve efficiency. Figure 2 shows AC UPS operation when in eco-mode. Efficiency is improved by bypassing the conversion in the inverter; however, this introduces the potential for reduced system reliability. Critical loads are no longer isolated from the mains or subject to the tight voltage regulation Double Conversion normally provided by the inverter, and UPS complex synchronization circuits are needed to ensure reliable power transfer. In the event of a power interruption, a switching function is required to bring the load back on to the inverter, and mains need to be quickly isolated to prevent power feedback into the distribution system. No matter how fast or reliably this switching occurs, there is still a chance it will fail when it is needed most. There has been discussion in the industry about simplifying the AC distribution scheme by eliminating the step-down in the power distribution unit and delivering higher voltages to the IT equipment. One example, illustrated in Figure 3, takes 277V AC output from the UPS and delivers it directly to the server power supply. This approach Transformer may have potential in the future but is not viable today for a number of reasons. First, by connecting loads phase-to-neutral, additional harmonic currents may be introduced, offsetting some of the anticipated efficiency gains. Second, because of the elevated voltages at the rack, arc flash concerns for IT personnel working in the rack will increase. Finally, there are no commercially available power supplies at this input level. All in all, this architecture needs further development before it can be considered a true alternative. Consequently, 48V power may prove to be the best alternative to 480V/208V AC power distribution for organizations seeking to optimize reliability and efficiency today. 480V AC 480V AC 208V AC Rectifier AC 12V Figure 1. Typical 480V AC to 208V AC data center power system configuration. Double Conversion UPS 480V AC 480V AC Rectifier 208V AC 12V AC Transformer Figure In In eco-mode, incoming incoming power bypasses power the bypasses inverter to the increase inverter UPS system to increase efficiency. UPS system efficiency. Double Conversion UPS 480V AC 480V/277V AC 277V AC 12V Rectifier AC Figure V 480V AC to AC 277V to 277V AC data AC center data power center system power configuration. system configuration. Switch 4
5 480V AC Rectifier 480V AC Rectifier Transformer 208V AC AC 12V Transformer Figure 1. Typical 480V AC to 208V AC data center power system configuration. Figure 1. Typical 480V AC to 208V AC data center power system configuration. Double Conversion UPS A Practical Approach Double to Conversion in the UPSData Center Historical Background Today, telephone central offices -48V power supplies at the point of use. The 48V 480V ACpower has a long history in telecommunication networks. It is inherently These facilities exhibit levels of availability 12V and lower voltages for internal uses. (exchanges) are 480V still AC powered by -48V. 208V ACpower supplies 12V Rectifier AC step the voltage down to 480V AC 480V AC Transformer 208V AC 12V Rectifier AC Transformer simple and reliable with few conversion as high as 9-nines, as confirmed in a study It is easy to see the benefits of this stages to the point of use. In Alexander of 23,000 power systems over 10 years approach when applied to the data center. Graham Bell s day, 48V was chosen as by NTT Facilities 1. Downstream of the AC/ rectifiers, the the Figure standard 2. In eco-mode, for two incoming reasons: power bypasses the inverter to increase In most UPS telecommunications system efficiency. installations, the Figure 2. In eco-mode, incoming power bypasses the inverter to increase UPS system efficiency. power is completely isolated from the 1. power was felt to be more reliable 48V power system is deployed as three mains and is considered safety extra low than AC because it could be directly distinct elements as shown in Figure 4: voltage (SELV) per IEC/UL and can connected to backup Double batteries Double Conversion during Conversion UPS V AC to -48V modular be maintained live by trained personnel. UPS grid outages; power system In addition, there is no need to derate 2. 48V was considered the optimal 2. banks for extended capacity to account for phase balancing or run time tradeoff between transmission harmonics, which are not a factor with 480V AC (at least 480V/277V 8 hours) AC 277V AC 12V 480V AC Rectifier 480V/277V AC 277V AC AC distance and human 12V Rectifier safety because power. Personnel AC safety is also improved 3. distribution cabinets (BDFB/) it is considered safe to touch during when servicing equipment in the rack maintenance or accidental exposure. These elements are connected with large because arc flash is not a concern at -48V. copper bus bars and wires routed around However, unlike telecommunications central offices, data centers are not designed the facility to distribute power directly to Figure V AC to 277V AC data center power system configuration. Figure V AC to 277V AC data center power system configuration. with large copper bus bars to distribute power to racks. Fortunately, with new row-based topologies, these large Switch Switch copper runs are no longer necessary. In this row-based configuration, power is converted from AC to very close to 480V AC Rectifiers 48V 48V 12V 480V AC Rectifiers (N+m) 48V 48V 12V the point of use, which decreases the (N+m) conductor size and cost [see Figure 5]. Figure V power power as typically as typically implemented implemented in telecommunications in telecommunications central offices. Figure V power as typically implemented in telecommunications central offices. central offices. Row-Based Row-Based UPS UPS 480V AC Rectifiers 48V 12V 480V AC Rectifiers (N+m) 48V 12V (N+m) Data centers are entering a new stage of maturity where the emphasis is on reliably delivering more computing capacity to the organization at lower cost and with reduced power consumption. Row-based power represents a practical and affordable solution for reducing data center complexity, increasing efficiency and enabling growth. Figure 5. row-based UPS minimizes the amount of copper and floor space required for installation in the data center. Figure 5. A row-based UPS minimizes the amount of copper and floor space required for installation in the data center. Figure 5. A row-based UPS eliminates the long copper runs and is optimized for the data center. 5
6 Factors Affecting Power Distribution Selection When selecting an optimal power architecture for a particular facility, the number of factors data center designers and managers have to consider is substantial. Understanding the impact of each factor is essential to making an informed choice for your data center. Efficiency End-to-end power system efficiency can be difficult and time consuming to accurately calculate due to the complexity of variables involved, but it is still useful to consider and approximate efficiency based on specific site conditions and priorities. In light of recent improvements in the efficiency of both AC and architectures, two vendor-neutral studies have been published by The Green Grid and Intel to provide an objective, yet simplified, comparison of the efficiency of various power system configurations. The results from The Green Grid s study, Quantitative Efficiency Analysis of Power Distribution Configurations for Data Centers 2, for the power architectures discussed here, evaluated at 50 percent operating load, are summarized below: 480V AC to 208V AC (legacy): 63 percent efficient [Figure 1] 480V AC to 208V AC (current): 88 percent efficient [Figure 1] 480V AC to 277V AC: 89 percent efficient [Figure 3] 480V AC to 48V : 90 percent efficient [Figures 4 & 5] Intel conducted a similar analysis, Evaluation of 400V Distribution in Telco and Data Centers to Improve Energy Efficiency 3 and found that the highest overall system efficiencies are achieved with a 400V system; however, this technology is not yet commercially available. Overall, this study concluded that power (both 400V and 48V) was consistently more efficient than AC at all voltages. Intel concluded that power (both 400V and 48V) was consistently more efficient than AC at all voltages. While each study created scenarios that allowed for direct comparison of different configurations, many aspects of the power distribution system are complex and vary by application, making general comparisons difficult. Aspects which were not considered in either study include the degree of desired redundancy, the impact of harmonics and load variations, and the added load on cooling created by inefficient systems. In cases where these factors are present, the gaps between and AC would likely be wider, as the following analysis reveals. Redundancy The degree of redundancy in the power distribution system can impact both availability and efficiency. In the case of AC power distribution, these two factors may be mutually exclusive greater redundancy increases availability but lowers overall efficiency. The highest availability is achieved through 2N redundancy in which each UPS module is designed to run at no more than 50 percent load. However, since the data center is rarely operating at peak capacities, the redundant systems are almost always operating at less than 50 percent capacity. With derating, maximum capacity may be closer to 40 percent, and, in normal operation, each unit may operate at 20 percent load or less. Most equipment efficiency curves drop dramatically below 30 percent load, resulting in actual operating efficiencies significantly less than ideal conditions. In the case of power, redundancy can be seamlessly integrated into the UPS. In addition, Emerson Network Power offers an efficiency-optimizing feature that maintains near-peak efficiencies at system loads as low as 5%, allowing the system to achieve both high availability and efficiency in real world conditions. Harmonics Harmonics are a distortion of the normal AC waveform generally transmitted by non-linear loads. In the data center, the switch-mode power supplies used in AC servers represent a non-linear load that can create harmonics. Harmonic currents accumulate in the neutral wire, causing distribution losses and increased heat generation. If the cumulative level of harmonics known as total harmonic distortion becomes too high, damage to sensitive electronics and reduced efficiency can result and may require equipment derating to overcome. These losses are difficult to predict in complex AC distribution systems, but could be quite significant. Harmonics are not present in systems because there are no waveforms to contend with. Data Center Variations Many data centers are operating at significantly less than 100 percent of design load much of the time, with real-time loads changing frequently. This variation further complicates efficiency modeling. As servers are turned on/off and utilized at different rates, the loading on each phase of a 3-phase power system changes, making alignment between the three phases difficult. Unbalanced loads lower total system efficiency and produce additional heat. 6
7 In the white paper Phase Balancing: The Last Few Inches of a High- Efficiency Power System 4, Technology analyzes the impact of unbalanced loads on a 30A, 240/415V 3-phase circuit loaded in a Wye configuration. If the load is balanced, the current through each input phase is 8A, and losses can be calculated at 19 watts per 100 feet of cable. In the most unbalanced case, current through one phase is 24A and losses escalate to 115 watts per 100 feet of cable. This shows that power loss and heat generated in feeder cables can increase by as much as 600 percent because of unbalanced loads. Additionally, keeping track of which base loads are on which phase can be time consuming and tedious depending on the sophistication of the site and the tools available. balancing issues are also specific to three-phase AC power and are not a concern with. Power-Related Heat s After the IT equipment itself, the cooling system is the next largest user of power in the data center. Not only is cooling required for the heat generated from the IT equipment, but it also must offset the heat generated by power conversion losses. With fewer required conversions and greater overall efficiencies, a power system generates less heat than an AC system, reducing data center cooling energy consumption. As a rule of thumb, each watt of heat generation removed from the data center leads to an additional 1.4 to 2 watts saved in cooling. Availability Both AC and power systems can be designed to achieve high availability. The highest availability facilities will likely continue to use 2N redundancy because of its ability to support a dual-bus architecture that can eliminate downtime from system failures across the entire power distribution chain. However, that availability comes with a cost, both in terms of upfront equipment and ongoing operating efficiencies. Many organizations can achieve desired levels of availability from N +1 redundancy in which redundancy is maintained at the module level. At the system level, there are two ways that power systems offer high availability. First, the power conversion system has fewer components than a comparable AC system, which contributes to a higher mean time between failure (MTBF) rate and more uptime. In addition, the UPS uses an array of discrete rectifiers to deliver conditioned, isolated power to a distribution bus. These rectifiers provide built-in redundancy; the system can accommodate the failure of any individual rectifier without immediately affecting performance or capacity. Individual rectifiers can be safely hot-swapped out in the field without impacting system operation, thus minimizing system mean-time-to-repair (MTTR), a major contributor to unavailability. Scalability With equipment and rack density rising steadily, the power system can become a constraint to growth. As a result, modular approaches to data center design and expansion are gaining in popularity as demonstrated by the trend toward containerized data centers. With a complete data center power and cooling infrastructure integrated into a fully enclosed container, these systems can be delivered to a site and quickly plugged into power, communications and chilled water systems to enable additional computing capacity. With its built-in redundancy and compact footprint, a UPS is an excellent solution for these applications. This same philosophy is also manifesting itself in the move toward row-based equipment, which enables modular expansion of existing facilities or support for high density rows. Both AC and UPS systems provide scalability in a row-based format, but the UPS has the benefit of built-in redundancy and will occupy at least 50 percent less floor space than a comparable row-based AC system. Cost The main purpose of the critical power system is to eliminate power-related downtime; any cost comparison should consider the level of availability required and the cost of downtime. In general, rowbased power applications will be less expensive to install, operate and maintain than a comparable AC system and will support redundancy levels of at least N + 1. Some savings may be offset by increased IT equipment costs in a system list prices for servers with power supplies can be up to 10 percent higher than the more common AC servers. These costs may be negotiable and should come down with the higher volumes that accompany increased adoption. Overall, a -based end-to-end power architecture can be as much as 30 percent less expensive than an AC system, depending on many of the factors above. 7
8 NetSure ITM Row-Based UPS The NetSure ITM is a data center-optimized row-based 48V UPS from Emerson Network Power. It is designed to support the move to higher efficiency, density and flexibility enabled by row-based power and cooling. Instead of deploying one large power plant, which would require power to be distributed across the facility, 480V AC power is delivered directly to the NetSure ITM, which then provides protected power to racks of 48V equipment in close proximity [Figure 6]. When additional racks of IT and communications equipment are required for data center growth, new UPS units can be added without disruption. The NetSure ITM integrates power conversion, battery backup and branch distribution into a compact, highly reliable power protection system. (12) individual AC/ power conversion units (PCUs) deliver 70kW per module of conditioned, isolated 48V power to an internal distribution bus that charges the batteries and distributes power directly to the IT or communications equipment. Backup time is 5-10 minutes at full load with the included 10 year-vrla batteries; traditional systems may be more appropriate if more than 60 minutes of backup is required. The system provides up to 22 branch circuits protected by 100A to 200A circuit breakers. Each branch is monitored in the controller for load and trip condition and is designed to support varying rack densities. Power distribution in the rack is provided by NetSure RDB Series zero-u distribution units that feature plug-and-play connectors for easy installation and tool-less maintenance [Figure 7]. Figure 6. The NetSure ITM is positioned within the row to provide power to multiple racks. This UPS comes pre-assembled and factory tested to simplify installation. The only field connections required are the AC input to the module and the output to loads. In addition, individual components are user replaceable and can be swapped out while the system is operating, allowing live maintenance without bypass or generator switchover. The NetSure ITM features an integrated control and monitoring system that provides data on input and output parameters (including branch circuit loads), as well as advanced Albér battery management. An Energy Optimization Mode featuring Intelligent Power Matching ensures nearpeak efficiency for loads down to 5 percent Figure 7. A zero-u power distribution unit provides power to 48V input loads. 8
9 by keeping a minimum number of PCUs near full load and putting the rest on standby with the ability to respond quickly to changing load conditions. Because it eliminates the need for large copper runs and offers the reliability and scalability inherent in power, the NetSure ITM is ideal for a variety of data center applications, including: Sites with an existing constrained power infrastructure or problems with harmonics Data centers seeking to optimize efficiency and availability while establishing a path for growth by using power in concert with existing AC systems Modular or pre-configured data center layouts High-density scalable blade deployments Conclusion Direct current is already a fundamental part of your IT infrastructure: critical loads consume power and all backup sources generate it. Furthermore, the electric grid distributes AC power. So, the question becomes, where is the optimal point at which to convert AC to power while providing suitable protection from outages? If the conversion occurs too early, power must be transported long distances, which requires large conductors to reduce losses. If it occurs too late, additional conversions are introduced into the process which may compromise efficiency and reliability and increase costs. In many applications, the ideal point for power conversion and energy storage is as close as possible to the load. A row-based, 48V UPS allows for optimal efficiency, reliability and flexibility in these data center environments. The NetSure ITM from Emerson Network Power, combined with the availability of -powered IT equipment from major manufacturers, makes 48V power a practical, efficient and cost-effective solution for managing the conversion from AC grid power to power required by IT equipment. The simplicity, efficiency and reliability inherent in the NetSure ITM system can reduce complexity and costs in a variety of applications and should be seriously considered for mid-size data centers and facilities with increasing capacity needs. References [1] Reliability Field Data of Power Systems. NTT Facilities. INTELEC [2] Quantitative Efficiency Analysis of Power Distribution Configurations for Data Centers. The Green Grid [3] Pratt, Annabelle et al. Evaluation of 400 V Distribution in Telco and Data Centers to Improve Energy Efficiency. Intel [4] Phase Balancing: The Last Few Inches of a High-Efficiency Power System. Technology
10 Emerson (NYSE:EMR), based in St. Louis, Missouri (USA), is a global leader in bringing technology and engineering together to provide innovative solutions for customers in industrial, commercial, and consumer markets through its network power, process management, industrial automation, climate technologies, and appliance and tools businesses. For more information, visit: Emerson.com. Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and power, precision cooling, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. For more information on Emerson Network Power s full suite of solutions specifically supporting the communications network infrastructure, visit: EmersonNetworkPower.com/EnergySystems. Learn more about the NetSure ITM UPS from Emerson at: EmersonNetworkPower.com/NetSureITM. This publication is issued to provide outline information only which (unless agreed by Emerson Network Power Energy Systems, North America, Inc. in writing) may not be used, applied or reproduced for any purpose or form part of any order or contract or be regarded as a representation relating to the products or services concerned. Emerson Network Power Energy Systems, North America, Inc. reserves the right to alter without notice the specification, design or conditions of supply of any product or service. Emerson, Emerson Network Power, Business-Critical Continuity and NetSure are trademarks of Emerson Electric Co. and/or one of its subsidiaries. Additionally, this brochure references the following company trademarks: NTT Facilities, The Green Grid, Intel and Technologies. Names of companies and products are trademarks or registered trademarks of the respective companies. Any questions regarding usage of trademark names should be directed to the original manufacturer. Emerson Network Power Energy Systems, North America 4350 Weaver Parkway, Warrenville, IL Toll Free: (USA and Canada) Telephone: Fax: Web: EmersonNetworkPower.com/EnergySystems Emerson Network Power. The global leader in enabling Business-Critical Continuity. AC Power Connectivity Power Embedded Computing Embedded Power Infrastructure Management & Monitoring Outside Plant Power Switching & Controls Precision Cooling EmersonNetworkPower.com Racks & Integrated Cabinets Services Surge Protection 2010 Emerson Network Power Energy Systems, North America, Inc. All rights reserved. Code: 124W-DATA / 1010
Qualitative Analysis of Power Distribution Configurations for Data Centers
Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,
Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime
Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime Containerized Infrastructure for Business-Critical Continuity Are you deploying a remote site faster than you can
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
NetSure DC Power Solutions with esure High-Efficiency Technology
NetSure DC Power Solutions with esure High-Efficiency Technology NetSure solutions with esure high-efficiency technology Our Efficiency Without Compromise promise Among the array of ever-changing challenges
Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM
Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity
SmartDesign Intelligent, Integrated Infrastructure For The Data Center. Solutions For Business-Critical Continuity
SmartDesign Intelligent, Integrated Infrastructure For The Data Center Solutions For Business-Critical Continuity Prepare Your Data Center For What s Next Efficiency. Availability. Capacity. Control. One
Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity
Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top
Applying Data Center Infrastructure Management in Collocation Data Centers
Applying Data Center Infrastructure Management in Collocation Data Centers Infrastructure Management & Monitoring for Business-Critical Continuity TM Applying Data Center Infrastructure Management (DCIM)
High-Efficiency AC Power Distribution for Data Centers
High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies
NetSure DC Power Solutions with esure High-Efficiency Technology. DC Power for Business-Critical Continuity TM
NetSure DC Power Solutions with esure High-Efficiency Technology DC Power for Business-Critical Continuity TM NetSure solutions with esure high-efficiency technology Our Efficiency Without Compromise promise
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Calculating Total Power Requirements for Data Centers
Calculating Total Power Requirements for Data Centers By Richard Sawyer White Paper #3 Executive Summary Part of data center planning and design is to align the power and cooling requirements of the IT
DC Power Solutions Overview. DC Power Solutions for EVERY Network Application.
DC Power Solutions Overview DC Power Solutions for EVERY Network Application. DC Power Solutions for Every Network Application Eaton recognizes the challenges that are unique to different customers applications.
Microsoft Technology Center: Philadelphia
A Customer Success from the Experts in Business-Critical Continuity TM. Background Microsoft Technology Center: Philadelphia Microsoft Technology Centers are collaborative, state-of-the-art facilities
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International
How To Make A Data Center More Efficient
IT Solutions for Business-Critical Continuity Emerson Network Power Data Center Infrastructure Many Needs. One Source. Emerson Network Power, a division of Emerson Electric Co., is a global company that
Server Technology, Inc.
Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill
Protecting Our Information, Protecting Our Resources
Solutions For Business-Critical Continuity Protecting Our Information, Protecting Our Resources Energy Efficient Power And Cooling For IT And Telecommunications Network Infrastructures The Challenge You
Data Center Trend: Distributed Power in the White Space
Data Center Trend: Distributed Power in the White Space By Jason Anderson Product Line Manager Eaton Executive summary Cloud computing vendors and colocation data centers make every effort to maximize
Alternative data center power
Alternative data center power A quantitative TCO comparison of 400V AC and 600V AC power systems Abstract Power efficiency has become a critical focus for IT and facilities managers as they struggle to
How To Improve Energy Efficiency In Data Center Management
A White Paper from the Experts in Business-Critical Continuity TM Data Center Users Group Special Report Energy efficiency and capacity concerns increase Fall 2012 Survey Results Executive Summary The
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture By Neil Rasmussen White Paper #129 Executive Summary Significant improvements in efficiency, power density, power monitoring,
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International
Meeting the FCC Backup Power Mandate From Site Audit to Total Site Solutions. DC Power, Outside Plant & Services for Business-Critical Continuity
Meeting the FCC Backup Power Mandate From Site Audit to Total Site Solutions DC Power, Outside Plant & Services for Business-Critical Continuity Integrated Backup Power Solutions to increase your network
Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency
Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency Infrastructure Management & Monitoring for Business-Critical Continuity TM DATA CENTER INFRASTRUCTURE MANAGEMENT
Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring
Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring A White Paper from the Experts in Business-Critical Continuity Summary The first decade of the 21st century
Secure, Remote Access for IT Infrastructure Management
Infrastructure Management & Monitoring for Business-Critical Continuity TM Secure, Remote Access for IT Infrastructure Management ACS Advanced Console Server Secure, Remote Access for IT Infrastructure
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture White Paper 129 Revision 1 by Neil Rasmussen > Executive summary Significant improvements in efficiency, power density,
Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications
W H I T E P A P E R Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications Executive Summary One of the fundamental decisions in the design of data centers, server rooms
Radware ADC-VX Solution. The Agility of Virtual; The Predictability of Physical
Radware ADC-VX Solution The Agility of Virtual; The Predictability of Physical Table of Contents General... 3 Virtualization and consolidation trends in the data centers... 3 How virtualization and consolidation
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen
An Uninterruptible Power Supply Topology to Manage the Arrival of Big Data Kenny Green
An Uninterruptible Power Supply Topology to Manage the Arrival of Big Data Kenny Green Biography Kenny Green is Technical Support Manager for Uninterruptible Power Supplies Ltd. He is a graduate of Imperial
Optimizing Power Distribution for High-Density Computing
Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive
Selecting a UPS Topology for your Data Center. by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions
Selecting a UPS Topology for your Data Center by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions Uninterruptible Power Supplies (UPS) are both reaching into new markets and expanding in new ways
Revolutionizing Data Center Infrastructure Management
Infrastructure Management & Monitoring for Business-Critical Continuity TM Revolutionizing Data Center Infrastructure Management The Trellis Platform A Real-Time Solution to Continuous Performance Improvement
Distributed versus centralized power backup strategies
Distributed versus centralized power backup strategies Choosing the right UPS deployment architecture for your data center By Ed Spears Product Manager, Eaton Power Quality Solutions Operation Eaton Corporation
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Liebert APM from 30-150 kw. The Compact Row-Based UPS With FlexPower Technology TM
Liebert APM from 30-150 kw The Compact Row-Based UPS With FlexPower Technology TM Emerson Network Power, a division of Emerson, is a global company that combines technology with design to supply innovative
Three-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
The Trellis Dynamic Infrastructure Optimization Platform
Infrastructure Management & Monitoring for Business-Critical Continuity TM The Trellis Dynamic Infrastructure Optimization Platform Delivering Confidence through Connection TM Is Your Data Center Operating
RagingWire Enterprise Solutions
Background Enterprise Solutions was founded in May 2000 to be an enterprise-class Managed Services Provider (emsp) that could provide and support colocated data center services for Fortune 1000 customers.
IT White Paper. N + 1 Become Too Many + 1?
IT White Paper Balancing Scalability and Reliability in the Critical Power system: When Does N + 1 Become Too Many + 1? Summary Uninterruptible Power Supply (UPS) protection can be delivered through a
Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability
Considerations for a Highly Available Intelligent Rack Power Distribution Unit A White Paper on Availability Introduction Data centers are currently undergoing a period of great change. Data center managers
Smart Data Center Solutions
Smart Data Center Solutions New Data Center Challenges Require New Solutions Data Center Architecture. Inside and Out. Data centers are mission-critical facilities. A silo-based approach to designing,
Reference Guide: SmartDesign Approach: Common Data Center Challenges:
Smart Solutions Reference Guide Solutions For Business-Critical Continuity 1100kW Tier 3 With High Density Design Intelligent, Integrated Infrastructure for the Data Center Reference Guide: 1100kW Tier
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity
Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry
Mitigating data center harmonics
Mitigating data center harmonics Patricia Matwijec Product Manager Eaton Ed Spears Product Marketing Manager Eaton Executive summary Line harmonics can have costly and disruptive effects on electrical
Is an energy-wasting data center draining your bottom line?
Abstract Is an energy-wasting data center draining your bottom line? New technology options and power distribution strategies can dramatically reduce the cost and carbon footprint of your data center.
PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions
PMCS Integrated Energy Management Solution Unlock the Full Potential of Power Networks Through Integration Power Management Control System (PMCS) is a highly customizable, fully integrated end-to-end Energy
How Microsoft Designs its Cloud-Scale Servers
How Microsoft Designs its Cloud-Scale Servers How Microsoft Designs its Cloud-Scale Servers Page 1 How Microsoft Designs its Cloud-Scale Servers How is cloud infrastructure server hardware design different
How To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
Unified Infrastructure Monitoring, Access and Control
A White Paper from the Experts in Business-Critical Continuity Unified Infrastructure Monitoring, Access and Control Streamline Infrastructure Management with a Single, Multi-Purpose Appliance the Avocent
Data Center Solutions
Data Center Solutions New Data Center Challenges Require New Solutions Data Center Architecture. Inside and Out. Data centers are mission-critical facilities. A silo-based approach to designing, deploying
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
Data Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert
Data Center Consolidation Trends & Solutions Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Agenda Traditional Data Centers Drivers of a Changing Environment Alternate
Server Technology Inc.
Server Technology Inc. Efficiency Gains with 480V/277V Power at the Cabinet Level White Paper STI-100-012 2011-May-2 Headquarters Server Technology, Inc. 1040 Sandhill Drive Reno, NV 89521 United States
Increased power protection with parallel UPS configurations
Increased power protection with parallel UPS configurations Making the selection between Centralized Bypass and Distributed Bypass systems Janne Paananen Application Engineer, Large Systems Group Eaton
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure White Paper 37 Revision 7 by Neil Rasmussen > Executive summary The physical infrastructure of data centers and network rooms
Galaxy VM. Three-phase power protection. schneider-electric.com
Galaxy VM Three-phase power protection schneider-electric.com 2 schneider-electric.com schneider-electric.com 3 Galaxy VM trusted partner for your business continuity Features and benefits Highly efficient,
DISTRIBUTED REDUNDANCY:
DISTRIBUTED REDUNDANCY: MAXIMUM AVAILABILITY AT MINIMAL COST A White Paper by: Liebert Corporation As the need for greater system availability intensifies across virtually every industry from global banking
Standardization and modularity as the foundation of data center UPS infrastructure
ABB White Paper Standardization and modularity as the foundation of data center UPS infrastructure - ABB Power Protection Product Group Doc name: Advantages of modular and standardized UPS Date: 19.11.2013
AC vs. DC Power Distribution for Data Centers
AC vs. DC Power Distribution for Data Centers White Paper 63 Revision 6 by Neil Rasmussen > Executive summary DC power distribution has been proposed as an alternative to AC power distribution in data
Measuring Energy Efficiency in a Data Center
The goals of the greening of the Data Center are to minimize energy consumption and reduce the emission of green house gases (carbon footprint) while maximizing IT performance. Energy efficiency metrics
NetXtend Flex Series Integrated Outdoor Enclosure Solution. Outside Plant for Business-Critical Continuity
NetXtend Flex Series Integrated Outdoor Enclosure Solution Outside Plant for Business-Critical Continuity Features & Benefits Full flexibility and scalability one enclosure for various telecommunication
Distributing Power to Blade Servers
Distributing Power to Blade Servers Ten steps to selecting the optimal power distribution design With the growth in blade servers with dual or triple power supplies, a single rack of equipment can easily
Common Access Card Application
Infrastructure Management & Monitoring for Business-Critical Continuity TM Common Access Card Application The introduction of smart cards and common access cards (CAC) can create real challenges in environments
Power protection for data centers
Power protection for data centers Power protection for data centers Data centers are major power users, with larger installations consuming tens of megawatts. As customers are often highly reliant on the
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS
IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS Executive Summary IT managers who are used to implementing power protection for IT network or data
Data centre experts. Advanced power protection for data centres
Data centre experts Advanced power protection for data centres A robust power protection strategy is critical to successful data centre operations. Uninterruptible Power Supplies Limited (UPSL), a Kohler
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center
A Comparison of AC and DC Power Distribution in the Data Center Transcript
A Comparison of AC and DC Power Distribution in the Data Center Transcript Slide 1 Welcome to the Data Center University course on the A Comparison of AC and DC Power Distribution in the Data Center. Slide
High Availability for Non-Traditional Discrete and Process Applications Ensuring Continuous Operations With Increased Controller Reliability
GE Intelligent Platforms High Availability for Non-Traditional Discrete and Process Applications Ensuring Continuous Operations With Increased Controller Reliability High Availability for Non-Traditional
NO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM
NO-BREAK KS 7e Concentrated Energy e 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM Data Centre owners, operators and designers are required to meet ever increasing and
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ 2011 Raritan Inc. Overview Data center managers are faced with increasingly challenging demands: supplying additional computing
Data Centre Solutions... energy efficient by design. APC by Schneider Electric Elite Data Centre Partner. APC s leading Elite Data Centre Solutions
Data Centre Solutions... energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration
CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers
CEMEP UPS The high environmental performance solution for power supply to high-availability data centers Exchanges of information and communication needs are growing at an exponential rate. That growth
The Different Types of UPS Systems
White Paper 1 Revision 7 by Neil Rasmussen > Executive summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics. Each of these UPS types is
The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity
The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
Power to the adaptable data center
Business Unit Manager, Data Center Solutions, Eaton s electrical group IT managers have more options than ever to tailor the power infrastructure to their unique data center and business requirements.
The Different Types of UPS Systems
The Different Types of UPS Systems By Neil Rasmussen White Paper #1 Revision 5 Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics.
Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth
Applying Proper Cable Management In IT Racks A Guide For Planning, Deployment And Growth Integrated Cabinet Solutions For Business-Critical Continuity Why Proper Cable Management Is So Important Your rack