BATTERY AND SUBSYSTEM ELEMENTS OF A HVDC SYSTEM FOR THE TELECOMMUNICATIONS AND DATA NETWORKS. FIRST, DO NO HARM.
|
|
|
- Ethel Greene
- 10 years ago
- Views:
Transcription
1 BATTERY AND SUBSYSTEM ELEMENTS OF A HVDC SYSTEM FOR THE TELECOMMUNICATIONS AND DATA NETWORKS. FIRST, DO NO HARM. Dan McMenamin William Cantor, P.E. Phillip Zakielarz Thomas Flores Dan McMenamin and Test Products Inc. Test Products Inc. Verizon Wireless Associates (TPI) (TPI) INTRODUCTION Traditional telecommunications facilities and data centers both rely on dc battery systems to provide interruption free power to critical equipment. In the telecommunications world, lower voltage dc power is distributed directly to the equipment, while in data centers the loads typically require ac power. Over time, data center and telecommunication loads have become very similar, essentially computer based equipment. Since both telecommunications centers and data centers require high reliability, some have questioned why there are two distinct architectures. At the same time, both data center and telecommunications industries are examining higher voltage dc (HVDC) as an alternative means to distribute power. The concept of dc for data communications facilities is not a new one. The concept was discussed at length during INTELEC 97 in Melbourne Australia, and the first of many papers was published at INTELEC 98 in San Francisco, California (Åkerlund, et al) i ii. Recently, interest in higher voltage dc has expanded to include traditional telecommunications applications. While there are proven benefits to using HVDC, the practical implications are not all fully understood. Low voltage dc systems have been deployed for nearly a century during which time the reliability and safety of these systems has been proven. Traditional double conversion UPS systems have a large installed base where safety and reliability is well known. On the other hand, HVDC systems are still in their infancy and the architecture, voltage level and grounding schemes have not been standardized. There is arguably insufficient data to assess the reliability of distributed HVDC systems. This is not to state that HVDC systems are unreliable; there is just insufficient data to draw any conclusions at this time. This paper proposes an HVDC architecture designed with the intention of minimizing risk to operations and maintenance personnel, while maximizing the system uptime and reliability. Details on the selection process of the proposed design concepts will be included along with a comparison of the various considered options. PLANT ARCHITECTURE Due to the voltages anticipated, reliability would be enhanced and safety for maintenance workers improved dramatically if the HVDC plant could be deenergized for routine or unplanned maintenance. A 2N architecture can provides a high level of uptime availability and maintenance accessibility. Such a system might look like Figure 1. The load for such a system are the dual inputs of servers and the like that are equipped with power supplies suited for 384 Volt dc inputs. Each server would be cord-connected to a pair of secondary dc distribution modules, typically outlet strips arranged with receptacles designed for arc-flash resistant plugs. The bus between primary and secondary dc distribution could be a busduct arrangement or could employ traditional wiring methods in raceways suitable for the application. The battery for each plant would consist of two or more parallel strings of 180 Vented Lead Acid (VLA) or Valve Regulated Lead Acid (VRLA) cells. Ideally, the rectifiers would be of a modular type to facilitate growth and eliminate costs associated with over capacity. The rectifiers should operate with high efficiency across a broad range of output loading. 5-1
2 Figure 1 a 2N plant architecture for HVDC plant in critical applications BATTERY ISSUES Virtually all ac UPS and dc power plants use a storage battery, usually a lead acid battery of either the vented or the valve regulated technology. With a nominal voltage below 50 volts, traditional -48 volt battery systems have been placed in good stead with the various code articles that otherwise might require numerous protective devices such as disconnects and design constraints such as separation distances, etc. Arguably, HVDC systems will have to comply with all safety aspects of codes and standards that go far and above those required for -48 volt systems. Additionally, telephone company technicians, long accustomed to working around -48 volt power plants and batteries will need training and appropriate Personal Protective Equipment (PPE) adequate for the elevated shock and arc-flash hazards; otherwise, they have no legitimate authority to enter the battery room. Companies will need to determine whether they choose to train and equip their technicians accordingly or contract such work to properly trained and equipped electricians and/or battery technicians. With codes and standards as minimum requirements, we believe that there are relatively low-cost features and engineering guidelines that would make a HVDC battery system safer to install and maintain. Traditional ac UPS systems can employ an ungrounded battery system because ground for the servers or other load is provided by a separately derived neutral, either at the inverter section of the UPS, or downstream at the transformers housed in power distribution units (PDU). Because the battery is ungrounded, UPS systems typically use ground fault detection monitors to protect technicians servicing the battery, and identify situations where a second ground fault could precipitate a battery fire. Further, with an ungrounded battery, there is little risk for technicians who might come into contact between some energized part of the battery and the grounded battery stand. HVDC systems cannot use transformers, and other means of isolating the battery are encumbered with equipment costs and reduced system efficiency, so the entire system, including the battery, will be grounded. With a grounded battery installed on a grounded stand, or inside a grounded cabinet as might be the case of a VRLA battery, it is appropriate to reduce the battery voltage with respect to ground. One option, using a 180-cell battery, would be to arrange the cells into two 90-cell strings with a midpoint ground. This would reduce technician voltage exposure by half. Figure 2 is a sketch of such a topology. 5-2
3 Figure 2 A 2-pole disconnect switch is used to isolate a 180-cell battery into two 90-cell strings and remove the ground for system maintenance. One drawback of the design shown in Figure 2 is that when the battery disconnects are opened, the system may be left ungrounded. A more attractive approach is to use a floating battery, where the battery is implicitly grounded by arranging the rectifiers to be center-grounded between positive and negative 200V outputs (Figure 3). Figure 3 depicts a center-grounded 400V rectifier plant arrangement with a floating battery. 5-3
4 With this arrangement, a 400 volt ungrounded battery is connected to the plant via fused safety switches or other overcurrent protection with auxiliary contacts used to signal the plant controller and/or the alarm system that the battery is disconnected. The reason for this alarm event is that occasionally, battery technicians actually forget to reconnect the battery leaving the plant vulnerable to failure. During battery maintenance the OSHA Lockout/Tagout iii procedure covered in 29 CFR should be followed. This arrangement is not considered a single point of failure because the overall topology is based on at least two battery strings per plant and a 2N plant architecture as was covered previously and in Figure 1. Although traditional metallic grounded battery stands have been used successfully for low voltage dc systems and ungrounded high voltage systems, they may be problematic with high voltage grounded systems. Batteries that develop small leaks can create a path to ground via conductive electrolyte. For ungrounded battery systems these ground paths can be detected by a ground fault detector. Even on low voltage systems it is possible for these types of ground paths to cause fires and/or thermal runaway, but likely due to the lower voltage to ground, the issues are not wide spread. With the higher voltage dc systems, these potential paths to ground may quickly develop into serious issues. The other problem with building HVDC systems using traditional grounded metallic battery stands is that they introduce significant shock and arc-flash potential. Although the plan is to isolate the battery strings during routine maintenance, there may be times when the battery has to be worked on while energized. A potential fix to these issues is to use insulated and/or non-metallic battery stands. In the 1970 s Lucent Technologies (Formerly AT&T Network Systems/Western Electric Co.) and now called Lineage Power Division of General Electric designed a nonmetallic battery stand for their legendary KS Round Cell Battery. The battery stand was designated KS and it is a polyester-glass design intended for both non-shock/vibration areas and seismic area deployments. If facility space permits, and the battery loading will be a relatively low-rate discharge, the KS battery mounted on KS polyester-glass stands would provide a demonstrated long battery life iv and a nonconductive battery stand that enhances safety. Because this particular battery has a 40 to 70 year design life at 25 o C (77 o F), one could capitalize on that abundant life and reduce the facility air conditioning cost by operating the battery area as high as 35 o C (95 o F), and still yield a 20 year or more battery life. Figure 4 Lineage Power Round Cell battery cells on polyester-glass stands 5-4
5 The down side of the Round Cell is its high floor space requirements. If one must deploy rectangular cells for purposes of battery room density, are nonconductive stands still a possibility? HVDC might well create a market for a nonconductive battery stand that would support rectangular vented batteries. Figure 5 Approximate footprints of traditional Round Cells (top) on polyester-glass stands and a poly material stand that could be designed for rectangular vented battery cells (bottom). Figure 6 Side view of a rectangular vented cell arrangement on polyester-glass. One possibility is a polyester-glass system similar to that of the Lineage Power design. Basically, the stand might consist of bases that fasten together by means of keyed wedges. Vertical panels would provide support for a second or third tier and no conductive parts would be used. It remains to be seen whether or not such a stand would meet seismic zone 4 requirements. Regardless, there are many data centers and central offices in seismic zones 1 3, so the potential market for a battery stand with a limited seismic rating could still be substantial. 5-5
6 The existing polyester-glass system ships in small containers and assembles quickly with wedge keys that require no special tools or torquing of fasteners. The wells in which the cells sit are spaced so that there is no need to shove or pry cells back and forth on the battery stand to make the intercell connectors align. These advantageous features could be incorporated into an updated battery stand design. Alternatively, traditional seismic rated metal stands could be made nonconductive by the application of dielectric epoxy or similar product in place of powder-coat paint. Such a conformal coating would be both acid-resistant and provide an insulating barrier between the grounded battery stand and the energized parts of the battery cells and intercell connections. Figures 7, 8 and 9 provide sketches of a conformally coated battery stand arrangement. The grounding arrangement shown in Figure 9 is intended that the ground lead would be disconnected during battery maintenance further enhancing safety from shock or arc-flash event. Insulation dielectric should be determined from IEC60950 v. Using the general rule of thumb, 2U + 1,000V the appropriate dielectric for a 400V battery system would be 1,800 Volts. A potential problem with insulated or non-metallic racks is that there is an increased possibility of a static discharge when a technician touches a cell. With an increased possibility of a static discharge comes an increase possibility of igniting hydrogen gas emanating from the cell. Maintenance procedures would have to be carefully written as to minimize this increased risk. Spill containments should be provided for vented battery arrangements per local requirements. Figure 7 Side view of a rectangular vented cell arrangement on a conformal coated steel battery stand Covering all energized parts of the intercell connections and posts are a requirement under NFPA 70E and it s likely that a market could emerge for safer coverings for intercell to post connections. Transparent coverings are highly desirable, since they facilitate inspection for damage from electrolyte leakage or seepage. Figures 10 and 11 offer some thoughts on how such products might appear. To comply with fire resistance requirements, such insulating materials should be UL 94V-0 rated. 5-6
7 If cabinets are used to house VRLA cells, it is advantageous the interior of the cabinet have no exposed metal in the areas of the battery posts or intercell connections. Such surfaces should be lined with a GPO-3 non-tracking mineral filled, continuous strand, fiberglass-mat-reinforced thermoset unsaturated polyester material, such as the trade name Glastic or its equivalent. Cabling supports should be structural assemblies of similar material. The dielectric rating should be at least 1,800 volts. Figure 8 Insulating caps for all bolts or other conductive fasteners on a conformal coated steel battery stand Figure 9 Grounding arrangement and insulating cap for steel framework on a conformal coated steel battery stand 5-7
8 Figure 10 shows a cut to fit transparent insulating cover that would slide onto intercell connections. The dielectric rating should be at least 1,800 volts. Figure 11 shows covered intercell connector and cube shaped transparent battery post covers. The dielectric rating should be at least 1,800 volts. Monitoring is an important part of such a system, particularly if the battery reserve time is less than one hour. Because individual cell or jar monitoring is relatively cheap these days, it s prudent to provide such monitoring so that weak cells are quickly identified and corrected before they can contribute to a system failure. Cell voltage, per string current, total battery current and ambient temperature should be monitored. Further, if VRLA cells are deployed, the International Fire Code requires that Thermal Runaway conditions be detected and rectifiers backed down to prevent such conditions or other potentially catastrophic events either caused by elevated temperature or resulting in elevated battery temperature. Oddly, in the telecommunications business it is often the case that alarm events become mismanaged due to poor communication that results in technicians misinterpreting alarm events. Major failures have occurred when, for instance a BD (Battery on Discharge) alarm indication was interpreted to mean, Building on Diesel. Accordingly, given the relatively cheap cost of digital memory and display and the dramatically high cost of a system failure, alarm events should be spelled out and not be abbreviated. A Battery on Discharge alarm should read exactly that on any local display or remote monitor display at a surveillance center. A Discharge Fuse Alarm should read just that and so on for all alarm reporting events. 5-8
9 BATTERY MONITORING As is the case with any UPS, whether ac or dc, the overall uptime availability is only as reliable as the battery backing the system. A permanently wired battery monitor capability should be a requirement. Ideally, battery monitoring that is built into a manufacturer s HVDC product is prudent. If the feature isn t available, the ability to interface with a commercially available battery monitor should figure prominently in the overall design specification, particularly if the battery will be VRLA. The International Fire Code, Section requires that VRLA battery systems be equipped with a listed or approved means of preventing thermal runaway. Thermal runaway is best prevented by monitoring float current and temperature. If the HVDC plant controller isn t capable of meeting the IFC requirement internally, it should be arranged for an external Form-C contact open condition to cause the rectifiers to treat the event like an impending Thermal Runaway and reduce output. Additionally, monitoring cell or monobloc voltages should be a minimum requirement. Ideally, intercell resistance and cell Ohmic testing also is valuable. Finally, the battery system must be equipped for Ground Fault monitoring utilizing either a resistive bridge arrangement or a Current Summing type of detector vi. DISTRIBUTION Several dc distribution architectures are practical, cable bus architectures, busducts and the like. The industry has seen critical failures where through error, data center technicians have plugged both inputs of a dual power supply server into the same feeder of a redundant source. The fact that several manufacturers have developed suitable plugs and receptacles for 400 Volt applications provides a simple distribution architecture to solve that potential problem by using two different types of connector and cord as shown in Figure 12. Figure 12 shows a plug, cord and receptacle arrangement to improve network reliability. 5-9
10 EMERGENCY POWER OFF (EPO) Although shunt-trip devices were sketched into the battery disconnects shown in Figure 3, to EPO or not to EPO is a huge question that begs consideration across the telecommunication industry as Internet Protocol (IP) based systems expand almost limitlessly. From a standards viewpoint, three NFPA standards apply to the discussion. NFPA 75 vii Standard for the Protection of Information Technology Equipment clearly covers the data center environment in which an EPO is a requirement and also Article 645 of the National Electrical Code viii speaks to it as well. Telecommunications facilities fall under the purview of NFPA 76 ix Standard for the Fire Protection of Telecommunications Facilities. Important, is the fact that NFPA 76 does not require an EPO. With the wide proliferation of IP-based backhaul systems for telecommunications services wireless service in particular the nature of the data passing through the many routers, servers and other elements comprising the electronic fabric of a facility, is clearly telecommunications traffic. Article 1.1 of NFPA76 covers the scope and reads: Scope. This standard provides requirements for fire protection of telecommunications facilities where telecommunications services such as telephone (landline, wireless) transmission, data transmission, internet transmission, voice-over internet protocol (VoIP) transmission, and video transmission are rendered to the public. Accordingly, it s important that telecommunications companies make a clear distinction that although their facility might look like a data center and employ many of the same systems as a data center, it is in fact a telecommunications facility. Therefore, as a telecommunications facility it should cleave to NFPA 76 in order to protect the public safety aspects of telecommunications services. If an AHJ rejects that argument, an alternate approach to avoiding an EPO is to declare the facility a Critical Operations Data System under NEC Articles and provided that the five conditions in are met. These conditions include, an approved plan for equipment zone power and airflow depowering, 24/7 availability of qualified technical staff, smoke sensing fire detection, a fire suppression system, and proper use of plenum rated cabling in such spaces x. THE HIGH COST OF SAVING A BUCK If human altruism isn t enough to make us realize that the safety of those who install and maintain the systems we design is important, then the hard facts of business life in an increasingly regulated industry and litigious society should remind us that it also makes good business sense. Injuries and their related costs are very real Operational expenditures (Opex) that must factor mightily into the engineering judgment weighed as design plans roll out. Can HVDC save Opex and even perhaps some capital money? We think so. Would the cost of the first serious injury consume any savings realized? Probably. Accordingly, safety must be designed into the product and into all procedures for installing, operating and maintaining it. Any such deployment though, needs to bring safety to the drafting table first, and then to the power room. The principal elements of personnel safety rely heavily on: Reducing the voltages to ground to which a technician might be exposed Isolating the system to the extent practicable Providing adequate training, documentation and procedures to the technicians Providing appropriate tools and PPE and having a formal program in place to enforce their proper use Maintaining an attitude of professionalism in all aspects of the HVDC deployment and plant operation CONCLUSIONS HVDC shows promise lots of it. The keys to exploiting dollar savings from the technology include maximizing system efficiency across a varying load profile, good service life, system modularity, ease of site engineering and product ordering, cabling management, installation, operation and maintenance. Solid, reliable system documentation is important to avoid engineering and procedural errors, which remain a big problem in the industry and often lead to safety concerns. The extent to which the industry is able to deliver on all these factors and designed-in safety will determine whether in fact HVDC is a winning technology. 5-10
11 REFERENCES i Intelec Adhoc group, the INTELEC white paper, Powering the Internet, Datacom Equipment in Telecom Facilities, IEEE INTELEC 1998, Session 1-3. ii Case Studies Supporting -48VDC as the Power Input of Choice for Computer Equipment Deployed in the Telecom Network D. McMenamin INTELEC `98 Session 12-2 iii 29 CFR The Control of Hazardous Energy iv The Round Cell: Promises vs Results 30 Years later D.O. Feder et al INTELEC 2004 Session 23.2 v IEC60950 Safety Standard for Information Technology Equipment vi DC Ground Fault Detection Provided for Uninterruptible Power Supplies Edward P. Rafter, P. E. Battcon 2006 Session 5 vii NFPA 75 Standard for the Protection of Information Technology Equipment viii NFPA 70 National Electrical Code ix NFPA 76 Standard for the Fire Protection of Telecommunications x 2011 National Electrical Code Changes of Interest to Data/Comm Cabling Contractors, Users and Code Enforcement Officials - Stanley Kaufman, Ph.D. Communication Cable and Connectivity Association, Inc. ("CCCA") 5-11
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS
MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
Qualitative Analysis of Power Distribution Configurations for Data Centers
Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,
Powering the Data Center - Distributed 48Vdc is an Effective Choice. Dan McMenamin President Dan McMenamin and Associates, Inc.
Powering the Data Center - Distributed 48Vdc is an Effective Choice Dan McMenamin President Dan McMenamin and Associates, Inc. INTRODUCTION Effective management takes creativity. The engineer, as both
DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES
DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES Edward P. Rafter, P. E. Principal Tier IV Consulting Group Lee s Summit, Missouri 64064 INTRODUCTION There are concerns among owners
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
Errata NFPA 70. Proposed 2014 Edition
Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
Executive Summary. Technical Description
Executive Summary The Cellwatch system is built using modules. The majority of the system is constructed with Data Collection Modules (DCMs). The DCMs are optically linked to Control Units (CUs) that in
MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS
MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS Gary P. Guagliardi Director Sales & Marketing HindlePower, Inc. Easton, PA Introduction This paper explores the use of mobile DC power systems for three
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options
Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options By Stephen McCluer White Paper #30 Revision 11 Executive Summary The lead-acid battery is the predominant choice for Uninterruptible
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
Union County Public Schools. Facilities Department. Electrical. Safe Work Practices
1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County
Canadian Regulatory Compliance for Stationary Battery Systems North American Update
Canadian Regulatory Compliance for Stationary Battery Systems North American Update ComplianceKnowledgeCenter.com What is Compliance? In general: compliance means conforming to a rule, such as: a specification,
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity
Tel.X Ni-Cd battery. The compact solution for stationary applications
Tel.X NiCd battery The compact solution for stationary applications Tel.X, delivering highenergy performance in a compact maintenancefree package Tel.X: guaranteed power continuity for remote or hard to
SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC
Public Overview of the EMerge Alliance Data/Telecom Center Standard Version 1.0
of the EMerge Alliance Data/Telecom Center Standard Version 1.0 A standard defining low voltage dc power distribution system requirements for use in data centers and telecom central offices Excerpted With
Battery Technology for Data Centers and Network Rooms: Fire Safety Codes USA
Battery Technology for Data Centers and Network Rooms: Fire Safety Codes USA By Stephen McCluer White Paper #31 Revision 6 Executive Summary Fire safety regulations and their application to UPS battery
Mission Critical Data Center Systems
Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,
How To Plan Out An Array Of Solar Panels
CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a
Mixing Sodium and Lead Battery Technologies in Telecom Applications
Mixing Sodium and Lead Battery Technologies in Telecom Applications Paul Smith Shanon Kolasienski Technical Marketing Manager Application Engineer GE Critical Power GE Energy Storage Plano, TX 75074 Schenectady,
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers
9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade
Stationary Storage Battery Systems
ORANGE COUNTY FIRE AUTHORITY Planning & Development Services Section 1 Fire Authority Road, Building A Irvine, CA 92602 714-573-6100 www.ocfa.org Stationary Storage Battery Systems Guideline G-10 Date:
USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018
USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and
in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.
DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
Contractors Guide Central Inverter System Installation
Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.
UPS Applications and VRLA Battery Sizing
TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the
Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) Matthew Theriault Designer Hindle Power Inc. Easton, PA SCOPE AND PURPOSE OF THE PAPER Why do we bother to monitor
PORTABLE GENERATORS AND OSHA CONSTRUCTION REGULATIONS
PORTABLE GENERATORS AND OSHA CONSTRUCTION REGULATIONS Monograph by: John Grizzy Grzywacz, Professor OSHA National Training Institute Arlington Heights, Illinois Contributing: Michael Kovacic, President
Tel.X Ni-Cd battery. The compact maintenance-free solution for telecom networks
Tel.X Ni-Cd battery The compact maintenance-free solution for telecom networks Tel.X, delivering high-energy performance in a compact maintenance-free package Tel.X: guaranteed power continuity for remote
County of Riverside Building and Safety Department
County of Riverside Building and Safety Department Mike Lara Director Photovoltaic Permitting Guidelines The information provided in this document is general and is intended only as a guide. Each project
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
AC-DC Converter Application Guidelines
AC-DC Converter Application Guidelines 1. Foreword The following guidelines should be carefully read prior to converter use. Improper use may result in the risk of electric shock, damaging the converter,
User s Manual AURORA 1.2K/2.2K
User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable
Charging what can be more simple? SAE J1772
Charging what can be more simple? SAE J1772 Charging What Can Be More Simple? We charge our electronic devices everyday Laptops Cell phones PDAs Bluetooth devices Power tools MP3 players Toys Other Why
Understanding Arc Flash
Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which
DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
Co-location Interconnect Power Panel (CIPP) Installation Guide
Co-location Interconnect Power Panel (CIPP) Installation Guide Document INS-97xxxxxxx This guide covers the following part numbers- Trimm 97xxxxxxx Series Table of Contents Section 1 - General Information...
Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime
Containerized Infrastructure Solutions Fast and efficient deployment, anywhere, anytime Containerized Infrastructure for Business-Critical Continuity Are you deploying a remote site faster than you can
PITE 3921 Battery Monitoring System User Manual P-140606-V1.0
User Manual P-140606-V1.0 4/F, Bldg A, Chiwan Industrial Park, Shaodi Rd., Chiwan, Shekou Area, Shenzhen, China TEL: +86-755-2680 5759 FAX: +86-755-2688 0310 www.pitetech.com 1 Catalog 1. INTRODUCTION...
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS
Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity
Effects of AC Ripple Current on VRLA Battery Life A Technical Note from the Experts in Business-Critical Continuity Introduction Given the importance of battery life to UPS system users and the fact that
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
Power Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
What s up with Arc Flash?
What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition
Self Monitoring Power Supply (BPSM)
LIFETIME REPLACEMENT WARRANTY Self Monitoring Power Supply (BPSM) Application - When interfacing with a fire alarm system where the system s auxiliary relay cannot handle the full current potential of
ELECTRICAL SAFETY. The standard unit for measuring electrical current.
ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety
Solar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
SOLAR PV SYSTEM MAINTENANCE GUIDE
SOLAR PV SYSTEM MAINTENANCE GUIDE GUYANA HINTERLANDS STAND-ALONE SOLAR PV INSTALLATIONS IMPROVING HEALTH FACILITY INFRASTRUCTURE (IHFI) GUYANA CONTRACT NO. EPP-I-00-03-00008-00, TASK ORDER 07 APRIL 2013
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center
Data Center Commissioning: What you need to know
Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
Server Technology, Inc.
Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill
30-120 3 Phase Modular Finally the benefits of Modular ups are for all
MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS Paul A Zoubek, CSP, CIH Occupational Services, Inc. San Diego, CA 619-861 861-0612 [email protected] OCCUPATIONAL SERVICES, INC. BACKGROUND Update Update
Understanding Emergency Power Off (EPO)
Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
Specification Requirements DBL 700MX and 1000MX Series UPS
Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without
How to reduce exposure to arc flash hazards
GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not
Mike Holt s Illustrated Guide to. Rule 220.87, Articles 445, 700, 701, and 702. Based on the 2011 NEC
Mike Holt s Illustrated Guide to NEC Requirements for Generators and Standby Power Systems Rule 220.87, Articles 445, 700, 701, and 702 Based on the 2011 NEC Extracted from Mike Holt s Illustrated Guides
Arc Flash Energy Mitigation Techniques
Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal
Cabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
Video Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity
Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top
Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks
Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks White Paper Anil K. Trehan, Vice President, Energy Solutions CommScope, Inc. May 28, 2013 Contents
NOTE: Additional user information for your printer may be available in the "Manuals" section at support.dell.com.
CAUTION: General Safety Instructions Use the following safety guidelines to help ensure your own personal safety and to help protect your equipment and working environment from potential damage. NOTE:
Doe Residence - 5.64 kw DC Roof Mounted Photovoltaic System
EQUIPMENT SUMMARY 20 LG 300W solar panels 1 SMA SE6000AUS Inverter Everest Solar Systems Cross Rail Racking System QuickMount PV Quick Hook Curved Tile Mount QMCTH SHEET INDEX T01 COVER PV01 SITE MAP &
Arc Flash Avoidance and its Application to Overhead Traveling Cranes
Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles
Solar Photovoltaic (PV) Systems
ARTICLE 690 Solar Photovoltaic (PV) Systems INTRODUCTION TO ARTICLE 690 SOLAR PHOTOVOLTAIC (PV) SYSTEMS You ve seen, or maybe own, photocell-powered devices such as night lights, car coolers, and toys.
Dan McMenamin Dan McMenamin & Associates, Inc. [email protected]
What Does A Telco Need for 400 VDC To Find A Place In The Central Office 400 Volts: Even though the technology isn t quite here yet, it s not just for data centers anymore Dan McMenamin Dan McMenamin &
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Emergency Response. Prepared for Fire Service, Law Enforcement, Emergency Medical, and Professional Towing Personnel by American Honda Motor Co., Inc.
Emergency Response Guide 2013 Prepared for Fire Service, Law Enforcement, Emergency Medical, and Professional Towing Personnel by American Honda Motor Co., Inc. Introduction This guide has been prepared
ELECTRICAL EMERGENCY SYSTEM PLAN REVIEW OVERVIEW OF CODE REQUIREMENTS
ELECTRICAL EMERGENCY SYSTEM PLAN REVIEW What to Look for during Plan Review OVERVIEW OF CODE REQUIREMENTS First determine the type of emergency power system; is the system designed for Emergency or Legally
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems A. General This Net Metering Standard for Customer-Owned Grid Connected Electric Generating Systems sets forth the