SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
|
|
|
- Ada Hoover
- 10 years ago
- Views:
Transcription
1 PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting NFPA requirements for local, auxiliary, and remote station protective systems. 1.2 RELATED SECTIONS A. The WORK of the following Sections applies to the WORK of this Section. Other Sections of the specifications, not referenced below, shall also apply to the extent required for proper performance of this WORK. 1. Section Finish Hardware 2. Section Fume Hoods 3. Section Hydraulic Passenger Elevators 4. Section Fire Protection Piping 5. Section Wet-Pipe Sprinkler System 6. Section Air Handling and Moving Equipment 7. Section Air Distribution, Devices and Accessories 8 Section Basic Electrical Materials and Methods 1.3 CODES A. The WORK of the Section shall comply with the current editions, with revisions, of the following codes and City of San Diego Supplements: 1. Uniform Building Code 2. Uniform Fire Code 3. National Electrical Code 1.4 SPECIFICATIONS AND STANDARDS A. Except as otherwise indicated, the current editions of the following apply to the WORK of this Section: 1. NFPA 72A Installation, Maintenance, and Use of Local Protective Signaling System for Guard's Tour, Fire Alarm, and Supervisory Service. 2. NFPA 72B Installation, Maintenance, and use of Auxiliary Protective Signaling System for Fire Alarm Service. 3. NFPA 72C Installation, Maintenance, and Use of Remote Station Protective Signaling System. 4. NFPA 72E Automatic Fire Protectors. 5. NFPA 72G Notification Appliances for Protective Signaling Systems. 6. NFPA 72H Guide for Test Procedures for Protective Signaling Systems. [NOVEMBER 1997] [CONTRACT NO.]-[CONTRACT TITLE]
2 7. NFPA 101 Life Safety Code. 1.5 SHOP DRAWINGS AND SAMPLES A. The following shall be submitted in compliance with Section 01300: 1. Manufacturer's product data including catalogue cuts. 2. Block diagram showing system relationships of major components, quantities and interconnecting cables. 3. Plans showing locations of devices. 4. Connection details (typical) for each device. 5. Control panel factory wiring and field wiring terminations, devices, and special mounting details. 6. Initiating device circuit descriptions with programming. 7. Wiring diagrams showing terminal identification for field-installed wiring. 8. Manufacturer's certificate that system complies with indicated requirements. 9. Documentation of Fire Department approval of manufacturer and installer. 1.6 OWNER'S MANUAL A. The following shall be included in the OWNER'S MANUAL in compliance with Section 01300: 1. Operating instructions and maintenance and repair procedures. 2. Manufacturer representative's letter stating that system is operational. 1.7 QUALIFICATIONS A. Manufacturer: Company specializing in [smoke detection and] fire alarm systems and having Fire Department approval. B. Installer: Company specializing in [smoke detection and] fire alarm systems [certified by [the Fire Department] as fire alarm installing contractor.] 1.8 SERVICES OF MANUFACTURER A. Local Service: The manufacturer shall have a local service agency (within 50 miles of the site) which maintains properly trained personnel and adequate spare parts and is able to respond and complete repairs within 24 hours. 1. Demonstration: Operation of the fire alarm system shall be demonstrated to the CONSTRUCTION MANAGER to prove that the system operates and complies with this Specification. [CONTRACT NO.]-[CONTRACT TITLE]
3 PART 2 -- PRODUCTS 2.1 GENERAL A. The system shall: 1. Be [UL] [and] [FM] listed. [2. Conform to requirements of NFPA 101.] 2.2 SYSTEM DESCRIPTION A. The system shall comply with the following: 1. Fire Alarm System: [NFPA 72A;] [NFPA 72B;] [NFPA 72C;] [automatic] [and] [manual] fire alarm system. 2. System Supervision: System shall be electrically-supervised system, with supervised alarm initiating and alarm signaling circuits. Occurrence of single ground or open condition in initiating or signaling circuits shall place circuit in TROUBLE mode. Component or power supply failure shall place system in TROUBLE mode. [Occurrence of single ground or open condition on alarm initiating circuit shall not disable that circuit from transmitting in ALARM.] [Occurrence of single ground or open condition on signaling circuit shall not disable that circuit from transmitting in ALARM.] 3. Alarm Sequence of Operation: Actuation of [manual fire alarm station] [or] [automatic initiating device] shall cause system to enter ALARM, and shall include the following operations: Sound and display local fire alarm signaling devices with [non-coded] [zone-coded] signal. Transmit [non-coded] [zone-coded] signal to [municipal connection.] [and] [remote station equipment.] Indicate location of alarm zone on fire alarm control panel[.] [and on remote annunciator panel.] Transmit signal [by zone] to building smoke removal system. Transmit signals to building elevator control panel to initiate return to [main] [ ] floor. Transmit signal to building mechanical systems to initiate shutdown of fans and damper operation. Transmit signal to release door hold-open devices[.] [by zone.] 4. Alarm Reset: Key-accessible RESET function shall reset alarm system out of ALARM if alarm initiating circuits have cleared. 5. Trouble Sequence of Operation: System trouble, including grounding or open circuit of supervised circuits, or power or system failure shall cause system to enter TROUBLE mode and shall include the following operations: [CONTRACT NO.]-[CONTRACT TITLE]
4 Visual and audible trouble alarm [by zone] at control panel. Visual and audible trouble alarm at annunciator panel. Manual ACKNOWLEDGE function at control panel silences initiating trouble alarm; visual alarm is displayed until initiating trouble is cleared. [Transmit trouble signal to [municipal connection.] [remote station.] 6. Lamp Test: Manual LAMP TEST function shall cause alarm indication at each zone at fire alarm control panel[.] [and at annunciator panel.] 7. Drill Sequence of Operation: Manual DRILL function shall cause ALARM mode operation to: Sound and display local fire alarm signaling devices. Indicate location of alarm zone on fire alarm control panel[.] [and on remote annunciator panel.] 2.3 FIRE ALARM AND SMOKE DETECTION CONTROL PANEL A. The control panel shall include the following: 1. Control Panel: Modular construction with [flush] [surface] wall-mounted enclosure. 2. Power Supply: Designed to serve control panel modules, [remote detectors,] [remote annunciators,] [door holders,] [smoke dampers,] [relays,] [ ] and alarm signaling devices; [and including battery-operated emergency power supply with capacity for operating system in standby mode for [24] [60] [ ] hours followed by alarm mode for [5] [10] [ ] minutes.] [3. Detection Circuits: Supervised zone module with alarm and trouble indication.] 4. Signal Circuits: Supervised [zone coded] signal module, sufficient for signal devices connected to system. [5. Municipal Trip Circuit: With output connections for [future use.] [connection to [local energy] [shut trip] [parallel telephone circuit] municipal master fire alarm box.] [connection to remote station transmitter.] [and including municipal trip DISCONNECT switch.] 6. Remote Station Signal Transmitter: Electrically supervised, capable of transmitting alarm and trouble signals over telephone lines to remote station receive. [7. Remote Station Signal Receive: Electrically supervised, capable of receiving signals from remote station transmitter over telephone lines with up to [4000] [ ] ohms loop resistance, and visually annunciating alarm signals [by zone] and common trouble signal; and including circuit for remote audible alarm and trouble signal, accessory alarm and trouble relays with single pole, double throw (SPDT) contacts, and separate manual alarm and trouble SILENCE functions.] 8. Auxiliary Relays: With sufficient SPDT auxiliary relay contacts [for each detection zone] to provide accessory functions specified. [CONTRACT NO.]-[CONTRACT TITLE]
5 9. Switches: With TROUBLE ACKNOWLEDGE, DRILL, and ALARM SILENCE switch. 2.4 INITIATING DEVICES A. Initiating devices shall comply with the following: 1. Manual Station: [Semi-flush] [Surface] mounted, [single action] [double action] manual station with break-glass rod[,][.] [and auxiliary contacts for [operating remote annunciator.] [performing accessory functions indicated.] 2. Heat Detector: [Fixed temperature,] [Combination rate-of-rise and fixed temperature,] rated [135 degrees F][,][.] [ ] degrees F[,][.] [and temperature rate of rise of [15 degrees F.] [[ ] degrees F.]] 3. Ceiling Mounted Smoke Detector: NFPA 72E; [ionization type] [photoelectric type] with [adjustable sensitivity,] [plug-in base,] [auxiliary relay contact,] [integral thermal element rated 135 degrees F] [and] visual indication of detector actuation, suitable for mounting on 4-inch outlet box; [two-wire detector with common power supply and signal circuit] [four-wire detector with separate power supply and signal circuits]. 4. Duct Mounted Smoke Detector: NFPA 72E; [ionization type] [photoelectric type] with [auxiliary SPDT relay contact,] key-operated NORMAL-RESET-TEST switch, duct sampling tubes extending width of duct, and visual indication of detector actuation, in duct-mounted housing; [two-wire detector with common power supply and signal circuit] [four-wire detector with separate power supply and signal circuits]. 5. Water Flow Detector: Complying with Section [ ]. 6. Valve Supervisory Switch: Complying with Section [ ]. 7. Flame Detector: NFPA 72E; [ultraviolet] [infrared] radiation type. 8. Remote Test Switch: Key-operated switch mounted on flush cover with lamp to indicate detector actuation, [with one switch for each duct mounted smoke detector.] 2.5 SIGNALING DEVICES A. Signaling devices shall include: 1. Alarm Bells: NFPA 72G; electric [vibrating,] [single stroke,] [8] [10] [ ] inch bell with operating mechanism behind dome; sound rating of [81] [ ]db at 10 feet. [with integral [strobe] lamp and flasher with [red] [ ] lettered FIRE on [white] [ ] lens. 2. Alarm Lights: NFPA 72G; [strobe] lamp and flasher with [red] [ ] lettered FIRE on [white] [ ] lens. 3. Alarm Horn: NFPA 72G; [surface] [flush ] [projector] type firm alarm horn; sound rating: [87] [ ] db at 10 feet [with integral [strobe] lamp and flasher with [red] [ ] lettered FIRE on [white] [ ] lens.] 4. Remote Annunciator: [Supervised] remote annunciator including audible and visual indication of fire alarm by zone, and audible and visual indication of system trouble. Install in [flush] [surface] wall-mounted enclosure. [CONTRACT NO.]-[CONTRACT TITLE]
6 2.6 AUXILIARY DEVICES A. Auxiliary devices shall include: 1. Door Release: [Door closer complying with Section ] [.] [Magnetic door holder with integral diodes to reduce buzzing, [[24] [ ]VDC] [[120] [ ] VAC] coil voltage.] 2.7 FIRE ALARM WIRE AND CABLE A. Wire and cable shall comply with the following: 1. Fire Alarm Power Branch Circuits: Building wire complying with Section [ ]. 2. Initiating and Signal Circuits: [Building wire complying with Section [.] [Non-power limited fire-protective signaling cable, copper conductor, 150 volt insulation rated 60 degrees C.] [Power limited fire-protective signaling cable, copper conductor, 300 volts insulation rated 105 degrees C.] [ [Power limited fire-protective signaling cable classified for fire and smoke characteristics, copper conductor, 300 volts insulation rated 105 degrees C, suitable for use in air handling ducts, hollow spaces used as ducts, and plenums.] 2.8 SPARE PARTS A. The WORK of this Section includes the following spare parts: 1. [Ten] [ ] manual station break-glass rods. 2. [Two] [ ] keys of each type. 3. [Five] [ ] smoke detectors. 2.9 MANUFACTURERS A. Smoke Detectors: Smoke detectors, of the model indicated, shall be manufactured by one of the following (or equal): ADT [32521 Series] [3506] [ ] Pyrotronics Model ]DS-2] [PB-300] [ ] Simplex [4262-5] [ ] ESL [611U] [ ] B. Heat Detectors: Heat detectors, of the model indicated, shall be manufactured by one of the following (or equal): ADT [Model 4222] [ ] Pyrotronics [Model DT-200F] [135R] [ ] Simplex [4255] [ ] C. Manual Fire Alarm Stations: Manual fire alarm stations, of the model indicated, shall be manufactured by one of the following (or equal): ADT Model 5012 Pyrotronics Model MS-5 [CONTRACT NO.]-[CONTRACT TITLE]
7 D. Fire Alarm Control Panels: Panels shall be manufactured by one of the following (or equal): PART 3 -- EXECUTION 3.1 INSTALLATION ADT [Model ] Pyrotronics [Model ] [System 3] Simplex [Model ] ESL [Series 2000] A. General: System and products shall be installed in accordance with the manufacturer's written installation instructions and as follows: 1. Manual station installed with operating handle [54] [ ] inches above floor; and audible and visual signal devices installed [90] [ ] inches above floor. 2. With [16] [14] [ ]AWG minimum size conductors for fire alarm detection and signal circuit conductors; and wiring installed in [conduit.] [cable.] 3. With outlet box for electric door holder mounted to withstand 80 pounds pulling force. 4. With conduit and wiring connections to [door release devices,] [sprinkler flow switches,] [sprinkler valve tamper switches,] [fire suppression system control panel,] [duct smoke detectors,] [and] [.] 5. With automatic detector installation complying with NFPA 72E. 3.2 FIELD QUALITY CONTROL A. Systems shall be tested in accordance with [NFPA 72H][.] [and] [local fire department requirements.] B. The WORK of this Section includes the services of [certified] technician to supervise installation, adjustments, final connections, and system testing. 3.3 FIRE ALARM AND CABLE COLOR CODE A. Except as otherwise indicated or required by requirements of the City of San Diego Fire Department, fire alarm circuit conductors with color coded insulation, or color coded tape at each conductor termination and in each junction box shall comply with the following: 1. Power Branch Circuit Conductors: [Black, red, white.] [.] 2. Initiating Device Circuit: [Black, red.] [.] 3. Detector Power Supply: [Violet, brown.] [.] 4. Signal Device Circuit: [Blue (positive), white (negative).] [.] 5. Door Release: [Gray, gray.] [.] [CONTRACT NO.]-[CONTRACT TITLE]
8 6. Municipal Trip Circuit: [Orange, orange.] [.] 7. Municipal Fire Alarm Loop: [Black, white.] [.] ** END OF SECTION ** [CONTRACT NO.]-[CONTRACT TITLE]
SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Fire alarm and smoke detection systems. 1.2 REFERENCES 1.3 NFPA 72 1.4 NFPA 101 1.5 REGULATORY REQUIREMENTS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM
SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
C. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
DTW Works Master Specification Version 2006
Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
Module 5. Fire and Emergency Alarm System Part I- Basics
Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.
FIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
FIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
SECTION 16721 MULTI-FIRE ALARM SYSTEM
PART 1. GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification Sections, apply to this Section.
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM
KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
Module 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface
1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.
GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
A. This Standard outlines the requirements for an addressable fire detection and alarm system.
1.00 GENERAL 1.01 Scope: A. This Standard outlines the requirements for an addressable fire detection and alarm system. B. This Standard consists of all materials, equipment and services necessary and
B. NICET: National Institute for Certification in Engineering Technologies.
PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.
SECTION 16760 - PLANT INTERCOMMUNICATION SYSTEM. City of San Diego, CWP Guidelines
PART 1 - GENERAL SECTION 16760-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing plant intercommunication systems with power supplies, signal amplifiers,
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this
SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION
SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application
PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the
ENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
JULY 2013 UCB STANDARDS 16720-1
SECTION 16720 FIRE ALARM AND DETECTION SYSTEMS PART 1 GENERAL 1.01 Reference A. Related Sections 1. Section 15300 Fire Protection 2. Section 15950 Controls 3. Division 16 Electrical 4. Division 14 - Conveying
FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
FIRE DETECTION AND ALARM
FIRE DETECTION AND ALARM GENERAL INFORMATION 1.1 In general, follow the guidelines below when designing and specifying addressable fire alarm systems. Unless specifically indicated otherwise, these guidelines
Rancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
16720S01 - FIRE ALARM SYSTEM (HARDWIRED), MANUAL AND AUTOMATIC
1. GENERAL 1. Fire alarm system shall be manufactured by Simplex, Autocall or Edwards. Simplex part numbers are provided in this spec for clarification only and do not exclude equivalent part numbers of
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION
Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus
D287/D288/D292/D293A/D293E
D87/D88/D9/D9A/D9E EN Installation Guide Smoke Detector Bases D87/D88/D9/D9A/D9E Installation Guide.0 Overview.0 Overview The D87/D88/D9/D9A/D9E Smoke Detector Bases are designed for use with the D8 Ionization
University of Houston Master Construction Specifications Insert Project Name
SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT
SECTION 16610 FIRE DETECTION AND ALARM SYSTEM
SECTION 16610 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply
Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work
GE Security Small Building Life Safety Solutions Affordable FireShield Conventional Fire Alarm Control Panels imagination at work cost Location: Environment: Solution: Flower shop Finely decorated, gentle
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL
C. NICET: National Institute for Certification in Engineering Technologies. D. Definitions in NFPA 72 apply to fire alarm terms used in this Section.
SECTION 283100 - FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
A. This Section covers addressable fire alarm systems for wet and dry sprinkler systems, clean agent systems, and building fire alarms.
SECTION 283111 - PART 1 - GENERAL 1.1 SUMMARY A. This Section covers addressable fire alarm systems for wet and dry sprinkler systems, clean agent systems, and building fire alarms. 1.2 GENERAL REQUIREMENTS
University Design Standard. Fire Alarm Systems
University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
Release Control Fire Alarm Systems
SYSTEM ABORT PUSH AND HOLD COIL SUPERVISION MODULE (2 AMP) 2081-9046 RED INSTALLATION INSTRUCTIONS 574-437 REV YEL NAC+ MAINTAIN 1/4" SEPARATION BETWEEN POW ER LIMITED (RED/) AND NONPOWER S LIMITED (YEL/)
Engineer s Project Number: 298-1062 Section 28 31 00 Page 1 FIRE ALARM AND DETECTION SYSTEMS
Engineer s Project Number: 298-1062 Section 28 31 00 Page 1 SECTION 28 31 00 PART 1 GENERAL 01 SUMMARY A. This Section covers fire alarm systems, including initiating devices, notification appliances,
SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM
SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Fire alarm system requirements B. Fire alarm equipment C. Fire alarm peripheral devices 1.02 RELATED SECTIONS
Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?
5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,
SECTION 16700 FIRE ALARM SYSTEM
SECTION 16700 FIRE ALARM SYSTEM PART ONE: GENERAL 1.1 GENERAL REQUIREMENTS A. Definition of Work : This section of the specification includes the furnishing, installation, connection and testing of the
SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System with automatic detection and control. The work described in this
SECTION 16620 FIRE ALARM SYSTEM
SECTION 16620 PART 1 GENERAL FIRE ALARM SYSTEM 1.01 SUMMARY A. Work included: Labor, materials and equipment necessary to complete the installation required for the item specified under this Division,
Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015
Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 13860 (283100) FIRE ALARM SYSTEM The following standard shall be followed for the design of University
MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
PROJECT TITLE PROJECT NO: 0000000 CONTRACT TITLE GRANT NO: 0000000 UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA
Fire alarm--all types of occupancies. The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate
CBD-233. Fire Alarm and Detection Systems
Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually
SECTION 28 31 00 FIRE DETECTION AND ALARM
SECTION 28 31 00 PART 1 - GENERAL 1.1 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the fire alarm equipment to form a complete coordinated
1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
DUCT SMOKE DETECTOR D4120
Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation
FIRE ALARM AND DETECTION SYSTEM DESIGNS AND INSTALLATIONS
FIRE ALARM AND DETECTION SYSTEM DESIGNS AND INSTALLATIONS UNIVERSITY CONTACT: Bernie Alexander, Fire Protection Engineer, Occupational Health & Safety (302) 831-8475 Table of Contents: General...1 References/Required
Invitation to Bid FIRE ALARM & DETECTION SYSTEM
Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066
CAN/ULC-S524-06 Installation of Fire Alarm Systems Amendment 1. Canadian Fire Alarm Association (CFAA) D. GOODYEAR FIRE CONSULTING
CAN/ULC-S524-06 Installation of Fire Alarm Systems Amendment 1 Canadian Fire Alarm Association (CFAA) CAN/ULC-S524 AMENDMENT 1 PUBLISHED February 2011 WHY Clarifications New requirements (Technology changes)
SILENT KNIGHT MODEL 5207
SILENT KNIGHT MODEL 5207 Fire Control / Communicator Installation, Programming, and Operation Manual Part Number 150865 Rev. C, 04/03 Contents Section 1 Introduction.......................................................................1-1
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
FIRE DETECTION AND ALARM
Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-28 31 64.00 10 (August 2009) --------------------------------- Preparing Activity: USACE Superseding UFGS-28 31 64.00 10 (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS
EDWARDS SIGNAL SOLUTIONS www.edwards-signals.com DISTRIBUTED BY: Lee Dan Communications, Inc. www.leedan.com [email protected] Toll-Free: 800-231-1414
EDWARDS SIGNAL SOLUTIONS www.edwards-signals.com DISTRIBUTED BY: Lee Dan Communications, Inc. www.leedan.com [email protected] Toll-Free: 800-231-1414 Fire Alarm CONTROL S y s t e m s CONVENTIONAL FIRE ALARM
INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description
INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's
FIRE ALARM SYSTEM Section 16750 Page 1
FIRE ALARM SYSTEM Section 16750 Page 1 PART 1 - GENERAL 1.1 REQUIREMENTS A. Provide a complete operational, stand-alone local protective signaling system in each defined building as indicated on the contract
Security Systems Intrusion Alarm
Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted
FC-72 SERIES FIRE ALARM SYSTEM
FC-72 SERIES FIRE ALARM SYSTEM INSTRUCTION/OPERATING MANUAL Copyright 1988 Part Number: 9000-0007 Published in the U.S.A. Version 5.1 All rights reserved Serial Number 301 2nd Ave. Waltham, MA 02451-1133
Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply
FIRE DETECTION, ALARM AND MASS NOTIFICATION SYSTEMS Inspection, testing, and maintenance of fire detection, alarm and Mass Notification systems shall be performed in accordance with the manufacturer's
CalMod Design-Build Electrification Services
SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor
283100 FIRE ALARM AND DETECTION SYSTEMS
283100 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose
Life Alarm Fire Alarm Controls
FIRE SUPERVISORY SUPV SILENCED SILENCE AC POWER RESET UL, ULC Listed FM Approved MEA Approved* Life Alarm Fire Alarm Controls Fire Alarm Controls 4005 Series Fire Alarm Control Panels Eight through Thirty-Six
FIRE ALARM SYSTEM CHECK LIST
FIRE ALARM SYSTEM CHECK LIST BUILDING NAME: DESIGNER: INSPECTION BY: LOCATION: INSTALLER: DATE: Preparation for Acceptance Test Fire authorities have been notified of the system test. Also notify any location
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance
NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.
NFPA 72 3.3.7.2 3.3.7.2 False Alarm. Activation or reporting of an alarm for which no such alarm condition, fire or emergency actually exists. Additionally, False Alarm is the willful and knowing initiating
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 25-POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1. DESCRIPTION: A. This section of the specification
FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
rpsa FIRE PROTECTION ENGINEERS
R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Sample Fire Alarm System Calculations 1. A fire alarm manufacturer specifies