ELECTRICAL DISTRIBUTION STUDY

Size: px
Start display at page:

Download "ELECTRICAL DISTRIBUTION STUDY"

Transcription

1 ELECTRICAL DISTRIBUTION STUDY FOR UNIVERSITY OF NORTH TEXAS DENTON, TEXAS JUNE 17, 2011 THE SEAL APPEARING ON THIS DOCUMENT WAS AUTHORIZED BY R. TIM YAGGI, P.E ON JUNE 17, YAGGI ENGINEERING, INC W. I-20, Suite 270 Arlington, Texas / fax YEI Project No Texas Registration No. F-9622

2 TABLE OF CONTENTS I. PURPOSE AND SCOPE II. III. EXECUTIVE SUMMARY BUILDING LOAD INFORMATION Existing Main Campus Building Peak Loads (3 Year Peak) Existing Eagle Point Building Peak Loads (2 Year Peak) Existing Building Peak Loads (By UNT Feeder) IV. LOAD FLOW ANALYSIS Existing (Normal Conditions) Existing (Outage Feeder #1A) Existing (Outage Feeder #2) Existing (Outage Feeder #3) Existing (Outage Feeder #4A) Existing Conditions Plus Future (Normal Conditions) Main Campus Existing Conditions Plus Future (Normal Conditions) Eagle Point V. PRIMARY SWITCHGEAR VI. RECOMMENDATIONS AND OPINION OF PROBABLE CONSTRUCTION COST

3 TAB 1

4 I. PURPOSE AND SCOPE The purpose of this study is to evaluate the capacity and configuration of the existing primary (13.2 KV) electrical distribution system for the Main Campus and Eagle Point Campus. A similar electrical distribution study was completed in 2003 and this study will update information in that study as it relates to loads, 13.2 KV feeder capacities and Utility Company service capacity. Unlike the 2003 study, this study is limited to evaluation of the primary system configuration and capacity, and does not include equipment and conductor condition assessment, or evaluation of transformer and building service capacities. Normal conditions and worst case outage conditions are considered in the evaluation of the campus feeders and substations serving those feeders. This study is based on electrical load information provided by UNT and Denton Municipal Electric (DME), and includes existing and anticipated future loads. The study provides general recommendations and concepts for improvements necessary to properly serve these loads. The study does not provide specific switchgear, feeder and substation designs. In order to develop construction documents necessary to implement the concepts, it will be necessary to analyze and coordinate substation upgrade options and new substation options with Denton Municipal Electric. An extensive site investigation will also be necessary to determine pathways for new 13.2 KV feeders and duct banks. Yaggi Engineering, Inc.

5 TAB 2

6 II. EXECUTIVE SUMMARY Both the capacity and configuration of the 13.2 KV distribution system for the Main Campus should be upgraded to properly serve existing and anticipated future loads. Loss of any of the four DME feeders will likely result in an overload condition on the UNT and DME systems, depending on load at the time of feeder loss. Loss of any of the major UNT 13.2 KV substation feeder exits may result in an overload condition, the severity of which will depend on which feeder and the load at the time of the outage. The current DME service capacity for the Main Campus is 20 MVA. The projected diversified load which includes anticipated future loads is 29.1 MVA. This diversified load is well below the cumulative maximum demand load for each building; therefore 29.1 MVA should be considered the absolute minimum DME service capacity considered in any upgrade option. The current configuration of the campus distribution system does not allow for seamless transfer of loads from one UNT feeder to another without impacting the load on the DME system feeders. This is because the main loops are created by a source switch at each substation instead of the same substation. The system should be reconfigured to allow transfer of loads without the requirement to notify DME; however emergency ties should be provided to transfer loads to an alternate DME feeder during an emergency condition. Advantages of constructing a high voltage substation should also be discussed with DME. This substation could supplement the existing DME feeders or replace them. Additional recommendations are included in Section VI, along with a very preliminary order of magnitude opinion of probable construction cost. Upon selection of the desired DME service capacity upgrade option, construction documents for UNT feeder upgrades can be developed. At that time, refined cost information can be developed for each specific upgrade option. Various items can be designed as alternates, such as conversion of selected radial feeds to loop feed. Yaggi Engineering, Inc.

7 TAB 3

8 III. BUILDING LOAD INFORMATION A three year history of individual building KW demand was provided by UNT for the Main Campus and two year history for Eagle Pont. This maximum demand value was used to determine the total worst case maximum demand for each UNT feeder. This worst case UNT feeder maximum demand was compared to DME feeder maximum demand information provided by DME. By comparing the values, a diversity factor was developed for each UNT feeder. Resulting diversity factors ranged from 71% to 82%. This allows each UNT feeder to be evaluated both for worst case maximum demand and actual recorded diversified maximum demand. Included in this section are the maximum peak loads for the Main Campus on a per building basis for 2008 through The same information is provided for Eagle Point for 2008 and The maximum demand for the periods above is summarized by UNT feeder. These tables also provide individual building area (square feet), peak watts per square foot, and peak load amps at 13.2 KV. Yaggi Engineering, Inc.

9 EXISTING BUILDING PEAK LOADS Building 3 Year Peak Date KW ART BLDG AUGUST AUDITORIUM-ENGLISH BLDG FEBRUARY BAIN HALL APRIL BRADLEY ST APARTMENTS APRIL BRUCE HALL JANUARY BUSINESS ADMIN BLDG JANUARY BUS LEADERSHIP BUILDING JANUARY CHEMISTRY BLDG AUGUST CHESTNUT HALL JULY CHILTON HALL NOVEMBER CLARK HALL SEPTEMBER COLISEUM JUNE CRUMLEY HALL SEPTEMBER CURRY HALL OCTOBER EAGLE STUDENT SERVICES JUNE ENVIR SCIENCE BLDG FEBRUARY FACILITIES COMPLEX APRIL

10 EXISTING BUILDING PEAK LOADS Building 3 Year Peak Date KW GATEWAY CENTER FEBRUARY GAB AUGUST GAB CITC NORTH AUGUST GOOLSBY CHAPEL JUNE HICKORY HALL & ACCELERATOR SEPTEMBER HIGH MAST LIGHTS MARCH HONORS HALL JANUARY HURLEY ADMIN BLDG APRIL ISB APRIL ISB CC APRIL INTRAMURAL FIELD SEPTEMBER KEN BAHNSEN GYM JANUARY KERR HALL AUGUST LANGUAGE BLDG SEPTEMBER LEGENDS HALL JULY LIFE SCIENCES BUILDING "A" SEPTEMBER LIFE SCIENCES BUILDING "B" OCTOBER MAPLE STREET HALL SEPTEMBER MARQUIS HALL FEBRUARY MATTHEWS HALL FEBRUARY MATTHEWS HALL ANNEX SEPTEMBER

11 EXISTING BUILDING PEAK LOADS Building 3 Year Peak Date KW MCCONNELL HALL FEBRUARY MOZART SQUARE HALL SEPTEMBER MUSIC ANNEX MARCH MUSIC BLDG AUGUST MUSIC PRACTICE COMPLEX JULY PARKING GARAGE APRIL PERFORMING ARTS ANNEX JUNE PERFORMING ARTS CENTER JULY PHYSICAL EDUCATION BLDG NOVEMBER PHYSICS BLDG SEPTEMBER POWER PLANT FEBRUARY RADIO,TV, FILM & PERF ARTS FEBRUARY RESIDENCE HALL ASSOCIATION JULY SANTA FE SQUARE HALL APRIL SCIENCE RESEARCH BLDG FEBRUARY SCOULAR HALL FEBRUARY STADIUM METER NOT OPERATIONAL 35 STADIUM COMPLEX SEPTEMBER

12 EXISTING BUILDING PEAK LOADS Building 3 Year Peak Date KW STOVALL HALL FEBRUARY STUDENT REC CENTER SEPTEMBER TERRILL HALL JUNE TRADITIONS FIELDS - ALL FEBRUARY TRADITIONS HALL SEPTEMBER UNIVERSITY SERVICES BLDG AUGUST UNIVERSITY UNION OCTOBER WEST HALL SEPTEMBER WILLIS LIBRARY SEPTEMBER WOOTEN HALL JANUARY

13 EXISTING EAGLE POINT BUILDING PEAK LOADS BUILDING 2 Year Peak Date KW DUCK POND AUGUST E.P. ATHLETIC CENTER JUNE E.P. INTRAMURAL REC SPORTS DECEMBER E.P. UTILITY BLDG. APRIL E,P. VICTORY HALL APRIL E.P. WARANCH TENNIS COMPLX NOVEMBER MEAN GREEN VILLAGE AUGUST MGV BLDG L-POLICE K9 UNIT DECEMBER MGV BLDG P UNIV COMM & MKT JUNE MGV - WOMENS SOFTBALL FLD MARCH

14 EXISTING BUILDING PEAK LOADS (UNT FEEDER 1A) PEAK PEAK PEAK KW BLDG WATTS/ LOAD BUILDING NAME DEMAND SQ. FT. SQ. FT. AMPS BAIN HALL CHESTNUT HALL CHILTON HALL COLISEUM HURLEY ADMINISTRATION BLDG KEN BAHNSEN GYM MUSIC PRACTICE COMPLEX PHYSICAL EDUCATION BLDG SANTA FE SQUARE HALL STUDENT RECREATION CENTER TRADITIONS HALL CALCULATED MAXIMUM DEMAND TOTAL

15 EXISTING BUILDING PEAK LOADS (UNT FEEDER 1B) PEAK PEAK PEAK KW BLDG WATTS/ LOAD BUILDING NAME DEMAND SQ. FT. SQ. FT. AMPS FACILITIES COMPLEX WEST HALL CALCULATED MAXIMUM DEMAND TOTAL

16 EXISTING BUILDING PEAK LOADS (UNT FEEDER 2) PEAK PEAK PEAK KW BLDG WATTS/ LOAD BUILDING NAME DEMAND SQ. FT. SQ. FT. AMPS AUDITORIUM BRUCE HALL BUSINESS ADMINISTRATION BLDG CHEMISTRY BLDG ENVIRONMENTAL SCIENCE BLDG GAB & GAB CITC NORTH ( ) HICKORY HALL ISB & ISBCC ( ) LANGUAGE BLDG LEGENDS HALL LIFE SCIENCES BLDG "A" & "B"( ) MARQUIS HALL MCCONNELL HALL POWER PLANT SCIENCE RESEARCH BLDG TERRILL HALL CALCULATED MAXIMUM DEMAND TOTAL

17 EXISTING BUILDING PEAK LOADS (UNT FEEDER 3) PEAK PEAK PEAK KW BLDG WATTS/ LOAD BUILDING NAME DEMAND SQ. FT. SQ. FT. AMPS CLARK HALL CRUMLEY HALL GATEWAY CENTER GOOLSBY CHAPEL HONORS HALL KERR HALL MAPLE STREET HALL MATTHEWS HALL MOZART SQUARE HALL MUSIC ANNEX MUSIC BLDG PERFORMING ARTS ANNEX PERFORMING ARTS CENTER RES. HALL ASSOC. & HIGH MAST LITES SCOULAR HALL STADIUM (METER NOT WORKING) STADIUM COMPLEX STOVALL HALL UNIVERSITY SERVICES BLDG WILLIS LIBRARY CALCULATED MAXIMUM DEMAND TOTAL

18 EXISTING BUILDING PEAK LOADS (UNT FEEDER 4A) PEAK PEAK PEAK KW BLDG WATTS/ LOAD BUILDING NAME DEMAND SQ. FT. SQ. FT. AMPS ART BLDG CURRY HALL EAGLE STUDENT SERVICES CENTER MATTHEWS HALL ANNEX PARKING GARAGE PHYSICS BLDG POWER PLANT RADIO,TV, FILM & PERFORMING ARTS UNIVERSITY UNION WOOTEN HALL CALCULATED MAXIMUM DEMAND TOTAL

19 TAB 4

20 IV. LOAD FLOW ANALYSIS Using the demand load information provided by UNT and DME, load flow diagrams were developed for normal operating conditions and worst case outage conditions. The load values in KW and amps on the load flow diagrams are based on UNT maximum building demand information as described in Section III. Both UNT maximum demand information and DME diversified demand information are included in tabular form for normal conditions and each outage condition. This provides evaluation of feeders from both a worst case and actual DME metered basis. Worse case outage conditions for the UNT feeders exist when a UNT feeder exit is lost on either substation. A loss of the substation feeder exit requires that the entire feeder be transferred to another feeder served from the opposite substation. The Northwest Substation located on North Texas Blvd. at Sycamore is served from DME Hickory substation feeders #214 and #222. The Southeast Substation located on Maple St. between Avenue A and Central Ave. is served from DME Locust substation feeders #211 and #233. All four DME feeders serve UNT and non-unt loads. Under normal operating conditions DME reserves 5 MVA of feeder capacity for UNT on each of the four feeders serving UNT for a total of 20 MVA. Under emergency conditions, it is permissible for UNT to transfer load from one DME feeder to another due to a DME or UNT feeder loss. During this emergency load transfer period, DME can serve a maximum 9 MVA UNT load on any single DME feeder. Transfer of load to alternate DME feeders must be approved by DME. The duration of this load transfer may also be limited by DME. Normal operating loads are as follows: NW Substation DME Feeder HK214 (UNT Feeder #1A/#1B) o Calculated UNT Max Demand 6.0 MVA o DME Recorded Max Demand 4.3 MVA DME Feeder HK222 (UNT Feeder #2) o Calculated UNT Max Demand 9.8 MVA o DME Recorded Max Demand 6.5 MVA SE Substation DME Feeder L211 (UNT Feeder #4A) o Calculated UNT Max Demand 4.9 MVA o DME Recorded Max Demand 3.9 MVA DME Feeder L233 (UNT Feeder #3) o Calculated UNT Max Demand 6.0 MVA o DME Recorded Max Demand 4.9 MVA Eagle Point DME Feeder RD222 o DME Recorded Max Demand 1.5 MVA Yaggi Engineering, Inc.

21 DME Feeder Loading Summary (Main Campus) The peak demand of 6.5 MVA as recorded by DME indicates that UNT Feeder #2 at the NW Substation exceeded the normal allowable load of 5 MVA on DME Feeder HK222. UNT Feeder #3 measured demand of 4.9 MVA is very near the normal DME allowable load of 5 MVA on DME Feeder L233. Addition of the cell tower load will push the demand beyond the 5 MVA limit. An additional feeder has recently been installed to provide service to the new Business Leadership Building and Parking Garage/ Power Plant. This feeder is connected to DME Feeder L211 (UNT Feeder #4B). This added load will increase the load on DME Feeder L211 to 12.4 MVA, well beyond the normal allowable limit of 5 MVA. DME-L211 DME-L233 DME-HK214 DME-HK222 Existing 78% (DME Demand) 98% (Calculated) w/ Future 248% (DME Demand) 268% (Calculated) Existing 98% (DME Demand) 120% (Calculated) w/ Future 118% (DME Demand) 140% (Calculated) Existing 86% (DME Demand) 120% (Calculated) w/ Future 86% (DME Demand) 120% (Calculated) Existing 130% (DME Demand) 196% (Calculated) w/ Future 130% (DME Demand) 196% (Calculated) The above feeder loading summary is based on 5 MVA normal load limit set by DME. Under certain conditions, these loads may approach calculated UNT maximum demand levels. Basically the DME normal service capacity to the main campus is 20 MVA (four feeders at 5 MVA each). Based on the anticipated future loads identified in this study, the projected DME diversified load (existing plus future) is 29.1 MVA, which exceeds the existing DME service capacity by 9.1 MVA MVA is the minimum DME service capacity required. If calculated worst case loads were used, this capacity would need to be increased by an additional 20% to 30%. UNT Feeder Loading Summary (Main Campus) Yaggi Engineering, Inc. Main Campus feeders are generally adequate under normal loading conditions based on DME diversified loads, however if any of the UNT substation feeder exits are lost under maximum calculated load conditions, it will result in an overloaded feeder at the opposite substation.

22 With all feeders available, UNT substation feeder exit #2 is loaded at 92% under calculated maximum demand periods and 61% under DME diversified load conditions. This particular feeder has a very high demand diversity (66%) which means that the DME recorded demand of 6.5 MVA is much less than the calculated maximum demand of 9.8 MVA. For this feeder, the potential is high that the actual demand could exceed the DME recorded maximum demand under certain conditions. Other feeder demand diversity factors range from 71% to 82%, which means that the recorded DME demand is 71% to 82% of the calculated worst case demand. With anticipated future load growth, the 13.2 KV distribution system will be taxed under normal and emergency conditions. Any loading above 40% limits the feeder s ability to serve as an alternate source to pick up load due to another feeder outage. Using DME demand diversities and calculated maximum demand, the primary feeders will be loaded as follows: UNT 1A/1B 40% (DME Demand) 57% (Calculated) UNT 2 61% (DME Demand) 93% (Calculated) UNT 3 55% (DME Demand) 66% (Calculated) UNT 4A 37% (DME Demand) 46% (Calculated) UNT 4B UNT Feeder Loading Summary (Eagle Point) 80% (Calculated no load history) The Eagle Point section of the UNT campus is not served from the main campus substations and feeders. It is served through a primary metering point located on Bonnie Brae St. south of IH-35E. Since this portion of the campus is served from a single radial, there are no provisions to sectionalize and bypass a fault. All feeder sections are adequately rated to serve the current load. Future stadium, chiller and student housing loads will require upgrade of the existing 13.2 KV distribution system. Yaggi Engineering, Inc.

23 DME RECOMMENDED MAX NORMAL LOADING PER DME FEEDER DME EMERGENCY LOADING PER DME FEEDER UNT FEEDER RATING (500 CU) FEEDER LOAD FLOW ANALYSIS - EXISTING (NORMAL CONDITIONS) 219 AMPS 394 AMPS 465 AMPS DME RECORDED MAXIMUM DEMAND DME UNT MVA AMPS TOTAL AMPS DIVERSITY FACTOR AMPS MVA 1A HK % B HK CALCULATED UNT FEEDER MAX DEMAND % MVA 9 MVA 10.6 MVA L % L211 4A %

24 DME RECOMMENDED MAX NORMAL LOADING PER DME FEEDER DME EMERGENCY LOADING PER DME FEEDER UNT FEEDER RATING (500 CU) 219 AMPS 394 AMPS 465 AMPS DME UNT MVA AMPS TOTAL AMPS DIVERITY FACTOR AMPS MVA 1A HK % B HK222 FEEDER L L211 4A 4.9 LOAD FLOW ANALYSIS - EXISTING (OUTAGE FEEDER #1A) CALCULATED UNT FEEDER MAX DEMAND % % % NOTE: TRANSFER UNT #1A LOAD OF 5.0 MVA TO UNT #3. DME RECORDED MAXIMUM DEMAND 80% MVA 9 MVA 10.6 MVA

25 DME RECOMMENDED MAX NORMAL LOADING PER DME FEEDER DME EMERGENCY LOADING PER DME FEEDER UNT FEEDER RATING (500 CU) FEEDER LOAD FLOW ANALYSIS - EXISTING (OUTAGE FEEDER #2) DME UNT MVA AMPS TOTAL AMPS DIVERITY FACTOR 1A HK % 1B HK222 2 CALCULATED UNT FEEDER MAX DEMAND % 219 AMPS 394 AMPS 465 AMPS DME RECORDED MAXIMUM DEMAND AMPS MVA 9 MVA 10.6 MVA MVA L % 215 L211 4A % % 284 NOTE: TRANSFER UNT #2 LOAD OF 9.8 MVA TO UNT #4A

26 LOAD FLOW ANALYSIS - EXISTING (OUTAGE FEEDER #3) DME RECOMMENDED MAX NORMAL LOADING PER DME FEEDER DME EMERGENCY LOADING PER DME FEEDER UNT FEEDER RATING (500 CU) FEEDER CALCULATED UNT FEEDER MAX DEMAND 219 AMPS 394 AMPS 465 AMPS DME UNT MVA AMPS TOTAL AMPS DIVERITY FACTOR AMPS % 155 1A HK % B % 31 HK % DME RECORDED MAXIMUM DEMAND MVA 9 MVA 10.6 MVA MVA L % L211 4A % NOTE: TRANSFER UNT #3 LOAD OF 6.0 MVA TO UNT #1A

27 DME RECOMMENDED MAX NORMAL LOADING PER DME FEEDER DME EMERGENCY LOADING FOR DME FEEDERS UNT FEEDER RATING (500 CU) FEEDER 219 AMPS 394 AMPS 465 AMPS DME UNT MVA AMPS TOTAL AMPS DIVERITY FACTOR AMPS MVA 1A HK % B HK % % 172 L LOAD FLOW ANALYSIS - EXISTING (OUTAGE FEEDER #4A) CALCULATED UNT FEEDER MAX DEMAND MVA 9 MVA 10.6 AMPS DME RECORDED MAXIMUM DEMAND 82% L211 4A % NOTE: TRANSFER UNT #4A LOAD OF 4.9 MVA TO UNT #2

28 SE SUBSTATION LOAD FEEDER TOTAL TOTAL AMPS MVA DESCRIPTION DME UNT AMPS MVA EXISTING LOAD L211 4A EXIST BUSINESS LEADERSHIP BLDG L211 4B APR POWER PLANT AND GARAGE L211 4B JAN POWER PLANT CHILLERS (2) L211 4B APR AUDITORIUM L211 4B SUBTOTAL L EXISTING LOAD L EXIST CELL TOWER L SUBTOTAL L TOTAL (SE SUBSTATION) NW SUBSTATION LOAD FEEDER TOTAL TOTAL AMPS MVA DESCRIPTION DME UNT AMPS MVA EXISTING LOAD HK EXIST FUTURE LOAD HK222 2 SUBTOTAL HK EXISTING LOAD HK214 1A/1B EXIST FUTURE LOAD LOAD FLOW ANALYSIS - EXISTING PLUS FUTURE (NORMAL CONDITIONS) HK214 1A/1B SUBTOTAL HK214 1A/1B TOTAL (NW SUBSTATION) TOTAL MAIN CAMPUS AMPS MVA DATE DATE

29 LOAD FLOW ANALYSIS - EXISTING PLUS FUTURE (NORMAL CONDITIONS) EAGLE POINT LOAD FEEDER TOTAL TOTAL AMPS MVA DATE DESCRIPTION DME UNT AMPS MVA EXISTING LOAD RD222 EP EXIST STADIUM RD222 EP JUL CHILLER RD222 EP JUL STUDENT HOUSING RD222 EP TOTAL EAGLE POINT AMPS MVA

30 TAB 5

31 V. PRIMARY SWITCHGEAR Existing campus switchgear consist of freestanding metal clad S&C switchgear at the Northwest Substation and Southeast Substation, pad mounted PMH style S&C switchgear and Vista switchgear. The switchgear provides sectionalizing capability and fuse positions provide cable protection, transformer protection and selective coordination. The scope of this study did not include evaluation of fuse sizes and selective coordination. Physical inspection and evaluation of the switchgear condition were also not included in the study. Under normal conditions, the switchgear is adequately rated to serve main campus distribution feeders. Under outage conditions 2 and 4A, the following switchgear will be overloaded based on calculated worst case conditions: Outage Feeder #2 Outage Feeder #4A P45-A, P46A, Feeder #4A Sub Exit P21-A, P29A, Vista 422, Feeder #2 Sub Exit Using DME demand loads for each outage condition, all 600 amp distribution switchgear is adequate for main line service. When future loads are added to the system, some switchgear loads will approach or exceed the 600 amp switchgear nameplate rating for all four major outage conditions where the substation feeder exit is lost. The following table includes distribution switchgear data sorted by device number, building location, switchgear type, fuse ratings and buildings served. Yaggi Engineering, Inc.

32 13.2 KV SWITCHGEAR UNT Device Building Number Location Type *Fuse Serves P5-A P6-B P6-C P7-A P10-A STADIUM & USB STUDENT REC. FAC & WEST HALL TRADITIONS & SANTA ATHLETICS PMH-9 PMH-9 PMH-9 PMH-9 PMH-12 80A 200A 30A 80A 100A STADIUM 2400Y P7-A WEST HALL TRADITIONS STADIUM AND USB 65A 100A 20A 80A 20A USB STUDENT REC. FACILITIES SANTA FE ATHELETICS P12-A PAC ANNEX PMH-9 125A (2) PMH DEVICES 15A PAC ANNEX P12.5-A LEGENDS VISTA 85A LEGENDS P12-B PERF ARTS CNTR PMH-9 150A PAC 150A (3) PMH DEVICES P17-A GATEWAY PMH-9 50A GATEWAY 200A (4) PMH DEVICES P17-B COLISEUM PMH-9 175A COLISEUM P18-A MOZART HALL PMH-9 40A MOZART P19-A ENVIR.SCI. EESAT PMH-9 65A ENVIR SCIENCE P21-A McCONNELL PMH-9 65A McCONNELL P22-A PHYS ED BLDG PMH A PHYS ED BLDG P22-B CHILTON HALL PMH-9 30A CHILTON P22-C CHESTNUT HALL VISTA 100A CHESTNUT P23-A MUSIC PRACTICE PMH-9 40A MUSIC PRACTICE P23-B BAIN & KEN BAHN GYM PMH-9 40A BAIN 20A BAHNSEN GYM P26-A CLARK & HONORS PMH-9 65A CLARK 50A HONORS * DATA OBTAINED FROM UNT RECORDS.

33 13.2 KV SWITCHGEAR UNT Device Building Number Location Type *Fuse Serves P28-A SCIENCE RESEARCH PMH-9 100A SCI. RES. 80A PMH DEVICE P19-A P28-B TERRILL & CHEM PMH-9 125A CHEMISTRY 65A TERR & MARQ P29-A BRUCE PMH-9 100A PMH DEVICE P28-C 30A BRUCE P29-B LIFE SCIENCE VISTA P29-C P30-B P32-A P32-B P36-A P36-B BIOLOGY ADMINISTRATION LIBRARY MUSIC BUILDING KERR MAPLE PMH-9 PMH-9 PMH-9 PMH-10 P33-A STOVALL/SCOULAR PMH-12 P33-C EAGLE STUDENT SER PMH-9 P34-A P34-B N.E. COR.CRUMLEY CRUMLEY/ MUSIC ANN PMH-13 PMH-9 P34-C RES.HALL ASSOC. PMH-9 PMH-9 PMH-9 P37-A HICKORY PMH-9 P37-B GAB CITC NORTH PMH-9 P38-A I.S.B. PMH-11 P38-B BUSINESS & I.S.B. PMH-9 * DATA OBTAINED FROM UNT RECORDS.?? LIFE SCIENCE 65A BIOLOGY 120/208V 50A BIOLOGY 277/480V 40A 175A 65A (2)15A 80A 40A 20A 5A 175A 50A 65A 40A 65A 50A 40A 15A ADMIN. BLDG LIBRARY MUSIC BUILDING MUSIC BUILDING MATTHEWS STOVALL & SCOULAR STUDENT SER CRUMLEY MUSIC ANNEX RES HALL ASSOC KERR MAPLE HICKORY ACCEL HICKORY HALL GAB CITC NOR. I.S.B. BUSINESS AD I.S.B. COMPUTER

34 13.2 KV SWITCHGEAR UNT Device Building Number Location Type *Fuse Serves P38-C POWER PLANT PMH-9 175A POWER PLANT 10A POWER PLANT P38-D POWER PLANT PMH-9 175A POWER PLANT P38-E GAB PMH-7 50A GAB 50A GAB P38-F LANGUAGE PMH-9 50A LANGUAGE 15A AUDITORIUM P38-G CURRY & PHYSICS PMH-9 40A PHYSICS 20A CURRY 040-C BUS LEAD BLDG VISTA?? PMH DEVICE P33-A P43-A ART BUILDING PMH-9 50A ART BUILDING P43-B RADIO/TV FILM PMH-9 40A RADIO/TV P45-A STUDENT UNION PMH-9 200A PMH DEVICE P33-C 100A STUDENT UNION P45-B UNION/ MATT ANNEX PMH-13 P45-C MATTHEWS ANNEX PMH-9 P46-A WOOTEN HALL PMH-9 * DATA OBTAINED FROM UNT RECORDS. 15A 50A MATT ANNEX WOOTEN HALL

35 TAB 6

36 VI. RECOMMENDATIONS AND OPINION OF PROBABLE CONSTRUCTION COST 1. Increase DME service capacity to the Main Campus from existing capacity of 20 MVA to new capacity of 29.1 MVA (minimum). This service capacity is required to serve existing loads and future loads identified in the study. This can be accomplished in several ways and will require strategic planning to minimize the impact to the existing UNT distribution system which is necessary to control construction cost. Possible solutions include: a. DME to increase service capacity of the four existing DME feeders. Cost for this item would be determined by DME. b. DME to install additional feeder capacity to the SE Substation area to relieve load on that substation and the associated UNT feeders. These new feeders would then be used to relieve load on the NW substation. This area has the highest concentration of future loads. Cost for this item would be determined by DME. c. Install a third DME substation in the area of the existing football stadium. The disadvantage of this approach is the distance from the highest concentration of campus load; therefore UNT feeder cost would be higher than other options. The advantage of this approach is available space for incoming DME feeder facilities. Cost for this item would be determined by DME. d. Provide a true substation on campus to transform from DME transmission voltage to 13.2 KV. A very preliminary range of construction cost for this item is from $2,000,000 to $3,000,000 depending on capacity, location, screening, etc. e. Each item above requires UNT feeder upgrades, extensions, and switchgear to utilize and distribute the added capacity. Those cost are addressed below and will vary depending on which DME upgrade approach is selected. 2. Install additional UNT feeder facilities to support existing and future loads, and allow for sectionalizing during feeder outage conditions without the need to curtail loads. The approach for this item is dependent on which DME service capacity upgrade option is selected. A preliminary range of cost for this item is $1,000,000 to $2,500,000 depending on the DME service capacity approach selected. 3. UNT feeders should be configured to allow transfer of loads between feeders originating from the same substation and same DME feeder. Currently, transfer of UNT loads from one feeder to another results in transferring loads from one DME feeder to another, making it difficult for DME to control loads on their feeders. It is also a burden to UNT to notify DME each time load is transferred. Emergency ties should still be provided between DME feeders in case of DME feeder loss. Cost of this item will range from $250,000 to $750,000 depending on which DME service capacity approach is selected. 4. That the 4/0 conductor from P10-A to P5-A be replaced with 500KCMIL and that P5-A be replaced with VISTA switchgear. Yaggi Engineering, Inc.

37 5. Areas served by radial feeds should be served from the main loop or a sub-loop to improve service reliability. Justification of this item will be on a case by case basis, depending on the facilities served from the radial feed. Cost will be dependent on which radials are selected for conversion to loop feed or alternate feed. 6. Provide a second DME feeder to serve the Eagle Point and Stadium area south of IH-35E. This will allow a phased approach of providing a loop feed or alternate feeds to all or selected facilities in this area. Redundant UNT feeds could be provided to selected facilities without the additional DME feeder, however due to the critical nature of the Stadium, a second DME feeder is recommended. Cost for this item would be determined by DME. UNT feeder cost will be dependent on which facilities are selected for loop feed or alternate feed. Yaggi Engineering, Inc.

Minimizing Impact of Electric Utility Outages with Backup Generation

Minimizing Impact of Electric Utility Outages with Backup Generation Minimizing Impact of Electric Utility Outages with Backup Generation Introduction of the Speaker Michael Dempsey, PE Senior Electrical Engineer Carter & Burgess, Inc. Energy & Power Solutions Facility

More information

Comprehensive Electrical Distribution Master Planning at North Carolina State University. Alan Daeke Michael Dempsey

Comprehensive Electrical Distribution Master Planning at North Carolina State University. Alan Daeke Michael Dempsey Comprehensive Electrical Distribution Master Planning at North Carolina State University Alan Daeke Michael Dempsey CAMPUSENERGY2015 Agenda Campus Overview Overview of Existing System Project Goals Project

More information

Electrical Distribution System Study

Electrical Distribution System Study Electrical Distribution System Study Final Study Report Revised December 16, 2011 Primary Electrical Distribution System Study Kennesaw State University REVISED December 16, 2011 INDEX TITLE PAGES Executive

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Schematic Plan Submittal, 21 November, 2011 Roesling Nakamura Terada Architects

Schematic Plan Submittal, 21 November, 2011 Roesling Nakamura Terada Architects To r r e y P i n e s H i g h S c h o o l M a s t e r P l a n Schematic Plan Submittal, 21 November, 2011 Roesling Nakamura Terada Architects I n t r o d u c t i o n 1.0 INTRODUCTION The vision for the

More information

Rule 5.500 Fast Track Analysis for National Life Insurance Co.

Rule 5.500 Fast Track Analysis for National Life Insurance Co. Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

Wholesale Data Center Suites Available Now

Wholesale Data Center Suites Available Now Wholesale Data Center Suites Available Now FROM 2,500 to 100,000 Sq Ft A secure, fortified Mission Critical data center facility located in Innovation Park, Charlotte, NC Scalable data center suites available

More information

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings

More information

NEW JERSEY CENTER OF EXCELLENCE

NEW JERSEY CENTER OF EXCELLENCE Overview NEW JERSEY Page 1 The Plant (CUP) provides electricity via a cogeneration system, chilled water for environmental cooling, steam for heating, and compressed air primarily for HVAC control Serves

More information

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering Title 20 PUBLIC SERVICE COMMISSION Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES Chapter 02 Engineering Authority: Public Utility Companies Article, 2-121, 5-101 and 5-303, Annotated Code of Maryland.

More information

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements

More information

Data Center:Build-to-Suit

Data Center:Build-to-Suit Data Center:Build-to-Suit A fortified 100,000 SqFt mission critical build-to-suit constructed on a secured 5 acre parcel at Innovation Park Charlotte, NC On-Site 120MW Substation Sourced from Two Independent

More information

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0. Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M

More information

Treasure Valley Electrical Plan

Treasure Valley Electrical Plan Treasure Valley Electrical Plan Community Advisory Committee January 25, 2006 Agenda 10 a.m. Welcome 10:10 a.m. Follow up DSM discussion 10:30 a.m. TVEP CAC process update 10:40 a.m. Transmission Presentation

More information

Digital Chicago. 600 south FeDeraL - chicago 9333 9377 grand ave - FranKLin ParK 350 east cermak - chicago

Digital Chicago. 600 south FeDeraL - chicago 9333 9377 grand ave - FranKLin ParK 350 east cermak - chicago Digital Chicago 600 south FeDeraL - chicago 9333 9377 grand ave - FranKLin ParK 350 east cermak - chicago The Digital Chicago portfolio consists of three state-of-the-art data center facilities: 600 South

More information

Synergy. The purchase of Stellar Dynamics by GE Harris is a refreshing example of rational long-term thinking. 6 Customer Spotlight FINGRID pg

Synergy. The purchase of Stellar Dynamics by GE Harris is a refreshing example of rational long-term thinking. 6 Customer Spotlight FINGRID pg Synergy The purchase of Stellar Dynamics by GE Harris is a refreshing example of rational long-term thinking. Stellar Dynamics & GE Harris pg 2 OCTOBER 1999 Global Perspectives pg 6 Customer Spotlight

More information

TERMS AND CONDITIONS

TERMS AND CONDITIONS Virginia Electric and Power Company TERMS AND CONDITIONS XXIV. GENERATOR INTERCONNECTION STANDARD Electric generator interconnection service includes only the ability to interconnect an electric generator

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

UTILITIES AND ENERGY MANAGEMENT

UTILITIES AND ENERGY MANAGEMENT UTILITIES AND ENERGY MANAGEMENT University of Texas at Austin increases investment in co-generation to achieve greater utility reliability and economy. ENVIRONMENTAL BENEFITS AND ENERGY SAVINGS Power plant

More information

Phase Attribute Identification using GPS Technology

Phase Attribute Identification using GPS Technology Phase Attribute Identification using GPS Technology Date 11 June 2009 John Sinclair Power Quality Manager Slide 1 Topics of Discussion Remote Phase Identification How it works Principals of operation Benefits

More information

Hendrix Spacer Cable

Hendrix Spacer Cable Hendrix Spacer Cable What is Spacer Cable? Covered Conductor Withstands temporary branch contact Eliminates temporary faults Protects wildlife Less clearance issues Compact Configuration Multiple Circuits

More information

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe NETWORKS ESB Networks Response to ERGEG Consultation on Voltage Quality Regulation in Europe Date: 22 February 2007 Distribution System Operator ESB Networks Page 1 of 12 Contents 1.0 INTRODUCTION...3

More information

Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process

Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process Presented by: Marianne Mannschreck Date: Welcome A Look at the Net Energy Metering

More information

Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX

Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX March 10, 2009 Agenda DFW Capital Development Program

More information

2015 CAMPUS STATEMENT

2015 CAMPUS STATEMENT STATE UNIVERSITY OF NEW YORK UNIVERSITY AT STONY BROOK 2015 CAMPUS STATEMENT The University at Stony Brook got its start in 1957 at a temporary location on the Planting Fields estate in Oyster Bay, Long

More information

Proceedings of the 38th Hawaii International Conference on System Sciences - 2005

Proceedings of the 38th Hawaii International Conference on System Sciences - 2005 The use of Multi-Attribute Trade-Off Analysis in Strategic Planning For an Electric Distribution utility: An Analysis of Abu Dhabi Distribution Company Richard D. Tabors, Ph.D. Rick Hornby Tabors Caramanis

More information

Calculating Total Power Requirements for Data Centers

Calculating Total Power Requirements for Data Centers Calculating Total Power Requirements for Data Centers By Richard Sawyer White Paper #3 Executive Summary Part of data center planning and design is to align the power and cooling requirements of the IT

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

Primary Electric Distribution for Industrial Plants

Primary Electric Distribution for Industrial Plants PDH Course E242 Primary Electric Distribution for Industrial Plants Adolph A. Biss, P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114.

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114. Generation Interconnection System Impact Study Report For PJM Generation Interconnection Request Queue Position X1-114 Sandyston January 2012 Preface The intent of the System Impact Study is to determine

More information

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions

More information

UCSB EMERGENCY ASSEMBLY POINTS (EAPs)

UCSB EMERGENCY ASSEMBLY POINTS (EAPs) Alumni House, Building #517 Primary location: South to Lot 12, 100 feet from building Anacapa Residence Hall, Building #547 Primary location: South to lawn near Lagoon road Secondary location: West to

More information

Vision 2050 An Asset Management Strategy. Jaclyn Cantler Manager, Transmission Planning, PHI

Vision 2050 An Asset Management Strategy. Jaclyn Cantler Manager, Transmission Planning, PHI 1 Vision 2050 An Asset Management Strategy Jaclyn Cantler Manager, Transmission Planning, PHI 2 Agenda Case for Change About Vision 2050 Status Closing System Design Cybersecurity Interface with distributed/dispersed

More information

Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report

Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives (Required per CPUC Decision No. C10-1328) Final Report (Submitted with Public Service s 2011 ERP) Executive Summary The objective

More information

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES C. Schwaegerl*, M.H.J. Bollen, K. Karoui #, A. Yagmur + *Siemens AG, # Tractebel STRI AB

More information

ABSTRACT DCMCCT PROJECT OVERVIEW

ABSTRACT DCMCCT PROJECT OVERVIEW Title: Case Study of the Austin Energy Dell Regional Children s Medical Center of Central Texas Packaged Hybrid CHP Energy Plant in Austin, Texas Authors: Mr. Ed Mardiat, Burns & McDonnell Mr. Jim Teigen,

More information

UTSA FY 2012. The University of Texas at San Antonio UTILITY COST / CONSUMPTION. Office of Facilities

UTSA FY 2012. The University of Texas at San Antonio UTILITY COST / CONSUMPTION. Office of Facilities The University of Texas at San Antonio UTILITY COST / CONSUMPTION FY 2012 UTSA Office of Facilities ENERGY MGR: Dagoberto Rodriguez UTILITIES ENGINEER: Rene Colunga FY12 Utility Cost and Consumption Report

More information

University of Maryland College Park District Energy System. IDEA Campus Energy Conference February 9, 2012

University of Maryland College Park District Energy System. IDEA Campus Energy Conference February 9, 2012 University of Maryland College Park District Energy System IDEA Campus Energy Conference February 9, 2012 UMCP District Energy System The University of Maryland district energy system consists of a well

More information

Addendum #2 Contract UK-11-13

Addendum #2 Contract UK-11-13 Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)

More information

MISSISSIPPI VALLEY STATE UNIVERSITY Facilities Management. E-911 Building Address listing

MISSISSIPPI VALLEY STATE UNIVERSITY Facilities Management. E-911 Building Address listing MISSISSIPPI VALLEY STATE UNIVERSITY Facilities Management E-911 Building Address listing BUILDING NAME H G CARPENTER AUDITORIUM WILLIAM W SUTTON ADMINISTRATION BUILDING EARNEST A BOYKINS ACADEMIC SKILLS

More information

LOGAN TERMINAL B SUBSTATION UPGRADE

LOGAN TERMINAL B SUBSTATION UPGRADE AIRPORTS LOGAN TERMINAL E AND HEATING PLANT 5 KV AND 15 KV UPGRADES D 2015 Design replacement of two double-ended substations, HVAC upgrades for six substations, upgrades to 400 hertz gate power central

More information

The electrical energy produced at the gen

The electrical energy produced at the gen 300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5

More information

261000 Medium Voltage Electrical Distribution

261000 Medium Voltage Electrical Distribution Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This

More information

Current Transformers

Current Transformers Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide

More information

Radial Distribution Test Feeders

Radial Distribution Test Feeders Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it

More information

Electrical System Studies

Electrical System Studies Electrical System Studies INTRODUCTION s experienced professionals provide electrical systems planning and design services to improve the safety and the reliability of electric power systems. The planning,

More information

OPERATOR - FACILITY ADDRESS - DATE

OPERATOR - FACILITY ADDRESS - DATE . Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.

More information

Columbus State Community College MASTER PLANNING

Columbus State Community College MASTER PLANNING Columbus State Community College MASTER PLANNING Current State Facilities and Utilities Assessment November 2011 Columbus State Community College MASTER PLANNING EXISTING UTILITIES AND FACILITIES ASSESSMENT

More information

AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)

AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:

More information

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY

More information

4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS

4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS 4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED MEDIUM VOLTAGE

More information

Report to the Minister Responsible for the Qulliq Energy Corporation. Respecting:

Report to the Minister Responsible for the Qulliq Energy Corporation. Respecting: Report to the Minister Responsible for the Qulliq Energy Corporation Respecting: An Application by the Qulliq Energy Corporation For Approval of Major Project Permit to Upgrade the Iqaluit Distribution

More information

FIXED CHARGE: This is a cost that goes towards making the service available, including

FIXED CHARGE: This is a cost that goes towards making the service available, including ELECTRICITY BILL COMPONENTS FIXED CHARGE: This is a cost that goes towards making the service available, including installation and maintenance of poles, power lines and equipment, and 24-hour customer

More information

Paralleling Switchgear

Paralleling Switchgear Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING

REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING Revised October, 2013 TABLE OF CONTENTS 1.0 INTRODUCTION... 3 2.0 REQUIRED DRAWINGS... 3 2.1 Site Plan... 3

More information

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation Stand Alone POTS Fiber Optic System P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit Description & Installation Printed in USA 09/11 TO466 Rev. A Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT

More information

16 West Coast Regional Plan

16 West Coast Regional Plan 16 West Coast Regional Plan 16.1 Regional overview 16.2 West Coast transmission system 16.3 West Coast demand 16.4 West Coast generation 16.5 West Coast significant maintenance work 16.6 Future West Coast

More information

Applying For New or Revised Electric Service

Applying For New or Revised Electric Service Applying For New or Revised Electric Service Dear Customer: ComEd is happy to assist you in initiating new or revised electric service to your location. Please complete, sign and return the attached service

More information

The total estimated PFC revenue for the application is $266,900,000. The estimated charge effective date for this application is December 1, 2016.

The total estimated PFC revenue for the application is $266,900,000. The estimated charge effective date for this application is December 1, 2016. Public Notice of Application for Authority to Impose and Use Passenger Facility Charges (PFCs) at EWR, LGA, JFK and SWF and Amendment to Approved PFC Applications at EWR, LGA, and JFK The Port Authority

More information

Texas State University Utility Analysis. Sheri Lara, CEM, CEFP Texas State University Morgan Stinson, PE, LEED AP - EEA Todd Schmitt, PE, LEED AP EEA

Texas State University Utility Analysis. Sheri Lara, CEM, CEFP Texas State University Morgan Stinson, PE, LEED AP - EEA Todd Schmitt, PE, LEED AP EEA Texas State University Utility Analysis Sheri Lara, CEM, CEFP Texas State University Morgan Stinson, PE, LEED AP - EEA Todd Schmitt, PE, LEED AP EEA Texas State University - San Marcos The rising STAR

More information

Generation Interconnection Feasibility Study Report-Web Version. PJM Generation Interconnection Request Queue Position Z1-055

Generation Interconnection Feasibility Study Report-Web Version. PJM Generation Interconnection Request Queue Position Z1-055 Generation Interconnection Feasibility Study Report-Web Version For PJM Generation Interconnection Request Queue Position Z1-055 South Bend Generation Project March 2014 PJM Interconnection 2014. All rights

More information

MEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED

MEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED CCG Facilities Integration Incorporated

More information

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s

More information

Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems

Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems Centre for Sustainable Electricity and Distributed Generation Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems Predrag Djapic and Goran Strbac July 2008 FUNDED BY BERR URN 08/1144

More information

EPCOR Distribution & Transmission Inc.

EPCOR Distribution & Transmission Inc. Decision 3478-D01-2015 Victoria E511S Substation Expansion February 17, 2015 Alberta Utilities Commission Decision 3478-D01-2015 Victoria E511S Substation Expansion Proceeding 3478 Application 1610934-1

More information

ICM Project Station Infrastructure and Equipment

ICM Project Station Infrastructure and Equipment EB 0 00 Schedule B. ( pages) ICM Project Station Infrastructure and Equipment (THESL) EB 0 00 Schedule B. I EXECUTIVE SUMMARY 0. Project Description Many Municipal Substations (MS) located outside of downtown

More information

Status of Significant Projects

Status of Significant Projects Status of Significant Projects October 5, 2015 Antonio Calcado Vice President University Facilities & Capital Planning 1 Budget Page Project Type New Brunswick @ Busch 1 Chemistry & Chemical Biology Building

More information

Simulation of Cable Overloading Problem on a University Distribution System

Simulation of Cable Overloading Problem on a University Distribution System Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 3, Number 6 (2013), pp. 765-770 Research India Publications http://www.ripublication.com/aeee.htm Simulation of Cable Overloading

More information

SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD

SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD HOLLAND CLIFF HEWITT ROAD 230 KV TRANSMISSION LINE PROJECT ELECTRIC ALTERNATIVE EVALUATION STUDY BLACK & VEATCH CORPORATION B&V Project 146026(G)

More information

BASIC NEC CODE RULES AND DESIGN PRACTICE

BASIC NEC CODE RULES AND DESIGN PRACTICE BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,

More information

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G 100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior

More information

How To Get A Power Line Extension

How To Get A Power Line Extension GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Phase Balancing of Distribution Systems Using a Heuristic Search Approach

Phase Balancing of Distribution Systems Using a Heuristic Search Approach Phase Balancing of Distribution Systems Using a Heuristic Search Approach Lin, Chia-Hung*, Kang, Meei-Song**, Chuang, Hui-Jen**, and Ho, Chin-Ying** *National Kaohsiung University of Applied Sciences **Kao

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information

How To Visit An Internet Data Center

How To Visit An Internet Data Center AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina

More information

datacentersites.com www.datacentersites.com Security, Infrastructure Redundancy Tier 3+/Tier 4 Data Center Sites

datacentersites.com www.datacentersites.com Security, Infrastructure Redundancy Tier 3+/Tier 4 Data Center Sites datacentersites.com Tier 3+/Tier 4 Data Center Sites Home of Apple s $1 billion, 500,000sf data center and two 20+ MW solar facilities NC Data Center Corridor home to nearby data centers for Facebook,

More information

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1

More information

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA

More information

N O W A V A I L A B L E

N O W A V A I L A B L E N O W A V A I L A B L E 5 0, 0 0 0 S F P O W E R E D S H E L L D A T A C E N T E R I I Data Center Park Catawba County, North Carolina Contact Doug Hollidge for more information Email: [email protected]

More information

IESO Supply Deliverability Guidelines

IESO Supply Deliverability Guidelines PUBLIC IMO_GDL_0021 IESO Supply Deliverability Guidelines Issue 3.0 This document is to be used to evaluate long-term system adequacy and connection assessments Public Disclaimer The posting of documents

More information

Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc.

Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc. Grounding Practice at Data and Communications Centers David Brender, P.E., CPQ National Program Manager Copper Development Association Inc. Overview of This Presentation Elements of building wiring and

More information

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747 POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609

More information

Electric Service Guide for Commercial Construction

Electric Service Guide for Commercial Construction Electric Service Guide for Commercial Construction Contents Contacting KCP&L... 2 Voltages... 2 Temporary Service... 2 Customer-Provided Temporary Service... 2 KCP&L-Provided Temporary Service.... 2 Current

More information

REQUIREMENTS FOR CUSTOMER-OWNED PRIMARY SERVICES SUPPLIED AT 4 kv TO 35 kv PRIMARY GUIDE

REQUIREMENTS FOR CUSTOMER-OWNED PRIMARY SERVICES SUPPLIED AT 4 kv TO 35 kv PRIMARY GUIDE BC Hydro Distribution Standards REQUIREMENTS FOR CUSTOMER-OWNED PRIMARY SERVICES SUPPLIED AT 4 kv TO 35 kv PRIMARY GUIDE JUNE 2010 Changes Visible Edition This document shows all changes that have been

More information

How To Build A Data Center For Ragingwire

How To Build A Data Center For Ragingwire TURN-KEY AND BUILD-TO-SUIT WHOLESALE DATA CENTER SOLUTIONS RAGINGWIRE CA3 SACRAMENTO, CA NOW LEASING LARGEST DATA CENTER IN CALIFORNIA WITH LOWEST COST POWER RagingWire s new CA3 data center facility brings

More information