1 Innovation Park Charlotte. NC DRAFT V0.1
2 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M renovation of the campus, including the launch of the CyberFortress Data Center, a mission critical-ready facility with a depth of in-place infrastructure, redundancy, security and scalability unrivaled in the Southeastern United States. By way of background, with a portfolio consisting of approximately 500 tenants and 5.5 million square feet of commercial office space, BECO has a 25 year track record as an owner actively engaged with its tenants throughout its portfolio in Metropolitan Washington, DC and Charlotte, NC. For the past decade, BECO-owned affiliates have constructed approximately 500,000 square feet of rapidly commissionable Tier II and Tier III data center facilities in metropolitan Washington, DC, Chicago, IL (and now Charlotte, NC). Known as CyberFortress facilities, these data center buildings have been constructed specifically for use as mission critical data centers. Each CyberFortress is constructed with much of the long-lead time critical infrastructure in-place (electrical power, fiber capacity and various layers of security and redundancy), providing a cost effective, rapidly commissionable facility where the data interior is controlled exclusively by the tenant and built to their exact tier and design specifications. Current occupants of CyberFortress facilities include, JPMorgan Chase, Verizon Communications, Discovery Communications and the Federal government.
3 Page 3 Location INNOVATION PARK CHARLOTTE, NORTH CAROLINA AERIAL MAP OF INNOVATION PARK
4 Page 4 Available Infrastructure (MEP/FP) The mechanical, electrical, plumbing and fire protection systems at Innovation Park have a great track record of reliability and are very well maintained. Below are brief descriptions that illustrate the services available for data center clients. Mechanical Systems Central Utility Plant: Four (4) chillers operating in parallel with an N+1 topology. Nominal chiller capacity of 1,250 tons each for a total of approximately 3,750 tons (13.1 MW) of cooling capacity distributed to the campus and 1,250 tons of additional reserve cooling capacity. Five 100,000 gallon thermal storage tanks (four of which are always full) support peak utility rate shaving for the central plant operation. 13 F water temperature range with design supply chilled water temperature of 42 F and 55 F chilled water return. 24x7 monitoring through Building Management System in addition to 24x7 on-site engineering staff and security personnel. Six cross flow BAC cooling towers set to operate in parallel fashion. Cooling tower topology N+2, indicating that two cooling towers are placed in standby and readily available as back up. Each cooling tower has a nominal capacity of 1,250 tons (357kW). Robust common concrete sumps with sectionalizing capability for maintenance and domestic water storage. Dual feeds of chilled condenser water piping to condenser water pump header. Six (6) 125 HP Condenser Water (CW) Pumps operating in parallel (by VFD) with an N+2 topology. Six (6) primary chilled water pumps are 40HP, operating in an N+2
5 Page 5 topology and four (4) secondary chilled water pumps are 200HP, operating in a 2N topology. Chilled Water Distribution: Chilled water (CHW) piping is routed through the campus in secure, underground tunnels. CHW piping includes taps and sectionalizing valves for future connections. The distribution through each building can be modified to fit the needs of the tenant. The chilled water is distributed to the individual AHUs which currently provide conditioned air to the tenant spaces. Data center clients that require larger chilled water distribution are able to connect to the main and distribute chilled water as necessary to accommodate their cooling demand. Boiler / Compressed Air Infrastructure: Three (3) comfort heating boilers. Two boilers provide hot water at a range of 130 F to 190 F. The hot water is distributed to the campus and is intended to serve perimeter heating units, and the main air handlers which are found in each building. An additional boiler can provide steam at 50 60psi, and is currently used for humidity control The central plant contains five (5) operational air compressors. Pneumatic controls are base building standard, however, DDC is provided at the tenants request (0 10V) The campus has high pressure air available to all buildings.
6 Page 6 Building Management System (BMS): The BMS is a Siemens 600 Apogee operating system which monitors the central utility plant and provides the building engineering staff with critical information on the operation of the central plant. The BMS is able to monitor and control terminal equipment in the campus buildings. The BMS is backed up by UPS power (locally). The BMS includes a redundant program for emergency backup. HVAC System: The CyberFortress is equipped with central built up Air Handling Units. The units have hot water reheat for comfort conditioning. The units are equipped with variable speed fans which force supply air through a ductwork distribution system. The ductwork is connected to Variable Volume Units (VVUs) which can be controlled to maintain a specific set point such as an office temperature. Each facility has a smoke exhaust system which is capable of purging the volume of the building. This is ideal for gaseous suppression purging, if required by the tenant. Electrical Systems Utility Capacity: Located on the Innovation Park campus, two 100 kv Duke Energy feeders (North Charlotte Black and North ON-SITE SUBSTATION DUKE ENERGY AT INNOVATION SUBSTATION PARK 1
7 Page 7 Charlotte White) fed from two separate substations (North Charlotte Substation and Harrisburg Substation). Each feeder can provide approximately 40 MW. Two 20 MVA Duke Energy forced air substation transformers to step the voltage down to kv. Redundant capacity is approximately 18 MW. Campus Distribution: 1200A 15 kv medium voltage A and B side switchgear with a normally closed tie breaker. 1200A individual medium voltage distribution circuit breakers with relay over current protection. Redundant 5 MW underground feeders (Feeders 2A and 2B) from the 15 kv medium voltage switchgear serve the unit substations in the CyberFortress Manual throw over switches at each unit substation allow the source to be transferred to the alternate source. Three (3) 2000 kva unit substations within the CyberFortress step the voltage down to 480V. MEDIUM VOLTAGE DISTRIBUTION CIRCUITS Plumbing & Fuel Systems Plumbing: Potable water is provided by City source. Backflow prevention is provided at service entrance and on mechanical system make up. Storm water is removed by roof drains. The underground storm water is directed to a campus retention pond and removed from site to the
8 Page 8 municipal storm water system. Fuel Systems: Bulk Fuel Storage: Welded steel above ground tanks located in earthen clay berm containment area. Fuel Storage Capacity: 2-250,000 gallon tanks 2-100, 000 gallon tanks 500,000 gallon containment berm Diesel fuel is piped in a loop INNOVATION PARK FUEL STORAGE FIELD around the campus. The loop currently serves 8 generator sets located around the campus and the boilers. The boilers are dual fuel with the primary source being natural gas. Fire Suppression Systems Campus Loop: The campus is served by a 10 loop which is fed by 12 city main off of IBM Drive which is fed by a 16 line on WT Harris Blvd. This 16 main is fed from two additional, diverse mains. Loop pressure is boosted by diesel engine driven pumps connected to a 250,000 gallon above ground water storage tank. 20 loop isolation valves installed in the main loop. Two diesel powered fire booster pumps (175hp each) feed the loop in an N+1
9 Page 9 topology. Main loop pumps rated for 1500 gpm at 125 psi boost. Latest NFPA required annual pump test produced 130 psi discharge with 6 psi suction at a flow rate of 1489 gpm. The resulting 124 psi boost is 99% of design rating. 28 Hydrants (hand use only) are fed by loop 47 8 service entrance lines are in use and fed from the main loop. Tested Quarterly per NFPA requirements. Main control valves are locked and have tamper switch. Fiber / Telecom Infrastructure Building Topology: Two (2) service provider demarcation rooms, East & West. East Demarcation Room [EDR]: Six (6) 4 conduits from the underground telecom manhole system. Providers: AT&T, Verizon, TW Telecom, Zayo Networks and Time Warner Cable have services available from the EDR. West Demarcation Room [WDR]: Has conduit infrastructure from the East Demarcation Room and from diverse underground entry. TW Telecom has redundant fiber to this room. AT&T and TW telecom have services available from WDR. There is a cable tray system between the EDR, WDR and The CyberFortress Data Center, enabling easy routing and redundant pathways from the Demarcation Rooms to the tenant.
Wholesale Data Center Suites Available Now
Wholesale Data Center Suites Available Now FROM 2,500 to 100,000 Sq Ft A secure, fortified Mission Critical data center facility located in Innovation Park, Charlotte, NC Scalable data center suites available
More informationData Center:Build-to-Suit
Data Center:Build-to-Suit A fortified 100,000 SqFt mission critical build-to-suit constructed on a secured 5 acre parcel at Innovation Park Charlotte, NC On-Site 120MW Substation Sourced from Two Independent
More informationNEW JERSEY CENTER OF EXCELLENCE
Overview NEW JERSEY Page 1 The Plant (CUP) provides electricity via a cogeneration system, chilled water for environmental cooling, steam for heating, and compressed air primarily for HVAC control Serves
More informationCOMMODITIZING THE DATA CENTER MARKET
COMMODITIZING THE DATA CENTER MARKET Site Summary The building at 1360 Kifer Road has approximately 94,500 SF of server and support space and is currently divided into two independent data center areas.
More informationThe main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.
MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating
More informationUniversity of Maryland College Park District Energy System. IDEA Campus Energy Conference February 9, 2012
University of Maryland College Park District Energy System IDEA Campus Energy Conference February 9, 2012 UMCP District Energy System The University of Maryland district energy system consists of a well
More informationNORTHERN VIRGINIA ONE (NoVa) DATA CENTER OVERVIEW
VAZATA 9651 Hornbaker Road Manassas, VA 20109 VAZATA.COM VAZATA's NoVa One data center located at 9651 Hornbaker Road in Manassas, Virginia is engineered from the ground up to deliver highly reliable and
More informationUTILITIES AND ENERGY MANAGEMENT
UTILITIES AND ENERGY MANAGEMENT University of Texas at Austin increases investment in co-generation to achieve greater utility reliability and economy. ENVIRONMENTAL BENEFITS AND ENERGY SAVINGS Power plant
More informationTour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units
More information100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G
100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the
More informationMinimizing Impact of Electric Utility Outages with Backup Generation
Minimizing Impact of Electric Utility Outages with Backup Generation Introduction of the Speaker Michael Dempsey, PE Senior Electrical Engineer Carter & Burgess, Inc. Energy & Power Solutions Facility
More informationsan francisco//usa data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in San Francisco, USA. We can colocate standard rack-mountable servers
More informationData Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
More informationExperience Matters...
Experience Matters... Travelport Data Center offers confidence and space to meet your demanding IT needs Transwestern presents the Travelport Data Center in Denver, Colorado totaling 267,000 SF with 121,600
More informationAT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)
AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:
More informationColumbia University Master Planning & Optimization
Columbia University Master Planning & Optimization February 20, 2014 Mr. Frank Martino Vice President, Operations 1 Agenda Columbia University Campus District Energy Overview Evolution of Columbia s District
More informationDavid Payne, P.E. Associate Director February 18, 2014
David Payne, P.E. Associate Director February 18, 2014 Overview of Texas A&M University State's first public institution of higher education, was opened on Oct. 4, 1876 as the Agricultural and Mechanical
More informationOPERATOR - FACILITY ADDRESS - DATE
. Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.
More informationElement D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
More informationIron Hill Corporate Center Newark, DE
Iron Hill Corporate Center Newark, DE Delaware s Premier Suburban Office Park Contact: John Kaczowka (302) 661-6709 or Brian Hopkins (302) 661-6712 Total Project Size 463,085 RSF Red Wing Built in 1988
More informationSan Francisco State University Campus Master Plan. Chapter 10. Campus Infrastructure
San Francisco State University Campus Master Plan Chapter 10. 10. The master plan projects the infrastructure needs of the campus for the planning horizon, to the year 2020. The following discussion focuses
More informationAT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)
AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.
More informationDATA CENTERS. VAZATA Headquarters: 6900 Dallas Parkway, Suite 800 Plano, TX 75024 VAZATA.COM
DATA CENTERS VAZATA Headquarters: 6900 Dallas Parkway, Suite 800 Plano, TX 75024 VAZATA.COM DAL I MIDWAY ROAD CARROLLTON TX OVERVIEW 4025 Midway Road is a full service, enterprise-class data center colocation
More informationPOLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747
POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609
More informationKU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationPerforming Arts Research/Lab Campus Life Athletics Student Housing Academics Campus Infrastructure Food Services
Performing Arts Research/Lab Campus Life Athletics Student Housing Academics Campus Infrastructure Food Services York State College Pittsburgh www.ba-inc.com Barton Education has provided MEP design services
More informationHow To Visit An Internet Data Center
AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina
More informationAT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)
AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA
More informationHVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
More informationSolveXia Business Continuity Planning
Business continuity planning is the term we use to describe all the steps we take at SolveXia to ensure that our service is up and running when you need it. As a 'Software as a Service' provider, our aim
More informationF O R S A L E F O R L E A S E
F O R S A L E F O R L E A S E 3 0, 0 0 0 S F T R I A N G L E D A T A C E N T E R RALEIGH DURHAM AREA CARY, NORTH CAROLINA Email: doug@five9sdigital.com Phone: 704.651.2210 Online: www.five9sdigital.com
More informationX-tier Data Facility. Prepared by X-tier SAE Corporation
X-tier Data Facility Company Profile X-tier Corporation X-tier is based in Leawood, Kansas. X-tier provides business agnostic, security hardened, custom and turnkey Cloudbased software systems, services,
More informationAT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA)
AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA) Site Biography Market Area: Washington, DC Area Location: Ashburn, VA 20147-6011 Address: All deliveries should be sent to
More informationN O W A V A I L A B L E
N O W A V A I L A B L E 5 0, 0 0 0 S F P O W E R E D S H E L L D A T A C E N T E R I I Data Center Park Catawba County, North Carolina Contact Doug Hollidge for more information Email: doug@five9sdigital.com
More informationDATA CENTERS. VAZATA Headquarters: 6900 Dallas Parkway, Suite 800 Plano, TX 75024 VAZATA.COM
DATA CENTERS VAZATA Headquarters: 6900 Dallas Parkway, Suite 800 Plano, TX 75024 VAZATA.COM OVERVIEW VAZATA's NoVa One data center located at 9651 Hornbaker Road in Manassas, Virginia is engineered from
More informationLEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT.
LEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT. THE SCALE TO SUPPORT GLOBAL ENTERPRISE IT Designed and equipped to meet
More informationDepartment of Administration DATA CENTER Two Phase Approach Located at the State Defense Building
DATA CENTER Two Phase Approach Located at the State Defense Building July 17, 2015 Compiled by: Office of Facilities and Property Management 800 SW Jackson, Suite 600 Topeka, Kansas 66612-1216 i I. Programming
More information215 W. Ohio St. 5th Floor Chicago, IL 60564. Enterprise-Class Security, Performance and Redundancy
215 W. Ohio St. 5th Floor Chicago, IL 60564 Call Us Toll-Free 1 (866) 817-2811 Follow Us @SingleHop Like Us facebook.com/singlehop Phoenix #1 (PHX-1) Enterprise-Class Security, Performance and Redundancy
More informationLocation. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport
Welcome Zenium Istanbul One provides 12,000 square metres of high specification technical space across three purpose-built data centers. It is Turkey s first wholesale data center offering; the data halls
More informationSecond Place: Industrial Facilities or Processes, New
Second Place: Industrial Facilities or Processes, New Photo: Paul Howell Texas Medical Center in Houston is the largest medical center in North America. It has a chilled water system of 160,000 tons. Big
More informationMiami University Design Standards
Miami University Design Standards INDEX General Division 01 Supplemental Conditions Division 02 Existing Conditions Division 03 Concrete Division 04 Masonry Division 05 Metals Division 06 Wood, Plastics,
More informationData Center Commissioning: What you need to know
Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationPlanned and Emergency Utility Outage Guidelines
Revised: April 4, 2014 GUIDELINES: PURPOSE: The purpose of these guidelines is to define roles and responsibilities in requesting, coordinating scheduling, and executing utility outages and restoration
More informationData Centre Stockholm II, Sweden Flexible, advanced and efficient by design.
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Equinix Telecity Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 se.info@telecity.com www.telecitygroup.se
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationExample Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
More informationN O W A V A I L A B L E
N O W A V A I L A B L E 5 0, 0 0 0 S F P O W E R E D S H E L L D A T A C E N T E R I I Data Center Park Catawba County, North Carolina S P E C I F I C A T I O N S Contact Doug Hollidge for more information
More informationUTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN
Page 1 of 27 UTILITIES DEPARTMENT NORTH CAMPUS DISASTER RECOVERY PLAN Page 2 of 27 Table of Contents 1. OBJECTIVE... 4 2. SCOPE... 4 3. COMMUNICATION... 4 4. LOSS OF NATURAL GAS SUPPLY... 5 5. LOSS OF
More informationAvailable Princeton Area Data Center / Disaster Recovery Lab / R&D
Available Princeton Area Data Center / Disaster Recovery Lab / R&D As exclusive listing agent, The Schultz Organization is pleased to offer space available at 109 Morgan Lane. is part of the Enterprise
More informationCase Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
More informationPAYGO for Data Center -- Modular Infrastructure
PAYGO for Data Center -- Modular Infrastructure Introduction The infrastructure costs for Data Centers are increasing at a significant pace. Construction costs and their environmental impact are also soaring.
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationDenver International Airport Total Facility Optimization. Josh Foerschler Aurom Mahobian
Denver International Airport Total Facility Optimization Josh Foerschler Aurom Mahobian AGENDA DIA Intro BMcD-DIA History Optimization Projects Results Conclusion Denver International Airport Opened February
More informationDallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX
Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX March 10, 2009 Agenda DFW Capital Development Program
More informationDatacentre London 1. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk
Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. At we own and manage 30,000 square feet of highly available, geographically diverse
More information21.1 Functions, Basic Configuration, and Interfaces
21 (6.2.M) Site Services Building 21.1 Functions, Basic Configuration, and Interfaces 21.1.1 Functions The primary functions performed by the site services building are to house, support, provide a suitable
More informationSanta Clara, CA 95054
Leading-Edge Datacenter Facility Silicon Valley GENERAL In excess of 41,000 sq. ft. of raised floor 9 MVA of utility power into facility Purpose built Green Datacenter Sutton Roley Lic. 00793235 (408)
More information19 Site Location, Design and Attributes. Site Location, Design and Attributes
1 Site Location, Design and Attributes The Primary Data Center shall be physically located on Oahu, Hawaii. 2 Site Location, Design and Attributes The Primary Data Center shall be located at least 1 mile
More informationHVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
More informationDatacentre Studley. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk
Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. At we own and manage 30,000 square feet of highly available, geographically diverse
More informationData Center Planning. PUE Overview
Data Center Planning PUE Overview Steve Carter, Americas Managing Principal Charles Prawdzik Jr., Project Manager HP Critical Facility Services delivered by EYP Mission Critical Facilities, Inc. 2008 Hewlett-Packard
More informationISOMEDIA COLOCATION WWW.ISOMEDIA.COM/COLOCATION
ISOMEDIA COLOCATION WWW.ISOMEDIA.COM/COLOCATION Your business needs a robust infrastructure that is secure, cost effective and reliable in order to remain competitive in today s market. ISOMEDIA s colocation
More informationCHICAGO S PREMIERE DATA CENTER
CHICAGO S PREMIERE DATA CENTER White City collocation was founded in June, 2010 by a highly experienced industry executive in conjunction with several investment companies. The strategy of White City is
More informationOPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa
OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is
More informationNYC Department of Education Building Condition Assessment Survey 2014-2015 BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 10004
School: InspectionId Asset Data Inspection Type Building Assessment Survey 204-205 BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 0004 Time In Last Edited 255 MECHANICAL 205-05-8 09:00AM
More informationMechanical, Plumbing, and Fire Protection Conditions
Mechanical, Plumbing, and Fire Protection Conditions Mechanical Conditions The mechanical systems within the building consist of a combination of the original 1926 systems and renovations that occurred
More information1301 Fannin. Houston Data Center & Office Facility
1301 Fannin & Office Facility 1301 FANNIN Building Features Building Location Building Typical Floor plans Systems Infrastructure Amenities BUILDING FEATURES YEAR BUILT/RENOVATED: 1984/2009 TOTAL LEASE
More informationFIRE DETECTION BUILDING AUTOMATION CAPITAL PROJECTS HVAC SERVICES SECURITY SYSTEMS PROJECT MANAGEMENT. www.msssolutions.
HVAC SERVICES BUILDING AUTOMATION FIRE DETECTION SECURITY SYSTEMS CAPITAL PROJECTS 877-372-4344 PROJECT MANAGEMENT HVAC SERVICES Superior Technical Staffing Unrivaled Customer Service Industry-wide Reputation
More informationDigital Chicago. 600 south FeDeraL - chicago 9333 9377 grand ave - FranKLin ParK 350 east cermak - chicago
Digital Chicago 600 south FeDeraL - chicago 9333 9377 grand ave - FranKLin ParK 350 east cermak - chicago The Digital Chicago portfolio consists of three state-of-the-art data center facilities: 600 South
More informationSubject: County of Los Angeles Data Center Space Requirement
Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,
More informationNOTRE DAME UTILITIES DEPARTMENT
NOTRE DAME UTILITIES DEPARTMENT TABLE OF CONTENTS History 2 Location and Facilities 5 Energy and Environmental Stewardship 6 Systems and Equipment 7 Distribution Systems 13 Departmental Services 15 HISTORY
More information2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationWorld s Greenest High Performance Data Center
World s Greenest High Performance Data Center EcoDataCenter Sustainability for future generations Our Services Colocation Data Center for Mission Critical Requirements Lockable racks, cages, private rooms
More informationTitle: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
More informationTech Report 2: Electrical System Existing Conditions
, Tech Report 2: Electrical System Existing Conditions Oct 12, 2013 Yucheng Lu Lighting/Electrical AE Faculty Consultant: Dr. Shawn Good Executive Summary This report is a summary of my study about the
More informationProduct Data Bulletin
Product Data Bulletin Adjustable Frequency Drives and HVAC Systems An Application Guide September, 1994 Raleigh, NC, U.S.A. INTRODUCTION All buildings pose the same problem: how to heat or cool the air
More informationCOOK PHYSICAL SCIENCE BUILDING RENOVATIONS. Engineering & Architectural Services CONCEPT DESIGN MAY 11, 2012. BVH Project No.
COOK PHYSICAL SCIENCE BUILDING RENOVATIONS Civil Structural Mechanical Electrical Technology Engineering & Architectural Services CONCEPT DESIGN Commissioning 50 Griffin Road South Bloomfield, CT 06002
More information1.2 Refrigerant Equipment. General
Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or
More informationWater cooled chiller plant (cp/vs)
Data Center Water cooled chiller plant (cp/vs) Design Envelope File No: 9.573 Date: december 16, 2014 Supersedes: 9.573 Date: november 14, 2014 design envelope s performance improvements are among the
More informationRobson Forensic Engineers, Architects, Scientists & Fire Investigators
PROFESSIONAL EXPERIENCE 2015 to Robson Forensic, Inc. present Associate Provide technical investigations, analysis, reports, and testimony for failure analysis toward the resolution of commercial property
More informationData Center CH1. Elk Grove Village, IL
Data Center CH1 Elk Grove Village, IL powerful/ efficient /reliable solutions > Data Center CH1 ABOUT DUPONT FABROS TECHOLOGY (DFT) DFT is a leading owner, developer, operator and manager of wholesale
More informationTES for Medical Center
First Place: Industrial Facilities or Processes, New This article was published in ASHRAE Journal, November 2012. Copyright 2012 ASHRAE. Reprinted here by permission from ASHRAE at www.tecothermalenergy.com.
More informationPresentation to Senate Select Committee on Government Facilities: Deferred Maintenance for State Supported Living Centers and State Hospitals
Presentation to Senate Select Committee on Government Facilities: Deferred Maintenance for State Supported Living Centers and State Hospitals Les Butler Associate Commissioner for Business and Regional
More informationCurrent state of plant Functioning as a peak and emergency centre. Statistics Accumulated operating hours:
Current state of plant Functioning as a peak and emergency centre Statistics Accumulated operating hours: D1-2-3-6-7: 43000 to 48000 hrs D4-5: 53000 to 57000 hrs D8: 33000 hrs Layout of the plant Index:
More informationOVERVIEW. Key Attributes
OVERVIEW Welcome to 3000 Skyline Dallas, a purpose-built, powered shell for data centers designed, developed and engineered to accommodate today s technology and tomorrow s growth. 3000 Skyline provides
More informationSecure I Reliable I Flexible COPT DC-6. 9651 Hornbaker Road, Manassas, Virginia
Secure I Reliable I Flexible COPT DC-6 9651 Hornbaker Road, Manassas, Virginia Specialized Space by a Specialized Team 2 C O P T D A T A C E N T E R S O L U T I O N S Corporate Office Properties Trust
More informationCITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN Adopted October 5, 2009 Table of Contents Chapter Description Page 1 Facility Descriptions... 3 1.1 Municipal Power Plant, 1001 Park
More informationANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
More informationAbout Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services
About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier
More informationCurrent as of 11/10/08 1 of 1
BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that
More informationDesign Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)
Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+) 1. In addition to the information scheduled below, the pre-tender designer is responsible for: (i)
More informationData Centre Services. JT First Tower Lane Data Centre Facility Product Description
JT First Tower Lane Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room enviroment with protected incoming power supplies, state-of-the-art security
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
More informationDEVELOPMENT OF A CAMPUS WIDE DISTRICT CHILLED WATER SYSTEM SAMFORD UNIVERSITY
DEVELOPMENT OF A CAMPUS WIDE DISTRICT CHILLED WATER SYSTEM SAMFORD UNIVERSITY Mr. Rick Stephens, Director of Campus Planning Samford University, Birmingham, Alabama Mr. David W. Wade, P. E., President
More informationEstablishment of State s Second Data Center. Business Continuity and Disaster Recovery. North Carolina. Office of Information Technology Services
Establishment of State s Second Data Center North Carolina Office of Information Technology Services National Association of State Chief Information Officers 2008 Recognition Awards Nomination June 2,
More informationSecure I Reliable I Flexible
Secure I Reliable I Flexible COPT DC-6 Tour for CareFirst Agenda» Welcome and Introductions» COPT Data Center Practice and COPT DC-6 Overview» Tour of the data center facility» Qs & As COPT Overview Why
More information