VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES
|
|
|
- George Claud Nicholson
- 9 years ago
- Views:
Transcription
1 VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES C. Schwaegerl*, M.H.J. Bollen, K. Karoui #, A. Yagmur + *Siemens AG, # Tractebel STRI AB + Tubitak PTD SE NC Engineering Germany Sweden Belgium Turkey [email protected] ABSTRACT The hosting capacity for distributed energy resources (DER) identifies the acceptable degree of DER penetration under given circumstances. It depends on various parameters such as the characteristics of the generation units, the configuration and operation of the network, the requirements of the loads as well as national and regional requirements. To determine the hosting capacity and to find ways to expand it by overcoming existing barriers is one subject of the ongoing European research project EU- DEEP. This paper describes the impacts of non-controlled DER units on the resulting voltage profiles as these impacts showed to be a main limitation for the hosting capacity for DER in existing distribution networks. The methodology for the analysis is introduced and basic results of the case studies performed are demonstrated. Generally the hosting capacity for DER can be extended applying different technical measures all leading to additional investments into the network. In future active distributions networks will provide a cost-effective solution to increase DER penetration. IMPACT OF DER ON VOLTAGE PROFILE Voltage control in existing distribution systems is based on radial power flows from the substation to the loads and on the fact that real power magnitude decreases with increasing distance from the substation. But, the introduction of DER in distribution systems impacts the methods of voltage control. DER may change the direction of power flows. This may lead to a reduced performance of the voltage control. It remains required that the system operates with adequate security and within statutory limits,. despite the fact that the Distribution System Operator (DSO) does not exert control over the generation.. Depending on the spatial relationship of loads and generation units, on the type of DER, its active and reactive power output, feeder parameters and loading power flow and therefore voltage can increase or decrease along a feeder. At periods of high generation output and low load, the upper statutory voltage level may be violated, while during periods of low generation and high load problems with the lower statutory limit may be reached. The variations in power output of some types of distributed generation will further lead to an increase in voltage variations. HOSTING CAPACITY FOR DER The hosting capacity for DER identifies the acceptable degree of DER penetration under given circumstances. It is possible to integrate DER units into existing networks as long as its performance is acceptable. The performance depends on different parameters such as the characteristics of the generation units, the operation of the network and requirements of the loads. As soon as the performance drops below the acceptable limit the hosting capacity is exceeded (Figure 1). Performance indices may vary between different countries or even between different DSOs depending on network configuration and operation as well as on the requirements of the loads connected. performance index hosting capacity Figure 1. Definition of the hosting capacity limit penetration level (% DER) If the performance index is not impacted by increasing DER penetration the hosting capacity of the network is unlimited. There are various issues that define the hosting capacity for DER like reliability, power quality, short circuit contribution and fault levels, or transient stability aspects, partly with
2 strong dependencies between different impacts. Actually figure 1 should be a multi-dimensional graph considering all dependencies. But, constraints for the maximum hosting capacity are set as soon as one aspect of the performance index exceeds acceptable limits. Keeping the voltage within acceptable or statutory bandwidths is a major limitation for the introduction of higher amounts of DER into existing networks. The concept of hosting capacity has been developed for cases in which DER integration potentially leads to a reduction of the system performance, mainly to identify barriers for DER integration. There are however situations in which DER may actually bring advantages to system performance, i.e. alleviate heavy loading in distribution systems or improve system reliability. To determine the hosting capacity for all considerable dependencies for both steady state and dynamic behaviour of DER and to find ways to expand it overcoming existing barriers is one subject of the ongoing European research project EU-DEEP (The birth of a EUropean Distributed EnErgy Partnership that will help the large-scale implementation of distributed energy resources in Europe [1]) that is funded by the European Commission under the 6 th framework programme for research and development. Within this project a partnership of 39 utilities, manufacturers, research organisations, professionals, national agencies and a bank, implements with a 29 million budget a demand-pull rather than technology-push approach for massive deployment of DER in Europe. Final results are scheduled for end PERFORMANCE INDICES To quantify the impact of DER units on voltage suitable performance indices and limits have to be defined. It is possible to use overall performance indices as well as indices dedicated to specific customers or to a specific phenomenon that is affected by DER. Further performance indices can be of general nature or express small deviations from an ideal or nominal value thus leading to values starting from 0 % or % increasing or decreasing with increasing DER penetration. In any case hosting capacity is reached if a given limit is exceeded. The main source for indices concerning steady state operation is the European voltage characteristics standard EN A more general approach is to study voltage variations in three different time scales: The percentile of the 10-minute rms voltage averages during one week as in EN50160; Voltage flicker as in IEC ; Voltage variations in the timescale between 3 seconds and 10 minutes [4]. These indices identifying small deviations from an ideal or nominal value correspond to normal operation conditions. Additionally, there are dynamic events in the system like voltage dips, interruptions and large-scale blackouts that also have to be covered, but are out of scope of this paper. DEFINITION OF DER PENETRATION The DER penetration level can be expressed as an absolute value (for example the total installed capacity of all DER units, the number of DER units, the total generated power or energy of all units) or as a relative value. The latter (referred to as % DER) is more convenient when comparing different systems as it is, but will introduce some additional methodological questions. To make the results independent of the system size normalization is needed. The absolute value of the power (rated power or generated power) is divided by a reference value. Commonly used definitions are: Ratio of rated DER power to the local fault level (the short-circuit capacity of the system): The disadvantage of this normalization is that the hosting capacity will be a small value. A load or generation size equal to 10% of the fault level will already cause a very large impact of the system. Further many phenomena depend more on actual power flow than on rating, which especially for renewable sources like wind and sun deviates significantly from the actual power output. Two systems with the same relative penetration level may show a completely different performance. Ratio of rated DER power and transformer rating: For a given voltage level the rating of the HV/MV or MV/LV transformer is related to the fault level, so that this normalization is equivalent to the first definition. Ratio of Active Power (power generated by DER and the total power of the local load): When the ratio is equal to %, all loads are supplied by DER. For studies covering a longer period it must be defined which values are taken for both the numerator and the denominator: minimum, maximum or mean values; each decision leading to different penetration levels. CASE STUDIES To assess the impact of DER power flow simulations are carried out for worst-case situations. Assuming a DER operation at maximum generation capacity at minimum load leads to largest reverse power flows with greatest local voltage change, thus identifying possible violations of acceptable limits. To give general recommendations it was decided to perform a thorough analysis of the effects of DER on voltage control in distribution networks depending on DER penetration level, DER generation technology (inverter, synchronous machines, or induction machines) (see [2] for detailed effects), DER generation characteristics (i.e. constant power output for combined-heat-and-power units, intermittent for solar and wind plants), DER spatial location,
3 network characteristics (load level, feeder design, regional requirements, ), national and regional requirements. Today, DER units do not actively contribute to system control. Therefore only passive distribution networks were considered for the simulations that have been performed in a first step. Several rural, urban and industrial test networks, typical for different European countries, with different sizes and characteristics, have been selected or have been artificially created to perform the simulations. Figure 2 shows the basic structure of an example test network supplying different kind of customers that are equally distributed in typical LV networks with underground cables and overhead lines. Additionally, a distinction was made between MV and LV networks as they have different structures and components; DG resources connected to MV or LV networks have different characteristics in term of reactive power requirements and voltage regulation. 500 m cable, urban network or 5 km ov erhead line, rural network 500 m R=0,156 Ohm/km X=01226 Ohm/km C=235 nf/km 20 kv Sn = 2000 kva Sn = 630 kva Sn = 630 kva Sn = 250 kva 0,4 kv net 1 net 2 net 3 net 4 Figure 2. Example of a test network SIMULATION RESULTS number and type of loads, total installed capacity of the feeder: industry 1200 kw 4 different loads business 800 kw 150 different loads household 400 kw 200 different loads agriculture kw 5 different loads Two examples are presented here to demonstrate the basic results. Example test network As long as there is no active control of distribution networks the injection of active power leads to a voltage rise for customers connected to the distribution feeder. The rise is increasing with increasing feeder length and line impedance. As long as the maximum generation is smaller than the minimum load there is no feedback to higher-level networks. Mostly, there are also no limitations within the feeder considering 10-minute average values. The penetration level can be very high in a certain part of the system, but still rather small in the system as a whole. In the network example presented in figure 2 limitations arise in net 4. Mainly at the end of the feeder (node 6) the voltage exceeds the limits. Additionally, the hosting capacity is significantly smaller when DER units are located towards the end of the feeder (figure 3 and 4). As the location of most DER units depends on the availability of the resource and the territory of the owner that mostly is not the DSO there is only a limited choice for the placement of the sites that can be geographically and electrically remote from load centres. 110 % nodes along the feeder DER kw, cosphi = 1, node2 DER kw, cosphi = 0.9, node2 DER kw, cosphi = 0.9, node4 DER kw, cosphi = 0.9, node6 DER kw, cosphi = 1, node6 Figure 3. Voltage along line in net4, maximum load 115 % nodes along the feeder DER kw, cosphi = 1, node2 DER kw, cosphi = 0.9, node2 DER kw, cosphi = 0.9, node4 DER kw, cosphi = 0.9, node6 DER kw, cosphi = 1, node6 Figure 4. Voltage along line in net4, minimum load It has been assumed in the study that the load is constant for a sufficiently long time to reach a steady-state situation so that the voltage at the MV side of the HV/MV transformer equals the nominal voltage. The tap-changer control of this transformer is thus set to the nominal voltage. No line-drop compensation is used. In terms of EN the voltages resulting from the calculations can be interpreted as the 10-minute rms voltages. If we assume a 106% upper limit for the %-value, the hosting capacity is exceeded for all loading situations for node 6, cos φ = 0.9. For a number of other cases (node 6, cos φ = 1.0 node 4, cos φ = 0.9) the hosting capacity is exceeded only part of the time. Examples of the load shape in case of a working day in winter are presented in figure 5 for the feeder end in net 4. The voltage raise is even higher if the DER units are also feeding in reactive power.
4 % 85 00:00 06:00 12:00 18:00 time 00:00 DER kw, cosphi = 0.9, node6 DER kw, cosphi = 1, node6 DER kw, cosphi = 0.9, node4 Figure 5. Voltage shape, working day in winter, net 4, node 6 Voltage control by on-load tap changers may even worse the situation as they increase the secondary voltage in case of low feeder load. Reverse power flows increase the voltage estimation error at target position and lead to a even higher rise in voltage at DER location at dead-end feeders. Turkish distribution network The Turkish distribution system tested here includes one transformer 12.5MVA, 66/10 kv and three radial cables (figure 6). Normal operation of the distribution system is in radial mode and connections at node F with radial feeders 2 and 3 are normally open. The total load of the system is 3.69 MW, 1.76 MVAr; all loads consuming constant power. External Grid A/66kV B/10 kv TRF41470 LATERAL 1 LATERAL 2 LATERAL 3 Etiler 101 Levent 101 Line C_D C/10 kv Line H_K H/10 kv Line M_N M/10 kv Etiler 102 Levent 102 Line D_E D/10 kv Line K_L K/10 kv Line N_P N/10 kv Etiler 103 Levent 103 E/10 kv L/10 kv P/10 kv F/10 kv Voltage 1 0,9 0,99 0,985 0,98 Without DER Syn 0.5 MW Syn1.5 MW Syn 2 MW A C D E F H K L M N P B Bus Name Figure 7. Voltage profile of buses with different DER power output Dynamic Voltage Stability Without DER loads are supplied by the transformer from the grid. In case of an out of service of the line between nodes B and M dynamic simulations showed an immediate voltage drop at node N from 98.4 % to 97.6 %. With the synchronous generator (output power is 1.5 MW), which is equipped with exciter and governor control system, connected to node N the voltage at node N recovers within seconds after the line between node B and M is opened (figure 8). At the same time the connection between node P and F was closed to supply also the other nodes. Generally, DER showed positive effects on voltage stability raising the voltage and reducing voltage dips Base Case (Without DG) p.u MW DG 0.9 p.u. 1.5 MW DG p.u. Maslak 101 Maslak 102 Maslak Base Case (Without DG) p.u Figure 6. Turkish distribution system Steady State Voltage Stability A synchronous generator with nominal power 4.85 MVA is connected to node N and simulated with 0.5 MW, 1.5 MW, 2 MW power output at power factor 0.98 leading with DER penetration level of 15 %, 40 % and 55 % of total load, respectively. The power output of the generator raises the voltages compared to the base case. The voltage rise is higher due to reactive power support (figure 7). The voltage levels of the nodes in the distribution system also increase with increasing DER penetration level or DER power output power. For higher penetration levels, an overvoltage might occur s 10s 20s 1s 10s 20s Figure 8. Dynamic voltage at bus N without and with DER GENERAL OUTCOMES Even for one phenomenon the hosting capacity is not a fixed value: it depends on various local parameters like structure and degree of automation of the network, type, generation characteristic and spatial location of the DER unit, kind and behaviour of load, climate parameters (in case of wind or solar power), different regional requirements. As it is not possible to quantify the impact of some dependencies to allow comparisons between different national and regional systems values for the hosting capacity should
5 be handled with care. The hosting capacity may by increased by technical means, including: Reconfiguration or upgrading of the network (upgrading conductors and transformer, installation of new lines or substations), Connection of DER units at higher voltage levels or closer to the feeder, Reduction of primary substation voltage, Operation of generator at leading power factor, Temporarily constraining of DER generation according to network loading conditions. In any case the solutions imply additional costs in term of capital investment and ongoing operating costs. Vice versa, it is always possible to increase the hosting capacity with additional investments (figure 9 and figure 10). For that reason, the integration of DG into distribution systems becomes an economic issue rather than a technical one. Who is paying for the measures is an important further discussion, but is out of the scope of this paper. As it is generally much more cost-effective to implement monitoring, communications and control facilities than it is to reinforce the network to accommodate the same level of DER penetration active management methods will be the future way to overcome barriers for DER integration and will therefore erase all limits for the hosting capacity. FUTURE RESEARCH Preliminary results have been shown in this paper. Analysis and simulations will continue considering more active distribution networks. Further there are strong interacts of DER penetration with operation, control, or stability. All these topics will also be handled within the EU-DEEP project. Publicly accessible reports on the various topics will be available for download at ACKNOWLEDGEMENT This work is funded by the European Commission as part of the EU-DEEP project under grant SES6-CT REFERENCES performance index increasing additional investments limit penetration level (% DER) Figure 9. Performance index for increasing investments [1] [2] V. Knayazkin, T. Ackermann, 2003, "Interaction between the distributed generation and the distribution network: operation, control and stability aspects", CIRED 2003, paper 4-40 [3] T. Bopp, A. Shafiu, I. Cobelo, I. Chilvers, N. Jenkins, G. Strbac, H. Li, P. Crossley, 2003, "Commercial and technical integration of distributed generation into distribution networks", CIRED 2003, paper R4-45. [4] M.H.J. Bollen, M. Häger, C. Schwaegerl, 2005, "Quantifying voltage variations on a time scale between 3 seconds and 10 minutes", this conference. hosting capacity additional investments Figure 10: Hosting capacity as a function of the investment. ACTIVE DISTRIBUTION NETWORKS AS A MEANS TO INCREASE DER PENETRATION Active management techniques enable the DSO to maximise the use of the existing circuits by taking full advantage of generator dispatch, control of transformer taps and any reactive compensation devices in an integrated manner [3]. It provides real time network monitoring and control at key network nodes combined with state estimation and real time modelling for critical issues. Coordinated voltage control communicates with generator controls (i.e. controlling power factor of synchronous generators and inverters), loads and network devices, such as reactive compensators (preferably at the point of DER connection to the network), voltage regulators, and on-load tap changers.
Distributed Generation and Power Quality Case Study
16 Distributed Generation and Power Quality Case Study Vu Van Thong and Johan Driesen C16.1 DISTRIBUTION NETWORK A segment of an existing Belgian medium-voltage distribution system is used to study the
APPLICATION NOTE. Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution
APPLICATION NOTE Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution INCREASING PV HOSTING WITH EMPOWER TM SOLUTION Executive Summary Distributed solar photovoltaic
Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns
Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns Mehmet H. Cintuglu, [email protected], Armando Altamirano, [email protected] Osama A. Mohammed, [email protected] Energy Systems
ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe
NETWORKS ESB Networks Response to ERGEG Consultation on Voltage Quality Regulation in Europe Date: 22 February 2007 Distribution System Operator ESB Networks Page 1 of 12 Contents 1.0 INTRODUCTION...3
De Jaeger, Emmanuel ; Du Bois, Arnaud ; Martin, Benoît. Document type : Communication à un colloque (Conference Paper)
"Hosting capacity of LV distribution grids for small distributed generation units, referring to voltage level and unbalance" De Jaeger, Emmanuel ; Du Bois, Arnaud ; Martin, Benoît Abstract This paper revisits
Voltage regulation in distribution systems - Tap changer and Wind Power
CODEN:LUTEDX/(TEIE-5270)/1-59/(2010) Industrial Electrical Engineering and Automation Voltage regulation in distribution systems - Tap changer and Wind Power David Sáez Romero D of Industrial Electrical
PROGRAM. Giga Sponsors. Supported by. Media Partner. Organizer
PROGRAM Giga Sponsors Supported by Media Partner Organizer Harnessing PV inverter controls for increased hosting capacities of smart low voltage grids Recent results from Austrian research and demonstration
Network Consulting for Power Grid Optimization
Network Consulting for Power Grid Optimization Project experience in India Network Consulting Competences Page 1 Our worldwide representation Manchester The Hague Denver Schenectady San Diego Houston Mexico
SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS
Sawsan Henein AIT Austrian Institute of Technology Electric Energy Systems Research Group SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS Sustainable Places 2015 Savona,
Size template. Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer
Size template Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer The average system size has doubled since 2010 Key Network Issues Reverse power on up to 12 off 11 kv feeders
Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process
Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process Presented by: Marianne Mannschreck Date: Welcome A Look at the Net Energy Metering
What Matters for Successful Integration of Distributed Generation
What Matters for Successful Integration of Distributed Generation Thomas Ackermann Energynautics GmbH, Germany [email protected] Expert User of DIgSILENT PowerFactory for Power Systems Studies
RENEWABLE ENERGY INFEED R Herman, M Malengret and CT Gaunt University of Cape Town, South Africa
RENEWABLE ENERGY INFEED R Herman, M Malengret and CT Gaunt University of Cape Town, South Africa Technology and tariffs for renewable energy in-feed at LV and MV Ron Herman : Performance of LV feeders
Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply. www.siemens.com/siestorage
Totally Integrated Power SIESTORAGE The modular energy storage system for a reliable power supply www.siemens.com/siestorage Totally Integrated Power (TIP) We bring power to the point. Our products, systems,
ADMS(Advanced Distribution Management System ) in Smart Grid
ADMS(Advanced Distribution Management System ) in Smart Grid 柯 佾 寬 博 士 Yi-Kuan Ke, Ph.D. 2014/03/28 Smart Grid Solution Smart Grid Solution Overview Smart Grid Solutions Smart Network Operation - Distribution
Advanced Protection of Distribution Networks with Distributed Generators
Date:- 8 10 March 2011 Venue: University of Manchester EES-UETP Course title Advanced Protection of Distribution Networks with Distributed Generators Peter Crossley Director of the Joule Centre School
Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering
Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward
CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE
CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING
TERMS AND CONDITIONS
Virginia Electric and Power Company TERMS AND CONDITIONS XXIV. GENERATOR INTERCONNECTION STANDARD Electric generator interconnection service includes only the ability to interconnect an electric generator
Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid
Pakistan Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid Final Report: Executive Summary - November 2015 for USAID Energy Policy
PV GRID. Efficient Grid Integration of European PV: Project Results. Jörg Mayer, Managing Director German Solar Industry Association (BSW-Solar)
PV GRID Efficient Grid Integration of European PV: Project Results Jörg Mayer, Managing Director German Solar Industry Association (BSW-Solar) 16th September 2014 1 PV GRID Key facts An Intelligent Energy
ACTIVE NETWORKS: DEMAND SIDE MANAGEMENT & VOLTAGE CONTROL. Master of Science in Energy Systems and the Environment. Jayanth Krishnappa
ACTIVE NETWORKS: DEMAND SIDE MANAGEMENT & VOLTAGE CONTROL A thesis submitted in partial fulfilment for the requirement of degree in Master of Science in Energy Systems and the Environment By Jayanth Krishnappa
Operating the power system while enabling more renewables : which solutions?
Operating the power system while enabling more renewables : which solutions? Sébastien GRENARD EDF R&D 22/06/2010 New environment for power systems design and operation European targets and attractive
Rule 5.500 Fast Track Analysis for National Life Insurance Co.
Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION
Venteea A Smart Grid demonstrator for the DRES integration on the MV distribution networks. www.venteea.fr/en/
Venteea A Smart Grid demonstrator for the DRES integration on the MV distribution networks www.venteea.fr/en/ Lille, le 26 novembre 2015 Agenda Project overarching objectives The consortium The added value
LV4MV: A CONCEPT FOR OPTIMAL POWER FLOW MANAGEMENT IN DISTRIBUTION GRIDS, USING DER FLEXIBILITY
LV4MV: A CONCEPT FOR OPTIMAL POWER FLOW MANAGEMENT IN DISTRIBUTION GRIDS, USING DER FLEXIBILITY Emmanuelle VANET Gaspard LEBEL Raphaël CAIRE G2Elab France G2Elab France G2Elab - France [email protected]
ENEL plans for storage introduction in Italian distribution network
ENEL plans for storage introduction in Italian distribution network Network technologies system manager Enel SpA Infrastructure and Network division Accumulo e rinnovabili: i sistemi e le tecnologie verso
Distributed Generation: Feeder Hosting Capacity. Dean E. Philips, P.E. FirstEnergy Service Corp Manager, Distribution Planning & Protection
Distributed Generation: Feeder Hosting Capacity Dean E. Philips, P.E. FirstEnergy Service Corp Manager, Distribution Planning & Protection Distributed Generation: Feeder Hosting Capacity Factors that contribute
GPS Interfacing of Banediya Feeder (M.P) Using MI Power Software
GPS Interfacing of Banediya Feeder (M.P) Using MI Power Software Swati Paliwal 1, V.K Tayal 2, H.P Singh 3 Assistant professor, Department of Electrical & Electronics Engineering, Northern India Engineering
How To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
Solar Power Plant Design and Interconnection
Solar Power Plant Design and Interconnection Wind & Solar Super Session July 27, 2011 E.H. Camm, S.E. Williams S&C Electric Company Outline Introduction Utility-scale PV power plant Grounding Reactive
Principles of Distribution charging:
Principles of Distribution charging: Electricity networks Introduction A three-stage approach involves the following steps: 1. The analysis and quantification of costs. The cost concept that is relevant
EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID
Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group
7. Reactive energy compensation
593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical
Context: significant penetration of DG = increased risks for system security
Distributed Generation: towards an effective contribution to power system security IEEE Tampa GM 2007: Panel on Impact of Dispersed Generation on Power System structure & security Bruno Meyer Outline Context:
Guidelines for Large Photovoltaic System Integration
1 Guidelines for Large Photovoltaic System Integration Silviu Darie, PhD(EE), PE(EE) Abstract- The paper summarizes the result of a research project funded by the Department of Energy (DOE) in collaboration
Experimental Verification of Advanced Voltage Control for Penetration of PV in Distribution System with IT Sectionalizing Switches
21, rue d Artois, F-75008 PARIS C6 _113 _2012 CIGRE 2012 http : //www.cigre.org Experimental Verification of Advanced Voltage Control for Penetration of PV in Distribution System with IT Sectionalizing
LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University
LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University PURPOSE: The purpose of this lab is to introduce PSS/E. This lab will introduce the following aspects of PSS/E: Introduction to
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
Power transformers. Special transformers Railway
Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together
Chapter 1. Network Structures
Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V
Grid codes for renewable energy integration
Rabat 2015-06-02 Grid codes for renewable energy integration Harald G Svendsen SINTEF Energy Research Norway [email protected] Work Package leader for grid integration activities in the EuroSunMed
Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas
Electric Power Systems An Overview Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Overview Power Generation Conventional power generation Power generation from renewables
A Network Reference Model for Distribution Regulation and Planning: the Spanish Case
A Network Reference Model for Distribution Regulation and Planning: the Spanish Case Jesús Pascual Peco González Instituto de Investigación Tecnológica (IIT) Universidad Pontificia Comillas, Madrid http://www.iit.upco.es
Smart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems
Smart Grid and Renewable Energy Grid Integration Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems 1 How Smart Can We Make This Grid? 2 Smart Grid Drivers Need to Use
Integration Capacity Analysis Workshop 11/10/15 California IOU s Approach
Integration Capacity Analysis Workshop 11/10/15 California IOU s Approach READ AND DELETE For best results with this template, use PowerPoint 2003 10 November 2015 Background and Importance of ICA Definition:
Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report
Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives (Required per CPUC Decision No. C10-1328) Final Report (Submitted with Public Service s 2011 ERP) Executive Summary The objective
ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH
Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT
COMPLIANCE REVIEW OF 2006/07 ASSET MANAGEMENT PLAN. Top Energy Limited
PB ASSOCIATES COMPLIANCE REVIEW OF 2006/07 ASSET MANAGEMENT PLAN Prepared for PB Associates Quality System: Document Identifier : 153162 Top Energy Final Report Revision : 2 Report Status : Final Date
Comparison of GIS and AIS systems for urban supply networks
Comparison of GIS and AIS systems for urban supply networks Studies carried out by ABB show that for urban supply networks the combination of HV gas-insulated switchgear (GIS) and HV cable has important
SHE Transmission. 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015
SHE Transmission 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015 Summary This paper presents SHE Transmission s views and approach on the impact of transmission losses on the transmission
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
13. Electrical network design methodology and application example
873 13. Electrical network design methodology and application example 874 13. ELECTRICAL NETWORK DESIGN METHODOLOGY AND APPLICATION EXAMPLE The profitability of an industrial installation is directly linked
MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION
MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION REPORT ON NETWORK RELIABILITY ASPECTS OF THE CHOICE LINE VERSUS CABLE FOR
Optimal Distributed Photovoltaic Generation Capacity: Puerto Rico Case Study
Optimal Distributed Photovoltaic Generation Capacity: Puerto Rico Case Study Capstone Research Project April 24, 2015 Daniel Schultz Jennifer Baker Michael Liu Jeffrey Smith Interdisciplinary Telecom Program
ASSET MANAGEMENT LCNI 2014 Wednesday 22 nd October. Jennifer Woodruff Innovation & Low Carbon Networks Engineer
ASSET MANAGEMENT LCNI 2014 Wednesday 22 nd October Jennifer Woodruff Innovation & Low Carbon Networks Engineer Asset Management Efficient asset management ensures that risk is effectively managed and returns
Distributed Generation and the Impact on a Distribution System. Brian Lassiter Technical Sales Engineer
Distributed Generation and the Impact on a Distribution System Brian Lassiter Technical Sales Engineer Company Overview Founded in 1989 in Abilene, TX Industry leader in Engineering and Operations Utility
Impact of Distributed Generation on Voltage Profile in Deregulated Distribution System
Impact of Distributed Generation on Voltage Profile in Deregulated Distribution System W. EL-KHATTAM M. M. A. SALAMA Electrical & Computer Engineering, Waterloo University, Ontario, Canada Abstract: Due
Networks. ESB Networks Ltd Basis of Charges for Connection to the Distribution System. Commercial and Customer Asset Management ESB Networks Ltd.
Networks ESB Networks Ltd Basis of Charges for Connection to the Distribution System Revision Date: 14/01/20010 Revision No.: 1 Document No: DOC-10129-AXQ Issued by: ESB Networks Ltd Approved by : CER
SOFTWARE FOR THE OPTIMAL ALLOCATION OF EV CHARGERS INTO THE POWER DISTRIBUTION GRID
SOFTWARE FOR THE OPTIMAL ALLOCATION OF EV CHARGERS INTO THE POWER DISTRIBUTION GRID Amparo MOCHOLÍ MUNERA, Carlos BLASCO LLOPIS, Irene AGUADO CORTEZÓN, Vicente FUSTER ROIG Instituto Tecnológico de la Energía
FUNCTIONS AND CAPABILITIES OF PV INVERTERS TO BE PART OF A SMART GRID
FUNCTIONS AND CAPABILITIES OF PV INVERTERS TO BE PART OF A SMART GRID As the number of decentralized energy generators grows, also the need for an intelligent power grid rises. In the Smart Grid of the
Wind Turbine Operation in Power Systems and Grid Connection Requirements
Wind Turbine Operation in Power Systems and Grid Connection Requirements A. Sudrià 1, M. Chindris 2, A. Sumper 1, G. Gross 1 and F. Ferrer 1 1 Centre for Technological Innovation in Static Converters and
Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION
Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Outline What is Reactive Power and where does it come from? Why is it important?
Integrating distributed generation into electric power systems: A review of drivers, challenges and opportunities
Electric Power Systems Research 77 (2007) 1189 1203 Integrating distributed generation into electric power systems: A review of drivers, challenges and opportunities J.A. Peças Lopes a,, N. Hatziargyriou
BL20A0501 Electricity distribution technology. Introduction Jarmo Partanen
BL20A0501 Electricity distribution technology Introduction Jarmo Partanen Introduction to ED Prof. Jarmo Partanen, D.Sc Jukka Lassila Topics of lectures Introduction to Electricity Distribution, 27.10
Brochure Introducing HVDC
Brochure Introducing HVDC ABB and HVDC The world s first commercial high-voltage direct current (HVDC) link, situated between the Swedish mainland and the island Gotland, was delivered by ABB already in
PSEG-LONG ISLAND SMART GRID SMALL GENERATOR INTERCONNECTION SCREENING CRITERIA FOR OPERATING IN PARALLEL WITH LIPA S DISTRIBUTION SYSTEM
PSEG-LONG ISLAND SMART GRID SMALL GENERATOR INTERCONNECTION SCREENING CRITERIA FOR OPERATING IN PARALLEL WITH LIPA S DISTRIBUTION SYSTEM PSEG-LI SGSGIP DG Screening Criteria 5-29-14 Table of Contents I.
16 West Coast Regional Plan
16 West Coast Regional Plan 16.1 Regional overview 16.2 West Coast transmission system 16.3 West Coast demand 16.4 West Coast generation 16.5 West Coast significant maintenance work 16.6 Future West Coast
SmartGrids SRA 2035. Summary of Priorities for SmartGrids Research Topics
SmartGrids SRA 2035 Summary of Priorities for SmartGrids Research Topics Version 19 June 2013 Setting Priorities related to SRA 2035 research areas and topics The following section reports on the conclusions
Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP
Grid Interconnection & Contract Development Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Submittal Instructions Prior to submitting your application and
Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E
SIEMENS Siemens Energy, Inc. Power Technology Issue 106 Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos Grande-Moran, Ph.D. Principal
Modeling Simulation Technology Research for Distribution Network Planning *
Energy and Power Engineering, 2013, 5, 980-985 doi:10.4236/epe.2013.54b188 Published Online July 2013 (http://www.scirp.org/journal/epe) Modeling Simulation Technology Research for Distribution Network
PSS SINCAL - Overview -
PSS SINCAL - Overview - PTI Day Buenos Aires, October 19/20, 2010 Dr. Michael Schwan,, Siemens PTI (Germany) www.siemens.com/energy/power-technologies PSS SINCAL Overview Page 3 Network Calculation Software
Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014
1 Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables Bob Yinger Southern California Edison April 15, 2014 Southern California Edison SCE provides power to: Nearly
FULL ELECTRICAL LNG PLANTS: HIGHEST AVAILABILITY AND ENERGY EFFICIENCY THROUGH OVERALL SYSTEM DESIGN
FULL ELECTRICAL LN PLANTS: HIHEST AVAILABILITY AND ENERY EFFICIENCY THROUH OVERALL SYSTEM DESIN Dr. Edwin Lerch Siemens A Infrastructure and Cities Sector, IC S SE PTI, ermany Phone: 49-9131-7-34052 Fax:
The design and performance of Static Var Compensators for particle accelerators
CERN-ACC-2015-0104 [email protected] The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,
Enel s experience on smart grids
Enel s experience on smart grids Projects and Strategy Shenzhen, September 2014 Agenda Enel profile Overview of smart grid technologies Smart Grids and Smart Cities projects in Italy and Europe 2 Enel:
Design of Electrical Power Supply System in an Oil and Gas refinery. Master of Science Thesis in Electric Power Engineering
Design of Electrical Power Supply System in an Oil and Gas refinery Master of Science Thesis in Electric Power Engineering Reza Vafamehr Department of Energy and Environment Division of Electric Power
Agenda do Mini-Curso. Sérgio Yoshio Fujii. Ethan Boardman. [email protected]. [email protected]
Agenda do Mini-Curso Sérgio Yoshio Fujii [email protected] Ethan Boardman [email protected] Agenda do Mini-Curso Sistemas de Distribuição (DMS) Characteristics of Distribution Network
CERN Accelerator School. Electrical Network and Power Converters. Hans Ulrich Boksberger Paul Scherrer Institute 5232 Villigen PSI Switzerland
CERN Accelerator School Electrical Network and Power Converters Hans Ulrich Boksberger Paul Scherrer Institute 5232 Villigen PSI Switzerland 1/ 21 / 17.5.2004 / HU Boksberger Outline Utility Standards
Radial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E
SIEMENS Siemens Energy, Inc. Power Technology Issue 104 Modeling of TwoWinding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos GrandeMoran, Ph.D. Principal Consultant
Energy Storage Systems in Grid4EU Demo4 and in Other Enel Distribuzione Projects Speaker
Energy Storage Systems in Grid4EU Demo4 and in Other Enel Distribuzione Projects Speaker Enel Distribuzione SpA Enel: a world dimension Focus on major areas of presence NORTH-CENTRAL AMERICA North America,
System Protection Schemes in Eastern Denmark
System Protection Schemes in Eastern Denmark Joana Rasmussen COWI A/S, Energy Department System Protection Schemes in Eastern Denmark 1.Advanced system protection schemes are investigated and perspectives
Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE
Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements
Coordinated and Optimized Control of Distributed Generation Integration
Coordinated and Optimized Control of Distributed Generation Integration Hui Yu & Wenpeng Luan China Electric Power Research Institute July, 2015 1 Background and introduction 2 Coordinated control of distributed
Executive summary. by Michel Clemence, Renzo Coccioni, and Alain Glatigny
998-2095-11-25-13AR0 by Michel Clemence, Renzo Coccioni, and Alain Glatigny Executive summary Annual electricity distribution losses average 4% in the European Union. These losses represent 7 billion Euros
Step Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
Test & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114.
Generation Interconnection System Impact Study Report For PJM Generation Interconnection Request Queue Position X1-114 Sandyston January 2012 Preface The intent of the System Impact Study is to determine
Executive summary 2. 1 Introduction 4
Flexible Networks for a Low Carbon Future Future Network Monitoring Strategy September 2015 Contents Executive summary 2 Glossary 3 1 Introduction 4 2 Fundamental principles of monitoring 5 2.1 LCT monitoring
EDP DISTRIBUIÇÃO S ASSET MANAGEMENT TOOL SUPPORTED BY REAL TIME MONITORING
EDP DISTRIBUIÇÃO S ASSET MANAGEMENT TOOL SUPPORTED BY REAL TIME MONITORING Hugo FERREIRA Pedro CARREIRA Rui BERNARDO Jorge GOMES EDP Distribuição - EDP Distribuição EDP Distribuição - EDP Distribuição
Modeling and Testing of Unbalanced Loading and Voltage Regulation
National Renewable Energy Laboratory Innovation for Our Energy Future A national laboratory of the U.S. Department of Energy Office of Energy Efficiency & Renewable Energy Modeling and Testing of Unbalanced
APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.
USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS Abstract This application note describes the necessary procedure to use a standard Pacific Power Source Model
Bill is the author of 15 papers and lectures on transmission lines and other power system topics.
Transmission Lines Electricity s Highway This talk starts with an explanation of Surge Impedance Loading and demonstrates how it is used for transmission line work. The St. Clair Curve widely used in transmission