Phase Balancing of Distribution Systems Using a Heuristic Search Approach
|
|
|
- Richard Luke Hodge
- 10 years ago
- Views:
Transcription
1 Phase Balancing of Distribution Systems Using a Heuristic Search Approach Lin, Chia-Hung*, Kang, Meei-Song**, Chuang, Hui-Jen**, and Ho, Chin-Ying** *National Kaohsiung University of Applied Sciences **Kao Yuan University Dept. of Electrical Engineering Dept. of Electrical Engineering Kaohsiung, Taiwan Kaohsiung, Taiwan Abstract In this paper, a heuristic backtracking search algorithm is proposed to adjust the phasing arrangement of primary feeders and laterals for phase balancing of distribution systems. The phase unbalance index of distribution feeders is calculated based on the phasing current magnitude of each line segment and branch, which has been solved by a 3-phase load flow program. The database of an outage management system (OMS) is used to retrieve the component attributes and the topology process is executed to determine the electrical network configuration and the customers served by each distribution transformer. By using the monthly energy consumption of customers in customer information system (CIS) and the typical daily load patterns of customer classes, the hourly loading profiles of distribution transformers and service zones can be derived to solve the individual phase loadings of each primary feeder and lateral. The phase balancing of distribution systems is enhanced by heuristic rule-based searching process to minimize the phase unbalance index. To demonstrate the effectiveness of proposed methodology, a practical distribution feeder with 2754 customers is selected for computer simulation to enhance three-phase balancing of distribution systems. It is concluded that three-phase balancing of distribution systems can be obtained by considering customer load characteristics. Keywords Automated mapping/facility management (AM/FM), Topology process, Node reduction, Customer information system (CIS) 1. INTRODUCTION For distribution systems in Taiwan Power Company (Taipower), the transformer banks with open-wye, open-delta connectivity are widely used to serve both 1-Φ and 3-Φ loads. The 100 kva 1-Φ transformer serves both 1-Φ and 3-Φ loads while the smaller 50 kva 1-Φ transformer serves only 3-Φ loads. Even with 3-Φ balance loading at the secondary side, the two phases at the primary side becomes unbalanced because of different load allocation due to 30 phase shift of primary and secondary windings [1]. Besides, only 2 out of 3 phases at the primary side are used to serve the transformer bank, it is very difficult to maintain three-phase balance with the variation of customer load demand. The current unbalance will lead to extra system losses, communication interference, equipment overloading and malfunction of protective relays. With the dramatically load growth for the past decade in Taiwan, more and more air conditioners are used in the commercial and residential areas of Taipower system. Three phase unbalance of distribution feeders becomes worse with load growth, which results in feeder tripping due to over neutral current, especially when load transfer between two feeders is performed. Distribution engineers have to practice phase swapping to improve phase loading balance based on system operation experience with trial-and-error methods. It is very labor intensive and time-consuming because phase balancing of distribution systems will be varied with the change of load characteristics of customers served by each distribution transformer. Besides, the magnitude of neutral current of distribution feeders is very stochastic and may cause random tripping of feeders due to neutral current constraint. In order to prevent unintentional service interruption by LCO protective relays due to over neutral current, the heuristic rules have been applied in this study to re-phase primary feeders and laterals within each service zone by considering the daily load patterns of customers served. To improve three-phase balance of distribution systems, two approaches have been presented [2], [3]. One is to reconfigure distribution systems by proper switching operation, which is primarily designed to solve the overload problem of main transformers/feeders [4]-[6]. On the other hand, phase arrangement is a direct and effective way to achieve phase balance of distribution feeders in terms of phase loading. Since the phase current loading of laterals and whole feeder will be time variant because of the stochastic load characteristics of customers over study time period, the optimization of phase arrangement becomes very complicated and tedious to be solved with conventional trial-and-error method. In this paper, a heuristic rule-based algorithm with backtracking search is proposed to solve the phase balancing problem. The connection types of distribution transformers/laterals in each service zone are identified and a three-phase load flow program with rigorous feeder model is executed to calculate phase current loading of each branch. The input bus data and branch data for three-phase load analysis can be obtained by retrieving the attributes of system components such as line segments, transformers, etc. in the database of automatic mapping and facility management system [7]. The hourly loading of each transformer is then derived by using the typical daily load patterns of customer classes and the monthly power consumption of customers served. The topology of distribution network is identified by executing the connectivity trace of system component. By this way, the data information required by load flow analysis is therefore generated automatically to enhance the efficiency and accuracy of computer simulation to solve phase currents
2 of primary feeders and laterals. 2. INFORMATION SYSTEM INTEGRATION To solve the hourly phase current loading of service zones and line segments by considering load characteristics of customers served, the electrical network topology of distribution systems has to be represented according to component attributes which are retrieved from the AM/FM database. The daily load patterns of customer classes derived by load survey study [8] and the energy consumption of customers in CIS database are applied to find the hourly power demand of each customer. With the customer-to-transformer mapping, the hourly loading of each distribution transformer is solved by integrating the power profiles of all customers served. The parallel distributed process is used to solve the phasing balance of laterals for different primary line segments simultaneously to accelerate the simulation process. Fig. 1 shows the overall structure of phase balancing with information system integration. 2.1 AM/FM database For more effective phase balancing study, the AM/FM database is used to support input data requirement by creating distribution circuit models and performing customer-totransformer mapping process. The Oracle database of AM/FM system in Taipower provides the capability to integrate the graphic representation of components with spatial relationship and information management. The database scheme is defined with several levels to represent real objects with data type of attributes according to data requirement of application functions to be supported. ID, node 1, node 2, supplying feeder1, supplying feeder2, and power direction are used to perform the connectivity trace of schematic circuit diagram. Fig. 2 illustrates the association of customers to service transformer and vice versa. The attributes of three tables (service transformer, meter, and customer address) are retrieved in the mapping process to identify all customers served by each transformer with meter ID. Table1 Attributes of connectivity table in Taipower AM/FM system Fig. 2. The identification of customer-to-transformer mapping. Fig. 1. Overall structure for phase balancing of distribution feeders. Table 1 shows the attributes of connectivity table for Taipower circuit model. The fields facility types, facility 2.2 Topology processing (TP) and node reduction Topology processing is to identify the network configuration of distribution feeders based on the attributes of network connectivity model and the dynamic switch statuses in AM/FM database. By tracing the FROM and TO fields of connectivity table, which points to the upstream and downstream device of each component, the system network configuration is determined and updated according to the operation of switching devices. A distribution system component can be categorized as either branch or node. Each branch is an arc connected to two nodes
3 while each node is a connecting point of branches attached to it. A branch can be any device with two terminals such as line sections, switches, transformers, etc., and a node is an electricity point that connects different branch devices together. The topology tracing can be executed by starting from a given node or a branch and continues by taking the other terminal (node) of a branch as the new node and all branches connected to the new node are represented as the new branches. The topology processing is completed when an open tie switch is reached or all devices have been completely traced. After topology processing, the node reduction is applied to remove those facilities such as power fuses, poles, high voltage mold joints, etc., which are redundant for phase balancing study. The radial network configuration of distribution feeders is verified by data validation and the impedances of line segments are calculated according to the corresponding conductor types and branch lengths. 2.3 Individual phase load evaluation by considering customer load pattern The evaluation of hourly loading of individual phase will affect the accuracy of phase balancing study. With the variation of customer load characteristics and load composition, it becomes very difficult to estimate phase loading of each service zone. This paper presents a systematic method to solve the hourly phase loading by using customer load patterns and monthly energy billing data of customers served at each load point. Typical daily load patterns of various customer classes are derived in this paper to determine the load variation of distribution transformers, primary feeders and laterals [9-11]. The load composition of each service transformer is divided into commercial, industrial, and residential loads. The load survey study has been executed in previous works [8] to derive the normalized typical load patterns of test customers which have been selected by stratification method. The customer billing data are retrieved from CIS database to find total monthly energy consumption by each customer. The hourly power consumption profiles of each customer class for both the weekday and weekend during various seasons are therefore determined by allocating the total power consumption to each hourly lot according to the typical load patterns. Based on the connectivity of customers and service transformers, the power demand of each distribution transformer is then determined. By executing three-phase load flow analysis with the phasing and hourly loadings of distribution transformers, the phase currents of service zones, laterals and primary feeders for each study hour can therefore be solved. 3. THE PROPOSED ALGORITHM 3.1 Problem formulation Before applying the heuristic search algorithm for phasing arrangement of laterals to achieve three-phase balance of distribution feeders, the phasing unbalance index (PUI) is defined as follows [12]: j j j j j j Max( I I, I I, I I ) a avg b avg c avg PUI = j j 100% Iavg (1) where I j, I j, I j a b c : current loadings of phase a, b, and c at node j, I : average phase current. j avg 3.2 Connection types In this paper, the notation (X, Y, Z) is used to represent the phasing arrangement of each lateral. The letters X, Y, and Z are phases of the lateral to be connected to location Pos1, Pos2, and Pos3 of the primary feeder as shown in Fig. 3. In this figure, the notations of phasing assignment for lateral 1 and 2 are (A, C, B) and (B, A, C), respectively. Fig. 3. Sample feeder with two connecting branches. The possible connection schemes for various types of phasing arrangement are listed in Table 2 for single-phase, two-phase, and three-phase laterals. For instance, a two-phase lateral which originally has phase A in position 1 and phase B in position 2 can have any of the following rephasing schemes: (A, *, B), (*, A, B), (B, A, *), (B, *, A), (*, B, A) where connection scheme (A, B, *) represents no phase adjustment. 3.3 Heuristic backtracking search algorithm In this paper, a backtracking search algorithm with heuristic information is proposed to solve the phasing readjustment of distribution systems from the start nodes in the child process to the goal node in the parent process. The major objective is to optimize the phasing balance of three-phase currents for all service zones, laterals and primary feeders.
4 Table 3 Phase currents of two laterals in Fig. 3. Table 2 Valid connection schemes for various types of laterals The typical load patterns and energy consumption of customers served are used to solve the hourly current loading of a distribution transformer. The three-phase load flow analysis is executed for each study hour by using the current loading of each transformer to find the phase currents of each service zone and each lateral. The phase currents of each lateral are considered as input for the heuristic search algorithm by taking 24-hour loads into account. Heuristic information is used to find the proper phase connection type for each node to enhance three-phase balance in each service zone. The following heuristic rules adopted by experienced engineers in conducting phase adjustment are illustrated as follows. Step 1. Execute backtracking search algorithm from the nodes of the deepest level in the child process to perform phase adjustment procedures. Step 2. Given a node labeled in the k th level (label k level represents the topology sequence) and execute the rephasing algorithm. The phase position of the lateral which connects to this node with the smallest PUI is referred as the based construction location. This lateral is called based branch (BR) before rephasing. The phase positions in other branches which have the maximum, medium and minimum currents are rephased according to the phase positions in BR with the minimum, medium, and maximum phase currents, respectively. The 3-phase currents of the upstream branches are updated according to above rephasing of the lateral. For the previous sample feeder in Fig. 3, the phase currents of two laterals are listed in Table 3. It is found that lateral 1 with the smallest PUI is referred as BR. Positions 1, 2, and 3 of lateral 1 are associated with phase A, C, and B. According to Step 2, the rephasing movement of lateral 2 for the phase associated with positions recommends that phase A, B, and C should be moved to position 1, 2, and 3 (A, B, C). The upstream branch currents I 1, I 2, and I 3 are then updated to be 90 A, 100 A, and 100 A. Step 3. After a lateral has been rephased, all downstream laterals in the branch are rephased according to the changes made at the node. For instance, when the upstream branch of position 1 is changed to position 2, all downstream lateral components which connected to this lateral in position 1 are changed to position 2 as well. Step 4. The rephasing algorithm is executed at each node in the (k-1) th level (backtracking search) if all nodes in the k th levels have been executed completely. After the goal node of the parent process has been reached to complete the rephasing algorithm, the process will stop by finalizing output the connection type of each node. Otherwise, repeat Step 2 and 3 with the next node in the k th level set. In this paper, the following operation constraints are taken into consideration for rephasing. 1. No main transformers, feeders and line switches are overloaded after rephasing. 2. Radial network configuration must be maintained for distribution feeders. 3. All service zones are connected and served by the feeder. 4. NUMERICAL RESULTS To demonstrate the effectiveness of the proposed methodology to enhance three-phase balance of service zones, laterals and distribution feeders, a practical distribution feeder GV52, in Taichung District of Taipower, is selected for computer simulation. The total length of the feeder is 2.2 Km and it serves 2754 customers with 73 single-phase transformers. Fig. 4 shows the one-line diagram of the test feeder, which has been derived by node reduction and topology process. Within each service zone (node), the equivalent loads are estimated by customer-to-service transformer (phase) mapping process from AM/FM database and customer billing data in CIS. Fig. 5 shows the power profile and load composition of service zone N57 during the summer season. It is found that both residential and commercial customers contribute most of the power consumption while industrial customers consume the least power. The peak load demand of N57 is 86.9 kw at 8 PM with the power demands of commercial and residential customers as 47.8 kw and 35.4 kw respectively.
5 phase unbalance occurs at 8 PM. After executing the proposed heuristic backtracking search algorithm to find the proper lateral rephasing at this time slot, the PUI has been reduced from 50.71% to 2.97% with the neutral current being reduced from 52.2 A to 6.5 A at 8 PM. Besides, the daily average PUI has been reduced from 45.6% to 2.9% and the mean value of the neutral current has been reduced from 35.2 A to 4.3 A. Table 4 Lateral rephasing of Feeder GV52 Fig. 4. The one-line diagram of Feeder GV52 for case studies. Fig. 6. Phase unbalance index and neutral currents of test feeder GV52 before and after rephasing. Fig. 5. Power profile and load composition at node N57. The circuit model of GV52 is retrieved from the AM/FM system with information such as conductor types and lengths, connectivity, transformer capacity and impedance. According to the hourly load estimation at each node, a power flow program with rigorous feeder model is executed to solve the phase currents at each node and the phase unbalance index of each node for heuristic search algorithm is then obtained. Fig. 7 illustrates the mean values of phase unbalance index, PUIs, for the selected service zones N57, N51, N37, N32, N4, and N3 over 24-hour period before and after lateral rephasing. It is found that the maximum PUI is reduced from 57.9% to 6.8% for service zone N3 and three-phase balance has been improved dramatically for all service zones. Besides, more PUI reduction at upstream service zones has been obtained than that at downstream service zones due to the accumulation of phasing balance of downstream service zones. By executing the proposed algorithm to solve the rephasing problem of laterals for Feeder GV52, three stages of phasing adjustment are recommended as shown in Table 4. The first stage is to rephase lateral 35 and 36 by swapping A phase and B phase. For the second stage, the original phase (A,B,C) is changed to phase (B,C,A) for lateral 37 and 38. For the third stage, the original phase (A,B,C) is changed to new phase (A,C,B) for lateral 13, and the original phase (*,B,C) is changed to (*,C,B) for the two-phase laterals 14, 15, and 16. Fig. 6 illustrates the resultant phasing unbalance index (PUI) and the neutral currents of Feeder GV52 before and after applying phasing adjustment. It is found that the worst three- Fig. 7. The average PUIs before and after lateral rephasing.
6 5. CONCLUSIONS The three-phase balance of distribution feeders has been enhanced by lateral rephasing with heuristic rules. The AM/FM system is used to generate distribution network models and input data files automatically to support load flow analysis of distribution systems to find three-phase current loadings of service zones, laterals and primary feeders. By executing customer-to-transformer mapping, the customers served by each distribution transformer are identified. The hourly loading of each distribution transformer is then derived by integrating the customer power demands, which has been solved by considering the typical load patterns and energy consumption of customers served. By this manner, the phase current loading obtained will be more accurate as compared to the conventional load allocation using the transformer capacity. To achieve better phasing balance of distribution feeders, the heuristic rules have been developed by considering operation regulation of distribution systems. A backtracking search algorithm is used to derive the proper phasings of service zones, laterals and primary feeders. To demonstrate the effectiveness of the proposed heuristic methodology to improve three-phase balance of distribution networks, a practical Taipower underground distribution system with two feeders has been selected for computer simulation. By the heuristic backtracking search algorithm to solve lateral rephasing, the neutral current and phase unbalance index of distribution feeders have been reduced. It is found that the proposed heuristic algorithm can solve the rephasing problem of distribution systems to enhance three-phase loading balance effectively by considering customer load patterns. Furthermore, the neutral current of distribution feeders can be reduced significantly to prevent feeder tripping due to over neutral current. References [1] C.S. Chen, C.Y. Chang, and S.Y. Jan, "Effect of openwye open-delta transformers on the operation of distribution systems," Electrical Power Systems Research, vol. 10, no. 3, pp , [2] J. Zhu, M. Y. Chow, and F. Zhang, "Phase balancing using mixed-integer programming," IEEE Trans. Power Systems, vol. 13, no. 4, pp , Nov [3] J. Zhu, G.. Bilbro, and M. Y. Chow, "Phase balancing using simulated annealing," IEEE Trans. Power Systems, vol. 14, no.4, pp , Nov [4] C.H. Lin, "Distribution network reconfiguration for load balancing with a colored petri net algorithm", IEE Proceedings Gen. Trans. Distri., vol. 150, no. 3, pp , May [5] C.H. Lin, C.S. Chen, C.J. Wu, M.S. Kang, "Application of immune algorithm to optimal feeder reconfiguration under multiple objectives," IEE Proceedings Gen. Trans. Distri., vol. 150, no. 2, pp , March [6] Y. Y. Hsu, J.H. Yi, S.S. Liu, Y.W. Chen, H.C. Feng, and Y.M. Lee, "Transformer and feeder load balance using a heuristic search approach," IEEE Trans. Power Systems, vol. 8, no.1, Feb. 1993, pp [7] T.E. Lee, C.S. Chen, Y.M. Tzeng, M.S. Kang, C.C. Lee, J.S. Wu, T. S.S. Liu, and Y.M. Chen, "The application of AM/FM system to distribution contingency load transfer," IEEE Trans. Power Delivery, vol.10, no. 2, April 1995, pp [8] C.S. Chen, J.C. Hwang, Y.M. Tzeng, C.W. Huang, and M.Y. Cho, "Determination of customer load characteristics by load survey system at Taipower,", IEEE Trans. on Power Delivery, Vol. 11, no. 3, July 1996, pp [9] M. Y. Cho, C. S. Chen and W. M. Lin, "Design of a distribution database with customer daily load patterns," Electric Power Systems Research, vol. 23, no.2, 1992, pp [10] C.S. Chen, J.C. Hwang, M.Y. Cho and Y.W. Chen, "Development of simplified loss models for distribution system analysis, " IEEE Trans. Power Delivery, vol.9, no. 3, July 1994, pp [11] T.H. Chen and J.T. Cherng, "Optimal phase arrangement of distribution transformers connected a primary feeder for system unbalance improvement and loss reduction using a genetic algorithm," IEEE Trans. Power Systems, vol. 15, no. 3, pp , Aug [12] IEEE Std , ANSI/IEEE C , IEEE C , and IEEE C
Phase Balancing of Unbalanced Distribution Network through Hybrid Greedy-Fuzzy Algorithm
Phase Balancing of Unbalanced Distribution Network through Hybrid Greedy-Fuzzy Algorithm M. Sathiskumar Department of Electrical and Electronics Engineering, P.A College of Engg. & Tech., P.O. Bo-642 2,
Modeling Simulation Technology Research for Distribution Network Planning *
Energy and Power Engineering, 2013, 5, 980-985 doi:10.4236/epe.2013.54b188 Published Online July 2013 (http://www.scirp.org/journal/epe) Modeling Simulation Technology Research for Distribution Network
How To Swap Output Phases Of A Power Supply With A Power Converter
211 2nd Power Electronics, Drive Systems and Technologies Conference A New phase sequence Detector for the Three-Phase Rotary Loads M. Alizadeh Bidgoli, A. Soori, M. Tavakoli Bina K. N. Toosi University
Impact of electric vehicles on the IEEE 34 node distribution infrastructure
International Journal of Smart Grid and Clean Energy Impact of electric vehicles on the IEEE 34 node distribution infrastructure Zeming Jiang *, Laith Shalalfeh, Mohammed J. Beshir a Department of Electrical
Neutral to Earth Voltage Reduction Methods in Three-Phase Four Wire Distribution Systems
Neutral to Earth oltage Reduction Methods in ThreePhase Four Wire Distribution Systems G. Ahmadi and S.M. Shahrtash ran University of Science and Technology (UST) [email protected] Center of Excellence
A Reactive Tabu Search for Service Restoration in Electric Power Distribution Systems
IEEE International Conference on Evolutionary Computation May 4-11 1998, Anchorage, Alaska A Reactive Tabu Search for Service Restoration in Electric Power Distribution Systems Sakae Toune, Hiroyuki Fudo,
ONE OF THE anticipated main benefits of a distribution
Reconfiguration and Load Balancing in the LV and MV Distribution Networks for Optimal Performance Mukwanga W. Siti, Dan Valentin Nicolae, Adisa A. Jimoh, Member, IEEE, and Abhisek Ukil Abstract To get
Optimal Feeder Reconfiguration with Distributed Generation in Three-Phase Distribution System by Fuzzy Multiobjective and Tabu Search
Optimal Feeder Reconfiguration with Distributed Generation in Three-Phase Distribution System by Fuzzy Multiobjective and Tabu Search Nattachote Rugthaicharoencheep and Somporn Sirisumranukul King Mongkut
Rule 5.500 Fast Track Analysis for National Life Insurance Co.
Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION
Radial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it
Network Reconfiguration for Service Restoration in Shipboard Power Distribution Systems
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 16, NO. 4, NOVEMBER 2001 653 Network Reconfiguration for Service Restoration in Shipboard Power Distribution Systems Karen L. Butler, Senior Member, IEEE, N. D.
IMPROVED NETWORK PARAMETER ERROR IDENTIFICATION USING MULTIPLE MEASUREMENT SCANS
IMPROVED NETWORK PARAMETER ERROR IDENTIFICATION USING MULTIPLE MEASUREMENT SCANS Liuxi Zhang and Ali Abur Department of Electrical and Computer Engineering Northeastern University Boston, MA, USA [email protected]
Xiaoguang Yang, Valentina Cecchi, Karen Miu, Chika Nwankpa
Reconfigurable Distribution Automation and Control Laboratory: A Network Reconfiguration Experiment for Load Balancing and Loss Reduction in Power Distribution Systems Xiaoguang Yang, Valentina Cecchi,
Conservation Voltage Reduction (CVR)
Conservation Voltage Reduction (CVR) Nicholas Abi-Samra Senior Vice President October 15, 2013 DNV GL Energy Table of Contents What does CVR do? Why Does CVR Work? DNV GL s CVR Project Experience Needs
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS
Definition: Zone Selective Interlocking (ZSI) - A method which allows two or more ground fault breakers to communicate with each other so that a short circuit or ground fault will be cleared by the breaker
Radial Distribution Network Reconfiguration for Loss Reduction and Load Balancing using Plant Growth Simulation Algorithm
International Journal on Electrical Engineering and Informatics - olume 2, Number 4, 2010 Radial Distribution Network Reconfiguration for Loss Reduction and Load Balancing using Plant Growth imulation
Optimal Branch Exchange for Feeder Reconfiguration in Distribution Networks
Optimal Branch Exchange for Feeder Reconfiguration in Distribution Networks Qiuyu Peng and Steven H. Low Engr. & App. Sci., Caltech, CA Abstract The feeder reconfiguration problem chooses the on/off status
Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers
Journal Journal of of Emerging Emerging Trends Trends in in Engineering Engineering and and Applied Applied Sciences Sciences (JETEAS) (JETEAS) 1 1 (1): (1): 72-78 72-78 Scholarlink Research Institute
Simulation of Cable Overloading Problem on a University Distribution System
Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 3, Number 6 (2013), pp. 765-770 Research India Publications http://www.ripublication.com/aeee.htm Simulation of Cable Overloading
DC/DC BUCK Converter for Renewable Energy Applications Mr.C..Rajeshkumar M.E Power Electronic and Drives,
DC/DC BUCK Converter for Renewable Energy Applications Mr.C..Rajeshkumar M.E Power Electronic and Drives, Mr.C.Anandaraj Assistant Professor -EEE Thiruvalluvar college of Engineering And technology, Ponnur
New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems
International Conference on Computer and Communication Engineering (ICCCE 2010), 11-13 May 2010, Kuala Lumpur, Malaysia New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System
OPTIMAL DISTRIBUTION PLANNING INCREASING CAPACITY AND IMPROVING EFFICIENCY AND RELIABILITY WITH MINIMAL-COST ROBUST INVESTMENT
OPTIMAL DISTRIBUTION PLANNING INCREASING CAPACITY AND IMPROVING EFFICIENCY AND RELIABILITY WITH MINIMAL-COST ROBUST INVESTMENT L.A.F.M. Ferreira, P.M.S. Carvalho IST S.N.C. Grave L.M.F. Barruncho L.A.
Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns
Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns Mehmet H. Cintuglu, [email protected], Armando Altamirano, [email protected] Osama A. Mohammed, [email protected] Energy Systems
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit
The following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering
Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward
Experimental Verification of Advanced Voltage Control for Penetration of PV in Distribution System with IT Sectionalizing Switches
21, rue d Artois, F-75008 PARIS C6 _113 _2012 CIGRE 2012 http : //www.cigre.org Experimental Verification of Advanced Voltage Control for Penetration of PV in Distribution System with IT Sectionalizing
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
De Jaeger, Emmanuel ; Du Bois, Arnaud ; Martin, Benoît. Document type : Communication à un colloque (Conference Paper)
"Hosting capacity of LV distribution grids for small distributed generation units, referring to voltage level and unbalance" De Jaeger, Emmanuel ; Du Bois, Arnaud ; Martin, Benoît Abstract This paper revisits
Implementation of High Step-Up Solar Power Optimizer for DC Micro Grid Application
Implementation of High tepup olar Power Optimizer for C Micro Grid Application hihming Chen, KeRen Hu, TsorngJuu Liang, and YiHsun Hsieh Advanced Optoelectronic Technology Center epartment of Electrical
Motor Protection Voltage Unbalance and Single-Phasing
Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the
Hybrid Power System with A Two-Input Power Converter
Hybrid Power System with A Two-Input Power Converter Y. L. Juan and H. Y. Yang Department of Electrical Engineering National Changhua University of Education Jin-De Campus, Address: No.1, Jin-De Road,
Application of Four-Pole Circuit Breakers within Data Centers
Application of Four-Pole Circuit Breakers within Data Centers December 2013/AT324 by Frank Waterer, Fellow Engineer, Schneider Electric Engineering Services Make the most of your energy SM Revision #1
3. TYPES OF SERVICE AVAILABLE. 3.1 Scope
3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service
Guidelines on the Short Circuit Current Rating for Industrial Control Panels
usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Assessing The Hazards Of High and Low Voltage Single-Phase Arc-Flash By Albert Marroquin One common question
The calm after the storm
The calm after the storm Human decision support in storm outage recovery Rafael Ochoa, Amitava Sen It s a fact of life that interruptions in an electrical distribution utility happen. Although they can
Simulation of Ungrounded Shipboard Power Systems in PSpice
Simulation of Ungrounded Shipboard Power Systems in PSpice Haibo Zhang IEEE Student Member Karen L.Butler IEEE Member Power System Automation Lab Electrical Engineering Department Texas A&M University
BALANCED THREE-PHASE CIRCUITS
BALANCED THREE-PHASE CIRCUITS The voltages in the three-phase power system are produced by a synchronous generator (Chapter 6). In a balanced system, each of the three instantaneous voltages have equal
Design of Four Input Buck-Boost DC-DC Converter for Renewable Energy Application
Design of Four Input Buck-Boost DC-DC Converter for Renewable Energy Application A.Thiyagarajan Assistant Professor, Department of Electrical and Electronics Engineering Karpagam Institute of Technology
NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM
NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM E.Babu 1,R.Subramanian 2 1, Department of Electrical and electronics engg 2 Department of Electrical
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
A Survey of Models and Algorithms for Emergency Response Logistics in Electric Distribution Systems - Part II: Contingency Planning Level
A Survey of Models and Algorithms for Emergency Response Logistics in Electric Distribution Systems - Part II: Contingency Nathalie Perrier Bruno Agard Pierre Baptiste Jean-Marc Frayret André Langevin
Three-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
Part 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
TERMS AND CONDITIONS
Virginia Electric and Power Company TERMS AND CONDITIONS XXIV. GENERATOR INTERCONNECTION STANDARD Electric generator interconnection service includes only the ability to interconnect an electric generator
The Application and Benefits of Multi-phase Auto-reclosing
he Application and Benefits of Multi-phase Auto-reclosing etsuya Miyoshi*, Atsushi Kasai* Abstract - In this paper we explain the disadvantages in using single- and three-phase auto-reclosing on double
A Routing Algorithm Designed for Wireless Sensor Networks: Balanced Load-Latency Convergecast Tree with Dynamic Modification
A Routing Algorithm Designed for Wireless Sensor Networks: Balanced Load-Latency Convergecast Tree with Dynamic Modification Sheng-Cong Hu [email protected] Jen-Hou Liu [email protected] Min-Sheng
Distributed Load Balancing for FREEDM system
Distributed Load Balancing for FREEDM system Ravi Akella, Fanjun Meng, Derek Ditch, Bruce McMillin, and Mariesa Crow Department of Electrical Engineering Department of Computer Science Missouri University
A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks
A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks Mohammad Ali Sandidzadeh School of Railway Engineering, Iran University of Science & Technology, Tehran, Iran Tel: 98-21-7749-1030
NEPLAN Training. NEPLAN AG Oberwachtstrasse 2 CH 8700 Küsnacht ZH Phone +41 44 914 36 66 Fax +41 44 991 19 71. www.neplan.ch
NEPLAN Training The concept of NEPLAN Training NEPLAN training courses offer an excellent opportunity to become familiar with NEPLAN, the power system software applied worldwide for network planning and
System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems
System Grounding and Ground-Fault Protection Methods for -Supplied Power Systems Bill Brown, P.E., Square D Critical Power Competency Center 1. INTRODUCTION The use of solid grounding for -supplied power
PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions
PMCS Integrated Energy Management Solution Unlock the Full Potential of Power Networks Through Integration Power Management Control System (PMCS) is a highly customizable, fully integrated end-to-end Energy
Integrated Design of Electrical Distribution Systems: Phase Balancing and Phase Prediction Case Studies
Integrated Design of Electrical Distribution Systems: Phase Balancing and Phase Prediction Case Studies by Murat Dilek Dissertation submitted to the Faculty of the Virginia Polytechnic Institute and State
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...
Voltage Unbalance and Motors
Voltage Unbalance and Motors Background Voltage unbalance occurs when the RMS line voltages on a poly-phase system are unequal. Voltages are seldom perfectly balanced between phases, but when this unbalance
Minimizing Impact of Electric Utility Outages with Backup Generation
Minimizing Impact of Electric Utility Outages with Backup Generation Introduction of the Speaker Michael Dempsey, PE Senior Electrical Engineer Carter & Burgess, Inc. Energy & Power Solutions Facility
DESIGN FOR MONITORING AND OPTIMIZATION OF POWER DEMAND FOR WIRELESSLY COMMUNICATING ELECTRIC LOADS
DESIGN FOR MONITORING AND OPTIMIZATION OF POWER DEMAND FOR WIRELESSLY COMMUNICATING ELECTRIC LOADS Patil Snehal S.S. 1, Mr. Shivdas S.S. 2 1 M. E. Electronics (II), Department of Electronics Engineering;
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
Monitoring Underground Power Networks
Monitoring Underground Power Networks By Mark Stiles Merve Cankaya ABSTRACT Underground electric distribution systems are common in large cities throughout the United States. Power usage for the entire
Design and Implementation of High Voltage Customer Service Portal
Design and Implementation of High Voltage Customer Service Portal Chin-Tun Wang Taiwan Power Research Institute, Taiwan Power Company 198, Roosevelt Road, Taipei 10091, Taiwan, Republic of China, [email protected]
Engineering Series Ratings: Is It Practical?
Engineering Series Ratings: Is It Practical? By the National Electrical Manufacturers Association The 2005 National Electrical Code (NEC) introduces a change regarding series ratings for circuit breakers
A Hybrid Load Balancing Policy underlying Cloud Computing Environment
A Hybrid Load Balancing Policy underlying Cloud Computing Environment S.C. WANG, S.C. TSENG, S.S. WANG*, K.Q. YAN* Chaoyang University of Technology 168, Jifeng E. Rd., Wufeng District, Taichung 41349
Data Deduplication Scheme for Cloud Storage
26 Data Deduplication Scheme for Cloud Storage 1 Iuon-Chang Lin and 2 Po-Ching Chien Abstract Nowadays, the utilization of storage capacity becomes an important issue in cloud storage. In this paper, we
Best Practices for Creating Your Smart Grid Network Model. By John Dirkman, P.E.
Best Practices for Creating Your Smart Grid Network Model By John Dirkman, P.E. Best Practices for Creating Your Smart Grid Network Model By John Dirkman, P.E. Executive summary A real-time model of their
Calculation of Voltage Sag Indices for Distribution Networks
Calculation of Voltage Sag Indices for Distribution Networks Juan A. Martinez-Velasco, Member, IEEE, Jacinto Martin-Arnedo, Nonmember Abstract This paper is presenting the main results of a work aimed
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS Claudio S. Mardegan [email protected] www.engepower.com Phone: 55 3579-8777
Chapter 12 Three-Phase Circuit
Chapter 12 Three-Phase Circuit 馮 武 雄 教 授 長 庚 大 學 電 子 系 1 Chapter 12 Three-Phase Circuits 12.1 What is a Three-Phase Circuit? 12.2 Balance Three-Phase oltages 12.3 Balance Three-Phase Connection 12.4 Power
Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6
Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International
Grounding of AC generators and switching the neutral in emergency and standby power systems
Power topic #6006 Part 2 of 2 Technical information from Cummins Power eneration rounding of AC generators and switching the neutral in emergency and standby power systems > White paper By Lawrence A.
Big Data Collection and Utilization for Operational Support of Smarter Social Infrastructure
Hitachi Review Vol. 63 (2014), No. 1 18 Big Data Collection and Utilization for Operational Support of Smarter Social Infrastructure Kazuaki Iwamura Hideki Tonooka Yoshihiro Mizuno Yuichi Mashita OVERVIEW:
Dynamic Load Balance Algorithm (DLBA) for IEEE 802.11 Wireless LAN
Tamkang Journal of Science and Engineering, vol. 2, No. 1 pp. 45-52 (1999) 45 Dynamic Load Balance Algorithm () for IEEE 802.11 Wireless LAN Shiann-Tsong Sheu and Chih-Chiang Wu Department of Electrical
Chapter 2 The Research on Fault Diagnosis of Building Electrical System Based on RBF Neural Network
Chapter 2 The Research on Fault Diagnosis of Building Electrical System Based on RBF Neural Network Qian Wu, Yahui Wang, Long Zhang and Li Shen Abstract Building electrical system fault diagnosis is the
Generic Reliability Evaluation Method for Industrial Grids with Variable Frequency Drives
Energy and Power Engineering, 2013, 5, 83-88 doi:10.4236/epe.2013.54b016 Published Online July 2013 (http://www.scirp.org/journal/epe) Generic Reliability Evaluation Method for Industrial Grids with Variable
Research on the UHF RFID Channel Coding Technology based on Simulink
Vol. 6, No. 7, 015 Research on the UHF RFID Channel Coding Technology based on Simulink Changzhi Wang Shanghai 0160, China Zhicai Shi* Shanghai 0160, China Dai Jian Shanghai 0160, China Li Meng Shanghai
Disjoint Path Algorithm for Load Balancing in MPLS network
International Journal of Innovation and Scientific Research ISSN 2351-8014 Vol. 13 No. 1 Jan. 2015, pp. 193-199 2015 Innovative Space of Scientific Research Journals http://www.ijisr.issr-journals.org/
Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
Chapter 24. Three-Phase Voltage Generation
Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal
LV4MV: A CONCEPT FOR OPTIMAL POWER FLOW MANAGEMENT IN DISTRIBUTION GRIDS, USING DER FLEXIBILITY
LV4MV: A CONCEPT FOR OPTIMAL POWER FLOW MANAGEMENT IN DISTRIBUTION GRIDS, USING DER FLEXIBILITY Emmanuelle VANET Gaspard LEBEL Raphaël CAIRE G2Elab France G2Elab France G2Elab - France [email protected]
ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe
NETWORKS ESB Networks Response to ERGEG Consultation on Voltage Quality Regulation in Europe Date: 22 February 2007 Distribution System Operator ESB Networks Page 1 of 12 Contents 1.0 INTRODUCTION...3
PSS SINCAL - Overview -
PSS SINCAL - Overview - PTI Day Buenos Aires, October 19/20, 2010 Dr. Michael Schwan,, Siemens PTI (Germany) www.siemens.com/energy/power-technologies PSS SINCAL Overview Page 3 Network Calculation Software
A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER
A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER 1 KARUNYA CHRISTOBAL LYDIA. S, 2 SHANMUGASUNDARI. A, 3 ANANDHI.Y 1,2,3 Electrical
Inverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
7. Reactive energy compensation
593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical
How To Balance Three Phase Power In A Balanced System
Three-Phase Circuits Three-Phase Circuit Three-Phase Circuits What is a Three-Phase Circuit? Balance Three-Phase oltages Balance Three-Phase Connection Power in a Balanced System Unbalanced Three-Phase
How To Improve Power Quality
Neutral Current compensation in three phase four wire DSTATCOM using Three Leg VSC and a Zig Zag Transformer 1 Ramya A R, 2 T.M.Vasantha Kumar, 3 K.R.Mohan 1,2,3 Dept. of Electrical and Electronics Engineering
THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.
THE PER-UNIT SYSTEM An interconnected power system typically consists of many different voltage levels given a system containing several transformers and/or rotating machines. The per-unit system simplifies
MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS
MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS C.P. ION 1 C. MARINESCU 1 Abstract: This paper presents a new method to supply single-phase loads using a three-phase induction
Beware of Simplistic Voltage Drop Calculations. By Aaron Hesse, PE, Coffman Engineers, Spokane, Washington INTRODUCTION
Subject: Beware of Simplistic Voltage Drop Calculations By Aaron Hesse, PE, Coffman Engineers, Spokane, Washington INTRODUCTION Iterative voltage drop calculations are some of the most tedious and time
Typical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com [email protected] Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
Voltage regulation in distribution systems - Tap changer and Wind Power
CODEN:LUTEDX/(TEIE-5270)/1-59/(2010) Industrial Electrical Engineering and Automation Voltage regulation in distribution systems - Tap changer and Wind Power David Sáez Romero D of Industrial Electrical