1 Addendum #2 Contract UK Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9) Proponents are advised this addendum shall form an integral part of the Request for Proposal and Contract Documents for the above noted project and shall be read in conjunction therewith. This addendum shall, however, take precedence over all requirements of the previously issued Request for Proposal with which it may prove to be at variance, unless otherwise clarified in writing by the Owner. If intending to submit a proposal, proponents shall confirm receipt of this addendum by reply to tbrackenbury@utilitieskingston.com upon receipt, and in the body of their proposal using the attached confirmation page. 1. The following is a summary of questions raised by Proponents and answers provided by Utilities Kingston at the Mandatory Site Meeting that occurred Thursday March 24, :00AM at 60 Notch Hill Road, Kingston, Ontario (Substation MS11); RFP UK Addendum #2 Page 1/8

2 Q.1 Can the list of firms attending the Mandatory Site Meeting be made available to all proponents? A.1 Yes, since there were no concerns or objections raised from attendees present at the site meeting about providing this information. The firms that attended the Mandatory Site Meeting are listed in alphabetical order below: ABB Ainsworth Inc. Eaton General Switchgear Industrial Electric KA Factor/Dualade Schneider Electric Siemens Tal Trees Inc. Tiltran Services Inc. Q.2 Is all access to the existing 5kV Switchgear Room to be through the existing double front doors? A.2 Yes. Q.3 What is the dimension from the back face of the existing ITE Switchgear (Y-Bus) to the wall face opposite the front of the existing McGraw-Edison Switchgear (Q-Bus)? A.3 This dimension was verified on-site and reported to be 185. Utilities Kingston encouraged proponents to verify additional dimensions during their site visit and not to rely on the approximate dimensions provided in the RFP. Q.4 Are there any plans to move the existing 44kV control panel? A.4 Yes, Utilities Kingston will relocate the 44kV control panel prior to the start of construction by the successful proponent. Please refer to Appendix A and the potential layout drawings in the RFP document for further details. Q.5 Are there any plans to replace the existing ITE Switchgear (Y-Bus)? A.5 There is currently no plan to replace the existing ITE Switchgear (Y-Bus) under this RFP. However, Utilities Kingston has requested proponents to contemplate future replacement of the Y-Bus with switchgear of similar style to that being proposed for the Q-Bus. Utilities Kingston has offered one potential single-line diagram and layout concept as well as a potential protection and control narrative description for the future Y-Bus upgrade in the RFP documentation. Utilities Kingston has also requested RFP UK Addendum #2 Page 2/8

3 proponents to consider the future Y-Bus upgrade in their Technical proposal and Financial proposal submissions. Q.6 Where will the transition splices shown on the Proposed Single Line Diagram (Drawing K E102) be installed and who is to supply and install them? A.6 The transition splices will be located in the cable pit below the switchgear. Utilities Kingston will supply and install the transition splices. Please refer to Note 1 on Drawing K E102. Q.7 What is the cloth-like material covering the existing roof drain and does the new switchgear need to be built around the existing roof drain? A.7 The cloth-like material covering the existing roof drain may contain asbestos. Utilities Kingston is conducting a Hazardous Building Material Assessment for this substation and plans to remove the covering from the existing roof drain prior to the start of construction by the successful proponent. Proponents may wish to consider relocating the roof drain to accommodate the new switchgear. The cover plate of the clean-out port that is exposed near the floor appears to be cast-iron. Q.8 Can the electrical equipment mounted on the wall facing the existing McGraw-Edison Switchgear (Q-Bus) be relocated from its existing location (e.g. heaters, bell telephone isolation equipment, etc.) to accommodate the new switchgear? A.8 Yes. Proponents should consider relocation of existing electrical equipment in their proposal to accommodate the new switchgear. Utilities Kingston has limited it s assistance with equipment relocation to the 44kV Control Panel and the hardware on the walls (e.g. wall brackets for existing switchgear tools). Q.9 What about venting for Type 2B Arc Resistant Switchgear? A.9 Proponents will need to ensure the new Type 2B Arc Resistant Switchgear has adequate venting of arc exhaust under a fault condition. Q.10 Can the existing dry-type station service transformer be re-used? A.10 No. Utilities Kingston plans to remove the existing dry-type station service transformer prior to the start of construction by the successful proponent. Please refer to Appendix A and Appendix B of the RFP for further details regarding the existing and new dry-type station service transformer. 2. The following questions were received after the Mandatory Site Meeting: RFP UK Addendum #2 Page 3/8

4 Q.11 Was this RFP intended primarily for Switchgear Manufacturers or Contractors? A.11 The original intent of this RFP was a quality based selection of proposals from Switchgear Manufacturer proponents who would provide turn-key installation and commissioning services. However, Utilities Kingston will accept proposals from other proponents. Q.12 Is it possible to schedule work after normal work hours for tie-in to the existing ITE Switchgear (Y-Bus)? A.12 Yes, Utilities Kingston will consider proposals from proponents that contemplate scheduling work associated with the tie-in to the existing ITE Switchgear (Y-Bus) after normal work hours in order to ensure that the Y-Bus remains in service for the majority of the project. Please refer to Note 5 on Drawing K E102 and the note regarding a Bus Transition for the existing Y-Bus on Drawing K E202 for further tie-in considerations. 3. Appendix A delete Section 2.0 Procurement & Installation in its entirety, and replace with the following amended text: 2.0 Procurement & Installation Procurement and installation will not proceed until acceptance of the business case by Utilities Kingston. Once the contract has been awarded, the proponent will be responsible for the construction and successful completion of the project in accordance with agreed benchmarks and timetables. 2.1 Site Preparation by Utilities Kingston Utilities Kingston will undertake the following work in preparation for the switchgear replacement project: a) Provide a report identifying designated substances. NOTE: Utilities Kingston will remove all asbestos coverings on cables and roof drain leaders prior to the contractor starting work on site b) Install a secondary transfer switch for the existing station service distribution panel (225A, 120/240VAC) and provide alternate external secondary station service supply c) Relocate the existing 44kV Auto-Transfer Panel d) Remove existing hardware on walls associated with existing switchgear tools to facilitate installation of new switchgear, associated accessories and conduit. e) Disconnect 3 PILC cables from T2-Q Bus PILC cables are 5kV, 3 conductor, 500MCM Copper. f) Disconnect 4 PILC cables; one from each feeder cell ( ) PILC cables are 5kV, 3 conductor, 500MCM Copper RFP UK Addendum #2 Page 4/8

5 g) Remove existing 5kV McGraw-Edison Switchgear (T2-Q-Bus) and associated equipment including: (1) Removal of a quantity of Amp frame feeder breaker cells (1106 through 1109) and associated electro-mechanical protection relays, metering, etc. (2) Removal of one Main 2000Amp Incoming Metering Cell (3) Removal of a all 3-phase bus-work from existing ITE feeder tie-switches to load side of McGraw-Edison feeder breaker cells (1106 through 1109). Utilities Kingston will also patch the openings on the top of the ITE switchgear. (4) Removal of existing 50kVA station service transformer and associated enclosure h) Install new SCADA Communication Box containing new Ethernet switch 2.2 Responsibilities of Proponent during Project The responsibilities of the successful Proponent for this project shall include but are not limited to the following: a) Assuming the role of Constructor in accordance with Ontario Occupational Health and Safety Act. NOTE: This may require the proponent to supply and install temporary barriers, hoarding, etc. to separate and secure the construction area affecting the T2-Q-Bus from the T1-Y-Bus that will remain energized during construction b) Completing all work in accordance with applicable legislative requirements c) Ensuring all high voltage electrical work complies with the Electrical Distribution Safety Regulation (EDSR) also known as Ont. Reg. 22/04 (refer to Electrical Safety Authority (ESA) document titled ESA Technical Guidelines for Section 6. Approval of Electrical Equipment, Section 7. Approval of plans, drawings and specifications for installation work, Section 8. Inspection and Approval of Construction Version 1.2 available for download from the ESA Website). More specifically, the proponent shall ensure that: (1) high voltage electrical equipment is approved in accordance with Rule of the Ontario Electrical Safety Code (OESC) to ensure compliance with Section 6 of the EDSR which refers to approval of electrical equipment. (2) a plan submission for high voltage installations is submitted to the ESA in accordance with Rule of the OESC and ESA Bulleting to ensure compliance with Section 7 of the EDSR which refers to approval of electrical plans, drawings and specifications for installation work (3) accurate as-built records are maintained during construction to facilitate Construction Verification by Utilities Kingston (4) sufficient time shall be allocated during construction for the purposes of Construction Verification of high voltage work by Utilities Kingston in accordance with Section 8 of the EDSR which refers to inspection and approval of construction work. Utilities Kingston will require accurate as-built RFP UK Addendum #2 Page 5/8

6 records from the proponent during construction in order to prepare partial and final Records of Inspection and Certificates of Inspection. NOTE: High Voltage equipment shall not be energized without the authorization of Utilities Kingston d) Ensuring all low voltage electrical work complies with the OESC e) Providing all construction documents to the appropriate authorities and obtaining all necessary permits and approvals from the appropriate authorities for construction f) Designing, supplying, installing, tie-in, commissioning and testing of new 5/15kV metal clad switchgear to meet or exceed the specifications found in Appendix B of RFP UK and within the constraints of the site. Designing, supplying, installing and tie-in includes all necessary building alterations including but not limited to venting, openings in floor for bottom entry of cables, etc. Commissioning and testing includes functional testing and electrical acceptance testing after installation. g) Installing a 13-JAW, Form 9S meter base and Meter Test Block (MicroElectric CT- 113) supplied by Utilities Kingston for T2-Q-Bus Interval Meter h) Supplying and installing 1-1/2 conduit raceway from instrument compartment of Main T2-Q-Bus to remote 13-JAW, Form 9S meter base and Meter Test Block i) Designing, supplying, installing, tie-in, commissioning and testing new Protection and Control equipment to satisfy the Protection and Control narrative found in Appendix C of RFP UK including but not limited to: (1) Supply SCADA RTAC rack as well as associated raceways, wiring and fibre optics for power, control and communication tie-ins. Work includes pulling Ethernet Communication Cables from new Protection Relays, GPS clock, etc. to SCADA communication cabinet and installing connectors. (2) Preparing a Protection and Coordination study for the purpose of programming the settings of the SEL Protection Relays and SEL RTAC unit. (3) Programming and configuring SEL Protection Relays, SEL RTAC unit, GPS clock etc. in order to perform functional testing and commissioning testing of both the switchgear and the SCADA equipment. NOTE: Utilities Kingston will play a role in programming, commissioning and testing of SEL Protection Relays, SEL RTAC unit as it relates to interfacing with the Utilities Kingston SCADA network. (4) Functional and commissioning tests of SEL Protection Relays, SEL RTAC unit, GPS clock etc. This testing shall include ringing-out wiring and operating devices using local and remote control functions. j) Preparing accurate As-Built records in both AutoCAD and PDF format 2.3 Responsibilities of Utilities Kingston during Project Utilities Kingston will be responsible for the following: a) Holding and maintaining a E&USA work permit for the duration of the work b) Switching and Energization as required to support contractor work c) Terminating primary cables on the Incoming terminals of the Main 2000Amp Breaker for the new switchgear (T2-Q-Bus) RFP UK Addendum #2 Page 6/8

7 d) Terminating primary cables on the Outgoing terminals of each 1200Amp feeder breaker cell (1106 through 1109) e) Installing all external low voltage power and control wiring as well as communication wiring and fibre optics in EMT conduit. f) Terminating DC connections at the existing DC Battery system g) Supply and Install two Interval meters (13-JAW plug-in) h) Connecting Ethernet Communication Cables from new Protection and SCADA equipment inside SCADA communication cabinet i) Updating Master Station SCADA screens for Substation MS11 j) Witnessing & Supporting Commissioning of SCADA equipment k) Support Switching & Isolation 2.4 Systems to Remain In Service During the Project The following systems in the 5kV switchgear room of MS11 shall remain in service during this project: a) Existing 5kV ITE Type HK Switchgear associated with the T1 Y- Bus shall remain in service (NOTE: temporary outages after hours may be required for tie-in with the new Bus-Tie breaker) b) Existing Survalent RTU cabinet shall remain in service c) Existing DC Battery system shall remain in service (NOTE: temporary outages after hours may be required to enable the proponent to tie-in conduit raceways and pull wiring) d) 120/240VAC external station service supply from street and associated branch circuit wiring for lighting, heating, battery charging, etc. (NOTE: temporary outages after hours may be required to enable the proponent to tie-in conduit raceways and pull wiring) e) Existing Security system shall remain in service f) Existing Washroom facilities shall remain in service 2.5 Working Restrictions The following working restrictions shall apply: a) Where work requires breaking into or connecting to existing services, or creates noise or dust, the proponent shall carry out work as directed by Utilities Kingston with a minimum of disturbance. b) Work must not interfere with the daily operations of Utilities Kingston. c) Work will be restricted to the immediate area of the site. d) Construction activities including parking of worker s vehicles, storage of construction equipment, and set up areas will be confined to areas approved by Utilities Kingston. e) Unless otherwise authorized by Utilities Kingston, on site construction activities will be limited to 7:00 am to 7:00 pm Monday to Friday. RFP UK Addendum #2 Page 7/8

8 f) Before commencing work, proponents will establish the location and extent of existing service lines in the area of construction and will submit scheduled shutdowns to Utilities Kingston for approval. g) All work will be performed within applicable environmental legislation. RFP UK Addendum #2 Page 8/8

9 Request for Proposal RFP# UK Addendum#2 Acknowledgement Form Addendum #2 to RFP UK-11-13, dated March 25, 2011, addresses several variances to the original RFP UK dated March 15, In summary, Addendum #2 includes variances as follows: 1. Questions and Answers related to the Mandatory Site Meeting that occurred Thursday March 24, :00AM at 60 Notch Hill Road, Kingston, Ontario (Substation MS11). 2. Subsequent Questions and Answers following the Mandatory Site Meeting. 3. Appendix A Section 2.0 Procurement & Installation. Our firm acknowledges receipt of Addendum#2, has confirmed receipt of the Addendum by ing to tbrackenbury@utilitieskingston.com and includes this completed form within our firm s proposal. Acknowledged by: Signature On behalf of: Company Name Date: RFP UK Addendum#2 Acknowledgement Form

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions

More information

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings

More information

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a

More information

CHUGACH ELECTRIC ASSOCIATION, INC. Anchorage, Alaska. February 10, 2014

CHUGACH ELECTRIC ASSOCIATION, INC. Anchorage, Alaska. February 10, 2014 CHUGACH ELECTRIC ASSOCIATION, INC. Anchorage, Alaska February 10, 2014 QUESTIONS AND ANSWERS TO: Prospective Proposers FROM: Chugach Electric Association, Inc. 5601 Electron Drive Anchorage, Alaska SUBJECT:

More information

Enhancing Personnel Safety with Arc Resistant Equipment

Enhancing Personnel Safety with Arc Resistant Equipment Enhancing Personnel Safety with Arc Resistant Equipment Carl Christian Power LV Offer Marketing Nashville, TN Sponsored by the Water Wastewater Competency Center 1 Enhancing Personnel Safety 5-10 Five

More information

City of San Diego Residential Photovoltaic Systems Inspection Guidelines

City of San Diego Residential Photovoltaic Systems Inspection Guidelines City of San Diego Residential Photovoltaic Systems Inspection Guidelines The purpose of inspections by DSD staff is to ensure compliance with the California Electrical Code (CEC), other applicable codes

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

County of Riverside Building and Safety Department

County of Riverside Building and Safety Department County of Riverside Building and Safety Department Mike Lara Director Photovoltaic Permitting Guidelines The information provided in this document is general and is intended only as a guide. Each project

More information

Remote Monitoring and REC 501 Control Unit Product Guide

Remote Monitoring and REC 501 Control Unit Product Guide Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

Request for Proposals for Photovoltaic System Installation

Request for Proposals for Photovoltaic System Installation Request for Proposals for Photovoltaic System Installation Presented by: Prepared by: Location: Contact: Date: Capitol Hill Housing Foundation Bonneville Environmental Foundation, Renewable Energy Group

More information

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114.

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114. Generation Interconnection System Impact Study Report For PJM Generation Interconnection Request Queue Position X1-114 Sandyston January 2012 Preface The intent of the System Impact Study is to determine

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

261000 Medium Voltage Electrical Distribution

261000 Medium Voltage Electrical Distribution Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This

More information

Ontario Electrical Safety Code 25 th Edition/ 2012

Ontario Electrical Safety Code 25 th Edition/ 2012 Ontario Electrical Safety Code 25 th Edition/ 2012 Ted Olechna Director, Codes and Standard Chief Engineer 1 What I Will Cover ESA s role is as the regulator Highlight of 2012 Code changes The Code and

More information

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY

More information

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

Extend the Life of Existing Switchgear

Extend the Life of Existing Switchgear Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...

More information

Utility generation line card

Utility generation line card Utility generation line card Integrated Power Solutions Integrated Power Assembly Integrated Power Assembly Deposit on Base Enclosure Medium Voltage COMPONENTS AND Assemblies VCP-W Switchgear Metal-Clad

More information

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general

More information

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s

More information

Top Commercial / Residential Electrical Requirements *

Top Commercial / Residential Electrical Requirements * Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

CalMod Design-Build Electrification Services

CalMod Design-Build Electrification Services SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor

More information

SWITCHGEAR. EGP Switchgear

SWITCHGEAR. EGP Switchgear SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS

PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS Butte County Department of Development Services PERMIT CENTER 7 County Center Drive, Oroville, CA 95965 Main Phone (530)538-7601 Permit Center Phone (530)538-6861 Fax (530)538-7785 FORM NO DBP-71 PERMIT

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

How To Plan Out An Array Of Solar Panels

How To Plan Out An Array Of Solar Panels CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured. SOLAR ALTERATIONS REQUIREMENTS August 2015 These requirements address typical alterations to solar installations; they cannot address every scenario. In Victoria, an alteration to a solar installation

More information

Power-Zone 4 Arc Resistant Low Voltage Switchgear

Power-Zone 4 Arc Resistant Low Voltage Switchgear Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Applying For New or Revised Electric Service

Applying For New or Revised Electric Service Applying For New or Revised Electric Service Dear Customer: ComEd is happy to assist you in initiating new or revised electric service to your location. Please complete, sign and return the attached service

More information

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify. SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.

More information

Electric Service Guide for Commercial Construction

Electric Service Guide for Commercial Construction Electric Service Guide for Commercial Construction Contents Contacting KCP&L... 2 Voltages... 2 Temporary Service... 2 Customer-Provided Temporary Service... 2 KCP&L-Provided Temporary Service.... 2 Current

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior

More information

Bypass transfer switch mechanisms

Bypass transfer switch mechanisms Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

CITY OF BELL PROFESSIONAL CONSULTING SERVICES FOR ROOF REPAIRS TO CITY OWNED FACILITIES

CITY OF BELL PROFESSIONAL CONSULTING SERVICES FOR ROOF REPAIRS TO CITY OWNED FACILITIES CITY OF BELL 6330 PINE AVENUE BELL, CA 90201 PH: (323) 588-6211 FAX: (323) 771-9473 CITY OF BELL PROFESSIONAL CONSULTING SERVICES FOR ROOF REPAIRS TO CITY OWNED FACILITIES I. INTRODUCTION City of Bell

More information

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation

More information

Sample - No Commercial Use

Sample - No Commercial Use COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort

More information

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service

More information

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management

More information

David Payne, P.E. Associate Director February 18, 2014

David Payne, P.E. Associate Director February 18, 2014 David Payne, P.E. Associate Director February 18, 2014 Overview of Texas A&M University State's first public institution of higher education, was opened on Oct. 4, 1876 as the Agricultural and Mechanical

More information

Approved Meter Sockets and Cabinets

Approved Meter Sockets and Cabinets Single Unit Residential Guide 1 PHASE, 120/240 VOLT S METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to center of meter ± 100 mm ( 4

More information

Power products and systems. Intelligent solutions for power distribution Zone concept

Power products and systems. Intelligent solutions for power distribution Zone concept Power products and systems Intelligent solutions for power distribution Zone concept Securing continuous power supply ABB is one of the world's leading power and automation technology companies whose products,

More information

Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015

Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 13860 (283100) FIRE ALARM SYSTEM The following standard shall be followed for the design of University

More information

Security Systems Intrusion Alarm

Security Systems Intrusion Alarm Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted

More information

SOLAR PV SYSTEMS PERMITTING PROCESS

SOLAR PV SYSTEMS PERMITTING PROCESS Department of Consumer and Regulatory Affairs SOLAR PV SYSTEMS PERMITTING PROCESS How to Reach Us 1100 4 th Street, SW Washington, DC 20024 dcra@dc.gov Permit Center Hours Monday, Tuesday, Wednesday &

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

Monitoring Underground Power Networks

Monitoring Underground Power Networks Monitoring Underground Power Networks By Mark Stiles Merve Cankaya ABSTRACT Underground electric distribution systems are common in large cities throughout the United States. Power usage for the entire

More information

3.) Remove Page Nos. 15, 16, 17, 18, 19, 20, 21, 22 of 30 and replace with Page Nos. 15, 16, 17, 18, 19 & 20 of 28 marked, REVISED 10/18/2013.

3.) Remove Page Nos. 15, 16, 17, 18, 19, 20, 21, 22 of 30 and replace with Page Nos. 15, 16, 17, 18, 19 & 20 of 28 marked, REVISED 10/18/2013. CITY OF HOUSTON Annise D. Parker Mayor P.O. Box 1562 Houston, Texas 77251-1562 Telephone Dial 311 www.houstontx.gov http://purchasing.houstontx.gov October 22, 2013 Subject: To: Letter of Clarification

More information

ICM Project Station Infrastructure and Equipment

ICM Project Station Infrastructure and Equipment EB 0 00 Schedule B. ( pages) ICM Project Station Infrastructure and Equipment (THESL) EB 0 00 Schedule B. I EXECUTIVE SUMMARY 0. Project Description Many Municipal Substations (MS) located outside of downtown

More information

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility

More information

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence

More information

Customer Metering and Services Guide

Customer Metering and Services Guide This document is an uncontrolled copy and may not be the most current copy. The most current copy is available at www.atcoelectric.com. This document is the property of ATCO Electric and may be updated

More information

REQUIREMENTS FOR CUSTOMER-OWNED PRIMARY SERVICES SUPPLIED AT 4 kv TO 35 kv PRIMARY GUIDE

REQUIREMENTS FOR CUSTOMER-OWNED PRIMARY SERVICES SUPPLIED AT 4 kv TO 35 kv PRIMARY GUIDE BC Hydro Distribution Standards REQUIREMENTS FOR CUSTOMER-OWNED PRIMARY SERVICES SUPPLIED AT 4 kv TO 35 kv PRIMARY GUIDE JUNE 2010 Changes Visible Edition This document shows all changes that have been

More information

How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work. Section 2 Types of Methods of Measurements page 4

How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work. Section 2 Types of Methods of Measurements page 4 How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work Table of Contents Section 1 Introduction page 3 Section 2 Types of Methods of Measurements page 4 Section 3 Project Specific

More information

APPLICATION FOR RENEWAL OF LICENCE TO USE OR OPERATE AN ELECTRICAL INSTALLATION (Please read Explanatory Notes before completing the Forms)

APPLICATION FOR RENEWAL OF LICENCE TO USE OR OPERATE AN ELECTRICAL INSTALLATION (Please read Explanatory Notes before completing the Forms) 2 FORM 1 APPLICATION FOR RENEWAL OF LICENCE TO USE OR OPERATE AN ELECTRICAL INSTALLATION (Please read Explanatory Notes before completing the Forms) PARTICULARS OF THE INSTALLATION Name of Electrical Installation/Company:

More information

Fusible Disconnect Switch

Fusible Disconnect Switch Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Whitepaper. Modular Substation Cable Termination Design. Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada

Whitepaper. Modular Substation Cable Termination Design. Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada Whitepaper Modular Substation Cable Termination Design Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada Abstract The methods for cable penetrations into modular industrial substations are

More information

DATAMENA COLOCATION SERVICE SCHEDULE

DATAMENA COLOCATION SERVICE SCHEDULE DATAMENA COLOCATION SERVICE SCHEDULE This Schedule is applicable to a Service Order for datamena Colocation Service(s) which has been submitted by Customer, and accepted by Supplier, in accordance with

More information

Solar Panel Installations

Solar Panel Installations Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

misconceptions about arc-flash hazard assessments

misconceptions about arc-flash hazard assessments misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation Stand Alone POTS Fiber Optic System P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit Description & Installation Printed in USA 09/11 TO466 Rev. A Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT

More information

How To Get A Power Line Extension

How To Get A Power Line Extension GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs

More information

Low Voltage Switchgear

Low Voltage Switchgear Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering

More information

Article 10 - ADMINISTRATIVE SECTION

Article 10 - ADMINISTRATIVE SECTION Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2011 Edition of the National Electrical Code (NFiPA-70-2011) as adopted by the

More information

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

Electrical. This section applies to the design and installation of building power distribution systems.

Electrical. This section applies to the design and installation of building power distribution systems. Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions

More information

1 General Responsibility. 1.1 Participants. 1.2 Documentation. 1.3 Lockout/Tagout

1 General Responsibility. 1.1 Participants. 1.2 Documentation. 1.3 Lockout/Tagout Electrical Safety Plan This plan establishes rules for both the design and operation of the LPRDS. These rules are intended to enhance the safety of the participants in the initial project and future users

More information

Synchropower Switchgear Replacement Cape Breton Regional Hospital Document Number: WS21717640

Synchropower Switchgear Replacement Cape Breton Regional Hospital Document Number: WS21717640 Nova Scotia Health Authority Tender Synchropower Switchgear Replacement Cape Breton Regional Hospital Document Number: WS21717640 A D D E N D U M #2 January 13, 2016 The Tender Documents, including Addenda,

More information

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

38. ACCESS CONTROL AND ELECTRONIC SECURITY SYSTEM

38. ACCESS CONTROL AND ELECTRONIC SECURITY SYSTEM 38. ACCESS CONTROL AND ELECTRONIC SECURITY SYSTEM 38.1 GENERAL Scope Modification and extension of the existing CDU Cardax security system and CCTV System including: Cardax (FT 3000 series) Access control

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

H.V.A.C. Design Plumbing Design

H.V.A.C. Design Plumbing Design H.V.A.C. Design H.V.A.C. Design Mira Costa College Arts Complex CP Upgrade 1. PART 1 GENERAL 1.1. DESCRIPTION SECTION 23 09 00 HVAC INSTRUMENTATION AND CONTROL 2. PART 2 - PRODUCTS 2.1. Materials

More information

Beaver Dam Unified School District Request for Proposal Video Surveillance and Door Access Control Systems

Beaver Dam Unified School District Request for Proposal Video Surveillance and Door Access Control Systems Beaver Dam Unified School District Request for Proposal Video Surveillance and Door Access Control Systems The Beaver Dam Unified School District (BDUSD) is requesting proposals from qualified companies

More information

OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B

OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B The OVR-3SP three-phase recloser style guide aids in the proper selection of your OVR-3SP style number. The OVR-3SP

More information

SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR

SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed

More information