Request for Proposal (RFP) for Technical and Functional Specifications for Building a Tier-III Data Center for Bhutan Telecom

Size: px
Start display at page:

Download "Request for Proposal (RFP) for Technical and Functional Specifications for Building a Tier-III Data Center for Bhutan Telecom"

Transcription

1 Request for Proposal (RFP) for Technical and Functional Specifications for Building a Tier-III Data Center for Bhutan Telecom (Version: 1.0 Date: 26 April 2013) TIMELINE FOR RFP: 1. Pre-bid Meeting: 10:00AM-5:00PM on 10 th May 2013 at Data Center Site, Bhutan Telecom Office, South- Western Region, Phuentsholing, Bhutan. 2. Deadline for RFP Submission: Only one sealed & signed original hard copy of RFP and a soft copy in PDF format should be submitted before or at 10:00AM on 24 th May 2013 in person or by post to: Manager Procurement Section Per & Adm Division PO Box 134 Bhutan Telecom, 2/28 Drophen Lam Thimphu Bhutan CONTACT POINT: All inquiries on this RFP should be directed to the following: Mr. Jichen Thinley, Project Manager (Regional Manager, South-Western Region), Bhutan Telecom jichen.thinley@bt.bt Phone: Fax: Mobile: Postal Address: PO Box No. 66, Bhutan Telecom, Phuentsholing, Bhutan Page 1 of 10

2 I. Introduction Bhutan Telecom (BT) is the leading telecommunications services provider providing landline telephony service as the sole operator; data (primarily Internet services as the biggest Internet Service Provider) service and domestic & international connectivity; and GSM (mobile) with 3G service (as the market leader) in Bhutan. BT has about 27,000 landline telephone customers, 17,000 fixed broadband subscribers, 230 enterprise customers for its data & connectivity services, and 421,700 mobile customers including that of 3G. The 4G LTE will be launched for trial for 2 sites in the capital Thimphu within this year. It is primarily to serve enterprise customers national and international (in the future) that BT plan to build a 5000 sq. ft. Data Center meeting the standards of Tier-III specifications as per the Telecommunications Industry Association s TIA-942 which comprises mainly the redundant & fully fault-tolerant capacity components including storage, chillers, HVAC, servers, etc. with dual-powered equipment and multiple uplinks guaranteeing an uptime of %. II. Size and Location The Data Center shall be built on the two floors: ground and the first; of approximate area of 2500 sq. ft. each making the combined total size of 5000 sq. ft. (approximately) in a 3-floor building which has been recently constructed in BT premise in Phuentsholing, Bhutan. The potential bidders are encouraged to visit the site before the submission of RFP. III. Scope of Work (in High-level) The Data Center and its infrastructure should be built on a turnkey basis meeting the standards of Tier-III as per TIA-942. Essentially, but not limited to, the Scope of Work shall include design, supply, installation, testing, commissioning and handing over with one year warranty the Data Center with necessary infrastructure like the: interior jobs with painting, precision air conditioning system, fire detection & supression, power, UPS & DG, electrical, lighting, network cabling, multilayer physical security using biometric/smart card, etc. based on access control, IP surveillance, water leakage & detection, rodent repellent, and other incidental and necessary components required to complete Tier-III Data Center specifications in all aspects. Further, the solutions should be proposed to establish very effective and efficient infrastructure monitoring & management systems/practices to ensure Tier-III reliability, availability, Quality of Services and security of information system. While the high-level scope of work has been outlined, Bidders are requested to prepare exact BOM required based on the total area provided in the RFP. IV. Design Considerations The Data Center should be capable to provide an uptime of %. It has to be compliant to a Tier-III standards as per TIA-942. The design should be scalable to offer scalability over a minimum period of 7 years and capable to house up to many nos. of 42U server racks (132 nos. if only racks) and cages. Key considerations should be taken in to build for redundancy, scalability, modularity, possibility of isolation and maintainability. The entire Data Center should be designed on the two floors clearly demarcated as per the architecture designs of Ground and First floors. All partitions should be constructed with fire-rated particle board and glass which will increase the aesthetic look. All doors should be 2 hours fire-rated glass. Necessary measures should be taken for making the Page 2 of 10

3 critical server farm area tight, fire proof and free from condensation and dust. The electrical system should be designed to Tier-III standards to allow concurrent maintainability. The secondary power should be DG set. Cooling should taken with N+1 redundancy for server farm area. The auxiliary areas should be provided with comfort AC with necessary redundancy. The structured cabling for the racks within the server farm area should meet CAT6A based design system with flexible deployment option in the form of enclosures in the flase floor. The physical security of the total Data Center area including Network Operation Center (NOC) room and Building Management System (BMS), viewing room should be taken care in multiple levels. Physical access restrictions shall be addressed through Access Control System in multiple doors. The critical areas shall be monitored through IP surveillance system with storing option. The equipment and human safety from the incidents shall be met with the help of fire alarm system. Further control action on fire/alarm shall be dealt using the fluid type NOVEC1230- based fire suppression system for server room and other rooms will be handled by portable fire extinguishers. The rodent repellent and water leakage detection systems should be installed in the server farm area. Physical infrastructure components will be controlled through BMS to provide alerts and alarms to the personnel operating and managing the infrastructure. The following but not limited to, are the major high-level systems design considerations that should included: S/N Systems 1 Interior Jobs i. Partitions ii. Doors iii. Thermal insulation on floor iv. Raised flooring v. POP and paints vi. Ramp 2 Electrical Works i. Power distribution system with LT panel ii. Cabling & wiring through cable tray iii. Lighting system iv. DG system v. UPS system vi. Earth 3 Cooling solution and PAC system 4 Physical Security with IP Survellance and Access Contol 5 Fire Suppression system with NOVEC Fire Detection system 7 Water Leakage & Detection 8 Passive Networking & Cabling 9 Rodent Repellant System 10 BMS system V. Guidelines for Technical & Functional Specifications of Major Components The following but not limited can be used as the guidelines to draw up and submit the full proposal for Technical & Functional Specifications for building a Tier-III Data Center for BT. Page 3 of 10

4 1. Architectural and Interior Jobs This should cover supply, design and implementation of architectural and interior jobs for the Data Center with supply of all accessories / tools required for aesthetic, durability and technically superior solution for the following but not limited to: i. Paint work with POP ii. False flooring iii. Floor insulation iv. Partitioning (fire-rated) v. Doors vi. Required miscellaneous civil work as per Data Center site s requirement Insulation Work The floor shall be heat-insulated or coated with a heat insulating material to avoid condensation on floors below and above to reduce heat transfer to the server/network rooms. Insulation should be done with minimum 9 mm thick self-adhesive aluminum foil face nitrite rubber. The ceiling and floor should be coated with epoxy paint Raised Floor for Server Farm and Associated Rooms The floor will cover server farm areas, BMS, fire panel and NOC rooms. The server farm are with combined area of 2x2500 sq. ft. should be provisioned to place many nos. of 42U (1000mm x 800mm) server racks (132 nos. if only racks) and cages in both floors. Supply and installation of false floor (450mm thickness) of fire retardant category which should be replaceable/interchangeable floor panels of 18 SWG steel, 600mm x 600 mm with top HPL of 1.5mm thickness with PVC beats. The floor system should be capable to withstand a UDL of 1080 kgs per sq. mt. and point load of 380 kgs. The understructure should be able to accept a pedestal axial load of 2200 kgs. The supply requires numbers of grommets for passive through wire and cables; and perforated tile for airflow. There should be thermal insulation of the base floor with thick insulation for all the areas Partitioning Work Fireproof aluminum composite panel with 8mm thick fire-rated particle board in bottom half and upper half with toughened glass of size 8mm thick with 2 hours minimum fire-rated for partition between server room, monitoring room and help Desk area on first floor room, and control room and viewing room on the ground floor. All gaps should be filled with rubber runner Doors All doors should be 12mm thick glass with fireproof aluminum composite panel and 2 hours fire-rated. The doors should be completed with all accessories. Door 1: Entrance to server farm area. Size: 3.5 ft. x 7 ft. for both the floors. Door 2: Control room door. Size: 3 ft. x 7 ft. on the ground floor. Page 4 of 10

5 Door 3: Monitoring room door. Size: 3 ft. x 7 ft. on the first floor. Door 4: Emergency door. Size: 3 ft. x 7 ft. for both the floors Painting It should be anti-dust. The existing surfaces should be cleaned with scratched before the application of punning material. After drying, the smoothening should be done rubbing with sandpaper. Upon the smoothened surface, one coat of primer and two coats of fire-rated paint of high-quality make and shade should be applied Ramp The ramp is of concrete (cement) and it will have to be finished with corrugated rubber mat at server farm entrance of both the floors. Size of each ramp is 4x5 ft. with an elevation angle of Electrical System and Equipment It shall cover design, engineering, assembly, testing and commissioning of complete electrical system and equipment and their accessories for efficient and trouble free operations and maintenance. The following design considerations can be taken: i. Electrical power load of 6KW per server rack (approximately). ii. Electrical power distribution should be provided with redundant path to avoid single point of failure. All elements of electrical systems including backup system are should be fully duplicated to provide N+1 redundancy iii. There should be provision to integrate additional power from second transformer. iv. More UPS systems and DG set should be able to integrate in the future. v. BT premise at where Data Center site is located currently has 500KVA capacity for the entire premise. Of this, 100KVA are in use and the rest 400KVA can be used for Data Center. vi. Electrical system should provide power to all utilities like the precision air conditioning, lighting, power distribution boards, utility UPS, etc. vii. The following tentative list of equipment should be supplied, installed and commissioned: 1. Modular type LT panel with multiple feeder 2. UPS panel with a provision of adding more UPS 3. Distributed inputs for precision AC supply system 4. BBT system with plug socket for power distribution to utilities 5. Distribution board for illumination 6. Power distribution board for raw power source 7. Distribution board from UPS system (UPSDB) 8. Cabling system with associated cables and cable trays 9. Earthing system for LT installations and UPS neutrals 10. Miscellaneous items for complete functioning of the system viii. Server farm load of about 132 nos. server racks with dual source of 32Amp industrial plug socket per rack. Page 5 of 10

6 3. UPS System There should be at least 400KVA UPS system in Parallel Redundant System (PRS) N+1 mode with backup (with SMF batteries) to cater to % reliability to feed power 30 nos. of server racks initially. In future, it is projected to require 3x400KVA with the same reliability with SMF battery bank connected in PRS N+1 mode that should be able to supply 800KVA power. Under PRS mode, all UPS should cater equal percentage of power i.e. if one fails; other(s) will supply 100% of the load. The monitoring of UPS enabled with SNMP card will be done through a LAN network. 4. Diesel Generator Set A DG set with automatic start-stop i.e. with all the automatic features should be used. The normal power supply for the Data Center shall be available from the LT panels. The DG set which will be used, as the standby power source will be connected to cater power in black out condition. LT panel should have an inbuilt arrangement of two bus sections: one for normal supply & another for DG supply. The interlocking features between two different sections of buses will have to be provided in the LT panel. The DG control panel should be integrated with this LT panel by power & control cabling. The system will should be installed with AMF panel along with required earth-pits. 5. Cooling Solution The precision air conditioning should be installed by considering the following design, scope and requirement. i. Design Considerations There should be fully redundant microprocessor-based digitalscrolled Precision Air Conditioning (PAC) system. Cool air feed should be bottom-charged or downward-flow type using the raised floor as supply plenum using perforated aluminum tiles for airflow distribution. The return airflow should be through false ceiling to cater to the natural upward moment of hot air. Cooling should be done by the Precision Air Conditioning system only. PAC should be capable of providing sensible cooling capacities at design ambient temperature & humidity with adequate airflow. As per the requirement, there would be around 130 racks. The PAC should be integrated with the BMS for effective monitoring. PAC system should cool the server rooms and other rooms on the basis of available rooms size and estimated load. 5 nos. of 30 TR floor discharge type PAC can be considered for each floor of Data Center. Out of five units, four units should be active while one can be in standby mode to provide redundancy. ii. Scope Considerations This shall include: Connecting the indoor unit with the main electrical point. Connecting indoor and outdoor units mechanically (with 18G hard Gauge copper piping). Connecting indoor and outdoor unit electrically. Page 6 of 10

7 Nitrogen pressure testing, triple vacuum, final gas charging. Connecting the humidity feed line with the point provided. Connecting the drain line with the point provided. iii. iv. Temperature and Humidity Requirement The inside environment of server rooms shall need to be continuously maintained at centigrade and ambient RH level shall need to be maintained at 50% +-5 non-condensing. Humidity sensors should be installed. PAC System Component Requirement a. 28TR Digital scrolled indoor unit b. Outdoor units for the above system c. Inbuilt network control card d. Required quantity of R407C refrigerant gas e. Copper piping with insulator f. Humidifier pipe g. Drain pipe h. Cable with other accessories to complete the system 6. Building Management System (BMS) BMS should be proposed by considering the following scope and design requirement. i. Scope Integrated MBS GUI software of high-performance, building automation system for monitoring and managing devices and systems, including HVAC, lighting, water, electrical equipment, etc. will be needed. It should be an application of building integrator platform utilizers conforming to open system standards to seamlessly integrate every control and information system with the facility/enterprise. Building integrator platform shall have singlewindow control over all building operations, and all the relevant data needed to maximize building performance. ii. System Design Architecture Enterprise building integrator platform should have architecture to provide a scalable system that accommodate configurations ranging from a small single-node system to an extended system with multiple stations connected across a LAN. It should cover: PAC monitoring Life safety monitoring Energy usage monitoring IP Surveillance systems LAN-based digital video management Time and attendance 7. Intelligent Addressable Fire Detection System Page 7 of 10

8 Intelligent addressable fire detection with alarm system with central monitoring system will be required. This system should be installed at server farm areas, NOC room, Help Desk room, control room and monitoring room. The system should incorporate following designs: Intelligent addressable fire alarm control panel with inbuilt battery Photo electric smoke detector Heat detector Response indicator Manual pull station Hooter Cable and other accessories require to complete the system 8. Fire Suppression System Following scope, design and information should be considered: i. Scope Fire suppression system with friendly fluid type NOVEC1230 agent can be used for the server farm areas only. This fire suppression system should be integrated with fire alarm system. For other areas, ABC-type portable fire extinguishers should be proposed. ii. Design The system should automatically discharge suppression agent after getting signal from the fire alarm panel. System can be designed with: a. Agent cylinder 120 ltr. capacity b. NOVAC1230 clean agent iii. c. Local manual actuator d. Flexible Discharge House e. Check value f. Discharge nozzle g. Pipes, cylinder manifold, fittings, etc. Information useful for consideration in clean agent fire suppression The lessor harmful fluid type agent NOVEC1230 should be proposed. Clean agent system considered for total flooding application is in compliance with the provisions of Kyoto protocol. Care should be taken that none of the Greenhouse gases identified in the Kyoto protocol is used for fire suppression application. The minimum criterion for the section of the clean agent Page 8 of 10

9 should be on: zero ozone depleting potential; global warming potential not exceeding one; atmospheric lifetime not exceeding 24 hours. Clean agent fire suppression system with FK-5-12 and inert Gas based systems are accepted as a replacement of HCFC and HFC as per Kyoto Protocol. The Clean Agent considered for the suppression system must be suitable for occupied areas with NOAEL level (No observable adverse effect level) of 10% to ensure high safety margin for the human in the hazard zone. Care should be given to ensure proper early warning detection system with minimum sensitivity of 0.03% per foot obscuration as per NFPA 318 & NFPA 72 to ensure that one gets a very early warning to investigate the incipient fire much before the other detectors activate the fire suppression system automatically. 9. Access Control System It should be IP-based access control system that will cover: normal door entry and exit with reader and controllers; emergency exits; locking devices, etc. and should have time attendance system with following design consideration. Design Consideration All doors should have access control security implemented. Biometric card reader should control the access to the server room door, main entrance doors on each floor. Proximity card reader will control the other two doors including emergency exit of each floor. The overall system will be controlled by BMS system with the following units: a. Multi door segment controller with power supply, IP connectivity and battery backup. b. Reader interface module to connect readers to central controllers. c. Proximity card reader. d. Biometric finger print reader. e. Single door electromagnetic lock. f. Magnetic contact (surface mount). g. Emergency release switch. h. Access management software with time and attendance features. 10. Surveillance System The system should an IP surveillance system to monitor the entire Data Center infrastructure and should be designed with: a. IP based colour dome fixed lens camera b. Indoor type HD PTZ camera Page 9 of 10

10 c. Video surveillance manager server d. Operation manager with software e. Video storage up to 30 days f. Virtual matrix software g. 80 LED display 11. Rodent Repellent System The pest repellent system should consist of one master console installed in Help Desk room and twelve satellites/transducers in the problem areas. The operation should be such that the powerful high frequency sound waves (well above the 30KHz frequency which is the upper limit of the hearing range of human ear) generated by the satellites are within the hearing range of many pests, but cause pain and discomfort thereby forcing them to abandon the areas. 12. Water Leakage Detection System Water leakage detection integrated with the BMS system should be designed to protect the air-conditioned premises and to alert the personnel about the leakage in the AC systems. The systems shall be capable of interfacing to water leakage detection sensors, condensation sensors/detectors, I/O modules and sounders all connected to control panel so that events are clearly reported on LED display indicating the nature of fault. 13. Passive Networking (LAN) The scope should comprise of design, supply, laying, installation, testing and commissioning of structured Local Area Networking (LAN) / cabling in the Data Center. The network will also connect associated rooms including Power (UPS) room to bring all the power system under LAN. The following design should be considered: a. The networking/cabling should be designed with CAT6A, which supports minimum of 10G both on copper and fiber cable. b. 4 Main Distribution Area (MDA) racks will be placed in Row 1 of each floor. c. On each floor there will two numbers of active network racks and two numbers of passive racks. d. There will be two MUX room one will be on the ground floor and other will be at the adjacent building. e. CAT6A 24 ports per rack. f. 48 fiber OM4 core per rack. g. The connection between the MUX room and MDA rack will be Fiber. Page 10 of 10

Zone B: comprises of NOC room, reception area, Help Desk area, Call Centre, Testing/Monitoring room. This zone requires approximately 1500 sq. feet.

Zone B: comprises of NOC room, reception area, Help Desk area, Call Centre, Testing/Monitoring room. This zone requires approximately 1500 sq. feet. Annexure 1 Best practices and Guidelines to Physical Security of the State Data Centre The Data Centre should ideally be built in a central location within the building complex. An approximate area of

More information

DESIGNING DATA CENTERS & SERVER ROOMS

DESIGNING DATA CENTERS & SERVER ROOMS DESIGNING DATA CENTERS & SERVER ROOMS Compton s Designing Data Center Services are an enterprise-wide, consultative approach to help you manage mission critical environments. The services encompass the

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

National Aluminium Co. Ltd.

National Aluminium Co. Ltd. National Aluminium Co. Ltd. [NALCO] EXPRESSION OF INTEREST FOR DATA CENTRE CO-LOCATION SERVICES Address for Communication The Project Manager ERP P/1, NALCO BHAWAN NAYAPALLI, BHUBANESWAR 751061 E mail:

More information

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while

More information

JAWAHARLAL NEHRU UNIVERSITY

JAWAHARLAL NEHRU UNIVERSITY School of Biotechnology JAWAHARLAL NEHRU UNIVERSITY New Delhi 110 067 Tender No. JNU/SBT/DBT-BUILDER/Data Centre/2015-16 Sealed Quotation for the establishment of a Data Centre for High-End Computational

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009 Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of

More information

Safeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive

Safeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive Co-Location Services Safeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive optimum performance 24x7. SERVICE

More information

Dedicated Hosting Services

Dedicated Hosting Services Dedicated Hosting Services Protect and manage your Servers/ Routers/ Switches/ storage devices/ security devices under a highly secure hosting space and get the finest performances out of them. SERVICE

More information

melbourne//australia data center specifications internet + intellectual property + intelligence tel: +61 2 9948 8888 fax: +61 2 9948 1111

melbourne//australia data center specifications internet + intellectual property + intelligence tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Melbourne,. We can colocate standard rack-mountable servers or other

More information

Data Center Presentation

Data Center Presentation Data Center Presentation The NetSource Datacenter. Agenda General Layout of Data Center Policies and Procedures Designed to Latest Standards High Performance High Reliability High Security Design Details

More information

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work

More information

Server Monitoring & Management Services

Server Monitoring & Management Services Server Monitoring & Management Services Monitor and manage your applications and servers under enterprise-class monitoring solutions, and protect your business from planned and unplanned downtime. ITI

More information

Netmagic Vikhroli Datacenter Infrastructure & Capabilities

Netmagic Vikhroli Datacenter Infrastructure & Capabilities Netmagic Vikhroli Datacenter Infrastructure & Capabilities CONTENTS INTRODUCTION... 3 INFRASTRUCTURE / FACILITIES... 4 FACILITY DETAILS... 5 POWER DISTRIBUTION... 6 HEAT VENTILATION AND AIR CONDITIONING...6

More information

Upgrading the PRS datacentres: space requirement. S. S. Mathur, GM-IT, CRIS

Upgrading the PRS datacentres: space requirement. S. S. Mathur, GM-IT, CRIS Upgrading the PRS datacentres: space requirement S. S. Mathur, GM-IT, CRIS PRS / UTS scenario: then and now Year 2000 PRS: 600 locations UTS: 0 locations Year 2008 PRS 1600 locations E-ticketing Passengers

More information

Reduce the cost and delays associated with troubleshooting with the help of round-the-clock Service Desk Support.

Reduce the cost and delays associated with troubleshooting with the help of round-the-clock Service Desk Support. Remote Support Reduce the cost and delays associated with troubleshooting with the help of round-the-clock Service Desk Support. SERVICE DEFINITION: REMOTE SUPPORT SERVICES ITI s Remote Support Service

More information

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier

More information

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.

More information

hong kong//china data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence

hong kong//china data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Hong Kong, China. We can colocate standard rack-mountable servers or

More information

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA

More information

Data Centre Services. JT First Tower Lane Data Centre Facility Product Description

Data Centre Services. JT First Tower Lane Data Centre Facility Product Description JT First Tower Lane Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room enviroment with protected incoming power supplies, state-of-the-art security

More information

Data Center Infrastructure & Managed Services Outline

Data Center Infrastructure & Managed Services Outline Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists

More information

Data Centre Services. JT Rue Des Pres Data Centre Facility Product Description

Data Centre Services. JT Rue Des Pres Data Centre Facility Product Description JT Rue Des Pres Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room environment with protected and backup power, security and bandwidth. Data Centre

More information

OPERATOR - FACILITY ADDRESS - DATE

OPERATOR - FACILITY ADDRESS - DATE . Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.

More information

Network Router Monitoring & Management Services

Network Router Monitoring & Management Services Network Router Monitoring & Management Services Get different parameters of routers monitored and managed, and protect your business from planned and unplanned downtime. SERVICE DEFINITION: NETWORK ROUTER

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Data Center Management

Data Center Management Data Center Management How Cisco IT Operates, Manages, and Protects Its Data Center A Cisco on Cisco Case Study: Inside Cisco IT 1 Overview The Cisco IT Operations Data Center on the San Jose, California

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Portable Energy Efficient Data Centre Solution

Portable Energy Efficient Data Centre Solution Portable Energy Efficient Data Centre Solution Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354 6447 www.workspace-technology.com

More information

South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime

South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in August 2002,

More information

singapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence

singapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Singapore. We can colocate standard rack-mountable servers or other

More information

Alarm and Detection/Suppression

Alarm and Detection/Suppression Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent

More information

EVT0002256 Services, Data Center Co-Location Updated Attachment A and B

EVT0002256 Services, Data Center Co-Location Updated Attachment A and B Attachment A Data Center Co-location Requirements 1. Scope This document defines KSDE s data center facilities requirements for reference in the Request for Proposal (RFP) for a Co-location Services Vendor

More information

This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits.

This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. DCD, DCOM, DCE DESIGN IMPLEMENTATION BEST PRACTICE OPERATION & MANAGEMENT DATA

More information

Technical specifications. Containerized data centre NTR CDC 40f+

Technical specifications. Containerized data centre NTR CDC 40f+ Technical specifications Containerized data centre NTR CDC 40f+ CONTENT 1 THE PURPOSE OF CDC... 3 2 BASIC PROPERTIES... 4 2.1 EXTERNAL DIMENSIONS... 4 2.2 INSTALLATION REQIREMENTS... 4 2.3 ELECTRICAL CONNECTION

More information

How To Visit An Internet Data Center

How To Visit An Internet Data Center AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina

More information

LEVEL 3 DATA CENTER ASSESSMENT

LEVEL 3 DATA CENTER ASSESSMENT Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments

More information

IPSIP M series-m Modular Data Center

IPSIP M series-m Modular Data Center IPSIP M series-m Modular Data Center IPSIP MODULAR TECHNOLOGIES. 1 With the rapid development of cloud computing and mobile Internet businesses, the growth of IT density and energy consumption are bringing

More information

vcloud SERVICE Virtual Tech in partnership with Equinix - vcloud Service

vcloud SERVICE Virtual Tech in partnership with Equinix - vcloud Service vcloud SERVICES vcloud SERVICE Virtual Tech offers competitive pricing on vcloud hosted services at our world class Tier 4 data centre facility fully equipped with redundant power, cooling, internet connectivity

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section

More information

AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)

AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

DATA CENTRE DATA CENTRE MAY 2015

DATA CENTRE DATA CENTRE MAY 2015 DATA CENTRE DATA CENTRE MAY 2015 CONCERTHOUSE MUSIC Concerthouse Music Data Centre services are located in the Equinix Internet Business Exchange (IBX ) Centre at Mascot. This IBX offers the highest level

More information

Jai om work meticulously around the clock to ensure our clients receive unrivalled expertise and solution to meet their requirements.

Jai om work meticulously around the clock to ensure our clients receive unrivalled expertise and solution to meet their requirements. SERVER ROOM, DESIGNING, DATA CENTER SOLUTIONS, SERVER RACKS, NETWORKING SOLUTIONS, RACKS PDU, SECURITY SYSTEM, FIRE SUPPRESSION (NOVEC 1230 FE227, FM200 ), VESDA, CCTV, FAS, ACS, RODENT AND WLD FALSE FLOORING,

More information

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power

More information

South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime

South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

MARULENG LOCAL MUNICIPALITY

MARULENG LOCAL MUNICIPALITY MARULENG LOCAL MUNICIPALITY Data Centre Physical Access and Environmental Control Policy Draft: Data Centre Access Control and Environmental Policy Page 1 Version Control Version Date Author(s) Details

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM

More information

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus. DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure

More information

BELLE VUE MANCHESTER DATA CENTRE

BELLE VUE MANCHESTER DATA CENTRE www.iracknet.com 0843 557 5712 bellevue@iracknet.com www.iracknet.com BELLE VUE MANCHESTER DATA CENTRE 02 BELLE VUE MANCHESTER HIGHLY ADVANCED DATA CENTRE PURPOSE BUILT TO DELIVER UNRIVALLED FLEXIBILITY

More information

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends

More information

Scalable. Affordable. Flexible. Fast.

Scalable. Affordable. Flexible. Fast. Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations

More information

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0. Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M

More information

NORTHERN VIRGINIA ONE (NoVa) DATA CENTER OVERVIEW

NORTHERN VIRGINIA ONE (NoVa) DATA CENTER OVERVIEW VAZATA 9651 Hornbaker Road Manassas, VA 20109 VAZATA.COM VAZATA's NoVa One data center located at 9651 Hornbaker Road in Manassas, Virginia is engineered from the ground up to deliver highly reliable and

More information

Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport

Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport Welcome Zenium Istanbul One provides 12,000 square metres of high specification technical space across three purpose-built data centers. It is Turkey s first wholesale data center offering; the data halls

More information

Data Center Overview Document

Data Center Overview Document Overview NetSource is a Chicago area (Naperville) hosting company that owns and operates its own world class datacenter. The initial datacenter buildout was put into operation in 2007 and expanded in 2013.

More information

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C COOLS conditioned server - racks for direct installation into the room COOLSIDE box INVERTER R410A E C 2 COOLSIDE box GENERAL FEATURES COOLSIDE BOX is a split system consisting of an outdoor motocondensing

More information

Zertico Rack Monitoring Unit

Zertico Rack Monitoring Unit Zertico Rack Monitoring Unit Typical applications of Zertico Monitoring devices: - Monitoring of IT infrastructure (e.g. data center) - Monitoring of technical rooms in branch offices - Remote monitoring

More information

Cannon T4 Modular Data Centres. For Outside Deployment & Challenging Environments

Cannon T4 Modular Data Centres. For Outside Deployment & Challenging Environments Cannon T4 Modular Data Centres For Outside Deployment & Challenging Environments A high performance, full specification Data Centre, up to Tier 4* resilience, instantly deployable A highly secure Data

More information

Department of Administration DATA CENTER Two Phase Approach Located at the State Defense Building

Department of Administration DATA CENTER Two Phase Approach Located at the State Defense Building DATA CENTER Two Phase Approach Located at the State Defense Building July 17, 2015 Compiled by: Office of Facilities and Property Management 800 SW Jackson, Suite 600 Topeka, Kansas 66612-1216 i I. Programming

More information

Colocation. Scalable Solutions for a Shared IT Infrastructure. Enterprise. Colocation

Colocation. Scalable Solutions for a Shared IT Infrastructure. Enterprise. Colocation Scalable Solutions for a Shared IT Infrastructure Global and domestic competition, rising real estate and power costs, and shrinking IT budgets are causing today s businesses to seek alternatives to building

More information

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center

More information

CoolTeg Plus Chilled Water (CW) version: AC-TCW

CoolTeg Plus Chilled Water (CW) version: AC-TCW version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420

More information

IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com. 2011 IBM Corporation

IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com. 2011 IBM Corporation IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com Overview Profile IBM owned facility 6447 m² IT-Space Infrastructure concurrent maintainable (Tier Level 3) Feed-ins of Power

More information

Colocation. Scalable Solutions for Shared IT Infrastructure. Enterprise. Colocation

Colocation. Scalable Solutions for Shared IT Infrastructure. Enterprise. Colocation Scalable Solutions for Shared IT Infrastructure Global competition, rising real estate and power costs, and shrinking IT budgets are causing today s businesses to seek alternatives to building their own

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE

DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE Molex Premise Networks EXECUTIVE SUMMARY The term data centre usually conjures up an image of a high-tech IT environment, about the size of a football

More information

Designing the Data Center

Designing the Data Center Designing the Data Center Asef Baddar, RCDD May -, 00 Talking points What are Data Centers? Why Data Centers? The components of the Data Center Approaching the Data Center design Breakdown of the components

More information

Keyword: TIA 942, Tier level, Nuclear Data Center. Introduction

Keyword: TIA 942, Tier level, Nuclear Data Center. Introduction Nuclear Data Center International Standard Towards TSO Initiative Raja Murzaferi Raja Moktar, Mohd Fauzi Haris, Siti Nurbahyah Hamdan, Saaidi Ismail,Radhiah Jamaluddin, Nursuliza Samsudin. IT Center, Technical

More information

T1 Backhaul Connectivity Solution All Products :: Application Note

T1 Backhaul Connectivity Solution All Products :: Application Note Telect 1 RU Customer Interface Panel (CIP) Enables Demarcation, Remote Circuit Maintenance and Trouble Isolation at the Backhaul Node The Application: T1 Demarcation and Testing in Backhaul Environments

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

Modular Datacenter based in a 20' container

Modular Datacenter based in a 20' container Modular Datacenter based in a 20' container RETEX, S.A. Avda Tecnología, 35. 08840 VILADECANS (Barcelona), SPAIN. T. +34 932 649 850 F. +34 936 592 368 info@retex.es www.retex.es INDEX 1. THE DATABOX SOLUTION...

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

DATACENTER COLOCATION. Flexible, Secure and Connected

DATACENTER COLOCATION. Flexible, Secure and Connected DATACENTER COLOCATION Flexible, Secure and Connected Flexible Solutions for Your Requirements Contents Your Goals 2 Compound and Buildings 4 Security 6 Infrastructure 8 Free Choice 10 Good Reasons 12 Our

More information

MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS

MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a

More information

IBM Portable Modular Data Center Overview for Critical Facilities Round Table

IBM Portable Modular Data Center Overview for Critical Facilities Round Table Brian Canney Global Services Executive, IBM GTS Site and Facilities Services April 2011 IBM Portable Modular Data Center Overview for Critical Facilities Round Table 2009 IBM Corporation Key messages Containers

More information

APC APPLICATION NOTE #92

APC APPLICATION NOTE #92 #92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Content Index. 1. General... 3. 2. Location and Building... 4. 3. Telecommunication Feeds... 6. 4. Electric Power... 7. 5. Climate Control...

Content Index. 1. General... 3. 2. Location and Building... 4. 3. Telecommunication Feeds... 6. 4. Electric Power... 7. 5. Climate Control... Content Index 1. General... 3 2. Location and Building... 4 3. Telecommunication Feeds... 6 4. Electric Power... 7 5. Climate Control... 8 6. Safety and Security... 9 7. Internal Procedures... 11 General

More information

AT&T Internet Data Center Site Specification New York III (Secaucus, NJ)

AT&T Internet Data Center Site Specification New York III (Secaucus, NJ) AT&T Internet Data Center Site Specification New York III (Secaucus, NJ) Site Biography Market Area: New York City, New Jersey, Upstate NY and Lower Connecticut Location: Secaucus, NJ 07094 Address: 15

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center

More information

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER Your Complete Turnkey Server Room Air Condition UPS THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER AVAILABLE IN WATER AND GAS SYSTEM MODEL AIR-CONDITIONED CABINET EXCELLENT TEMPERATURE CONTROL FOR

More information

RiMatrix S Make easy.

RiMatrix S Make easy. RiMatrix S Make easy. 2 RiMatrix S Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure, power

More information

Technical Specifications for West Campus Data Center HVAC System

Technical Specifications for West Campus Data Center HVAC System Technical Specifications for West Campus Data Center HVAC System I. Mechanical Systems Requirements A. HVAC Primary Data Centers, Automation HVAC is to be provided on a 24 hours per day, 365 days per year

More information

SPECIAL APPLICATIONS

SPECIAL APPLICATIONS Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

Raised Floor Data Centers Prepared for the Future

Raised Floor Data Centers Prepared for the Future Raised Floor Data Centers Prepared for the Future Raised Floors Protect My Investment by Providing a Foundation for Current and Future Technologies. Creating the Future Proof Data Center Environment The

More information

Request for Proposal RMA Construction of Integrated Data Center

Request for Proposal RMA Construction of Integrated Data Center ROYAL MONETARY AUTHORITY OF BHUTAN Request for Proposal RFP For CONSTRUCTION OF INTEGRATED DATA CENTER Date 18 th Sept. 2012 RMA: Thimphu Post Box: 154 Tel 975 2 323111 Ext. 126 Fax: 02 322847 Email: rma.itd@rma.org.bt

More information

DATA CENTRES POWERED BY EXCEL

DATA CENTRES POWERED BY EXCEL DATA CENTRES POWERED BY EXCEL MAXIMISE EFFICIENCY BOOST PERFORMANCE INCREASE R.O.I. WITHOUT COMPROMISE Excel is a world-class premium performance end-to-end infrastructure solution. Designed, manufactured,

More information

Integrated Building Management and Security System. Building Automation & Security. www.coba-group.com

Integrated Building Management and Security System. Building Automation & Security. www.coba-group.com Integrated Building Management and Security System Building Automation & Security www.coba-group.com INTEGRATED BUILDING MANAGEMENT AND SECURITY SYSTEM INDEX 1 GENERAL... 3 1.1 SYSTEM INTEGRATION... 3

More information

REVIEWED ICT DATA CENTRE PHYSICAL ACCESS AND ENVIROMENTAL CONTROL POLICY

REVIEWED ICT DATA CENTRE PHYSICAL ACCESS AND ENVIROMENTAL CONTROL POLICY LI_M_POPO PROVINCIAL GOVERNMENT :;:ED.JBl-C ()F SO"';-H AFR;IC. ':.,. DEPARTMENT OF CO-OPERATIVE GOVERNANCE, HUMAN SETTLEMENTS & TRADITIONAL AFFAIRS REVIEWED ICT DATA CENTRE PHYSICAL ACCESS AND ENVIROMENTAL

More information

Trends and Standards in LAN Cabling Systems Intelligent Buildings

Trends and Standards in LAN Cabling Systems Intelligent Buildings Trends and Standards in LAN Cabling Systems Intelligent Buildings A Sitaramaiah Managing Director CommScope Solutions India Intelligent Buildings Smart Cities Opportunities in Systems Integration Smart

More information