AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)
|
|
- Elfreda Logan
- 7 years ago
- Views:
Transcription
1 AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ Address: 1301 University Blvd. CLLI, POP, NPA/NXX Code: MESAAZLB, MESAAZTL, 480/615 History of Facility: Existing AT&T Telco center refurbished in 2000 to AT&T Internet Data Center Standards and Industry IDC Standards, expanded in 2006 and Center Amenities: Customer Lounge Facilities Customer Conference Rooms Customer Briefing/Visit Request: If you would like to schedule an IDC Tour, click here to use the scheduler If you are not a Certified Tour Manager and would like to schedule a visit to a Domestic IDC, please contact your local Enterprise Hosting Specialist. For the Corporate Briefing Center Online Visit Scheduling System Gross Sq. Feet: 143,600 Total Net (Raised Floor) Area: 72,200 SAS70: This site undergoes annual SAS70 Type 2 auditing. Network Internet (Front-end) IP Capacity: Minimum of two (2) high speed uplinks to the AT&T IP Network Redundancy: Administrative (Back-end) Connectivity: Redundant and path-diverse entrances and exits. Dual access routers connect the Internet Data Center to the AT&T IP Network via multiple network access points. Access the AT&T Back-End Connectivity Guide for options Mesa 1 of 6
2 Architectural Section Building Raised Floor Specifications: Loading and Receiving Dock: Power Watts / Square Foot: Raised floor for equipment spans the entire computer room area. Allowable load for the tiles is 150lbs per square foot. Loading dock facilities are available. Onsite security personnel monitor access to the loading dock. Customer shipments to the IDC require customer site ID # on all shipping labels. No unidentified packages will be accepted. The Power Density meets AT&T Internet Data Center Standards and IDC Industry Tier 4 Standards. Commercial Power: Standby Generator Systems: The Internet Data Center has one (1) commercial power service feed for this building. Seven (7) - 2,000kW diesel generators providing standby power to the Internet Data Center. N+1 redundancy exists throughout all phases. There are two 20,000-gallon underground diesel fuel storage tanks at the site. Uninterrupted Power Supply: Grounding Architecture: Commercial Power Contingency Arrangements: Environmental Controls HVAC Distribution: HVAC System: HVAC Redundancy Architecture: HVAC Contingency Arrangements: Fire Suppression: Four (4) - UPS systems, each with two (2) - 675kW/750kVA modules. Three systems act as primary source of power and the fourth system works as standby system. Each UPS system can support its designed full load of 1350kW 1500kVA (each) for 15 minutes via its internal battery plant. And Two (2) 3,000 kva/2,400 kw UPS in 2N configuration, with 15 minute battery life. Perimeter ground ring is tied into driven ground rods. The UPS systems, equipment cabinets, racks and associated metal parts are tied into the ground ring. In case of a commercial power failure, the standby generators provide power to the Internet Data Center within one minute of a power outage. The one-minute gap is covered by the UPS system. During an extended commercial power outage, the diesel generators can provide power for 96 hours using the fuel stored at the site. There are processes and procedures to connect a portable generator to ensure N+1 redundancy. The building has five (5) ton chillers, (with provisions for the addition of another ton chiller to accommodate future growth). Air Handling Units are redundant. They provide humidity control and air filtration for the computer room area. The raised floor, which is used as an air plenum, delivers conditioned air to the equipment cabinets/racks via the CRAC units. There are ninety eight (98) 20 ton CRAC units are strategically located on the raised floor area. Designed to AT&T Internet Data Center Standards and Industry Tier 4 Standards. Currently there are three (3) ton chillers to carry the site load with two (2) 750 tons chillers in standby. This represents an N+2 configuration. If a chiller fails, a standby chiller can carry the load continuously. Operations can choose to operate all (or some of the) CRAC units that share the cooling needs evenly operating at less than full capacity. If a CRAC unit fails, heat load gets distributed automatically. The Internet Data Center has pre-action dry pipe fire suppression system supported by a state-ofthe-art VESDA smoke detection and alarm system. The VESDA system is considered 100 times more sensitive than conventional, passive fire detection systems. Conventional smoke detectors are also utilized and are grouped into zones. When one or more detectors in different zones detect smoke, the fire alarm panel opens the deluge valve to fill the sprinkler piping with water. In case of an actual fire, the seal on the sprinkler heads will melt and discharge water on the affected area. Water will not be discharged in unaffected areas. For more information on the VESDA system, please visit Mesa 2 of 6
3 Architectural Section - continued Security Building Access: Security staffing 24x7, closed-circuit monitors (CCTV), secure-card key access, biometrics scanners, mantraps, and alarmed doors. Guards maintain access to the loading dock and access requires a card key. Security personnel also monitor the building. AT&T maintains a current list of authorized personnel. AT&T also maintains all keys for cabinets and cages in a lock box on-site. Secure-card keys are also left on-site. Customers must open a ticket before appearing at the Internet Data Center and then pass biometrics scan. Site Monitoring: 24x7 monitoring is performed on site and remotely. Shipping & Receiving: No unidentified packages will be accepted. Onsite security personnel monitor access to the loading dock. Customer shipments to the IDC require customer site ID # on all shipping labels. No unidentified packages will be accepted. Operations Staffing: Internet Data Center technicians and building engineers are available 24x7. Remote Hands: Available 24x7. See AT&T Enterprise Hosting Service Guide for details Mesa 3 of 6
4 Risk Assessment General Information Site Description: The site is located in a region of Low Seismic Activity. The building meets current seismic code. There are no major faults in the area. Building Description: The Web Hosting Facility is located in a three story building which originally functioned as a corporate data center, which has been totally re-purposed for hosting use, (no corporate data functions remain). The building was constructed in The building has structural steel moment resisting space frame construction with cast-in-place concrete floor slabs. The building has pre-cast concrete exterior wall panels Floors designed for the following live loads: Elect. (Battery grade) = 300 psf, Web Hosting floors = 150 psf General Condition: Building appears to be in good condition. No significant signs of distress have been observed. Earthquakes Hazard Assessment Seismic Load Site Class D Ground Shaking Hazard: Low Soil Liquefaction Hazard: Very Low Soil Compaction Hazard: Very Low Fault Rupture Hazard: none Tsunami Hazard: none Landslide Hazard: none Mesa 4 of 6
5 Risk Assessment - continued Building Risk Assessment: Web Hosting Building There is a very low potential steel frame connection damage, due to the very low seismic zone. No life safety hazards identified Equipment Risk Assessment: Equipment Anchorage Description Risk Assessment Data Center Racks Anchored to raised floor tile and tiles locked to raised floor framing w/ unistrut. Low Overhead Auxiliary Framing Suspended racking braced per AT&T Standards Low Raised Access Flooring Web Host Area Only Low CRAC Units Anchored to the concrete floor slab via steel stands through the raised floor. Low PDUs Anchored to the concrete floor slab via steel stands through the raised floor. Low UPS Anchored to concrete floor slab on concrete housekeeping pads. Low Switchgear Anchored to concrete floor slab on concrete housekeeping pads. Low Electrical conduits Supported per AT&T Standards Partially run underground Low Chillers Sit on spring isolators which are anchored to floor slabs in Mech. room Low Chilled Water Piping Supported per ANSI B31.9 Low Generators Anchored to concrete foundation on concrete housekeeping pads. Low Cooling Towers Supported by elevated steel structure and anchored to concrete foundation Low Regional Disaster Effects on Site Loss of Power: Power supplied by 1 utility feed. Standby generators can maintain power supply 48 hour diesel fuel storage on site Loss of Water: multiple utility feeds and multiple independent tanker supply providers. Network Connectivity: Two diversely routed telecom duct banks provided. Summary: Site is in general well prepared to resist the effects of an unlikely earthquake. Windstorms Hazard Assessment: Factory Mutual Design Wind Speed: 90 mph (3 second gust) Factory Mutual Ground Roughness Exposure Category: B Overall, lateral wind loads during a windstorm are more severe than earthquake loads at this site. Historic windstorm risk is very low for this location. Mesa 5 of 6
6 Regional Disaster Effects on Site - continued Building Risk Assessment: The building is assessed to have a low risk for wind damage. Equipment Risk Assessment: Interior equipment is adequately protected against the effects of a windstorm. Exterior equipment is adequately anchored to resist the effects of a windstorm. Regional Disaster Effects on Site Loss of Power: See Earthquake Risk Above Loss of Water: See Earthquake Risk Above Network Connectivity: See Earthquake Risk Summary: Site is in general well prepared to resist the effects of a windstorm. Flooding Hazard Assessment: Site is located above the 100-year flood plain level. Flooding is not considered to be a significant hazard for this site. Man-Made Hazards Crime Critical site equipment is fenced to protect outdoor equipment. At present, site has security guard coverage 24 hours a day, 7 days a week, year-round. Security system monitors property, gates, and all doors (interior and exterior). Controlled entry into data centers via biometric controls Considered to be a low risk Sabotage: Exposed exterior walls are concrete. Mesa 6 of 6
AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)
AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:
More informationHow To Visit An Internet Data Center
AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina
More informationAT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)
AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA
More informationAT&T Internet Data Center Site Specification New York III (Secaucus, NJ)
AT&T Internet Data Center Site Specification New York III (Secaucus, NJ) Site Biography Market Area: New York City, New Jersey, Upstate NY and Lower Connecticut Location: Secaucus, NJ 07094 Address: 15
More informationAT&T Internet Data Center Site Specification Dallas Area (Allen, Tx)
AT&T Internet Data Center Site Specification Dallas Area (Allen, Tx) Site Biography Market Area: Dallas and Fort Worth Areas of Texas Location: Allen, Tx 75013 Address: 900 Ventura Drive CLLI, POP, NPA/NXX
More informationAT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA)
AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA) Site Biography Market Area: Washington, DC Area Location: Ashburn, VA 20147-6011 Address: All deliveries should be sent to
More information100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G
100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the
More informationLEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT.
LEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT. THE SCALE TO SUPPORT GLOBAL ENTERPRISE IT Designed and equipped to meet
More informationN O W A V A I L A B L E
N O W A V A I L A B L E 5 0, 0 0 0 S F P O W E R E D S H E L L D A T A C E N T E R I I Data Center Park Catawba County, North Carolina S P E C I F I C A T I O N S Contact Doug Hollidge for more information
More informationOPERATOR - FACILITY ADDRESS - DATE
. Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.
More informationvcloud SERVICE Virtual Tech in partnership with Equinix - vcloud Service
vcloud SERVICES vcloud SERVICE Virtual Tech offers competitive pricing on vcloud hosted services at our world class Tier 4 data centre facility fully equipped with redundant power, cooling, internet connectivity
More information19 Site Location, Design and Attributes. Site Location, Design and Attributes
1 Site Location, Design and Attributes The Primary Data Center shall be physically located on Oahu, Hawaii. 2 Site Location, Design and Attributes The Primary Data Center shall be located at least 1 mile
More informationNORTHERN VIRGINIA ONE (NoVa) DATA CENTER OVERVIEW
VAZATA 9651 Hornbaker Road Manassas, VA 20109 VAZATA.COM VAZATA's NoVa One data center located at 9651 Hornbaker Road in Manassas, Virginia is engineered from the ground up to deliver highly reliable and
More informationNeuStar Ultra Services Physical Security Overview
NeuStar Ultra Services Physical Security Overview Mission-critical network operations must have the highest standards of quality, security and reliability. NeuStar Ultra Services currently locates its
More informationData Centre Barrie, Ontario
COGECO DATA SERVICES DATA CENTRE Data Centre Barrie, Ontario Cogeco Data Services offers flexible, secure, connected and fully managed ICT solutions at its Flagship Data Centre in Barrie, Ontario Data
More informationLocation. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport
Welcome Zenium Istanbul One provides 12,000 square metres of high specification technical space across three purpose-built data centers. It is Turkey s first wholesale data center offering; the data halls
More informationStrategic Data Centre Site Profiles. Data Centre Co-Location London East
Strategic Data Centre Site Profiles Data Centre Co-Location London East Document details Version: 1 Last Updated: 12/07/2013 Version 1.0 Page 1 of 5 Contents 1. LONDON EAST...3 1.1 LOCATION...3 1.2 TECHNICAL
More informationData Center CH1. Elk Grove Village, IL
Data Center CH1 Elk Grove Village, IL powerful/ efficient /reliable solutions > Data Center CH1 ABOUT DUPONT FABROS TECHOLOGY (DFT) DFT is a leading owner, developer, operator and manager of wholesale
More informationsan francisco//usa data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in San Francisco, USA. We can colocate standard rack-mountable servers
More informationX-tier Data Facility. Prepared by X-tier SAE Corporation
X-tier Data Facility Company Profile X-tier Corporation X-tier is based in Leawood, Kansas. X-tier provides business agnostic, security hardened, custom and turnkey Cloudbased software systems, services,
More informationChicago 1 (CHI-1) Data Center
215 W. Ohio St. 5th Floor Chicago, IL 60564 Call Us Toll-Free 1 (866) 817-2811 Follow Us @SingleHop Like Us facebook.com/singlehop Chicago 1 (CHI-1) Data Center Enterprise-Class, Downtown Chicago Facility
More informationContents Error! Bookmark not defined. Error! Bookmark not defined. Error! Bookmark not defined.
We Do It Better. Contents Introduction...3 Service and Support...3 Data Center Details...4 Security...4 Location...4 Power...4 Humidification...5 AC...5 Cooling...6 Datacenter Features...6 SAS 70...6 PCI
More informationIBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com. 2011 IBM Corporation
IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com Overview Profile IBM owned facility 6447 m² IT-Space Infrastructure concurrent maintainable (Tier Level 3) Feed-ins of Power
More informationExperience Matters...
Experience Matters... Travelport Data Center offers confidence and space to meet your demanding IT needs Transwestern presents the Travelport Data Center in Denver, Colorado totaling 267,000 SF with 121,600
More informationCOMMODITIZING THE DATA CENTER MARKET
COMMODITIZING THE DATA CENTER MARKET Site Summary The building at 1360 Kifer Road has approximately 94,500 SF of server and support space and is currently divided into two independent data center areas.
More informationAbout Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services
About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier
More informationSouth Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime
South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in
More informationStrategic Data Centre Site Profiles Data Centre Co-Location London North
Strategic Data Centre Site Profiles Data Centre Co-Location London North Document details Version: 1 Last Updated: 12/07/2013 Version 1.0 Page 1 of 6 Contents 1. LONDON NORTH...3 1.1 LOCATION...3 1.2 TECHNICAL
More informationDATA CENTERS. VAZATA Headquarters: 6900 Dallas Parkway, Suite 800 Plano, TX 75024 VAZATA.COM
DATA CENTERS VAZATA Headquarters: 6900 Dallas Parkway, Suite 800 Plano, TX 75024 VAZATA.COM OVERVIEW VAZATA's NoVa One data center located at 9651 Hornbaker Road in Manassas, Virginia is engineered from
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationOur Hosting Infrastructure. An introduction to our Platform, Data Centres and Data Security. www.in-tuition.net
Our Hosting Infrastructure An introduction to our Platform, Data Centres and Data Security www.in-tuition.net UK Infrastructure Infrastructure Overview Intuition Networks has provided managed Internet
More informationCyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.
Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M
More informationSafeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive
Co-Location Services Safeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive optimum performance 24x7. SERVICE
More informationSLA. Co-Managed. Do-It-Yourself
SLA Do-It-Yourself Co-Managed Co-Managed Fully Managed Operational Application Support DB Support Storage Planning Capacity planning Change Management Release Management Pro Services Systems Monitoring
More informationCurrent as of 11/10/08 1 of 1
BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that
More informationVOLICO. Colocation Hosting. Enterprise Hosting Solutions. 888 865 4261 sales@volico.com www.volico.com
888 865 4261 sales@volico.com www.volico.com Performance, reliability, and the peace of mind your business deserves Colocation Overview A Reliable and Secure Home Your Data Can Trust! Discover how Volico
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationDedicated Hosting Services
Dedicated Hosting Services Protect and manage your Servers/ Routers/ Switches/ storage devices/ security devices under a highly secure hosting space and get the finest performances out of them. SERVICE
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationLEVEL 3 DATA CENTER ASSESSMENT
Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments
More informationNetwork Router Monitoring & Management Services
Network Router Monitoring & Management Services Get different parameters of routers monitored and managed, and protect your business from planned and unplanned downtime. SERVICE DEFINITION: NETWORK ROUTER
More informationEstablishment of State s Second Data Center. Business Continuity and Disaster Recovery. North Carolina. Office of Information Technology Services
Establishment of State s Second Data Center North Carolina Office of Information Technology Services National Association of State Chief Information Officers 2008 Recognition Awards Nomination June 2,
More informationSouth Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime
South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in August 2002,
More informationAssessment of Existing Data Centers for Critical Facilities Round Table Group
Assessment of Existing Data Centers for Critical Facilities Round Table Group Chuck Shalley, P.E. Consulting Electrical Engineers BACKGROUND INFORMATION ASSIGNMENT Data Center Criteria Type Raised Floor
More informationWorld Class Data Center Features Our best practices for world class performance, reliability and service. echomountain - Rock Solid
echomountain - Rock Solid World Class Data Center Features Our best practices for world class performance, reliability and service 877.311.1980 sales@echomountain.com www.echomountain.com Best-Practices
More informationSanta Clara, CA 95054
Leading-Edge Datacenter Facility Silicon Valley GENERAL In excess of 41,000 sq. ft. of raised floor 9 MVA of utility power into facility Purpose built Green Datacenter Sutton Roley Lic. 00793235 (408)
More informationReduce the cost and delays associated with troubleshooting with the help of round-the-clock Service Desk Support.
Remote Support Reduce the cost and delays associated with troubleshooting with the help of round-the-clock Service Desk Support. SERVICE DEFINITION: REMOTE SUPPORT SERVICES ITI s Remote Support Service
More informationAppendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria
Appendix B 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria 423.25 Public shelter design criteria. 423.25.1 New facilities. New educational facilities for school boards
More informationData Centre Infrastructure
Data Centre Infrastructure LONDON DATA CENTRE Our data centre is located within the heart of Europe s centre of global finance London s Square Mile. The centre offers a combined net capacity of 1,520 m²
More informationSYSTRUST CERTIFICATION REPORT FOR COLLOCATION AND DATA CENTER HOSTING SERVICES FOR THE PERIOD FROM JANUARY 1, 2013 TO DECEMBER 31, 2013
SYSTRUST CERTIFICATION REPORT FOR COLLOCATION AND DATA CENTER HOSTING SERVICES FOR THE PERIOD FROM JANUARY 1, 2013 TO DECEMBER 31, 2013 TABLE OF CONTENTS SECTION I: INDEPENDENT PRACTITIONERS TRUST SERVICES
More informationSite Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center
More informationDepartment of Administration DATA CENTER Two Phase Approach Located at the State Defense Building
DATA CENTER Two Phase Approach Located at the State Defense Building July 17, 2015 Compiled by: Office of Facilities and Property Management 800 SW Jackson, Suite 600 Topeka, Kansas 66612-1216 i I. Programming
More informationPOWERING A CONNECTED ASIA. Pacnet Hong Kong CloudSpace1 Technical Specifications. Asia s Pioneering Facility with Direct Subsea Cable Access
POWERING A CONNECTED ASIA Pacnet Hong Kong CloudSpace1 Technical Specifications Asia s Pioneering Facility with Direct Subsea Cable Access Our purpose-built, 300 m 2 Pacnet Hong Kong CloudSpace1 (HKCS1)
More informationHow To Write An Infrastructural Standard For Data Center Infrastructure
Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers
More informationData Center Infrastructure & Managed Services Outline
Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists
More informationData Center Presentation
Data Center Presentation The NetSource Datacenter. Agenda General Layout of Data Center Policies and Procedures Designed to Latest Standards High Performance High Reliability High Security Design Details
More informationNY-1 DATACENTER AT A GLANCE. NY-1 is a Tier III-rated, SAS SSAE16 and HIPAA-certified data center
NY-1 1.866.WEBAIR.1 WWW.NY1.WEBAIR.COM NY-1 LONG ISLAND S MOST SECURE, FULLY-REDUNDANT DATA CENTER ENTERPRISE COLOCATION, PRIVATE AND HYBRID CLOUD SOLUTIONS, AND MANAGED SERVICES. DATACENTER Enjoy the
More informationTier IV Enterprise - Class Data Center
Tier IV Enterprise - Class Data Center Colocation Cloud Hosting Broward Data Center Datasheet Managed Hosting Dedicated Servers www.volico.com Site Specification Security Site Specification Floor Space
More informationISOMEDIA COLOCATION WWW.ISOMEDIA.COM/COLOCATION
ISOMEDIA COLOCATION WWW.ISOMEDIA.COM/COLOCATION Your business needs a robust infrastructure that is secure, cost effective and reliable in order to remain competitive in today s market. ISOMEDIA s colocation
More informationcolocation. perfected. Overview
colocation. perfected. Overview Welcome to COLO@ colocation perfected our network The expert team of COLO@ have the talent, tools, and facilities to power your operation all day, every day. Since 2008,
More information215 W. Ohio St. 5th Floor Chicago, IL 60564. Enterprise-Class Security, Performance and Redundancy
215 W. Ohio St. 5th Floor Chicago, IL 60564 Call Us Toll-Free 1 (866) 817-2811 Follow Us @SingleHop Like Us facebook.com/singlehop Phoenix #1 (PHX-1) Enterprise-Class Security, Performance and Redundancy
More informationcolocation. perfected.
colocation. perfected. colocation perfected The expert team of COLO@ have the talent, tools, and facilities to power your operation all day, every day. Since 2008, COLO@ has been providing the critical
More informationsingapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Singapore. We can colocate standard rack-mountable servers or other
More informationReport on FTHC, LLC d/b/a Miami Data Vault s Description of its Data Center System and on the Suitability of the Design and Operating Effectiveness
Report on FTHC, LLC d/b/a Miami Data Vault s Description of its Data Center System and on the Suitability of the Design and Operating (SOC 1) For the period August 1, 2014 through July 31, 2015 In Accordance
More informationDATACENTER COLOCATION. Flexible, Secure and Connected
DATACENTER COLOCATION Flexible, Secure and Connected Flexible Solutions for Your Requirements Contents Your Goals 2 Compound and Buildings 4 Security 6 Infrastructure 8 Free Choice 10 Good Reasons 12 Our
More informationCHICAGO S PREMIERE DATA CENTER
CHICAGO S PREMIERE DATA CENTER White City collocation was founded in June, 2010 by a highly experienced industry executive in conjunction with several investment companies. The strategy of White City is
More informationDatacenter Assessment
The Netmagic team has compiled this Checklist to help you evaluate, compare and select datacenter facilities to meet your hosting, business continuity and disaster recovery needs. Based on industry best
More informationPowering the Cloud Desktop: OS33 Data Centers
OS33 Data Centers info@os33.com (866) 796-0310 www.os33.com It is hard to overstate the importance of security and uptime, which is why we obsess over making sure that your corporate information assets
More informationAvailable Princeton Area Data Center / Disaster Recovery Lab / R&D
Available Princeton Area Data Center / Disaster Recovery Lab / R&D As exclusive listing agent, The Schultz Organization is pleased to offer space available at 109 Morgan Lane. is part of the Enterprise
More informationAFS Center. Data Center Info. Arizona Facility Services 2331 West Alameda Dr Tempe, AZ 85282 (602) 385-8100 Main (602) 385-8101 Fax
AFS Center Data Center Info 2331 West Alameda Dr Tempe, AZ 85282 (602) 385-8100 Main (602) 385-8101 Fax A. General Facility Information The AFS Center is located on the south side of Alameda Drive, just
More informationHealthcareBookings.com Security Set Up
HealthcareBookings.com Security Set Up Introduction... 2 Overview of the process for using HealthcareBookings.com... 2 Professionals... 2 Patients... 3 Passwords... 4 Hosting Security... 4 Overview of
More informationSCHEDULE 4. Data Center Facilities Requirements
SCHEDULE 4 TO THE COMPREHENSIVE INFRASTRUCTURE AGREEMENT Data Center Facilities Requirements Table of Contents TU1.0UT TUData Center Facilities ServicesUT...1 TU1.1UT TURPB Data Center Relocation RequirementsUT...1
More informationData Center Due Diligence List
Data Center Due Diligence List Name and address of site facility Date constructed Building owner/date purchased by current owner Name of previous owner Adjacent Property Descriptions North South East West
More informationPacnet Hong Kong CloudSpace2 Technical Specifications. Upholding the Principles of Efficiency and Sustainability in Data Center Design
POWERING A CONNECTED ASIA Pacnet Hong Kong CloudSpace2 Technical Specifications Upholding the Principles of Efficiency and Sustainability in Data Center Design Our purpose-built, 5,000 m 2 Pacnet Hong
More informationElectrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
More informationSubject: County of Los Angeles Data Center Space Requirement
Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,
More informationSolveXia Business Continuity Planning
Business continuity planning is the term we use to describe all the steps we take at SolveXia to ensure that our service is up and running when you need it. As a 'Software as a Service' provider, our aim
More informationDATA CENTERS. VAZATA Headquarters: 6900 Dallas Parkway, Suite 800 Plano, TX 75024 VAZATA.COM
DATA CENTERS VAZATA Headquarters: 6900 Dallas Parkway, Suite 800 Plano, TX 75024 VAZATA.COM DAL II MARSH LANE CARROLLTON TX OVERVIEW VAZATA s Dallas Data Center II (Dal II) is located at 2440 Marsh Lane
More informationWhite paper. SAS Solutions OnDemand Hosting Overview
White paper SAS Solutions OnDemand Hosting Overview Contents Overview...1 Cary 1 Facility Specifications...2 Cary 2 Facility Specifications (SAS New Cloud Computing Center)...3 Charlotte 1 Facility Specifications...4
More informationDATA CENTRE DATA CENTRE MAY 2015
DATA CENTRE DATA CENTRE MAY 2015 CONCERTHOUSE MUSIC Concerthouse Music Data Centre services are located in the Equinix Internet Business Exchange (IBX ) Centre at Mascot. This IBX offers the highest level
More informationData Centre Basiglio, Milan Flexible, advanced and efficient by design.
Data Centre Basiglio, Milan Flexible, advanced and efficient by design. TelecityGroup Via Francesco Sforza 13 Milano 3 City 20080 Basiglio MI Italy Tel: +39 02 36679500 it.info@telecity.com www.telecitygroup.it
More informationELECTRICAL EMERGENCY SYSTEM PLAN REVIEW OVERVIEW OF CODE REQUIREMENTS
ELECTRICAL EMERGENCY SYSTEM PLAN REVIEW What to Look for during Plan Review OVERVIEW OF CODE REQUIREMENTS First determine the type of emergency power system; is the system designed for Emergency or Legally
More informationOnsite Support: 24/7/365 onsite team. Security: 24/7/365 onsite manned security and CCTV. Monitoring: 24/7/365 Environmental monitoring and management
Zen DC1 Our Services: Colocation Cloud Solutions Managed Hosting Dedicated Servers Zen DC1 - Key Facts Size: 10,000 sq ft Capacity: 150 rack capacity Ownership: 100% independently owned, operated and managed
More informationServer Monitoring & Management Services
Server Monitoring & Management Services Monitor and manage your applications and servers under enterprise-class monitoring solutions, and protect your business from planned and unplanned downtime. ITI
More informationWhy Choose Go4Hosting Data Center?
Why Choose Go4Hosting Data Center? Security When it comes to web hosting we understand the level of technical sophistication and server security involved. At Go4Hosting Data Center we focus on Security,
More informationOccupancy: Assembly (A-3) and Business -Includes offices, seminar rooms, classrooms, and café facility. Duke University Medical School
Introduction Background The Duke School of Nursing building offers a new three-story state of the art facility that has helped strengthen the quality and integrity of the School of Nursing at Duke. The
More informationData Centre Stockholm II, Sweden Flexible, advanced and efficient by design.
Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Equinix Telecity Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 se.info@telecity.com www.telecitygroup.se
More informationGREENSBORO DRIVE @ TYSONS CORNER, VA
FEATURES :: RIGHT IN THE HEART OF CORNER: EASY ACCESS FROM I-495 & 267 :: DUAL AUTHENTICATION SECURED ACCESS, 24x7x365 MANNED FACILITY :: FULLY AUTONOMOUS; RIGHT BY THE LOADING DOCK :: MULTIPLE REDUNDANT
More informationAttracting Data Centers to Your Market
Attracting Data Centers to Your Market A Presentation for: Presented by: Wendy McArthur, CB Richard Ellis OVERVIEW Introduction Qualify Requirement Site Selection Cost Marketing CB Richard Ellis Page 2
More informationUC Berkeley Data Center Overview
UC Berkeley Data Center Overview Shelton Waggener Associate Vice Chancellor & Chief Information Office shelw@berkeley.edu August 2006 Berkeley s Data Center Opened July 2004 Our Previous Facility (don
More informationColocation Services. We offer a highly secure environment to deploy your computing, network, storage and IT infrastructure.
Colocation Services We offer a highly secure environment to deploy your computing, network, storage and IT infrastructure. v. 2015 About us Our Values McAllen Data Center s purpose is to help carriers
More informationScalable. Affordable. Flexible. Fast.
Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations
More informationCyrusOne Global Data Center Solutions
CyrusOne Global Data Center Solutions 1649 W Frankford Road, Carrollton, TX 75007 + Leader in Global Data Center Colocation Built for tomorrow. Ready today. CyrusOne has quickly emerged as a global leader
More informationData Center Overview Document
Overview NetSource is a Chicago area (Naperville) hosting company that owns and operates its own world class datacenter. The initial datacenter buildout was put into operation in 2007 and expanded in 2013.
More informationin other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.
DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationUnderstanding Sage CRM Cloud
Understanding Sage CRM Cloud Data centre and platform security whitepaper Document version 2016 Table of Contents 1.0 Introduction 3 2.0 Sage CRM Cloud Data centre Infrastructure 4 2.1 Site location 4
More informationVOLICO. Colocation Checklist. Key Data Center Evaluation Criteria
VOLICO Enterprise Hosting Solutions Colocation Checklist Key Data Center Evaluation Criteria Not all data centers are created equal. You need to know what to look for. Are they equipped with up-to-date
More informationFrankfurt Data Centre Overview
Technical Services Briefing Document Frankfurt Data Centre Overview Version 2.1 Contents Introduction... 3 TelecityGroup Data Centre in Frankfurt... 4 Data Centre Characteristics... 4 Technologies in Use
More informationBELLE VUE MANCHESTER DATA CENTRE
www.iracknet.com 0843 557 5712 bellevue@iracknet.com www.iracknet.com BELLE VUE MANCHESTER DATA CENTRE 02 BELLE VUE MANCHESTER HIGHLY ADVANCED DATA CENTRE PURPOSE BUILT TO DELIVER UNRIVALLED FLEXIBILITY
More information