OPTIMIZING YOUR COOLING ENERGY CONSUMPTION IN NEW AND EXISTING DATA CENTERS

Similar documents
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

STULZ Water-Side Economizer Solutions

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

Analysis of data centre cooling energy efficiency

How To Improve Energy Efficiency Through Raising Inlet Temperatures

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

How to Build a Data Centre Cooling Budget. Ian Cathcart

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

The Different Types of Air Conditioning Equipment for IT Environments

State of the Art Energy Efficient Data Centre Air Conditioning

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Elements of Energy Efficiency in Data Centre Cooling Architecture

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

News in Data Center Cooling

- White Paper - Data Centre Cooling. Best Practice

Direct Fresh Air Free Cooling of Data Centres

NetApp Data Center Design

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers

White Paper #10. Energy Efficiency in Computer Data Centers

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Improving Data Center Energy Efficiency Through Environmental Optimization

National Grid Your Partner in Energy Solutions

AIRAH Presentation April 30 th 2014

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE ? SLIDE 1

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

In Row Cooling Options for High Density IT Applications

How To Save Energy On A Power Supply

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

Economizer Modes of Data Center Cooling Systems

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit

Free Cooling for Data Centers

Defining Quality. Building Comfort. Precision. Air Conditioning

Excool Data Centre Cooling Product Comparison Report

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

Energy Efficient Cooling Solutions for Data Centers

Wet Bulb Temperature and Its Impact on Building Performance

Benefits of. Air Flow Management. Data Center

Data Center Energy Profiler Questions Checklist

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

European Code of Conduct for Data Centre. Presentation of the Awards 2014

BICSInews. plus. july/august Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment.

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

HVAC Systems: Overview

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

Technical Systems. Helen Bedford

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

STULZ Solutions and Services

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010

Top 5 Trends in Data Center Energy Efficiency

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

How To Design A Building In New Delhi

APC APPLICATION NOTE #112

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

Center. September 2013

Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling

Data Centre Cooling Air Performance Metrics

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 4, Lancaster University, 2 nd July 2014

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Hot-Aisle vs. Cold-Aisle Containment for Data Centers

EHDC. Cooling system for Data Center and server cabinets.

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

CRAC Precision climate control units for data centres

Element D Services Heating, Ventilating, and Air Conditioning

Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie

Datacenter Efficiency Program

Impact of Hot and Cold Aisle Containment on Data Center Temperature and Efficiency

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

Environmental Data Center Management and Monitoring

Thermal Storage System Provides Emergency Data Center Cooling

Learner s Guide. Labs, Data Centers, and High Tech Facilities. Instructors:

Best Practices in HVAC Design/Retrofit

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: Date: december 03, 2015 Supersedes: new Date: new

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

> Executive summary. Explanation of Cooling and Air Conditioning Terminology for IT Professionals. White Paper 11 Revision 2. Contents.

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Using Outside Air and Evaporative Cooling to Increase Data Center Efficiency

The New Data Center Cooling Paradigm The Tiered Approach

European Code of Conduct for Data Centre. Presentation of the Awards 2013

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

Data Center Heat Rejection

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

USE OF AIR SIDE ECONOMIZER FOR DATA CENTER THERMAL MANAGEMENT. A Thesis Presented to The Academic Faculty. Anubhav Kumar

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Transcription:

STULZ Optimizing your Cooling Energy Consumption in New and Existing Data Centers Practical Methods for Reducing the Overall Energy Consumption of Cooling Systems Within a Data Center David Joy 9/7/2012

OPTIMIZING YOUR COOLING ENERGY CONSUMPTION IN NEW AND EXISTING DATA CENTERS Practical Methods for Reducing the Overall Energy Consumption of Cooling Systems Within a Data Center David Joy, VP Sales and Marketing STULZ Data center IT equipment produces heat and requires precision cooling to protect it from operating at temperatures or humidity ranges that reduce life or lead to failure. and broader respectively than what was the standard in the previous ASHRAE standard. As an example, raising IT entering air temperatures from 75 to 95 F dry bulb increases CRAH sensible capacity by 66%, or provides same or better sensible capacity with 33% less fan power, and/or allows higher chilled water temperature for more efficient chiller operation. ASHRAE also developed ASHRAE 90.1 that outlines the use of air or water side economizers to provide free cooling. Water economizers must meet 100% of the expected load at the following conditions: cooling towers temperatures of 40⁰F dry bulb / 35⁰F wet bulb and dry coolers at temperatures of 35⁰F dry bulb. The problem is that data centers consume a lot of energy, between 2 and 3% of all energy usage in the U.S., and the cooling equipment represents approximately 50% of the total energy consumed. In order to self-regulate energy consumption, ASHRAE has developed ASHRAE TC9.9 to define recommended and allowable temperature and humidity ranges, higher Changes in data center best practices for precision cooling equipment includes the use of backward curved plenum fans with electronically commutated (EC) motors (FIGURE 1), chilled water as a cooling medium for medium-large data centers, adiabatic humidification using ultrasonics, Air Handlers and perimeter cooling with DX or CW as part of an air or water side economizer solution providing free cooling. EC fans provide over 20% energy savings running at full load, and over 60% energy savings is possible when running at partial load with the added benefit of built-in redundancy. (See TABLE 1) FIGURE 1: EC Fan

TABLE 1: COMPARISON OF FAN TECHNOLOGY differences between cold aisle supply air and the return air plenum. As we ve seen, return air at higher temperature allows the perimeter cooling unit to operate more efficiently. Today, racks can be organized so that cooled air from raised floor is pressurized in a cold aisle contained area. IT equipment draws in the cold air and exhausts out heated air. (FIGURE 2) Another best practice is to operate multiple CRAHs at a lower fan speed providing better energy savings and redundancy. Operating 3 x CRAHs @ 75 F / 50% EAT with 45 F water operating with 1 unit on standby capacity at an airflow of 2 x 17,000 cfm = 34,000 CFM, for a fan energy consumption of 2 x 9.1 = 18.2 kw. Operating 3 x CRAHs @ 75 F / 50% EAT with 45 F water with all three units operating at the same time at an airflow of 3 x 11,333 cfm = 34,000 cfm, for a fan energy consumption of 3 x 2.69 = 8.07 kw. FIGURE 2: COLD AISLE CONTAINMENT ON A RAISE FLOOR We mentioned the ASHRAE 90.1 standard which requires the use of water and air side economizers to provide free cooling. Water side economizers can save up to 60% energy by automatically switching to the best operating mode based on heat load and outside air conditions. There are several ways to accomplish this: Traditional free cooling (FIGURE 3) is comprised of a constant fan speed dry cooler, constant speed pumps, and glycol cooled free cooling CRACs with both a DX and a glycol cooling coil. The delta of 10.13 kwh / year = $8,874 of energy savings / year (at a cost of $0.10 / kwh). Traditional control of a CW valve and a centrifugal fan has been in series. Today it is possible to have independent control of a CW valve and an EC fan maximizing energy savings and limiting latent cooling. Over the past several years, perimeter cooling has been used to cool IT equipment in racks oriented in a hot aisle / cold aisle configuration. The challenge has been to avoid wasting energy by mixing air from the hot aisle to the cold aisle. Return air plenums were added to direct hot air back to the perimeter cooling. The plenum draws the hot air and reduces the possibility of hot air mixing. Hot/cold aisles also help to maintain a small pressure FIGURE 3: GLYCOL COOLED DX - FIXED Dynamic free cooling (FIGURE 4) is comprised of a variable fan speed dry cooler, variable speed pumps, and glycol cooled free cooling CRACs consisting of both a DX and a glycol cooling coil.

pumps, water cooled chiller, chiller pumps, control valves, and chilled water cooled CRAHs. FIGURE 4: GLYCOL COOLED DX - VARIABLE During warm weather months, the unit acts as traditional DX with a dry cooler that supplies glycol to the unit condenser. During in-between months, a combination of a glycol free cooling coil and one DX compressor will operate. During cold weather months, cooled glycol is transferred to a free cooling coil and the compressor is turned off. Fans on the dry coolers and pumps operate at the lowest possible speeds to supply required cooling, using the least amount of energy. As the ambient temperature increases, fans on the dry coolers and pumps increase speed to extend available free cooling. An evaporative tower providing free cooling (FIGURE 5) is comprised of an evaporative cooling tower, constant speed pumps, and water cooled free cooling CRACs with both a DX and a water cooling coil. FIGURE 6: CHILLED WATER UNITS During warm weather months, cooling tower supplies a chiller and the chiller supplies the CRAH. During cold weather months, the cooling from the tower directly supplies the CRAH and the chiller compressor is turned off. When it comes to air side economizers, there are also several options. Air side economizers can save up to 80% energy by automatically switching to the best operating mode based on heat load and outside air conditions. CRACs or CRAHs can be supplied with an integrated mixing box and damper controls provide free cooling. Units can be attached to the top of a CRAC or CRAH in a vertical or horizontal position. (FIGURE 7) FIGURE 5: WATER COOLED DX Finally, Free Cooling with Chilled Water (FIGURE 6) is comprised of an evaporative cooling tower, cooling tower

FIGURE 7: AIR SIDE ECONOMIZER WITH A VERTICAL MIXING BOX During warmer temperatures or higher or lower humidity conditions, dampers close & the CRAC/CRAH reverts to traditional operation. When temperatures are within a proper range, outside air is directly introduced through the dampers in the mixing box. When temperatures are colder than desired, dampers mix outside air & return air to achieve the desired temperature. When temperatures are below freezing, warm return air mixes with outside air before the filter to prevent freezing. In conclusion, ASHRAE standards and best practices are driving improvements in data center energy efficiency. Improvements in data center cooling is available for precision cooling equipment and controls. Free cooling with water and air side economizers is available to provide maximum energy efficiency. Presenter bio David Joy has over 20 years experience in supporting data center infrastructure. David currently works as VP of Sales and Marketing for STULZ, a manufacturer of precision cooling solutions for data centers. David previously held sales and marketing positions at McQuay, Emerson Network Power, and Rittal. David currently resides in Frederick, Maryland. He can be reached by email at djoy@stulz-ats.com or by phone at 240-529- 1334.