NetApp Data Center Design
|
|
- Phillip Haynes
- 8 years ago
- Views:
Transcription
1 NetApp Data Center Design Presentation for SVLG Data Center Efficiency Summit November 5, 2014 Mark Skiff, PE, CEM, CFM Director, IT Data Center Solutions
2 Data Center Design Evolution Capacity Build Cost Configuration Density kw/rack mw $/kw year power & cooling >1 PUE Generation 1 Multiple Smaller 1-3 n/a Generation Generation / 8 Generation 4 25 (scalable) 2.6 Hot / Cold Aisle Prior to 2006 < Cold Aisle Containment 2006 Gen 2 w/ Economizer 2007 (Delivered 2009) Gen 3 Plus Refinement to * Estimated annual 2
3 Data Center Design Evolution Capacity Build Cost Configuration Density kw/rack mw $/kw year power & cooling >1 PUE Generation 1 Multiple Smaller 1-3 n/a Generation Generation / 8 Generation 4 25 (scalable) 2.6 Hot / Cold Aisle Prior to 2006 < Cold Aisle Containment 2006 Gen 2 w/ Economizer 2007 (Delivered 2009) Gen 3 Plus Refinement to * Estimated annual 3
4 Measuring Performance with PUE Chiller Plant AHU UPS Humidity Control Transformer Lights IT Power Usage Effectiveness (PUE) ratio cited as the data center infrastructure efficiency metric Total power / IT equipment power Infrastructure systems account for half of total energy in data centers Typical data center PUE = 2.0 Lower the number the more efficient 0.0 Typical 2.0 PUE 4
5 Opportunity + Innovation 5
6 Typical Hot Aisle / Cold Aisle Configuration Supply Air Supply Air 6
7 Hot/Cold Aisle w/ VAV at 4 kw/rack (150 watts/square Foot) Control Damper Temp. Sensor C R A H R A C K Return Air 7
8 Contained Cold Aisle w/ Pressure Controlled Cooling C R A H Control Damper R A C K Press. Sensor Operational January kW / Rack (high density; 770 watts/sf) CRAHs Supply Constant Temp Neutral Cold Room Pressure Modulating Dampers Eliminates Air Mixing Uniform temperatures Infrared shows warm areas blanking gaps Return Air 8
9 Cold Room Cold Room Cold Room Cold Room Cold Room Cold Room Cold Room Cold Room Cold Room Cold Room Cold Room Cold Room Plan View & Cross Section AHU AHU AHU AHU AHU AHU AHU AHU AHU AHU AHU AHU Cold Room Hot Aisle 9
10 End of Aisle Air Handling and Center Aisle Air Handlers Main Aisle 10
11 Contained Cold Aisle (Cold Room) and Hot Aisle Cold Room Hot Aisle 11
12 NetApp Global Dynamic Lab (GDL) & IT Site 2 Opened March, ,166 racks, 12 kw per rack average load Predicted PUE = 1.2 (annualized) FIRST EVER ENERGY STAR RATED 12
13 Plan View 36 Cold Rooms x 60 cabinets Corporate IT 25 mw = 770 watts/sf R&D 13
14 GDL1 Outside Relief Dampers Outside Air Hot Air Return Mixing Dampers Cooling Coil Speed Control CRAH Fan 360 IT racks 6kW/rack Dual path UPS & generators 1800 Engineering racks 12 kw/rack Utility power only 30 Engineering Network racks 3 kw/rack Single path UPS & generator R A C K Pressure Sensor Cold Room Cold Room with Pressure Controlled Cooling Airside economizer Elevated Air and CHW Temps 14
15 Main Hall; 1 st Floor 15
16 Cold Room; 1 st Floor 16
17 Measuring Efficiency with PUE Typical 2.0 PUE Chiller Plant AHU UPS Humidity Control Transformer Lights IT Power Usage Effectiveness (PUE) ratio cited as the data center infrastructure efficiency metric Total power / IT equipment power Infrastructure systems account for half of total energy in data centers Typical data center PUE = 2.0 Lower the number the more efficient NetApp RTP Building 4, predicted PUE = Chiller Plant AHU UPS Humidity Control Transformer Lights IT State-of-the-Art Data Center EPA assumed PUE ratio PUE (Annualized) 17
18 Full FREE Cooling PUE = 1.07 Outside Air Temp = 73 o F (23 o C) Mixing Dampers Cooling Coil Speed Control Outside Relief Dampers 90% 90% CRAH 90% 10% 10% Fan Hot Air Return R A C K Return Air 91 o F (33 o C) R A C K Pressure Sensor Cold Room Cold Room 75 o F (24 o C) 18
19 Full PAY Cooling PUE = 1.30 Outside Air Temp > 91 O F (33 o C) Outside Relief Dampers 90% 100% 10% 90% Mixing Dampers Cooling Coil Speed Control CRAH Fan Hot Air Return Return Air 91 o (33 O C) R A C K Pressure Sensor Cold Room Cold Room 75 o F (24 o C) 19
20 PARTIAL Free Cooling PUE = Outside Air Temp >75 o F (24 o C) to <91 o F (33 o C) Outside Relief Dampers 90% 100% 90% 100% 10% Mixing Dampers Cooling Coil Speed Control CRAH Fan Hot Air Return Return Air Pressure Sensor 91 o (33 O C) Cold Room 75 o F (24 o C) R A C K Cold Room NetApp, Inc. All rights reserved. NetApp Confidential Limited Use 20
21 Raleigh Weather Data TEMP (F) #HRS/YR % of YR <75 o (24 o C) % o % o 585 7% o 426 5% >90 o (32 o C) 225 3% FREE PAY 21
22 Actual Performance: 2013 Free Cooling NetApp, Inc. All rights reserved. NetApp Proprietary Limited Use Only
23 Actual Performance: 4Year Average Free Cooling NetApp, Inc. All rights reserved. NetApp Proprietary Limited Use Only
24 Actual Performance: 4Year Monthly Free Cooling NetApp, Inc. All rights reserved. NetApp Proprietary Limited Use Only
25 Actual Performance: PUE Current PUE = NetApp, Inc. All rights reserved. NetApp Proprietary Limited Use Only
26 Lessons Learned and a Few Ah-Ha s PUE Range = (average annual 1.16) 4 kw / rack average after 5 years Construction Costs 20-33% of Industry TCOE 1/3 Site 1, 1/5 HQ, 1/7 Colo 60 Degree Chilled Water Temp Rise 16 degrees NetApp, Inc. All rights reserved. NetApp Proprietary Limited Use Only
27 Global Dynamic Lab 2 Project Goals Bigger, Better, Cheaper Project Completion; May, 2014 Predicted PUE
28 Data Center Space 28
29 Center Aisle GDL2 29
30 Mechanical System Improvements Increased Air Handling Capacity Incorporated Washable Outside Air Pre-filters Improved Air Distribution Eliminated Cooling Systems for Electrical Distribution Rooms Eliminated Evaporative Humidification Systems Selected More Efficient Fan Wheel Changed to Operable Window System Vs. Louver/Damper System 30
31 Air Handling Capacity 31
32 Washable Pre-Filters 32
33 Actual Performance: 2013 Free Cooling NetApp, Inc. All rights reserved. NetApp Proprietary Limited Use Only
34 Improved Air Distribution 34
35 Air Flow Through End of Hot Aisles 35
36 Eliminated Electrical Room Air Conditioning 36
37 Operable Window System for Exhaust 37
38 Exterior View (open) 38
39 Interior View (closed) 39 3
40 Interior View (open) 40
41 Summary and Recommendations Containment w/ Pressure Control Allows for High Density (and low construction cost) Air Side Free Cooling Required for Low PUE Sustainable Data Centers Low Energy Use Recycled Materials Non Potable for Cooling Tower Make-up Low Construction Costs Supplier (A/E, GC) Selection is Critical Success Factor Phased Construction Provides Flexibilty (first cost and purchasing) 41
42 Thank you NetApp, Inc. All rights reserved. NetApp Confidential Limited Use
How To Test A Theory Of Power Supply
A CASE STUDY ON: THE EFFECTS OF HIGHER OPERATING TEMPERATURES ON DATA CENTER EFFICIENCY Victor Garcia Director of Facilities Brocade October 24, 2012 Jeff Stein, PE Principal Taylor Engineering 2010 Brocade
More informationData Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationDealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationFree Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
More informationEnergy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
More informationDATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
More informationCase Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
More informationGreening Data Centers
Greening Data Centers Dallas Thornton SDSC Division Director, Cyberinfrastructure Services March 2, 2011 Data Centers Are Enormous Users of Power US Data Centers (TeraWatt Hours per Year) 125 US Televisions
More informationData Center Planning. PUE Overview
Data Center Planning PUE Overview Steve Carter, Americas Managing Principal Charles Prawdzik Jr., Project Manager HP Critical Facility Services delivered by EYP Mission Critical Facilities, Inc. 2008 Hewlett-Packard
More informationGreen Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
More informationData Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1
WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however
More informationEducation Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
More informationData Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
More informationUniversity of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
More informationDefining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
More informationExample Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
More informationMaximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
More informationHow to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
More informationData Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationAnalysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
More informationPresentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
More informationImperial College 3 March 2009 Green Data Centers: An Overview
Imperial College 3 March 2009 Green Data Centers: An Overview Updated: 26 Feb 09 LBNL s Data Center findings Benchmarking Efforts Energy Reduction Approaches Green Data Centers: An Overview 2 Scenarios
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationData Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
More informationCenter Thermal Management Can Live Together
Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots
More informationData Center Design and Energy Management
Agenda EasyStreet Online Services, Inc. Data Center Design and Energy Management Introduction to EasyStreet Speaker Bio EasyStreet Sustainability Data Center 1 (Retrofit completed May 2010) Data Center
More informationInternational Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
More informationSTULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
More informationEnergy Efficiency and CHP Opportunities for Data Centers
Energy Efficiency and CHP Opportunities for Data Centers Webinar #4: Case Studies of Data Centers Implementing Energy Efficiency and Combined Heat & Power Systems The 4th in a 4-Part Series of Educational
More informationDirect Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
More informationHVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
More informationControl of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project
Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify
More informationNational Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
More informationEnergy Efficient Cooling Solutions for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Energy Efficient Cooling Solutions for Data Centers Introducing an Emerson Network Power tool for evaluating cooling system total cost
More informationDesigning the Data Center. Gail M. Roper CIO City of Raleigh, North Carolina
Designing the Data Center Gail M. Roper CIO City of Raleigh, North Carolina Why Build for Raleigh Extend the life of an existing data center infrastructure. Rationalize the data center infrastructure across
More informationAlan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers
Information Technology and Data Centers HVAC Showcase November 26, 2013 Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers Welcome. Today s webinar is being recorded and will be
More informationImproving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
More informationIntroduction to Datacenters & the Cloud
Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview
More informationDataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
More informationEuropean Code of Conduct for Data Centre. Presentation of the Awards 2013
European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started
More informationBest Practices in HVAC Design/Retrofit
Best Practices in HVAC Design/Retrofit Little Server Room BIG $AVINGS Justin Lewis, P.E., LEED AP, DCEP Sr Energy Project Manager C:530.400.6042 O:530.754.4870 jlewis@ucdavis.edu 1 What s the problem here?
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
More informationEMC DURHAM CLOUD DATA CENTER
EMC DURHAM CLOUD DATA CENTER Energy efficient design and construction EMC IT was hard at work reducing operational costs, increasing IT agility, and preparing for a dynamic future in the cloud when it
More informationStanford University Server/Telecom Rooms Design Guide
Stanford University Server/Telecom Rooms Design Guide CONTENTS 1.0 How to Use this Guide...3 1.1 Document Organization...3 2.0 Summary Form and Sample Options Matrix...3 3.0 Options Matrix...7 4.0 Recommended
More informationRe Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
More informationEuropean Code of Conduct for Data Centre. Presentation of the Awards 2016
European Code of Conduct for Data Centre Presentation of the Awards 2016 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
More informationLegacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
More informationWhite Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
More informationData Centers: How Does It Affect My Building s Energy Use and What Can I Do?
Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? 1 Thank you for attending today s session! Please let us know your name and/or location when you sign in We ask everyone to
More informationENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
More informationEnterprise Data Centres
Enterprise Data Centres 09/12/2014 MAR0064 Cannon Data Campus s Pre-Engineered, factory built modules and systems combine to produce a high performance, efficient, Data Centre Campus. s White Space, Mechanical
More informationREAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center hansenkl@unmc.edu 402-559- 5301 402-630-
More informationUnderstanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM)
Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Salim Janbeh Physical Infrastructure Consultant uae-sj@panduit.com PANDUIT You Can t Manage What You Don t Measure:
More informationVerizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
More informationPaul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA
Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale
More informationAdvanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
More informationFEAR Model - Review Cell Module Block
F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data
More informationRittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy
Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Executive Summary Data center energy usage has risen dramatically over the past decade and
More informationHow To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
More informationDigital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is
More informationEuropean Code of Conduct for Data Centre. Presentation of the Awards 2014
European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
More informationIn Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
More informationBICSInews. plus. july/august 2012. + Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment.
BICSInews m a g a z i n e july/august 2012 Volume 33, Number 4 plus + Industrial-grade Infrastructure and Equipment + I Say Bonding, You Say Grounding + Data Center Containment & design deployment The
More informationEXAMPLE OF A DATA CENTRE BUILD
EXAMPLE OF A DATA CENTRE BUILD BT Harmondsworth Data Centre Hall 2 Upgrade Temperature Control have been involved in providing specialist to data centres for over 20 years, starting from providing specialist
More informationReference Guide: SmartDesign Approach: Common Data Center Challenges:
Smart Solutions Reference Guide Solutions For Business-Critical Continuity 1100kW Tier 3 With High Density Design Intelligent, Integrated Infrastructure for the Data Center Reference Guide: 1100kW Tier
More informationHow Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationGREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
More informationGREEN DATA CENTER DESIGN
Jeffrey Menig Global Facilities Facility Engineering The application of multiple available technologies resulting in improved energy optimization without significantly increasing capital investment. A
More informationData Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics
On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations
More informationEconomizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
More informationHIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants
HIGH PERFORMANCE CHILLED WATER SYSTEMS EarthWise HVAC Simon Ho e: Simon.Ho@irco.com 2012 EarthWise HVAC High Performance CHW Plants Low Flow Low Temperature Systems Variable Flow Systems Variable CHW Variable
More informationRecommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
More informationThe Data Center Dilemma - A Case Study
Second Place: Industrial Facilities or Processes, Existing The TCS data center makes use of white cabinets and reflective surfaces as one method to reduce power for its lights and cooling. Data Center
More informationCANNON T4 MODULAR DATA CENTRE HALLS
CANNON T4 MODULAR DATA CENTRE HALLS Halve up-front investment, use a Modular fit out approach Highly efficient, Low PUE, Scalable system with reduced Capex and Opex Turnkey solutions available complete,
More informationEnergy Efficient High-tech Buildings
Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory Wftschudi@lbl.gov Acknowledgements California
More informationData Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
More informationAward-Winning Innovation in Data Center Cooling Design
Award-Winning Innovation in Data Center Cooling Design Oracle s Utah Compute Facility O R A C L E W H I T E P A P E R D E C E M B E R 2 0 1 4 Table of Contents Introduction 1 Overview 2 Innovation in Energy
More informationScalable. Affordable. Flexible. Fast.
Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
More informationDOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers
DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and
More informationEngineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
More informationHot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
More informationTop 5 Trends in Data Center Energy Efficiency
Top 5 Trends in Data Center Energy Efficiency By Todd Boucher, Principal Leading Edge Design Group 603.632.4507 @ledesigngroup Copyright 2012 Leading Edge Design Group www.ledesigngroup.com 1 In 2007,
More informationHow To Benchmark Power Production
Energy Benchmarking Service for Data Centre Industry in Hong Kong and Initial Findings Simon Lam Acting Deputy Director, Business Marketing & Development Department, CLP Power Agenda 1. Introduction: Why
More informationAIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
More informationEnergy and Cost Analysis of Rittal Corporation Liquid Cooled Package
Energy and Cost Analysis of Rittal Corporation Liquid Cooled Package Munther Salim, Ph.D. Yury Lui, PE, CEM, LEED AP eyp mission critical facilities, 200 west adams street, suite 2750, Chicago, il 60606
More informationCase Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
More informationSpecialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
More informationAutomated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview
Automated Commissioning for Energy (ACE) Platform for Large Retail Property $62,900 dollars of energy savings identified during the first 6 weeks Overview The ability to pull large amounts of complex data
More informationVISIT 2010 Fujitsu Forum Europe 0
VISIT 2010 Fujitsu Forum Europe 0 Virtualization & Automation Room 13a Shaping tomorrow with you. Green Data Center Services Martin Provoost Director, Data Centers and Networks, Fujitsu UK & Ireland 14:00
More informationDoc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
More informationData Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
More informationBRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
More informationEnclosed Football Stadium Design History and Lessons Learned
Enclosed Football Stadium Design History and Lessons Learned Robert L. Towell, P.E., LEED AP, QCxP btowell@cxegroup.com CxE Group LLC St. Louis, Missouri 314-436-6543 With thanks to the St. Louis Convention
More informationData Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013
Data Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013 Ted Brown Sr. Energy Management Analyst Data Center / IT Energy Efficiency ted.brown@seattle.gov
More informationThe Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
More information