1 Technical Note: Using EC Plug Fans to Improve Energy Efficiency of Chilled Water Cooling Systems in Large Data Centers A Technical Note from the Experts in Business-Critical Continuity
2 Introduction A U.S. Environmental Protection Agency survey released in 2007 concluded that IT data centers consumed 61 billion kw of electricity at a total cost of $4.5 billion in As energy costs continue to rise, energy conservation has become a top-of-mind issue for data center management. The data center cooling system is a primary target for energy efficiency improvements. An Emerson Network Power analysis of data center energy usage found that cooling systems comprised of cooling and air movement equipment can account for approximately 38 percent of energy consumption. Recently, Emerson Network Power has been studying the energy efficiency of different types of fan systems because the fans that pressurize the raised floor are a primary energy consumer. On chilled water cooling units, the fan comprises most of the energy usage. Using electrically commutated (EC) plug fans and variable frequency drive (VFD) are two effective methods for improving energy efficiency by controlling the fan speed. The energy efficiency gains come from decreasing the input power. If cooling units are oversized, the fan speed can be reduced. The motor power varies with the cube of the motor speed. Motor kw2 = Motor kw1 x (speed2/speed1) 3 For example, a 10 percent reduction in fan speed results in an energy savings of 27 percent. A 20 percent reduction in fan speed results in 49 percent energy savings. In order to prevent over-dehumidification, the water flow rate to the chilled water coil should also be reduced by the same percent as the fan speed. 1
3 Energy Efficiency of EC Plug Fans Electrically commutated (EC) plug fans use a brushless EC motor in a backward curved motorized impeller (plug fan). An EC motor is actually a DC motor that can be connected to an AC supply line, due to a rectifier internal to the motor drive. control is achieved by varying the control voltage from zero to 10 VDC. Emerson Network Power wanted to compare the energy efficiency of centrifugal blower systems to EC fan systems. Rather than make the comparison based on estimations created using blower curves and static pressure calculations, three units were sent to independent testing lab Intertek for a live test. The first step was to determine the appropriate performance testing method. Standards for Blower Performance Testing It is imperative to use the same test method to make a fair comparison of the cooling capacity and energy use of various cooling systems. Results can vary widely because of the type of blower system, application of the blower system and test method used. Motor kw can be measured in the lab, while the air volume is related to the total static pressure applied to the cooling system. Different test methods will result in different total static pressures and air volumes. The total static pressure is made up of several components, expressed as: Total Pressure = coil pressure drop + filter pressure drop + cabinet loss + system losses When designing systems, manufacturers commonly select fans based on pressure drop data derived from coil pressure curves and filter pressure drop curves, plotted on fan curves. However, internal system losses are difficult to calculate and may be underestimated. System losses are difficult to calculate and can vary widely depending on test method, fan location within the cabinet, proximity of the blowers to each other, and air outlet effects. For example, a unit tested based on ASHRAE standard (which uses ASHRAE 37 straight ducts on individual blowers) compared to the new ASHRAE (a duct around the perimeter of the entire unit with measurement in the horizontal duct) will yield different results. At the same CFM and the same external static pressure, the difference in total static pressure is 28 percent higher for the ASHRAE duct (see figure 1) compared to the ASHRAE (ASHRAE 37) duct. The result is a 20.6 percent increase (for the method) in motor kw, due only to difference in measurement method. Intertek used the ASHRAE method to compare the performance of the blower systems on the three units we submitted for testing because: 1. It is now the American standard for computer room air conditioning. 2. It allows centrifugal blowers to be compared to EC plug fans using the same test method. 76 in Unit ASHRAE 127 test set-up 24 in 105 in 12 in Static pressure 2 places as shown ASHRAE 127 duct Collection Plenum The width of the unit tested was 120 inches, so the duct was 120 inches wide. Figure 1. ASHRAE duct set-up for EC plug fan test. 2
4 The Initial Test Two units were submitted to Intertek: - Unit 1: Liebert Deluxe System/3 model FH600C equipped with a centrifugal blower and VFD - Unit 2: Liebert Deluxe System/3 model FH600C with three(3) EC plug fans mounted inside the cabinet The test point examined was 17,000 CFM at 0.3 inches external static pressure, at 100 percent speed. Figure 2 shows additional testing parameters and the results of the energy usage comparison. Pushing EC Plug Fan Limits Because of Emerson Network Power s commitment to engineering the most energy efficient products possible, the results of this test only made our product engineers more curious: How could EC plug fan technology be put to work to drive even greater energy efficiency in the Liebert Deluxe System/3? Unit 1 Centrifugal blowers with VFD in unit Unit 2 EC plug fan in unit After all, this system is designed for large data centers where addressing cooling system energy efficiency is particularly critical. The trend of consolidating multiple data centers into fewer, larger enterprises has definite economic advantages; however, concentrating a lot of heat-generating IT equipment into one room places extreme demands on the cooling system. Our engineers set out to develop a better way for the EC plug fan to operate by reducing system losses associated with how air is directed through the cabinet. With the plug fan mounted inside the unit, the air is thrown horizontally in the cabinet and must be directed vertically through the cabinet openings. Additionally, the discharge of the air is positive pressure. This positive pressure has to be isolated from the rest of the cabinet, which is at a negative (suction) pressure. Isolating the two pressures can waste energy due to additional air-blocking that must be installed within the cabinet. Locating the fans under the floor allows for a continuous negative pressure in the cabinet, creating a suction that draws the air through. In theory, locating the fans under the floor provides a more direct path for the air to travel through the cabinet, so the fans operate more efficiently. Energy Savings of Centrifugal Blowers vs. EC Plug Fan Mounted in the Unit 100% speed Model FH600C, 72F/50% RH, 45EWT, 10 deg water TD, 0.3 External static pressure Centrifugal blowers w/vfd EC motorized impellar in unit Net Sensible Cooling Capacity (kbtuh) Savings from Base EER Motor kw (kbtuh/kw) CFM , , % Figure 2. Using ASHRAE , the tested EC plug fans mounted inside the precision air conditioning units drew 18.2 percent less power than the tested centrifugal fan due to the lower motor kw of the EC fans. 3
5 To see how this new configuration of the EC plug fan performed, a third configuration was tested: - Unit 3: Liebert Deluxe System/3 model FH600C with an EC plug fan suspended from the bottom of the unit to simulate operating the fans within the raised floor. Intertek again used ASHRAE , which provides an equivalent method for comparing the performance of an EC plug fan in the unit to one mounted under the unit. The test point examined was 17,000 CFM at 0.3 inches external static pressure, at 100 percent speed. Most significantly, this new test documented that installing the EC plug fan in the raised floor under the unit reduces energy consumption another 12 percent on top of the 18 percent savings gained by installing the plug fan inside the unit. Complete specifications and results are shown in Figure 3. Comparing EC Plug Fans to Centrifugal Fans with Variable Frequency Drives EC plug fans are inherently more efficient than centrifugal fans with variable frequency drives (VFDs) due to the difference in wheel design, and because direct drive systems eliminate belt losses, which account for losses of approximately five percent. Nonetheless, VFDs are a good option for improving energy efficiency in data centers when the site specifications do not warrant using EC plug fans. The EC plug fan mounted on the bottom of the Liebert Deluxe System/3 requires a minimum 24-inch raised floor. Centrifugal fans generally have a wider range of air volume and can provide more static pressure. EC plug fans may not be suitable for ducted upflow cooling units, where higher static pressures may be required. For our final tests, the Liebert Deluxe System/3 model FH600C was again used Unit 1 Centrifugal blowers with VFD in unit Unit 2 EC plug fan in unit Unit 3 EC plug fan in floor Energy Savings of Centrifugal Blowers vs. EC Plug Fan Mounted in the Unit vs. EC Plug Fan Mounted Under the Unit 100% Model FH600C, 72F/50% RH, 45EWT, 10 deg water TD 0.3 External static pressure Net Sensible Cooling Capacity (kbtuh) Motor kw EER (kbtuh/kw) CFM Savings from Base Centrifugal blowers w/vfd , EC plug fan in unit , % EC plug fan under floor , % Figure 3. Mounting EC plug fans in the raised floor under the Liebert Deluxe System/3 is approximately 12 percent more energy efficient than mounting the EC plug fan inside. 4
6 to compare energy efficiency of centrifugal fans to EC plug fans mounted in the base of the unit to EC plug fans mounted under the unit in the raised floor, at varying motor speeds. The centrifugal fan at 100 percent speed served as the base case. At 100 percent motor speed, the 15hp motor draws 11 kw. At the identical CFM, the EC plug fan installed in the base of the unit draws 9 kw. By locating the EC plug fan under the unit in the raised floor, the resistance against the blower is reduced, so the motor can work less to reduce the same amount of CFM. This reduction results in only 7.6 kw of power consumed. The same holds true at slower speeds, with additional reduction in motor kw as you slow down the motor RPM. (Note that the chilled water valve is throttled back proportionally as the fan speed is lowered). As previously shown, at similar speeds an EC plug fan draws approximately 18 percent less power than a centrifugal blower, and placing the fan in the floor saves an additional 12 percent. But by reducing the motor RPMs using VFD, even the centrifugal blower can achieve substantial energy savings 65.5 percent energy savings at 70 percent speed. These results are shown in Figure 4. EC Plug Fans: Worth the Investment? Answering this question requires determining how reduction in motor kw translates into payback. A payback analysis was conducted using Liebert Deluxe System/3 model FH600C (10 units) at 284 MBH sensible cooling per unit (N+2 redundant) in three configurations based on previous testing. The results of the payback analysis are shown page 6. Energy Savings of EC Plug Fans vs. VFD 100% 90% 80% 70% Model FH600C, 72F/50% RH, 45EWT, 10 deg water TD 0.3 External static pressure Net Sensible Cooling Capacity (kbtuh) EER (kbtuh/ kw) Savings from Base Motor kw CFM Centrifugal blowers w/vfd , EC motorized impellar in unit , % EC motorized impellar under floor , % Centrifugal blowers w/vfd , % EC motorized impellar in unit , % EC motorized impellar under floor , % Centrifugal blowers w/vfd , % EC motorized impellar in unit , % EC motorized impellar under floor , % Centrifugal blowers w/vfd , % EC motorized impellar in unit , % EC motorized impellar under floor , % Figure 4. Energy analysis of fan system options based on Intertek testing labs comparison using ASHRAE
7 The annual energy costs and ROI are shown below. Fan Option Centrifugal blower with no VFD (11 kw) Centrifugal blower with VFD (5.6 kw) EC plug fan under the floor (3.9 kw) Cost for 10 Units Annual Energy Cost* ROI Base price $96, Base price + $36,000 Base price + $50,000 $49,056 9 months $34, months *Assumes $0.10 per kwh and operation at 80 percent fan speed. Conclusion Based on the performance tests discussed in this application note, it is clear that operating the fan motor at lower speeds using EC plug fans or VFD provides substantial energy savings in the large data centers with chilled water cooling systems. It is easy to upgrade an installed Liebert Deluxe System/3 to VFD for the energy savings that solution offers. With new installations, the VFD offers lower capital costs compared to the EC plug fan, so it is a good option when budget constraints rule out installation of EC plug fans. In raised floor data centers in which it can be used to best advantage, however, the EC plug fan offers the lowest annual operating cost and is the best solution for the life of the product. For a comprehensive look at how businesses can save energy in the data center, see the white paper Energy Logic: Reducing Data Center Energy Consumption by Creating Savings that Cascade Across Systems at 6
8 Emerson Network Power 1050 Dearborn Drive P.O. Box Columbus, Ohio (U.S. & Canada Only) (Outside U.S.) Fax: EmersonNetworkPower.com Liebert.com While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Specifications subject to change without notice Liebert Corporation. All rights reserved throughout the world. Trademarks or registered trademarks are property of their respective owners. Liebert and the Liebert logo are registered trademarks of the Liebert Corporation. Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co Emerson Electric Co. TN TN Emerson Network Power. The global leader in enabling Business-Critical Continuity. AC Power Embedded Computing Outside Plant Connectivity Embedded Power Power Switching & Controls DC Power Monitoring Precision Cooling EmersonNetworkPower. com Racks & Integrated Cabinets Services Surge Protection
Liebert CW 26-181kW Chilled Water Cooled Precision Air Conditioning For Data Centers
Liebert CW 26-181kW Chilled Water Cooled Precision Air Conditioning For Data Centers Precision Cooling For Business-Critical Continuity A Chilled Water Precision System That Handles The Most Demanding
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
How To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
Technical Note: Comparing R407C and R410A as Alternatives for R22. A Technical Note from the Experts in Business-Critical Continuity
Technical Note: Comparing R407C and R410A as Alternatives for R22 A Technical Note from the Experts in Business-Critical Continuity Purpose The purpose of this document is to provide a brief overview of
Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity
Effects of AC Ripple Current on VRLA Battery Life A Technical Note from the Experts in Business-Critical Continuity Introduction Given the importance of battery life to UPS system users and the fact that
Liebert : The Right Cooling For IT Environments. Precision Cooling For Business-Critical Continuity
Liebert : The Right Cooling For IT Environments Precision Cooling For Business-Critical Continuity New Challenges To IT System Uptime Many IT professionals are finding that dedicated precision cooling
Centrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
Protecting Our Information, Protecting Our Resources
Solutions For Business-Critical Continuity Protecting Our Information, Protecting Our Resources Energy Efficient Power And Cooling For IT And Telecommunications Network Infrastructures The Challenge You
The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity
Liebert HPF The High Performance Floormount Indoor Package Cooling Solution Precision Cooling for Business-Critical Continuity We re Emerson Network Power, backed by Emerson, a global company that brings
Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM
Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity
Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity
Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry
Reference Guide: SmartDesign Approach: Common Data Center Challenges:
Smart Solutions Reference Guide Solutions For Business-Critical Continuity 1100kW Tier 3 With High Density Design Intelligent, Integrated Infrastructure for the Data Center Reference Guide: 1100kW Tier
DCIM Readiness on the Rise as Significant Data Center Capacity Remains Unused. A Research Report from the Experts in Business-Critical Continuity TM
DCIM Readiness on the Rise as Significant Data Center Capacity Remains Unused A Research Report from the Experts in Business-Critical Continuity TM Introduction Data center management is in a stage of
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
How To Improve Energy Efficiency In Data Center Management
A White Paper from the Experts in Business-Critical Continuity TM Data Center Users Group Special Report Energy efficiency and capacity concerns increase Fall 2012 Survey Results Executive Summary The
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
The Effect of Regular, Skilled Preventive Maintenance on Critical Power System Reliability
The Effect of Regular, Skilled Preventive Maintenance on Critical Power System Reliability A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Emerson Network Power has
DISCONTINUED PRODUCT. Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert icom-do. User Manual
Infrastructure Management & Monitoring For Business-Critical Continuity Liebert icom-do User Manual TABLE OF CONTENTS 1.0 INTRODUCTION............................... 1 2.0 INSTALLATION...............................
Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
Virginia Tech. Background. Case Summary. Results
Background Virginia Tech When Virginia Tech initiated plans to build a supercomputer by clustering hundreds of desktop computers, it had ambitious goals for the performance of the new system and a very
Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes
Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
Secure Remote Monitoring of the Critical System Infrastructure. An Application Note from the Experts in Business-Critical Continuity
Secure Remote Monitoring of the Critical System Infrastructure An Application Note from the Experts in Business-Critical Continuity TABLE OF CONTENTS Introduction................................................2
Directed Circuits Meet Today s Security Challenges in Enterprise Remote Monitoring. A White Paper from the Experts in Business-Critical Continuity TM
Directed Circuits Meet Today s Security Challenges in Enterprise Remote Monitoring A White Paper from the Experts in Business-Critical Continuity TM Executive Summary With continued efforts to reduce overhead,
Reliability of Air Moving Fans, and Their Impact on System Reliability. A White Paper from the Experts in Business-Critical Continuity TM
Reliability of Air Moving Fans, and Their Impact on System Reliability A White Paper from the Experts in Business-Critical Continuity TM Summary Air-moving fans are used to remove waste heat on all UPS
Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment
SmartDesign Intelligent, Integrated Infrastructure For The Data Center. Solutions For Business-Critical Continuity
SmartDesign Intelligent, Integrated Infrastructure For The Data Center Solutions For Business-Critical Continuity Prepare Your Data Center For What s Next Efficiency. Availability. Capacity. Control. One
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
Liebert HPM Designed for top level performance and reliability. Precision Cooling for Business-Critical Continuity
Liebert HPM Designed for top level performance and reliability Precision Cooling for Business-Critical Continuity Emerson Network Power, a Division of Emerson, is a global company matching technology and
Protecting The Critical IT Infrastructure of the United States
Solutions for Business-Critical Continuity Protecting The Critical IT Infrastructure of the United States Emerson Network Power Products And Support Services We Help Make Sure Systems Are Available IT
IT White Paper. N + 1 Become Too Many + 1?
IT White Paper Balancing Scalability and Reliability in the Critical Power system: When Does N + 1 Become Too Many + 1? Summary Uninterruptible Power Supply (UPS) protection can be delivered through a
HVAC Air Systems. Recirculation Air System Types
HVAC Air Systems Recirculation Air System Types Summary Recirculation air handler fan energy can account for 10 to 30% of total cleanroom energy use. There are three fundamental recirculation system configurations:
Energy Efficient Cooling Solutions for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Energy Efficient Cooling Solutions for Data Centers Introducing an Emerson Network Power tool for evaluating cooling system total cost
National Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
Unidrive M Energy Savings
Unidrive M Energy Savings Why is this important? Some Data: Money, Lots of Money >13.5m electric motors 1Hp or greater installed in US industrial process operations. Industry spends >$33b annually on electricity
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center
Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment
Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment The Intelligent Data Center Cooling Solution: Liebert CRV Trust the industry leader in Precision Cooling to deliver
DATA COLLECTION AND PUMP ENERGY SAVING OPPORTUNITIES. Presented By: Rick Rumsey, P.E.
DATA COLLECTION AND PUMP ENERGY SAVING OPPORTUNITIES Presented By: Rick Rumsey, P.E. Data Collection Customer Information Pump Motor Information Pump Information Irrigation System Information Historic
Knürr DCL Modular Rack Cooling from 6 kw to 60 kw
Knürr DCL Modular Rack Cooling from 6 kw to 60 kw Emerson Network Power Business-Critical Continuity so your success continues! Core competencies AC Power Connectivity DC Power Embedded Computing Embedded
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT
White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
Knürr CoolAdd The universal retrofit solution against overheating in server racks. Rack & Enclosure Systems
Knürr CoolAdd The universal retrofit solution against overheating in server racks Rack & Enclosure Systems Knürr CoolAdd When cold air is no longer enough! Data centers are subject to constant changes:
Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity
Modular architecture for high power UPS systems A White Paper from the experts in Business-Critical Continuity Abstract Today, more than ever before, energy efficiency and cost-savings are among the top
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency
Data Center Infrastructure Management Managing the Physical Infrastructure for Greater Efficiency Infrastructure Management & Monitoring for Business-Critical Continuity TM DATA CENTER INFRASTRUCTURE MANAGEMENT
Power and Cooling Best Practices for IP Communications. A White Paper from the Experts in Business-Critical Continuity
Power and Cooling Best Practices for IP Communications A White Paper from the Experts in Business-Critical Continuity Executive Summary IP telephony and Power over Ethernet (PoE) are driving the requirement
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
How To Make A Data Center More Efficient
IT Solutions for Business-Critical Continuity Emerson Network Power Data Center Infrastructure Many Needs. One Source. Emerson Network Power, a division of Emerson Electric Co., is a global company that
Enterprise Remote Monitoring
Enterprise Remote Monitoring Alarm Management, Predictive Maintenance, Advanced Network Security Services For Business-Critical Continuity Can You Really Afford Not To Know? Loss of productivity and the
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units Mike West, PhD, PE Advantek Consulting, Inc Standard Air Conditioning Unit Packaged Unit Split System DX (not chilled water) Air-cooled
Energy Savings With Adjustable Frequency Drives. for Centrifugal Fans
Energy Savings With Adjustable Frequency Drives for Centrifugal Fans 2 Centrifugal Fans Centrifugal Fan Fans are designed to be capable of meeting the maximum demand of the system in which they are installed.
Energy Audits Waste Water Treatment Plants
Energy Audits Waste Water Treatment Plants Ohio Water Environment Association Conference June 20, 2012 Presented by: Samuel J. Morgan, P.E., LEED AP CT Consultants, Inc. World Energy Trend US Total Energy
Liebert icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight
Liebert icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight All for One, One for All Optimize a Single Cooling Unit an Intelligent Control and Good Things Happen. Integrate
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS
IT White Paper IP TELEPHONY AND RELIABILITY: PROTECTING MISSION-CRITICAL PHONE SYSTEMS FROM POWER THREATS Executive Summary IT managers who are used to implementing power protection for IT network or data
Surface Technology. Centrifugal Fan GMD
Centrifugal Fan ATEX classed adapted for paint shops Wide assortment broad area of application Service friendly low maintenance costs Headquarters: Centrifugal Fan Centrifugal Fan is a direct driven industrial
Precision Cooling for Business-Critical Continuity. Liebert PCW. Cool the Cloud
Precision Cooling for Business-Critical Continuity Cool the Cloud Whether a data center houses three or 1000 IT racks, deployment of new technologies with high power densities are impacting the power and
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring
Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring A White Paper from the Experts in Business-Critical Continuity Summary The first decade of the 21st century
Introduction. Motor Types
QwikSEER+ Theory of Operation and Retrofit Potential Mainstream Engineering Corporation Rockledge, FL 32955 http://www.qwik.com/products/qwikseer/index.jsp Prepared by Robert P. Scaringe and R. Paul Roth
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
LIFECYCLE COSTING FOR DATA CENTERS: DETERMINING THE TRUE COSTS OF DATA CENTER COOLING
LIFECYCLE COSTING FOR DATA CENTERS: DETERMINING THE TRUE COSTS OF DATA CENTER COOLING Summary Experts estimate that the average design life of a data center is 10-15 years. During that time, equipment
Liebert IntelliSlot Web Cards
Monitoring For Business-Critical Continuity Liebert IntelliSlot Web Cards Firmware Upgrade Manual Liebert IntelliSlot Web Card, Liebert IntelliSlot Web Card-LB, Liebert IntelliSlot Web Card-LBDS, Liebert
Variable Frequency Drives and Energy Savings
Variable Frequency Drives and Energy Savings It s more than just fan and pump applications www.sea.siemens.com by: Stephen Prachyl www.usa.siemens.com/energysavings When discussing energy savings and variable
How to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS
Manual No. BLWR043 Rev. 4 September 2012 OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS CVF-8AC CVF-8AC50 CVF-6ACAN CVF-15ACAN CVF-25ACAN CVF-8A15KIT CVF-8A25KIT MODELS: CVF-8DC CVF-6DCAN CVF-15DCAN CVF-25DCAN
Commercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
RagingWire Enterprise Solutions
Background Enterprise Solutions was founded in May 2000 to be an enterprise-class Managed Services Provider (emsp) that could provide and support colocated data center services for Fortune 1000 customers.
Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)
Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
Liebert. Liebert Universal Monitor Monitoring, Control And Remote Communications For Critical Applications
Site Monitoring and Services for Business-Critical Continuity Liebert Universal Monitor Monitoring, Control And Remote Communications For Critical Applications Liebert MONITORING AND ALARM CAPABILITIES
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
CHILLED WATER DATA ROOM UNITS
Critical Infrastructure for the World s Leading Data Centers CHILLED WATER DATA ROOM UNITS Downflow Net Sensible Cooling 79 220kW Upflow Net Sensible Cooling 66 206kW A Nortek Company DATA CENTER COOLING
INDOOR COILS. RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES
FORM NO. C11-211 REV. 7 Supersedes Form No. C11-211 Rev. 6 INDOOR COILS RCFL- featuring Industry Standard R-410A Refrigerant CASED/UNCASED COILS FOR GAS AND OIL FURNACES AIRFLOW CAPACITIES 600-1,900 CFM
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity
The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
How To Run A Data Center Efficiently
Seven Best Practices for Increasing Efficiency, Availability and Capacity: The Enterprise Data Center Design Guide A White Paper from the Experts in Business-Critical Continuity TM Table of Contents Introduction...
Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability
Considerations for a Highly Available Intelligent Rack Power Distribution Unit A White Paper on Availability Introduction Data centers are currently undergoing a period of great change. Data center managers
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit
Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative
Performance Rating of Room Fan- Coils
ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS
Chapter 3.5: Fans and Blowers
Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist
Chilled Water Precision Air Conditioner For Critical Application
AIRSYS-P-SC-OPTIMA-HD-E1304V01.2 HD Chilled Water Precision Air Conditioner For Critical Application Cooling capacity: 42.1kW~161.5kW OPTIMA product family is designed for medium to large data center.
Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity
Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems A White Paper from the Experts in Business-Critical Continuity Executive Summary In enterprise data centers, designers face
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
Drives and motors. A guide to using variable-speed drives and motors in data centres
Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers