1 National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National Grid : John Weale Integral Group francis.boucher@nationalgrid.com
2 National Grid Support for IT and Telcom Facilities 1.Programs offered by NSTAR / Northeast Utilities as well 2.Fourth year for National Grid 3.$ millions in incentives 4.Studied over 75 projects 5.New, retrofit and end of life replacement 2 National Grid U.S. Brand October 2012
3 Bottom Line 1. Customer are getting $100 s of thousands for things they need to address anyway 2. Get HUGE incentives by Right stuff at the right time Going more efficient than planned Adding free cooling Replacing equipment before its 15 years old 4 National Grid U.S. Brand October 2012
4 Opportunity Capacity meets energy incentives Increasing Return air temps Containment / air flow management Additional coil capacity ( along with higher CHW temps.) Availability Eliminate hot spots that kill servers ECM fan motors remove fan belt dust Redundant cooling (get new and leave the old) Cooling towers, In Row cooling Replace aging equipment Temperature, humidity equipment status 5
5 The motivators that sell Buying anyway Fixing a problem (Load or reliability) End of life equip. Energy $
6 Common incentive winners 3 5+ CRACs, 24/7 operation 65 kw or more UPS load Vendors of efficient systems Data center expansion projects
7 Tough incentive efforts Existing in-row cooler systems Already achieved most savings Tough to retrofit additional measures UPS, rectifier opportunities Will discuss UPS and rectifier offers, but most of webinar not useful for in-row systems
8 What s hot now Data center cooling systems Variable flow on CRAC units Free cooling: Pumped refrigerant Chilled water in-row retrofits Controls UPS and Rectifiers
9 VARIABLE AIRFLOW RETROFITS (APPLICATION: ALL CONSTANT SPEED UNITS)
10 Sometimes not just variable flow: better fans 20%-30% savings supported by test from ECM fan wheels (work in unit or, even better, under floor installation Multiple manufacturers
11 Standard centrifugal fans
12 Retrofit existing with VFD kits Upgrades whole room: New motors Upgraded controls (icom) Improved cold aisle monitoring Retrofit costs $9,000 - $13,000 / unit Requires some air flow management can system achieve a return air temperature of 78F? Works for air cooled, glycol cooled, or chilled water Paybacks of 2-5 years for 20 ton or higher units.
13 Variable airflow options: New units VFDs are lowest cost $4,000 - $5,000 incremental ECM option provides variable airflow and more efficient fan $7,000 - $8,000 incremental 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% Lower power use Paybacks of 1-2 years on incremental cost 100% 90% 80% 70% 60% 0% 50% Lower fan speed
14 GLYCOL FREE COOLING
15 Econocoil (Glycool) option Application: New units cannot be retrofit; existing benefit from adding condensers, air flow management Benefits from excess air cooled condenser capacity Paybacks as low as 1 year after incentive (incremental cost of about $5,000)
16 Retrofit free cooling to air cooled chilled water plants with surplus capacity Application: Oversized air cooled chilled water system Increasing drycooler capacity increases savings Increase return air temperature increases savings
17 AIR MANAGEMENT
18 Retrofit Airflow Management Application: Spaces with hot spot problems, overloaded units (capacity shortfall); bonus if no halon-style fire control Plenum return Curtains
19 Plenum Return Capacity of CRAC units increases with increase in return air temperature. Create a hot exhaust configuration for optimum efficiency and to control hot spots in the datacenter. Properly managing airflow through hot/cold aisle configurations, ducted return plenums (seen above), and aisle containment curtains are common tactics. 7/5/
20 Upgrade to best practice
21 ADVANCED CONTROLS
22 Add control to stage off unneeded capacity intelligently Application: Spaces with gross excess operating cooling capacity Intelligent systems monitor space and cycle off units dynamically Simple systems place redundant capacity in cold standby (fan is off)
23 On/Off versus VFDs Best option is advanced control with VFDs Monitoring benefits to advanced on/off control Possibly lower cost with on/of VFDs provide better savings VFDs typically do not have temperature monitoring, alarming, etc VFDs online redundancy
24 IN-ROW COOLING UNITS
25 In-row units almost always work as new capacity Application: Adding or replacing cooling equipment, hotspot fixing Integrated airflow management, variable speed fan Free cooling difficult with air cooled units First cost needs to consider installation
26 Case Study New Capacity Location Average Load kw Annual Energy Savings kwh Cost savings per Year Incremental Cost Incentive Payback With Incentive Westborough ,415 $25,250 $91,550 $68, Real Costs (installed) In-row incremental cost (vs baseline) 1 x $91,550 = $91,550 Total cost of 125 kw N+1 (actually 2N) nominal capacity $91,550 installed *Estimated, Incentive (estimate, installation 75%) cost can vary significantly $68,660 Final simple payback with incentive 0.9 year
27 Big move opportunity Convert to chilled water with free cooling Application: 150 ton+ load, air cooled CRAC system, money for renovation of aging system Replace aging CRAC system with in row chilled water Move to higher capacity, lower maintenance central chilled water system Very large incentive from National Grid, but large investment
28 In-row conversion example 160 tons total load (500 kw UPS load) Incentive ($500,000+) Payback: 2.5 years +Full new system, no hotspots, advanced controls
29 UPS OPPORTUNITY
30 Uninterruptible Power Supplies Application: End of life, new replacement, radical downsizing Modular UPS systems increase efficiency at lower load factors, which constitutes a large portion of runtime for most facilities. State-of-the-art single conversion models can increase efficiency. UPS Size Load 25% 50% 75% 100% kva < % 89.1% 89.6% 89.6% 20 <= kva <= % 90.5% 91.1% 91.1% kva > % 92.2% 93.1% 93.3% 7/5/
31 UPS Combining Systems Replace oversized units (at 10% load, efficiency drops from 93% down to 85% or lower) Combine existing units into new modular system Best option near end of life, old battery systems, etc Replacing a mid-life UPS can avoid costly battery replacement and sometimes improves service contract costs, encouraging a move to new efficient unit.
32 HIGH EFFICIENCY AIR COOLED COMPUTER ROOM UNITS RETROFIT OPPORTUNITY
33 Pumped Refrigerant Freecooling with 85F Return Application: Air cooled site, adding capacity, replacing old CRAC Large savings during cool nights and winter over 5,000 hours/yr free cooling in Boston climate More efficient at all conditions
34 Example: Upgrade <15 year old traditional units to DSE Location Average Load kw Annual Energy Savings kwh Cost savings per Year Full Cost* Incentive Payback With Incentive Boston ,000 $35,000 $255,000 $128, Real Costs (installed) New DA125 with econophase installed 2 x $127,500 = $255,000 (estimated budget cost) Total of 125 kw N+1 (actually 2N) nominal capacity installed Rack reconfiguration Internal maintenance *Estimated, installation cost can vary significantly Total cost $255,000 Incentive (estimate, 50%) $127,500 Final simple payback with incentive 3.6 years
35 MAXIMIZING INCENTIVE OPP
36 Hybrid Opportunity (New and Existing Capacity Projects) Often linking upgrades of old units to new capacity Maximizes incentive by linking moderate payback measures (VFD retrofit kits) with very low payback measure (upgraded new unit) Sell the upgrade of whole room: New motors Upgraded controls (icom) Improved cold aisle monitoring
37 Sample Hybrid Solution Add one new 15 ton nominal / 20 ton nameplate unit with variable speed fan (ECM motor) Retro fit 3 existing CRACs with networked icom controls and VFDs Linking the projects adds $10,000 to incentive
38 DC RECTIFIERS
39 Direct Current: Rectifier opportunity Application: Age <15 years Capacity 20-70kW or higher Maintenance costs increasing (10+ years, capacitor service, grossly oversized, etc)
40 Example Rectifier upgrade Lower maintenance (capacitor replacement) Lower cooling costs Lower power costs Improved reliably
41 Case study Location Load kw Annual Energy Savings kwh Cost savings per Year Boston 81 29,000 $3,500 + $1,000 maintenance = $4,500 total Estimated Costs (installed) Rectifier Infrastructure $11, kW nominal capacity per unit 8 Rectifier Modules $27,000 N+1 configuration; total of 70 kw nominal capacity installed Total cost $38,000 Incentive (estimate) $19,000 Final simple payback with incentive 4.2 years
42 THERMAL MAPPING
43 What is thermal mapping for? Identifies hot spots by measuring the temperature across the entire floor wireless temperature sensors deployed to make map Provides hard data on effectiveness of datacenter conditioning Three step process
44 Step 1: Deploy sensors
45 Step 2: Generate thermal map
46 Step 3: Use the data!
47 Chiller plants are full of opportunity Modern VFD Chillers provide improved efficiency, especially at part load. Sequence of operations should be optimized, including proper condenser water temperature reset. Significant pumping energy can be saved by reconfiguring pumping scheme to remove secondary water loop, having primary flow modulated by VFDs.
48 Thank you for participating today Contact: Fran Boucher National Grid
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationFree Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
More informationState of the Art Energy Efficient Data Centre Air Conditioning
- White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationEnergy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
More informationAdaptive Cooling in Data Centers. Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009
Adaptive Cooling in Data Centers Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009 Maximizing Cooling Efficiency in a Concurrently Maintainable and Fault
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationData Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
More informationTour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units
More informationAnalysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
More informationElements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
More informationData Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
More informationControl of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project
Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify
More informationDealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges
More informationThe Pros and Cons of Modular Systems
The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated
More informationCase Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
More informationTop 5 Trends in Data Center Energy Efficiency
Top 5 Trends in Data Center Energy Efficiency By Todd Boucher, Principal Leading Edge Design Group 603.632.4507 @ledesigngroup Copyright 2012 Leading Edge Design Group www.ledesigngroup.com 1 In 2007,
More informationRe Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
More informationSTULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
More informationHow to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
More informationBenefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
More informationGREEN DATA CENTER DESIGN
Jeffrey Menig Global Facilities Facility Engineering The application of multiple available technologies resulting in improved energy optimization without significantly increasing capital investment. A
More information- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
More informationCase Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
More informationData Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
More informationIT@Intel. Thermal Storage System Provides Emergency Data Center Cooling
White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that
More informationEuropean Code of Conduct for Data Centre. Presentation of the Awards 2013
European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started
More informationData Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
More informationThe Different Types of Air Conditioning Equipment for IT Environments
The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.
More informationBlade Server & Data Room Cooling Specialists
SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling
More informationREAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center hansenkl@unmc.edu 402-559- 5301 402-630-
More informationEducation Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
More informationData Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
More informationAIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
More informationEuropean Code of Conduct for Data Centre. Presentation of the Awards 2014
European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
More informationData Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert
Data Center Consolidation Trends & Solutions Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Agenda Traditional Data Centers Drivers of a Changing Environment Alternate
More informationAEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical
More informationDatacenter Efficiency Program
Datacenter Efficiency Program Yuming Qiu, CLEAResult Anna Stieve, CLEAResult Michael Stachowiak, CLEAResult Abstract Worldwide, datacenter energy consumption is skyrocketing and datacenter energy efficiency
More informationWhite Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
More informationKU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
More informationIn Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
More informationLiebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity
Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry
More informationHow To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
More informationManaging Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationReducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
More informationAlan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers
Information Technology and Data Centers HVAC Showcase November 26, 2013 Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers Welcome. Today s webinar is being recorded and will be
More informationManaging Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
More informationData Center Design and Energy Management
Agenda EasyStreet Online Services, Inc. Data Center Design and Energy Management Introduction to EasyStreet Speaker Bio EasyStreet Sustainability Data Center 1 (Retrofit completed May 2010) Data Center
More informationData Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013
Data Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013 Ted Brown Sr. Energy Management Analyst Data Center / IT Energy Efficiency ted.brown@seattle.gov
More informationEnergy Impact of Increased Server Inlet Temperature
Energy Impact of Increased Server Inlet Temperature By: David Moss, Dell, Inc. John H. Bean, Jr., APC White Paper #138 Executive Summary The quest for efficiency improvement raises questions regarding
More informationPresentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
More informationSelf-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.
More informationLiquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
More informationEuropean Code of Conduct for Data Centre. Presentation of the Awards 2016
European Code of Conduct for Data Centre Presentation of the Awards 2016 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
More informationHow To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
More informationEnergy Efficient High-tech Buildings
Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory Wftschudi@lbl.gov Acknowledgements California
More informationRecommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation
Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation Version 1.0 - November, 2011 Incorporating Data Center-Specific Sustainability Measures into
More informationAIR-SITE GROUP. White Paper. Green Equipment Room Practices
AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider
More informationEnergy Efficiency Baselines for DATA CENTERS. Statewide Customized New Construction and Customized Retrofit Incentive Programs.
Energy Efficiency Baselines for DATA CENTERS Statewide Customized New Construction and Customized Retrofit Incentive Programs March 1, 2013* Revision 1 (Rectifier Efficiency Added) Written By: Integral
More informationI-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility
More informationDataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
More informationRecovering Stranded Capacity in the Data Center. Greg Bell Driving e-research Across the Pacific `09 Sydney: 11/13/09
Recovering Stranded Capacity in the Data Center Greg Bell Driving e-research Across the Pacific `09 Sydney: 11/13/09 2 Recovering Stranded Data Center Capacity most data centers are overcooled & inefficient
More informationCooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
More informationEXAMPLE OF A DATA CENTRE BUILD
EXAMPLE OF A DATA CENTRE BUILD BT Harmondsworth Data Centre Hall 2 Upgrade Temperature Control have been involved in providing specialist to data centres for over 20 years, starting from providing specialist
More informationCANNON T4 MINI / MICRO DATA CENTRE SYSTEMS
CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly
More informationAn Introduction to Cold Aisle Containment Systems in the Data Centre
An Introduction to Cold Aisle Containment Systems in the Data Centre White Paper October 2010 By Zac Potts MEng Mechanical Engineer Sudlows October 2010 An Introduction to Cold Aisle Containment Systems
More informationAgenda. Part I: Introduction to OptimumHVAC. Part II: Initial Energy Savings Analysis for MCO Main Terminal. Part III: Case Studies & Conclusion
OptimumHVAC Prepared for the: GOAA Energy Conservation & Environmental Initiatives Forum April 27, 2010 Jamie Wiecks Enterprise Account Manager Optimum Energy Mike Dillard Vice President, Business Development
More informationOverview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
More informationContainment Solutions
Containment Solutions Improve cooling efficiency Separate hot and cold air streams Configured to meet density requirements Suitable for commercial and SCEC endorsed cabinets Available for retrofit to SRA
More informationHigh Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
More informationData Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
More informationHow To Test A Theory Of Power Supply
A CASE STUDY ON: THE EFFECTS OF HIGHER OPERATING TEMPERATURES ON DATA CENTER EFFICIENCY Victor Garcia Director of Facilities Brocade October 24, 2012 Jeff Stein, PE Principal Taylor Engineering 2010 Brocade
More informationDirect Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
More informationCooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
More informationNetApp Data Center Design
NetApp Data Center Design Presentation for SVLG Data Center Efficiency Summit November 5, 2014 Mark Skiff, PE, CEM, CFM Director, IT Data Center Solutions Data Center Design Evolution Capacity Build Cost
More informationData Center Airflow Management Retrofit
FEDERAL ENERGY MANAGEMENT PROGRAM Data Center Airflow Management Retrofit Technology Case Study Bulletin: September 2010 Figure 1 Figure 2 Figure 1: Data center CFD model of return airflow short circuit
More informationBenefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
More informationAPC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
More informationData Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
More informationAIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland
AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course
More informationCooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
More informationAn Improved Architecture for High-Efficiency, High-Density Data Centers
An Improved Architecture for High-Efficiency, High-Density Data Centers By Neil Rasmussen White Paper #126 Executive Summary Data center power and cooling infrastructure worldwide wastes more than 60,000,000
More informationAgenda. Who we are What we do How we serve the BPO Industry
Achieving Energy Efficiency in Data Centres Agenda Who we are What we do How we serve the BPO Industry Energy Efficiency for Data Centres Jardine Matheson Founded as a trading company in China in 1832,
More informationStanford University Server/Telecom Rooms Design Guide
Stanford University Server/Telecom Rooms Design Guide CONTENTS 1.0 How to Use this Guide...3 1.1 Document Organization...3 2.0 Summary Form and Sample Options Matrix...3 3.0 Options Matrix...7 4.0 Recommended
More informationReference Guide: SmartDesign Approach: Common Data Center Challenges:
Smart Solutions Reference Guide Solutions For Business-Critical Continuity 1100kW Tier 3 With High Density Design Intelligent, Integrated Infrastructure for the Data Center Reference Guide: 1100kW Tier
More informationPrinting and Publishing Energy Savings Guide
Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand
More information2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms
Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power
More informationVerizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
More informationOptimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
More informationNRDC case study. NRDC s New York Data Center Upgrade: Efficiency Case Study
NRDC case study december 2014 CS:14-09-a NRDC s New York Data Center Upgrade: Efficiency Case Study DATA CENTER BUILD-OUT TEAM table of contents ARCHITECT: Croxton Collaborative Architects, PC GENERAL
More informationHow High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
More informationVariable-Speed Fan Retrofits for Computer-Room Air Conditioners
Variable-Speed Fan Retrofits for Computer-Room Air Conditioners Prepared for the U.S. Department of Energy Federal Energy Management Program Technology Case Study Bulletin By Lawrence Berkeley National
More informationVISIT 2010 Fujitsu Forum Europe 0
VISIT 2010 Fujitsu Forum Europe 0 Virtualization & Automation Room 13a Shaping tomorrow with you. Green Data Center Services Martin Provoost Director, Data Centers and Networks, Fujitsu UK & Ireland 14:00
More informationData center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
More informationLegacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
More informationThe New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
More information