Douglas Lighting Controls - Specifications W-2000 Networked Systems

Similar documents
Product Specifications Dialog System

SECTION LOW VOLTAGE LIGHTING CONTROLS

INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

EcoSystem Dimming Power Module for 3-wire Lutron Dimming Ballasts. EcoSystem One-Line. EcoSystem C5-BMJ-16A. EcoSystemR Dimming Module

Lighting Controls ! WARNING RISK OF ELECTRIC SHOCK. Installation Instructions DESCRIPTION

How To Use A Lutron Power Supply

Lighting Packages. 230 VAC Fluorescent Enclosure Light:

INTRUSION DETECTION SYSTEM Section

AT&T. PARTNER Plus Door Phone. Installation and Operation Manual

Future proof lighting management

LED DIMMING A HELPFUL GUIDE...

Reference Design. conference rooms

Basics of Dimming. ISC Learning Centre

T7560A,B,C Digital Wall Module

HVAC and Lighting Control Products for Open Building Automation Systems

GLPHASE System. System Components GLPHASE - KP- KP- KP- KP- OS- DS SpaceBuild Specification Worksheet. Touch Screens

HMI display Installation Guide

LIEBERT VNSA Installation Sheet

THERMAL MANAGEMENT SOLUTIONS

SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT

C-Bus Solutions. Complete commercial control. Make the most of your energy SM

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

LIGHTING CONTROL SYSTEM

PLAN REVIEW GUIDE FOR FIRE ALARM

Expansion Modules & Accessories

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

Switching Power Module

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

Electronic Control Devices The European Product Catalogue 2007

Understanding Emergency Power Off (EPO)

KNX Lighting Control System

MechoNet TM Network Interface (MNI) Specification Submittal

High Bay Occupancy Sensor Selection Guide

FIREDEX Conventional Fire Panels

WxGoos-1 Climate Monitor Installation Instructions Page 1. Connections. Setting an IP Address

EBDSPIR-DD, EBDSPIR-DD-IP

Electronic Control Devices The European Product Catalogue 2007

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Lighting Management solutions

920 Series. Dual-point heat-tracing control system. Product overview. 920*E4FWL*SIS302*SS3102 shown

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

GLPAC-DIMFLV Crestron Green Light Integrated Lighting System

Versatility, reliability and expandability are the three main features that make the N-1000 one of the most popular access control panels ever.

EBDSPIR-PRM, EBDSPIR-PRM-IP

EQUIPMENT SPECIFICATIONS

TR21, TR22, TR23, and TR24 Wall Modules

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Centro-Matic Automatic Lubrication Systems System Controls

Section TELEPHONE AUTOMATIC DIALER SYSTEM

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits and

LiteKeeper 4 & 8 Programming Guide and User Manual

TrueAlarm Fire Alarm Systems

LANTANA LUMINAIRE HI-LUME 1% ECOSYSTEM LED DRIVER L3DA4U1UMN-XXXXX

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

Square D Clipsal Two-Channel DIN-Rail DALI Gateway

EMBEDDED ACCESS CONTROL Hardware Installation Guide

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM

SECTION DETECTION AND ALARM

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES

Category 6 Solutions. 4. Category 6 Solutions. 09/ IN TrueNet Structured Cabling. Introduction Cable Patch Panels... 4.

WIRELESS READER INTERFACE - INDOOR

Technical Manual MDT Rain sensor

Vroom Hardware manual ver Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

contents Leading the way in intelligent automation INELS Wireless? Why Click Accessories Complete control

Product and functional description

Network Time Accessories LED CLOCK. (for NTP Synchronization)

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

video door entry system offer

How To Use A Ds340 (Dsp)

FX07 Field Controller

Model 2300DR Installation Guide

Operation and Installation Manual

SECTION MediaStation Model 125 Electric Lateral Files (ELF)

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

DIVISION 28 ELECTRONIC SAFETY AND SECURITY SECTION SECURITY AND ACCESS CONTROL SYSTEM

TSn SERIES Surge Protective Device

Talk-A-Phone Co. Model WEBS-MT/R Emergency Phone Tower Mount Architectural & Engineering Specification rev. 08/29/2011

Climate Ready Control Systems Technical Specifications

Advanced Heat-Tracing Control System

ScreenLogic Wireless Connection Kit. Installation Guide. pool/spa control system

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

15 Series - Electronic step relay and dimmer. Features SERIE

How To Wire Wireline Cable To A Cell Phone (New Zealand)

Products and solutions for lifting systems

RF Maestro Local Controls

AC-115 Compact Networked Single Door Controller. Installation and User Manual

B. Related Sections: 1. Section Raceway and Boxes for Electrical Systems.

On/Off Relay Switch and 3-Way Switch Kit

IntesisBox KNX - LON

SECTION INTERIOR LIGHTING FIXTURES, LAMPS, AND BALLASTS

40.3. Control Relays and Timers

Installation Guide Solar Connect-11

Owner s Manual. Walk-in Monitoring System 100. Cooler is Better! TM. Used in UL Listed Door Panel Assemblies

ETZGAR CONVEYOR COMPANY Controls Section v12.05

DUCT SMOKE DETECTOR D4120

Transcription:

1. PAR T 1 - General 1.1 Overview - Specifications W-2000 Networked Systems 1.1.1 Provide a complete low voltage lighting control system for the building as shown on the plans and specified herein. 1.1.2 Lighting control system shall utilize networking technology based upon LonWorks and the products are to be LonMark certified to Level 3.1 or 3.3. System shall be able to operate as a stand-alone entity with option of using a web server device so that programming and viewing of status can be accomplished by any PC connected to the same LAN or via the internet. 1.1.3 If the system is to be integrated with a Building Management System, the Lighting Controls Manufacturer must make available LNS plug-ins for each product connected to the data line. All programming, configuration and commissioning will be by the BMS Integrator. The network transceivers will be FTT-10, designed for free topology or serial loop data line architecture. 1.1.4 All relay panel interiors shall be pre-assembled complete with the necessary relays, transformers and devices. Relay panel interiors are to be separate from enclosure so as to permit easy mounting, conduit installation and wire pull to enclosures. Interiors to be inserted last and connections made. 1.2 Manufacturers 1.2.1 All components are to be supplied by same manufacturer. Manufacturer to be a supplier of this type of equipment for over 10 years. 1.2.2 Low voltage control system shall be manufactured by. 1.3 Prior Approval Submissions 1.3.1 Manufacturers wishing to submit quotations on the lighting control system must pre-qualify. Pre-qualification information must be submitted to the electrical consulting engineer not later than ten (10) working days prior to the final closing of tenders for this project. 1.3.2 The manufacturer must be prepared to demonstrate the equipment being proposed before the closing of tender. 1.3.3 Submit a one-line diagram of the proposed system configuration for review. 1.4 Instruction Manuals 1.4.1 Supply manuals on system components to permit ease of installation, system operation and maintenance including, but not limited to the following: Lighting control system step-by-step operating instructions. Relay panel schedules indicating circuits connected, inputs assigned, area controlled, panel location and panel equipment details. 1

2. PAR T 2 - Materials 2.1 Relays 2-wire HID Relay suited for all types of lighting loads: WR-6161 2.1.1 Lighting control relays mounted in relay panels shall be WR-6161 full load relays suitable for all types of lamp loads up to 20 Amperes. Load contacts shall be able to sustain 1500 amp fault currents for up to 20 milliseconds. 2.1.2 The relay shall be contained in a molded case containing both low and high voltage terminals and shall have a built-in operating lever marked ON/OFF for manual switching at the relay panel. 2.1.3 Switching the relay shall be accomplished with ONE signal wire and a common return. The signal wire shall be able to signal ON and OFF and shall also carry status current that indicates if the relay is ON or OFF. 2.1.4 UL Listing 20A : 120 & 277 VAC; CSA 20A : 120, 277 & 347 VAC 2-wire HID Relay, 2 pole, suitable for 480V applications: WR-6172 2.1.5 2-Pole lighting control relays mounted in relay panels shall be WR-6172 full load relays suitable for all types of lamp loads up to 20 Amperes. Load contacts shall be able to sustain 1500 amp fault currents for up to 20 milliseconds. 2.1.6 Switching the relay shall be accomplished with ONE signal wire and a common return. The signal wire shall be able to signal ON and OFF and shall also carry status current that indicates if the relay is ON or OFF. 2.1.7 The relay shall be contained in a molded case containing both low and high voltage terminals and shall have a built-in operating lever marked ON/OFF for manual switching at the relay panel. 2.1.8 UL Listing 20A : 120, 277 & 480 VAC; CSA 20A : 120, 277 & 347 VAC 2.2 Pre-assembled Relay Panels: PWEx Series 2.2.1 Where indicated on the drawings, provide a factory pre-assembled relay panel. The panel s enclosure shall be for surface or flush installation, with a screw-on cover or a hinged door assembly as required. 2.2.2 The panel shall consist of a pre-assembled interior insert; UL/CSA approved Douglas Cat No: CxxM or WxxM series with capacities for 12, 24, 36, 48 or 72 relays as required. Panel enclosure must be UL/CSA Approved. 2.2.3 Panel interior shall have the following pre-assembled and pre-wired: Suitable divider separating class 1 and class 2 compartments. Control transformer, UL/CSA approved for class 2 circuits, Douglas Cat. No. WR-4075- xxx where xxx = primary voltage. Low voltage relays as required by switched circuits shown on plans or schedules. Control devices as required. 2

2.3 Relay controls installed in relay panels Programmable Relay Scanners: WRS-2224 2.3.1 When groups of relays are to be switched by master switches or time controls and it still must be possible to switch individual relays by local switches, provide programmable relay scanner WRS-2224. 2.3.2 Each scanner shall be solid state and have 24 relay outputs. An output shall be capable of switching the connected relay ON and OFF and sensing if the connected relay is ON or OFF. 2.3.3 Each programmable relay scanner shall have 5 switch inputs to accommodate group switches. Each switch input can be set with the keypad built into the scanner to switch some or all of the 24 relay outputs of the scanner. Each switch input must indicate an ON state if any of the relays in the group is ON. If all relays are OFF, then indicate an OFF state to the group switch. 2.3.4 The scanner shall be able to provide an optional flick warn option for each of the 5 groups. After the flick warn, the occupant has 5 minutes to prevent the local lights from switching OFF by activating the local switch. 2.3.5 The scanner shall provide an optional time-out option. When activated, this option will allow any relay in the system when switched on, to be timed for a 2 hour interval before being switched off. Flick warn may also be added to this option. 2.3.6 The programming of the scanner shall be user friendly with instructions printed on the scanner label. 2.3.7 The relay scanner shall accept a plug-in module, WNX-2624 Network Node. The network node shall use LonWorks technology and shall be LonMark certified (V3.1). This node shall be capable of connecting to an FTT-10A data line to communicate with other scanners in different relay panels or with other vendors using LonWorks technology. 3

2.4 Relay Panel Network & LonWorks Technology Overview of Network nodes: WNX-2624 Node LonMark Certified to 3.1 2.4.1 Relay panels that are networked together with Douglas Scanners and Network nodes shall be able to operate as a stand-alone system or shall be able to be integrated as a part of a LonWorks Building Automation System that includes other functions of the building such as HVAC and Security. The WNX-2624 nodes shall use FTT-10 transceivers. 2.4.2 The network shall use LonWorks Inter-Operable technology and the network nodes attached to the relay scanners shall be LonMark certified to the Level 3.1 standard for lighting. Stand-alone system 2.4.3 The stand-alone system shall not require the services of an integrator or other software specialist to program the system. No PC or extra device shall be required for setting which relays are controlled by a group switch input. It shall be possible to view and edit which relays are controlled by a switch input with indicators and buttons built into the relay control devices. The stand-alone system shall provide the following features: Each input can control any group of relays located throughout the system. A single group of relays can be operated by more than one input. When connected to an input, a pilot light switch shall indicate the state of the relay group. If any relay in the group is ON, the switch shall indicate ON. If all relays of the group are OFF, the switch shall indicate OFF. Group inputs shall be able to accept signals from other devices such as time clocks, photocells or contact closures from other systems to provide automation of the lighting controls. Each relay group shall be able to support the flick-warn option. After the flick warn, the occupant has 5 minutes to prevent the local lights from switching OFF by activating the local switch. Each relay group shall be able to support the time-out option, which allows the occupant to activate by local switch a relay that will time-out after 2 hours. It shall be possible to enable and disable the feature with a time clock so that it is only active when needed (after hours). 2.4.4 WNS-2308 Input Module LonMark Certified 3.3 The input modules shall have 8 inputs that can be configured to accept 24VAC or diode pulse signals from switches or other devices. Functions that are supported by the inputs are ON, Off, flick warn, time out, delay off, delay on, housekeeping on and wink. Provide enough modules to accommodate the switches as shown on the drawings. The modules shall use FTT- 10 transceivers and be LonMark certified to level 3.3. 2.4.5 WBC-2512 Dimming Control Module LonMark Certified 3.3 The Dimming Control Modules shall have 12 outputs and provide 0-10VDC standard control to operate incandescent dimming modules or fluorescent dimming ballasts. Provide as required from schedules as shown on the drawings. Modules shall use FTT-10 transceivers and be LonMark certified to level 3.3. 4

2.5 Wall Switches & Accessories Switches - Hardwired 2.4.6 Remote control switches and switch hardware to mount to standard wall boxes. Standard switches mount up to 3 switches per gang. 2.4.7 Rocker switches shall be WR-8001. 2.4.8 Switches that require an indicator shall be WR-8501 push button switch. Switch shall have integral LED's that indicate both ON and OFF states (red=on, green=off). The switch shall have a plastic cap to permit holding a paper identification label. 2.4.9 Switches that require keyed operation shall be WRK-8201 Key switch complete with integral LED to indicate state. 2.4.10 Wiring of switches to be #18 AWG, solid conductor. Check with manufacturer regarding other gauges before installing. Switches - Networked 2.4.11 Network switches shall be WNS-2313 and have integral LED s that indicate both ON and OFF states (red=on, green=off). The switch shall have a plastic cap to permit holding a paper identification label. 2.4.12 Switches shall have FTT-10 transceivers and be LonMark certified to level 3.3. Switch plates 2.4.13 Select switch plates to suit number of switches as shown on the plans. Up to 3 switches can be installed in a 1 gang box. Use WN-3020 filler plugs where appropriate. 2.4.14 Switch plates are to be made of stainless steel shall be WN-76xx series cover plates. 2.5 Photocell & Daylight Controls Outdoor and Ceiling Mount Photocell: WPS-5941 & WPS-5951 Remote Sensor LonMark 3.3 2.5.1 Provide where required a photometric sensor, capable of sensing from 1-6,000 foot candles. The WPS-5941/5951 sensor is to be connected to the LonWorks data line and shall output a continual light level to the system controller. Sensors to be LonMark certified to level 3.3. Indoor Task Area Daylight Sensor for Dimmable Ballasts: WPC-5700 2.5.2 Provide where required an indoor daylight sensor WPC-5700 for applications that harvest daylight by regulating the electronic dimmable fluorescent ballasts. The sensor shall regulate the ballast so that when natural light is bright the lamp is dim and when natural light is dim the lamp is bright. The sensor shall be ceiling mounted and measures light reflected upward from the surface below. The sensor shall have a range setting and a set-point slider located under the front faceplate. 2.5.3 The sensor shall be compatible with Phillips/Advance Mark VII, Motorola Helios or any other ballast that uses the same 0-10V dimming control method. The sensor shall connect with 2 wires connected in parallel to a maximum of 50 ballasts. No other connections to the sensor are required for the dimming function. 5

3. PART 3 - Installation 3.1 Relay panels and conduit. 3.1.1 Ensure that conduit for line voltage wires enters panel in line voltage areas and conduit for low voltage control wires enters panel on low voltage areas. Check manufacturer s drawings for location of line and low voltage areas. 3.2 Low Voltage Wiring 3.2.1 For low voltage wiring, provide wire type as recommended by the manufacturer. 3.2.2 Adhere to manufacturer's recommendations as to maximum wire length and maximum quantity of relays per switch. 3.2.3 Data line shall be #16 twisted pair Beldin #8471 or equal. 3.3 Line Voltage Wiring 3.3.1 Use wire gauges from #12AWG to #14AWG as appropriately sized for the branch circuit. End of Section 6