T7560A,B,C Digital Wall Module
|
|
|
- Esmond Gordon
- 10 years ago
- Views:
Transcription
1 T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital Wall Module (DWM) wiring can be sized from 16 to 22 AWG (1.5 to 0.34 mm 2 ), depending on the application. The max. length of wire from a device to a DWM is 164 ft (50 m). Twisted pair wire is recommended for wire runs longer than 100 ft (30.5 m). CAUTION EMI Noise Introduction. Risk of erratic system operation. Keep wiring at least one ft (305 mm) away from large inductive loads such as motors, line starters, lighting ballasts and large power distribution panels. During installations, try to avoid areas of high EMI noise. Run DWM wiring separately from 50 Vac or greater power wiring. WARNING / CAUTION Risk of electric shock or equipment damage! Do not touch any live parts inside the DWM housing. Disconnect the power supply before making connections to or removing connections from the DWM's terminals. Do not reconnect the power supply until you have completed the installation. If the DWM is powered via terminal 8 and connected to earth ground, then the cable must be shielded. INSTALLATION INSTRUCTIONS Table 1. Types of DWM sensor 1 setpoint bypass fan override T7560A Tmp wheel button button T7560B Tmp/Hum wheel button button T7560C Tmp/Hum Tmp = Temperature sensor; Hum = Humidity sensor Table 2. Controller SW requirements for powering via terminal 5 and new LCD signaling VAV W7751H Fan Coil Unit W7752 W7754 Hydronic W7762 Chilled Ceiling W NOTE: A software module (ModAL module GNRSC02A) is available to adapt the DWM to the respective Excel 20, 50, 100, 500, 600, or 800 controller, making any further configuring obsolete. Contact your local Honeywell distributor for further details. DWM DISASSEMBLY The T7560A,B,C comes packed with a sub-base that mounts separately for ease of installation. The cover is fixed by a latch on the underside of the unit. Remove the cover as shown in Fig. 1 (T7560A,B) or Fig. 2 (T7560C): 1. Insert the tip of an awl or a similar narrow, pointed object into the small hole in the latch (T7560A,B) or simply depress the latch by hand (T7560C). 2. Pry off the cover. Observe precautions for handling electrostatic sensitive devices. Fig. 1. DWM disassembly (T7560A,B) U.S. Registered Trademark Copyright 2014 Honeywell Inc. All Rights Reserved
2 3. Verify DWM is wired according to Fig. 4. NOTE: For specific wiring requirements, see section Power below. Terminals Fig. 2. DWM disassembly (T7560C) INSTALLATION Mount the DWM on an inside wall approximately 54 in. (1.3 m) from the floor (or as specified on the installation drawings) to allow exposure to the average zone temperature. Do not mount the DWM on an outside wall, on a wall containing water pipes or near air ducts. Avoid locations that are exposed to discharge air from registers or radiation from lights, appliances, or the sun. The DWM is furnished with a terminal block; all field wiring connections are made to these eight terminals. The DWM must be mounted in vertical position with the LCD display to the top. Mount the subbase directly on a wall (see Fig. 3) using the type of screws appropriate for the wall material = Common 2 = Temperature sensor 3 = Setpoint (T7560C: Do not connect!) 4 = Bypass/fan* (T7560C: Do not connect!) 5 = LED input (T7560C: Do not connect!) 6 = Bypass** (T7560C: Do not connect!) 7 = Humidity output 8 = 24 Vac/dc input * With Excel 10 Controllers: W7750 (CVAHU), W7752 (FCU), and XL12 ** With Excel 10 Controllers: W7751H (VAV), W7762 (HYD), and W7763 (CHC) For W7753 (UV) and W7761 (RIO), see NOTE below. Fig. 4. Wiring of DWM NOTE: If connected to the W7753 (UV) Controller, both terminals 4 and 6 must be connected. NOTE: The W7761 Remote I/O Controller supports only terminals 2 (temperature), 7 (humidity), and 1 (common), as well as terminal 8 as voltage supply. NOTE: Wiring with terminal 8 is not necessary if: a) an FCU or CHC controller with software is connected (see Table 2); or b) an Excel 500 with 6V/8V/10V signaling from the controller is used. The T7560A must then be powered by terminal 5. Fig. 3. Mounting of DWM (T7560A,B shown) See Fig. 6 for T7560A,B,C mounting dimensions. WIRING Wire the terminal blocks as follows: 1. Strip 3/16 in. (5 mm) of insulation from the conductor. 2. Insert the wire in the required terminal location and tighten the screw to complete the termination. IMPORTANT Deviation from this rule can result in improper electrical contact. See Fig. 4. Power The DWM can be powered as follows: T7560A Preferably via the 5 V LED input (terminal 5); via terminal 8 is also possible. T7560B,C Via the 24 Vac/dc input (terminal 8). 2
3 IMPORTANT In the case of those controllers listed in Table 2, the DWM can be powered only via terminal 5, and only if a SW version listed in Table 2 or higher is installed. If the DWM is powered via terminal 5, the Excel 10 controller must be configured for LCD_DISPLAY (LED output continuously ON). NOTE: The 24 Vac power supply is needed only with the T7560B,C DWM (for the humidity sensor). Alternatively, a DC voltage source with V can be connected to terminal 5 (see IMPORTANT note above). Alternatively, a DC voltage source with V (e.g., 22 Vdc from W7750 CVAHU) can be connected to terminal Input Ratings Terminal 5 min. 5 Vdc, I max 3 ma, max. 15 Vdc, I max 4 ma, or the LED output of any Excel 10 controller Fig. 5. Mounting cover of T7560A,B DWM Terminal 8 24 Vac from controller, I MAX 6 ma, with a valid range of 18 V (I MAX 2.4 ma) to 27 V (I MAX 10 ma). Controllers with the following output ratings can be connected to terminal 5 (ratings are met by all Excel 10 controllers): 5 V with 389 Ω 4.3 V with 100 Ω 14.3 V with 1.5kΩ Use up to 16 AWG (1.5 mm 2 ) with a minimum of 18 AWG (1.0 mm 2 ) wire for connecting 24 Vac power to terminal 8. CAUTION Low Voltage Equipment. Risk of equipment damage. The 24 Vac power source for the DWM must be a Class II Power Source. To conform to Class II restrictions, transformers must not be larger than 100 VA. A transformer that is CE certified and meets the Low Voltage Device (LVD) requirements must be used in Europe for all installations of this product. The DWM power usage is 0.2 VA at 24 Vac. The DWM does not require a dedicated transformer. The DWM can get power from any convenient location in the 24 Vac power circuit. The 24 Vac power can come from the 24 Vac power terminals on the nearest controller or directly from a 24 Vac transformer, whichever is closer. When all wiring is complete, attach the cover of the DWM as is shown in Fig. 5. NOTE: Make sure that the latch on the underside of the DWM engages properly and in the case of the T7560A,B that the three control buttons protrude through the holes completely. Fig. 6. DWM dimensions in inches (mm) 3
4 CONFIGURATION (T7560A,B) After installation, the T7560A,B DWM must be configured in order to perform as desired. This is done by using the buttons and the setpoint wheel (see Fig. 7). NOTE: After approx. 10 seconds without further action, the DWM automatically falls back to normal mode. P1 Setpoint type setting / scale type setting Fahrenheit relative Fahrenheit absolute * Celsius relative Celsius absolute P2 Room temperature setting Do not display room temperature (setpoint, only) * Display room temperature Display room temperature and humidity, alternating every 5 seconds (T7560B, only) Fig. 7. Control elements of T7560A,B DWM NORMAL OPERATING MODE After the DWM is powered up by the controller, it will display the room temperature and will operate as configured by default. In the following, the respective default setting is marked with an asterisk (*). After power-up, all display segments are switched on for approx. one second (see Fig. 8). AUTO MANU PROG Fig. 8. Display of all segments after power-up ENTERING CONFIGURATION MODE 1. Press FAN OVERRIDE for at least 5 seconds. 2. Press UNIT ENABLE, then release FAN OVERRIDE, hold UNIT ENABLE for at least 5 seconds. 3. Release UNIT ENABLE. RESULT: The display shows and the DWM is ready for configuration (see below). 4. Press and hold FAN OVERRIDE while turning the setpoint wheel to select the parameter number. RESULT: The parameters with their currently set values are displayed; the behind the value indicates the currently set value (see below for values). 5. Release FAN OVERRIDE and turn the setpoint wheel to select the parameter value. 6. Confirm selection by pressing UNIT ENABLE. 7. Repeat steps 4 to 6 to configure next parameter, or press BYPASS to leave the configuration mode. P3 Bargraph use setting No Fan Auto, Off, On Auto, Off, 2 Speeds * Auto, Off, 3 Speeds P4 Controller type setting * New LCD signaling from controller (only for controllers and SW versions as listed in Table 2 or higher, in which case this setting must be selected; set Excel 10 controller to LCD_DISPLAY) LED override mode from controller, US signaling (100 ms pulses); with controllers W7750, W7751, W7753, W7761, and XL12 LED override mode from controller, European signaling (500 ms pulses); with controllers W7752, W7762, W7763, and XL12 (in the case of SW versions listed in Table 2 or higher, select ). LED occupancy mode from controller, European signaling (500 ms pulses); with controllers W7752, W7762, W7763, and XL12 Same as Excel 500 signaling from controller (10 V, 8 V, 6 V) P5 Pin 4 (Bypass/Fan) grounding Pin 4 not shorted to GND if override is pressed (UV-controller, W7753) * Pin 4 shorted to GND if override is pressed P6 Device type This item configures different devices. IMPORTANT: Keep the setting P6:1 and do not change to other configurations. 4
5 P7 Temperature offset * Temperature offset; values of 0 through 99 are valid. 50 = no change (default), 49 = -0.1 C, 51 = +0.1 C, etc. This offset varies the LCD display value, only. In order for this offset to have the proper effect, it must be set in the controller, too. P8 Remote reset of temperature setpoint overrides and fan speed overrides * disable remote reset of temperature setpoint override and disable remote reset of fan speed override. enable remote reset of temperature setpoint override and disable remote reset of fan speed override (takes effect ONLY if or has been selected AND or has been selected) disable remote reset of temperature setpoint override and enable remote reset of fan speed override (takes effect ONLY if or has been selected) enable remote reset of temperature setpoint override and enable remote reset of fan speed override (takes effect ONLY if or has been selected AND or has been selected) IMPORTANT In addition to P8, parameters P1 and P4 must also be set accordingly for the wall module see above! Explanation: The goal of this action is to reset those overrides which a room user has enacted at the wall module. Thus, in, e.g., hotels and office buildings, a typical requirement is to remotely reset the wall module setpoint override to zero, and to remotely reset the wall module fan speed override to Auto. NOTE: If the wall module has been set to OFF by the room user, it cannot be reset to auto. In the case of Excel 50 controllers, this reset can be done by sending 6 Volt (= unoccupied ) to the LED input of the wall module: As long as 6V is being sent to the LED input the wall module will be in unoccupied the local setpoint and/or fan speed setting will be reset and disabled. As long as 10V is being sent to the LED input the wall module will be in occupied the local setpoint and/or fan speed setting will be enabled. In the case of Excel 10 controllers, this reset can be done by switching from occupied to unoccupied. This will send a specially coded Excel 10 signal to the LED input of the wall module. "Unoccupied" means: Effective Unoccupied (moon on continuously), or Override Unoccupied (moon flashing). "Occupied" means: Effective Occupied (sun on continuously), or Override Occupied (sun flashing). P9 Limit setpoint - Limit setpoint to ±0 5 C (if set to Celsius) or to ±0 9 F (if set to Fahrenheit). Default (if set to Celsius): Default (if set to Fahrenheit): Example (units set to Celsius): A setting of means that the setpoint offset is limited to -3 to +3 C. Example (units set to Fahrenheit): A setting of means that the setpoint offset is limited to -8 to +8 F. PA Limit for humidity low limit output value - Limit the output value to 10 20% relative humidity in steps of 5%. This affects the output voltage at pin 7, only, and has no effect upon values appearing in the display. = 10%, = 15%, = 20% (default), = not used. RESETTING TO FACTORY DEFAULTS Pressing the left, middle, and right button simultaneously while powering the wall module will reset the wall module settings to the factory defaults values. When the reset has been completed, the display will show. HOW TO CHECK THE SOFTWARE VERSION Press the left and right button for approx. 5 seconds: After a LCD display test, you will see the current SW version of the device. 5
6 ACCESSORIES T7460LONJACK The T7460-LONJACK is a small board and allows easy access to LONWORKS or BACnet via the correspondingly wired wall module (apply appropriate wiring guidelines for LONWORKS or BACnet networks, as the case may be). The T7460-LONJACK provides an additional 3.5 mm jack socket for a 3.5 mm jack plug. Order quantity: set with 5 pieces Mounting Remove the setpoint wheel and put in the LonJack as shown in the following: LonWorks connection terminals PC connection (3.5 mm jack plug) Fig 9. T7460LONJACK Fig 10. Mounting T7460-LONJACK T7560 BLINDS Same material and color as housing; for covering nonoperational buttons. Order quantity: set of 50 pieces. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: Automation and Control Solutions Honeywell GmbH Böblinger Strasse Schönaich, Germany Phone: (49) Fax: (49) Subject to change without notice. Printed in Germany
TR21, TR22, TR23, and TR24 Wall Modules
TR21, TR22, TR23, and TR24 Wall Modules FEATURES INSTALLATI INSTRUCTIS The TR21, TR22, TR23, and TR24 family of wall modules include: Models with setpoint adjustment. Models with humidity output. Models
Electronic Control Devices The European Product Catalogue 2007
FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically
Radiant Temperature Sensor TY7321
AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional
Electronic Control Devices The European Product Catalogue 2007
FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
T7079A,B Solid State Remote Temperature Controllers
T7079A,B Solid State Remote Temperature Controllers FEATURES PRODUCT DATA Switch selection of heat or cool mode. Temperature sensing up to 400 feet. Does not require field calibration. 0K NTC temperature
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
N20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL
N2xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL SPECIFICATIONS Supply voltage N224A / N3424A N223A / N3423A PRODUCT DATA 24 Vac 15%, 5/6 Hz 23 Vac 15%,
CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual
Instruction Manual OPC-LM1-IL Option Card for Encoder of Line Driver Output CAUTION Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual
HMI display Installation Guide
HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC
TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER
TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER (PWM Input, 1.2A or 2A Output, Metal Box or PCB) PCB Board - P/N: PWMC-PCB-2A, PWMC-PCB-1.2A Packaged Driver (metal box with 1.5 m (5 ft.) cable)
Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7
THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3
TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C
Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the
Contents. Document information
User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB
Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains
Drayton Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Invensys Controls Europe Technical Helpline: +44 (0) 845 130 7722 www.draytoncontrols.co.uk Installation
T775U Series 2000 Electronic Stand-Alone Controller
T775U Series 2000 Electronic Stand-Alone Controller INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of universal controls capable of remote
Drayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
Y7230A CO 2 Alarm System
Y7230A CO 2 Alarm System FOR CO 2 GAS DETECTION PRODUCT DATA FEATURES APPLICATION Y7230A CO 2 alarm system is used to detect gas leaking from CO 2 beverage dispensing systems and posts an alarm to occupants
INSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811
Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The
Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet NV24A--RE Communicative globe valve actuator for 2-way and 3-way globe valves Actuating force 1000 N Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Nominal stroke
LOXONE 12 Channel Amplifier
LOXONE 12 Channel Amplifier Item no.: 200110 Thank you for purchasing the Loxone Twelve Channel Amplifier. The versatility of the Amplifier makes it the perfect choice for almost every type of custom multi-room
MINI MCR-SL-R-UI(-SP)
Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts
WD-AMX Water Detection Controllers
Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation
JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410
The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a
VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES
VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES PRODUCT DATA Design VC Series zone valves consist of: 2-way or 3-way valve housing available with various connection ends Spindle and cartridge
RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions
Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED
AC 800M. EtherNet/IP DeviceNet Linking Device LD 800DN. Power and productivity for a better world TM SP1134
AC 800M EtherNet/IP DeviceNet Linking Device LD 800DN SP1134 Power and productivity for a better world TM AC 800M EtherNet/IP DeviceNet Linking Device LD 800DN NOTICE This document contains information
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
MechoNet TM Network Interface (MNI) Specification Submittal
MechoNet TM Network Interface (MNI) Specification Submittal Models MechoNet Network Interface: MNI RJ (RJ45 Motor Ports): Stock No.: IMNI 0001 TP AS (US version) Stock No.: IMNI 0004 TP AS (UK version)
Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011
Instruction Manual 2in1 LAN Tester & Multimeter Model: LA-1011 1 Contents Introduction... Features... Safety Precautions.. Meter Description... Electrical Specification... Operation.. AutoRanging Multimeter.
FX07 Field Controller
Product Bulletin FX07 Field Controller Issue Date March 25, 2008 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,
TruPower-Portable-500W. Solar Starter kit
TruPower-Portable-500W Solar Starter kit This Solar starter kit is an easy to use solar power supply system that is the complete solution for all your solar power needs. It is a solar generator that converts
EDI Distributor Control Interface Wiring and Setup Instructions
Universal I/O EDI Distributor Control Interface Wiring and Setup Instructions EDI UNIVERSAL I/O INTERFACE MODULE The only interface needed for EDI-V5 controls Network compatible with all older EDI controls
User Manual THR840DUK Digital Thermostat
User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical
Installation Instructions. Wireless Adapter/Repeater. Introduction. 30-3001-887 Rev C
/Repeater Installation Instructions 30-3001-887 Rev C Workstation Ethernet bcx Controller Repeater Repeater Introduction Schneider Electric has designed a device that allows Andover Continuum controllers
EXTERNAL DIMENSIONS AND PARTS
FX2N-4DA SPECIAL FUNCTION BLOCK USER S GUIDE JY992D65901A This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX2N-4DA special
How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)
transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital
User Guide. Model 380260 Insulation Tester / Megohmmeter
User Guide Model 380260 Insulation Tester / Megohmmeter Introduction Congratulations on your purchase of Extech s Insulation Tester/Megohmmeter. The Model 380260 provides three test ranges plus continuity
T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ
TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size
CQM1-SF200/CS1W-SF200
Safety Relay Unit ( I/O Unit Type) CQM1-SF200/CS1W-SF200 CSM_CQM1-SF200_CS1W-SF200_DS_E_2_1 A Safety Relay Unit That Functions as a I/O Unit. Less Installation Space and Wiring Required. Safety Relay Unit
USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat
Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage
Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C
Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C DESCRIPTION FEATURES PRODUCT DATA Very low operating trip points LED status indication Integral DIN rail mounting
Multi Media Cable Tester TM-901N/TM-902/TM-903
Multi Media Cable Tester TM-901N/TM-902/TM-903 User Manual HB2TM9020010 TENMARS ELECTRONICS CO., LTD Table of Contents 1 Introduction... 1 2 Safety Precaution... 1 3 The verifier does the following:...
GSM HOME SECURITY SYSTEM
Cell /Mobile phone home security system GSM HOME SECURITY SYSTEM Model : GSM-120 TABLE OF CONTENTS 1. FEATURES... 1 2. APPLICATION... 2 3. SPECIFICATIONS... 3 4. FRONT PANEL & LAYOUT DESCRIPTION...6 5.
Series LC6D/LC6C. To power supply PLC. LC6C dedicated teaching box P.971. Options P.973
Series LCD To power supply Electric Actuator Series LCC Stepper Motor Driver LCD Series LX Dedicated Stepper Motor Driver and Positioning Driver Series LCD/LCC PLC Positioning unit (Not incl. To be provided
Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types
Installation Guide VisionPRO TH8000 Series Touch-screen Programmable Thermostat This manual covers the following models TH8110U: For 1 Heat/1 Cool systems TH8320U: For up to 3 Heat/2 Cool systems TH8321U:
MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 852 Group: Controls Part Number: IM 852 Date: June 2007 Supercedes: New MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)
! WARNING. Before using product, read and understand instructions.
McDonnell & Miller Installation & Maintenance Instructions MM-600G) Series FS8-W General Purpose Liquid Flow Switch OPERATION This control is an independently mounted water flow sensing device that makes
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Schneider Automation Modbus Plus Network Installing Clustered Node Devices 31000939 00 Version 2.0
Schneider Automation Modbus Plus Network Installing Clustered Node Devices 3000939 00 Version.0 Modbus Plus devices must be installed as specified in a network layout plan, showing each device s mounting
SLIM LINE FUME HOOD MONITOR
SLIM LINE FUME HOOD MONITOR Phoenix Controls FHM420 Fume Hood Monitor is sized to fit any fume hood and includes icons for simple and universal operation. The FHM420 slim line monitor works in conjunction
DLP-PU/E Instruction Manual
Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.
CompactLogix Power Supplies Specifications
Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types
Installation Guide LR-HWLV-HVAC TouchPRO Wireless Touchscreen Thermostat System Types Gas, oil, or electric heat with air conditioning Warm air, hot water, high efficiency furnaces, heat pumps, steam,
MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
LIEBERT VNSA Installation Sheet
LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
ADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
CAUTION OPC-LM1-ID. Option Card for Frequency Divider. Fuji Electric FA Components & Systems Co., Ltd. Instruction Manual
Instruction Manual Option Card for Frequency Divider Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual and understand the description
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
No. : EX##-OMF0004 OPERATION MANUAL. SI unit EX12#-SMB1
No. : EX##-OMF0004 OPERATION MANUAL EX12#-SMB1 Contents 1. Safety instructions ------------------------------------------------------ P3 2. Notes ------------------------------------------------------
Applied Electronics. Commercial Dimming System UPDATE NOTICE
REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with
Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate
1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration
Install Guide CT101. Caution. Caution
Install Guide CT101 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the
Inwall Room Temperature Unit
Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall
RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems
3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273
SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings
Smart Frame Wiring Diagrams and Dimensional Drawings Smart Frame Size 60 Vac:.5-7.5 HP 08/0 Vac: 0.75- HP SPECIFICATION DATA CONTENTS Smart Frame Wiring Diagrams... Frame, Fused Disconnect Wiring Diagrams...
Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868
Instruction Sheet 10-2004 Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868 PowerCommand is a registered trademark of Cummins Inc. InPower
INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
USER GUIDE. Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator. DM Engineering. Version 1.
USER GUIDE Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator Version 1.3 DM Engineering 2174 Chandler St. Camarillo, CA 91345-4611 805-987-7881 800-249-0487
SMART SENSOR COLLECTION
TEMPERATURE SENSOR This sensor measures temperature in degrees Celsius or Fahrenheit. It works with all SensorHawk base units (SensorHawk-2, SensorHawk-8 and SensorHawk8/20) as well as the SecurityHawk-8
Installation Instructions
TP-PRH-A, TP-NRH-A Performance Series Edge Thermidistat Control Installation Instructions Programmable Control A07049 A07048 Non Programmable Control Designed and Assembled in the USA. NOTE: Read the entire
CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB.
7I29 MANUAL Rev 1.5 CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB. THE 7I29 IS INTENDED FOR USE BY OEMS THAT WILL INTEGRATE IT INTO A SYSTEM WITH INTERLOCKS AND
SELECTION GUIDE INPUT CHARACTERISTICS. Voltage set point accuracy. Overall voltage error. Temperature coefficient of output voltage (slope)
OBSOLETE NMPD0 Series SELECTION GUIDE Order Code Nominal Input Voltage Output Voltage Efficiency (Min.) Power (Max.) V V % W NMPD003C 3. 9.50 NMPD005C 5. 9.5 NMPD0C. 0 0.00 NMPD05C 5. 9 0.00 FEATURES RoHS
162 CB CABLE TRACER. Filter Probe & Tone Generator INSTRUCTION MANUAL
162 CB CABLE TRACER Filter Probe & Tone Generator INSTRUCTION MANUAL INDEX PAGE 1. INTRODUCTION... 1 2. FILTER PROBE... 1-3 3. TONE GENERATOR... 3-6 4. SPECIFICATION... 7-8 5. MAINTENANCE... 8 1. INTRODUCTION
TS93 EMR T/PT/TDE. Surface applied door closer
TS EMR T/PT/TDE Surface applied door closer Installation instructions: Pull side track mount door closer with smoke detector (EMR T) Push side track mount door closer with smoke detector (EMR PT) Double
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual This 30Amp charge controller is designed to protect your 12Volt Lead-acid or Gel-cell battery from being overcharge by solar
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW
Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer
Digital inductive conductivity transmitter
Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections
User Manual Weather station V 0.2
& User Manual Weather station V 0.2 Last update: July 2012 All software-related descriptions refer to the software V1279. We recommend to update older versions of the system. Small deviations in the description
BLACK BOX. T1/E1 Link Extenders OCTOBER 2007 MT195A-T1 MT196A-E1
BLACK BOX NETWORK SERVICES OCTOBER 2007 MT195A-T1 MT196A-E1 T1/E1 Link Extenders Important This is a Class A device and is intended for use in a light industrial environment. It is not intended nor approved
Install Guide 3M-50. Caution. Caution
PG 1 Install Guide 3M-50 aution Your thermostat is a precise instrument, handle it with care. Turn off electricity to the HVA system before installing or servicing thermostat or any part of the system.
evohome Wireless Radiator Zoning Kit Installation & User Guide
evohome Wireless Radiator Zoning Kit Installation & User Guide Getting the most from your evohome system Installation & User Guide 1 Getting the most from your evohome system Thanks for choosing an evohome
Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!
Documentation Brake module AX5021 Please read this document carefully before installing and commissioning the brake module! Version : 1.2 : 2012.03.05 Date Article-no. : TDmlAX-5021-0000-0200 Page 2/8
Digital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.
Install Guide CT100 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the
AUTODIALLER / QUICKDIALLER - SA132
AUTODIALLER / QUICKDIALLER - SA132 INSTRUCTION LEAFLET ENGLISH www.thermomax-group.com CONTENTS 1 SETUP AT A GLANCE... 2 2 FOREWORD....... 3 3 INSTALLATION...... 4 4 KEYPAD AND INDICATORS...... 5 SETTING
Physical Specifications (Custom design available.)
Helmholtz Coils A useful laboratory technique for getting a fairly uniform magnetic field, is to use a pair of circular coils on a common axis with equal currents flowing in the same sense. For a given
UCC 1 USB-CAN CONVERTER
Owner s Manual UCC 1 USB-CAN CONVERTER Contents 1. Description... 17 2. Controls and Connections... 18 3. Installation... 19 3.1 Unpacking... 19 3.2 Rack-Mounting... 19 4. Initial Operation... 20 4.1 PC