1 KNX Lighting Control System Part 1 - Specification Lighting control system A. The following specification details the minimum standards for performance of components, material and operation of lighting control and dimming system proposed for this project. B. The contractor shall supply and install the lighting control system suitable to project requirement as indicated in the specification as well as in drawings. C. The manufacture shall have local support available through distributor/ system integrators and local office presence in the country to support their supplier in the local market. D. It shall be the contractor s responsibility to ensure that the equipment installed meets the specification requirements. Equipment not meeting this performance specification will not be accepted. PART 2 - PRODUCTS 2.1 GENERAL A. The Programmable Lighting Control System shall be designed & developed in accordance with the European Installation Bus technology (KNX open protocol system) and shall conform to EN CENELEC standard to cover lighting control (on/off) based on applications such as time, daylight, manual switches, etc. B. A two-wire bus cable shall link all sensors (push buttons, brightness sensors, motion sensors, timers, etc.) and actuators (on/off controllers, dimming controllers, etc.) to each other. The bus cable shall be a twisted pair, screened & shielded with solid conductors and shall be capable of handling information exchange and supplying power to the bus devices. Separate power supply to any of the sensors and actuators shall not be acceptable. The bus cable shall be laid in the building in the form of a linear, star or tree structure similar to the power mains. Systems requiring fixed wiring configurations shall not be acceptable. All the sensors & actuator devices shall be coupled to the bus via easy to install 2-wire bus connectors capable of accepting upto 4 bus connections. Systems requiring crimping, lugging or RJ45 bus connections using CAT 5 UTP or Cat 6 cable shall not be acceptable. 1 KNX Lighting control System Gulf specification - March 2015

2 C. The system shall be completely de-centralized and programmable. The programming shall be implemented via a PC or notebook computer located anywhere in the system and having access level passwords. Programming via local system switches or with no password security shall not be acceptable. Any device in the system shall be accessed for programming from the PC location without having to manipulate the device locally. D. Each device in the system shall be addressable via a software programmable physical address. Any device in the system shall communicate with any other device via software programmable group addresses (telegrams). Each individual device will respond to only those group addresses for which they are programmed to do so. There shall be an EEPROM storing the physical address, group addresses & other software parameters for every device, thus making it intelligent. No centralized processors or centralized memory storage devices shall be permitted. E. It shall be possible to program any of the devices on-line at the working site without affecting any of the system devices or the system operation as well as off-line prior to dispatch of the material to site. F. The entire system shall consist of bus lines each consisting of up to 64 devices. Two consecutive lines shall be connected to each other via line couplers that act as network filters and also provide communication between devices in different lines. In the event of failure of a device in one line, only the control functions controlled by that device shall be affected and all other devices shall continue to operate as normal. G. The power supply module feeding power to the network shall consist of a built in back-up power to compensate short voltage interruptions of upto 200 ms. This back-up power shall enable the system to put all actuators in a fail-safe position (either on or off or as it is) in the event of power failure. H. Each of the devices shall have a built-in push button along with a LED. The LED shall lit in the event the push button is pressed and if there is power to the device, thus depicting that the device is communicating in the system. I. All devices in the system should conform to CE standards and should be manufactured in accordance with the EMC guidelines and the low voltage guidelines. J. System shall be interfaced with the BMS via OPC Server or by BACNET open protocol. The BacNet Interface module shall be from the same manufacturer which shall be compatible with IP network. K. The Multi-protocol module is capable of bridging various protocols such as BacNet, Modbus, IP with KNX system and shall be able to support web based 2 KNX Lighting control System Gulf specification - March 2015

3 application to support smart phones and tablets to view / control the KNX devices in the network. The module shall be from same manufacturer. Third party manufacturers are not acceptable. L. Dimming control of fluorescent lighting shall be via the use of dimmable electronic ballasts. The lighting control system shall accept and compatible with 0-10V analogy control and Digital Addressable Lighting Interface (DALI) ballasts. M. Manual ON/OFF controlling of motion detectors shall be provided for the Open/Public area lighting. The maximum spacing between the motion detectors shall be no more than 5 meters. Upon field detection by body motion, the lighting shall be turned-on automatically for duration of 15 to 30 minutes software adjustable delay-off timer from the central lighting control system. N. The motion sensor shall be flush mounted into a ceiling and have a 360-degree field of view. Coverage shall be a minimum of 7 metres diameter circular at the working plane with a ceiling height of 2.5 metres. The motion sensors shall be with software programmable time delay function and adjustable sensitivity on the unit. O. The wall mounted button plate shall support 2-Button, 4-Button and 8 Button with LED indicator, which is used to indicate the operation status of each gang. The wall mounted button plate shall have the ability to be controlled remotely via infrared hand held remote control units. P. The lighting control system shall be provision for its own light control PC with graphical user interface to remote monitoring, ON/OFF control and dimming. The system shall utilize web based graphical user interface system so as to ensure that the programming is not stored in the PC, in case of PC failure still there will not be any single point of failure in the system. The system shall be possible to monitor segment wise, floor wise or area wise from the smart tablet to control and monitor which will ease the operator not to fully depending up on the central PC. 2.2 LIGHTING CONTROL CONCEPT A. All the Relay module, dimmer modules, switches, sensors and other controlling elements shall be addressable and programmable. Dry output switches and central processer units are not accepted. B. Output relays for the project (for total number required for the project refer DB schedule of points / Lighting control schematic) shall control manually via the central capacitive touch technology Display / Timer controller located in the security room, the touch screen size should be on a acceptable size such as 7, 10 or 15 so that the lettering and buttons will 3 KNX Lighting control System Gulf specification - March 2015

4 be on legible size. The Display & control device shall be a flush mounted device or surface mounted according to project requirement. All timer functions shall be controlled from this touch screen from facilities management room or from location decided at the time of construction as per consultant s engineer s approval. The touch screen shall also be able to connect directly via IP network addition to KNX in case of remote monitoring. The touch screen shall be able to work along with central server in case of multiple touch screens in the project, at least 10 touch screens shall be connected to one server where they will work in client server basis. The touch screen shall have ability to connect with IP cameras to monitor the building IP cameras; the system shall have ability to show at least 8 streaming tiles to monitor simultaneously. C. It shall also be possible to override each of these control relays manually from the Lighting Control Panel located in the electrical room. D. These control modules will be located in Lighting Control Panel located (LCP) next to the distribution boards in the electrical room on each of the floors or according to project requirement. E. There shall be multi channel dimmer modules (For number of channels required / DCP refer DB schedule of points / Lighting control schematic) located in the Dimmer control panels (DCP) on various floors to control the dimming of different types of light fittings as shown in layouts and DB schedule of points in that relevant room. F. In addition to the local dimming, the dimming system shall be interfaced with the A/V system via the KNX interface module to accept volt free contacts from the A/V system or via RS232 serial port. G. The lighting control system should operate at the extra low voltage of 24Vdc, 9.6kbit/s transmission. The bus cable is laid as a line, star or tree structure in the building. H. The programming of the system is carried out with the Engineering Tools Software (ETS) parameterization software via an RS232 or USB interface. They can be used in any location within the bus system. A programming of the KNX devices by the Ethernet shall also be possible via IP gateway. Area Control Concept: A. The Lighting Control system shall be programmed in such a way that unnecessary usage of power is minimized. Lighting control in different areas shall be as follows; 4 KNX Lighting control System Gulf specification - March 2015

5 B. Ground Floor & Entrance Lighting: lights should be controlled from Central Touch screen panel based on timer control.daylight harvesting should also be implemented in areas near to the peripheral of the building towards glassed exteriors. Unnecessary lights should be switched OFF during non activity hours to conserve energy, where ever indicated by the consultant /Client. C. Common Area / Public Area lighting: All lights in the lift lobbies, corridors, should be controlled using a movement/presence detector, Time schedule and central control. Lighting Circuits should be designed to achieve a minimum light level (say 35%) during non activity period. Staircases can be shall be controlled with Timer push button. During an emergency situation the lights should automatically be switched ON until the situation is restored. D. Covered Car park: All the covered car park should have lights controlled in such a way that during no activity the lights will be stay ON 30% / 50%. 100% lights will be ON in particular zone when any movement is detected within that zone using weather proof Movement/presence detector. All ramp lights should be kept ON always. Driveway lights can be designed to have split circuits to achieve 50% on no activity and 100% percent on activity period. Manual override switches should also be provided. During emergency situation all the lights should be switched ON until the situation is restored. E. Staircase lights: All staircase lights shall be controlled from local intelligent push switch timer push switch STANDARDS & QUALITY ASSURANCE A. All devices shall be CE listed specifically for the required loads (i.e., incandescent, fluorescent and magnetic low voltage transformer, etc.). Manufacturer shall provide valid supporting document upon request. B. Energy efficiency in Building control system EN C. Safety clearance must comply with IEC D. Installation shall comply in accordance with TH35 & EN60715, IEC/EN LIGHTING CONTROL MODULES i. The relay unit shall allow control of 2/4/8/12 independent loads, equipped with a voltage free, magnetically latched relay per channel or equivalent solid state electronic relay according to the project requirement. No derating shall be acceptable for inductive lighting loads. The load rating shall be of 16A per channel or 10A per channel as per project requirement, each relay operation shall be indicated on channel LED indicator or via the override knob. Local ON/OFF toggle knob shall allow individual channels 5 KNX Lighting control System Gulf specification - March 2015

6 to be manually overridden at each unit. The relays shall have interlocking facility feature for specific operation, and this shall be possible via software from central PC. The individual relays shall be DIN TH35 rail mounted within the LCP enclosure according to EN ii. Nominal voltage: AC 230 V, Hz and each contact shall have Nominal current rating of 16 A, with cosϕ = 0,6, with Capacitive load: AC 230 V, 16 A, max. 200 µf, and for 10A rated load, the nominal current shall be 10A in each channel with cosϕ = 1 & 0.6 and for capacitive load of AC230V, it shall with stand 10A with max of 105 µf. Peak inrush current (150µs) 600A, Peak inrush current (230µs) 480A, Peak inrush current (600µs) 300A iii. The module width shall have 4 modules width which is approx 72 mm. iv. In the event of power failure or bus wiring failure or control module failure, each of the relays shall attain a pre-programmed fail-safe position ( Switch On, Switch Off or Remain As it is ). v. The control modules shall be capable of been programmed with different applications to suit site requirements for e.g. staircase lighting function which switches Off the relays after a preprogrammed time from the time it has switched On. The application for which a relay has been programmed shall apply irrespective of the signal from which it is controlled. vi. Each of the relays shall be capable of being programmed with its own On and Off delays that shall be applicable irrespective of the signal from which the relays are controlled. vii. Each of the control module shall have its own individual address and shall be capable of being programmed from the central PC for the purpose of changing parameters without the need to access the module locally. viii. Central PC will be made available during testing and commissioning of the system and will then be taken back after successful commissioning DIMMING CONTROL MODULES The dimming module shall be capable of switching and dimming three independent groups (3 circuits) of luminaires with electronic ballasts (0-10 V or 1-10V control input). The control is carried out separately for all the outputs. Manual operation shall be possible to have in each 6 KNX Lighting control System Gulf specification - March 2015

7 channel, the switching state of the contacts shall display as status. The switch contact for switching the electronic ballasts/transformers shall be with Nominal voltage of AC 230 V, Hz with the current rating of 16 A with cosϕ = 0.6, 0-10 V interface current rating shall not exceed ma with the voltage range of DC 0-10 V. The service life of the device shall have greater than 50,000 switching cycles at nominal load, the load capacity of max 100mA (approx 50 electronic ballast). Capacitive load capacity of 3600W with 200micro Farad. Device width: 4 HP = ca. 72 mm Universal Dimmer Actuator A. The dimmer unit shall be capable of controlling 1, 2 and 4 independent loads, and the load rating shall be of 250W, 300W, 500W and 1000W per channel capacity, the load wattages shall be coordinated with MEP contractor. The dimmer unit shall have the facility to program a minimum level setting and power-up delay time via the lighting control software it shall also have local ON/OFF toggle buttons shall allow individual channels to be manually overridden at each unit. The unit readiness for operation shall be indicated by a green LED after the application has been loaded. B. Electrical isolation between the Extra Low (Bus) Voltage and the Low (mains) voltage side of the unit shall be provided with the use of optical isolators. C. Electricity input for each channel could be fed from different phases according to the requirement of project. D. The individual dimmers shall be DIN rail mounted within the unit enclosure. DALI Gateway A. The KNX DALI gateway shall connect the cross-function KNX bus with the DALI bus designed exclusively for lighting control. Luminaries with DALI electronic ballasts shall be integrated into a KNX system using this unit. The gateway shall serve as the DALI master and power supply for the connected electronic ballasts. Up to a maximum of 64 electronic ballasts according to IEC in a total of 16 groups can be switched, dimmed or set to a defined value. 7 KNX Lighting control System Gulf specification - March 2015

8 B. Brightness values or error messages in the DALI devices can be sent to the KNX and visualized on display units. The DALI is commissioned and configured with the integrated display and operator buttons. C. DALI gateway shall have an option to have IP port for programming. D. Each channel shall have ability to handle 64 devices individually. E. Installation shall comply to TH 35 according to EN 60715, with the bus connection made via a bus connecting terminal. F. The device should have feature of IP address allocation via DHCP service or fixed IP address and should have DC V, short circuit Proof (base isolation, no SELV) Movement / occupancy Sensor A. The presence detection / Movement detection sensor shall directly work on KNX bus as an integrated system, which shall send commands in KNX bus to switch on or switch off the lights based on the occupancy. Sensors with dry contract output is not acceptable, each sensor shall have an EEPROM memory to store its address and programming information. B. If sufficient day light and natural light brightness is available inside the room, the sensor shall have an intelligence to keep the lights in off condition though it detects the movement / presence in the room. C. Ceiling mounting sensor in a size 60 mounting box, with optimal installation at 2.5 m. Can also be mounted to ceilings using the surface mounting housing. D. It shall be possible to program the sensor from ETS software. Range: a Diameter of max. 7 m (at a mounting height of 2.50 m) Number of levels: 6 Number of zones: 136 with 544 switching segments Number of movement sensors: 4 Light sensor: internal light sensor infinitely adjustable from approx. 10 to 2000 Lux (ETS); external light sensor via KNX EC Directives: Low-voltage guideline 2006/95/EC and EMC guideline 2004/108/EC E. Incase of requirement for IR operation, the Sensor shall have an option to receive the IR codes. 8 KNX Lighting control System Gulf specification - March 2015

9 Energy Monitoring: A. The energy measurement unit shall be able to provide energy consumption, power, and current and provide the results via the KNX bus directly without any interface, the measured energy can easily be available in touch screen or in the central PC for the end customer to check. B. It shall also provide the active energy consumption (max 1.5%) per channel and total consumption with the accuracy of 10%. The device should have minimum of 3 channels and each channel should rate to measure 16A. The module should comply with TH35 DIN rain as per DIN EN C. The unit shall be integrated with status LED which shall indicate the overload, mains voltage absent and bus voltage etc., the unit shall be possible to program via ETS software. D. Operating voltage should be 230V 50/HZ +/- 10%, accuracy class of the unit shall comply to IEC The size shall not exceed 4 modules ( 90HX72WX65D mm) as it can be located in the DB/LCP according to the project requirement. Integrator Module/ Multi protocol gateway : A. The unit shall have following functionality to support the building lighting control system to integrate with BMS and Graphical user interface, the unit shall also work as embedded graphical user interface which enables to easily view the state of lighting control system in a building, B. It should support: KNX, Modbus, TCP/IP, BacNet, RS232, USB ( the connections should be rapid connection terminals, screw terminals are not acceptable). C. The unit shall work as a BACnet server for 500 points for TCP/IP bi-directional communication, the unit must be certified for BTL (BACnet Technical Laboratory) as a B-ASC (BACnet Application Specific Controler) D. The unit shall be integrating the following functions: E. Webserver / Internet gateway, Weekly and annual clock,knx IP router,logic module, Energy and technical dashboard. F. For high level integration and customization such as webservices or different communication protocols, the unit shall be flexible enough to program through LUA language. 9 KNX Lighting control System Gulf specification - March 2015

10 2.5 LIGHTING CONTROL PANELS (LCP s & DCPs) There shall be a dedicated Lighting Control Panel (LCP) / Dimmer Control Panel (DCP) as shown in the layouts. It shall house the system devices and the related control equipment depending on the no. of circuits being controlled. This is to ensure the power wiring between the DB s and the control modules inside these panels are kept to a minimum. The LCP / DCP shall be surface mounted with metal enclosures together with built-in DIN-rails for easy installation of the control equipment. 10 KNX Lighting control System Gulf specification - March 2015

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information. Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an

More information

Basics of Dimming. ISC Learning Centre

Basics of Dimming. ISC Learning Centre ISC Learning Centre July 2009 > Dimmers Contents What is a dimmer? Dimmers & customer benefits Dimmers at home Dimmers at the office Dimmers: technical choices Overview of the Schneider Electric offer

More information

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011 , 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.

More information

PCS0100en 02.2008. Persy Control Services B.V. Netherlands

PCS0100en 02.2008. Persy Control Services B.V. Netherlands P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for

More information

Product and functional description

Product and functional description Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected

More information

DALI DIM/CONVERTER CONTROL (DC NV) 1 10V (0-10 V) analog DALI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions

DALI DIM/CONVERTER CONTROL (DC NV) 1 10V (0-10 V) analog DALI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions DAI DIM/COVERTER COTRO (DC V) 1 10V (0-10 V) analog DAI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions Dim-and Switch Functions: The DAI Dim/Converter Control DC V is suitable

More information

Temperature & Humidity SMS Alert Controller

Temperature & Humidity SMS Alert Controller Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal

More information

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.2.1, 2CDG1101xxR0011

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.2.1, 2CDG1101xxR0011 Technical Data 2CDC505051D0205 ABB i-bus KNX Product description Switch Actuators SA/S x.16.2.1, 16 A are modular installation devices in ProM design for installation in the distribution board. They are

More information

WxGoos-1 Climate Monitor Installation Instructions Page 1. Connections. Setting an IP Address

WxGoos-1 Climate Monitor Installation Instructions Page 1. Connections. Setting an IP Address Instructions Page 1 Connections The WxGoos-1 is a self-contained web server and requires 6vdc of power at 300ma. A center-positive 2.1 mm plug is used. There are five ports: 1. 10/100 Ethernet RJ-45 receptacle

More information

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

IntesisBox KNX Modbus TCP master

IntesisBox KNX Modbus TCP master IntesisBox KNX TCP master Gateway for integration of TCP slave devices into KNX control systems. Integrate any TCP slave device into KNX. KNX TCP slave EIB Bus IntesisBox Ethernet slave LinkBoxEIB Configuration

More information

IntesisBox KNX - LON

IntesisBox KNX - LON IntesisBox KNX - Gateway for integration of devices into KNX systems. Integrate Air Conditioning from the main manufacturers (DAIKIN, Mitsubishi Electric, Mitsubishi Heavy Industries, Toshiba, Fujitsu,

More information

ABB i-bus KNX SA/S Switch Actuators Product Manual

ABB i-bus KNX SA/S Switch Actuators Product Manual ABB i-bus KNX SA/S Switch Actuators Product Manual Contents Contents Page 1 General... 5 1.1 Using the product manual...5 1.1.1 Structure of the product manual...6 1.1.2 Notes...6 1.2 Product and functional

More information

Climate Ready Control Systems Technical Specifications

Climate Ready Control Systems Technical Specifications Climate Ready Control Systems Technical Specifications Climate Ready Control Systems Climate Ready Control Systems consist collectively of motor controllers, other hardware and software packages that will

More information

IntesisBox KNX Modbus RTU master

IntesisBox KNX Modbus RTU master IntesisBox KNX RTU master Gateway for integration of RTU devices into KNX control systems. Integrate RTU devices (Chillers, Roof Tops, electricity meters, heating floors, heat pumps, PLCs ) into KNX control

More information

GLPHASE System. System Components GLPHASE - KP- KP- KP- KP- OS- DS- - - - - - SpaceBuild Specification Worksheet. Touch Screens

GLPHASE System. System Components GLPHASE - KP- KP- KP- KP- OS- DS- - - - - - SpaceBuild Specification Worksheet. Touch Screens SpaceBuild Specification Worksheet GLPHASE System The GLPHASE SpaceBuilder system is ideal for medium-sized spaces that require additional options such as expansion modules for more load types, touch screens,

More information

IntesisBox KNX Mitsubishi Heavy Industries AC

IntesisBox KNX Mitsubishi Heavy Industries AC IntesisBox KNX Mitsubishi Heavy Industries AC Gateway for integration of Mitsubishi Heavy Indsutries (MHI) Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB)

More information

HMI display Installation Guide

HMI display Installation Guide HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC

More information

contents Leading the way in intelligent automation INELS Wireless? Why Click Accessories Complete control

contents Leading the way in intelligent automation INELS Wireless? Why Click Accessories Complete control Wireless Control Systems Accessories Leading the way in intelligent automation contents Range Overview Typical Installations Transmitters Combined Modules Accessories Programming Switching & Dimmer Functions

More information

KNX Panasonic Air Conditioners

KNX Panasonic Air Conditioners IntesisBox KNX Panasonic Air Conditioners Gateway for Panasonic ECOi and PACi system integration into KNX networks Up to 30 Outdoor units Up to 64 Indoor units PA-AC-KNX-64/128 EIA485 U1U2 line U1U2 line

More information

IntesisBox Modbus Server Fidelio IP

IntesisBox Modbus Server Fidelio IP IntesisBox Server Fidelio IP Gateway for integration of Micros Fidelio Ho management system into (RTU and TCP) enabled control systems. Integrate your Micros Fidelio Ho management system into your master

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

SOLUTIONS FOR THE CONTROL OF THE WHOLE BUILDING

SOLUTIONS FOR THE CONTROL OF THE WHOLE BUILDING AUTOMATION SYSTEM Catalogue SOLUTIONS FOR THE CONTROL OF THE WHOLE BUILDING automation system Contents 4-11 Catalogue Control devices 4 Sensors 5 Modular controllers 6 False ceiling controllers and Automation

More information

40.3. Control Relays and Timers

40.3. Control Relays and Timers .3 Contents EASY500/700/800 Intelligent Relays........ EASY/MFD Expansion Modules............ MFD Intelligent Relays................... EASY/MFD Communication Modules....... EASY/MFD Power Supplies, Accessories

More information

basicdim DGC Compact control module

basicdim DGC Compact control module luxctrol lighting control sstem DGC Compact control module Product description Compact dimensions for luminaire installation For up to 0 DSI or LI ballasts ( per output channel) LI IN input LI/DSI output

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

Using installed Fieldbus Wiring to carry Ethernet Communications

Using installed Fieldbus Wiring to carry Ethernet Communications Using installed Fieldbus Wiring to carry Ethernet Communications Modbus Plus, Data Highway, GE Genius, Profibus, ControlNet, DeviceNet, InterbusS and many other RS232 or RS4422 cables Key Issues when upgrading

More information

Passion for KNX innovation

Passion for KNX innovation Passion for KNX innovation Touch-MyDesign 2 Touch-MyDesign is a KNX switch with capacitive buttons that satisfies the design requirements of any building thanks to its total customization: Everyone can

More information

ABB i-bus KNX Switch Actuators SA/S Product Information

ABB i-bus KNX Switch Actuators SA/S Product Information ABB i-bus KNX Switch Actuators SA/S Product Information ABB Stotz-Kontakt GmbH Your Partner with Know-How for Future-Oriented Electrical Installation Hugo Stotz, the company founder of ABB Stotz-Kontakt,

More information

ModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems.

ModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems. IntesisBox ModBus Server - KNX Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems. Integrate KNX based lighting control into your SCADA, BMS, PLC "talking" Modbus. Master

More information

Lighting Management solutions

Lighting Management solutions Lighting Management solutions Best practice guide for office buildings PUTTING A STOP TO ENERGY WASTE INTRODUCTION Table of contents 1 Lighting control Best Practice Guide for Office Buildings 2 Guide

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

EBDSPIR-DD, EBDSPIR-DD-IP

EBDSPIR-DD, EBDSPIR-DD-IP Product Guide EBDSPIR-DD, EBDSPIR-DD-IP Ceiling PIR presence detector DALI / DSI dimming Overview The EBDSPIR-DD PIR (passive infrared) presence detector provides automatic control of lighting loads with

More information

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2 Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male

More information

Installation and User Guide

Installation and User Guide Installation and User Guide 458-UNI8 8-Channel Universal Dimmer Module Introduction The 458/UNI8 is an 8-channel universal, digital transistor, dimmer module. Each channel s mode can be selected for either

More information

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001 Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.

More information

IDDERO HOME SERVER. Quick start guide. www.iddero.com 150302-02

IDDERO HOME SERVER. Quick start guide. www.iddero.com 150302-02 IDDERO HOME SERVER Quick start guide www.iddero.com 150302-02 TABLE OF CONTENTS 1 INTRODUCTION... 3 2 IDDERO CONFIGURATION SOFTWARE... 3 2.1 Installation and First Steps...3 3 IDDERO HOME SERVER CONFIGURATION...

More information

One Room One Cable Architectural Specification

One Room One Cable Architectural Specification One Room One Cable Architectural Specification ORC-1: One Room One Cable Kit: The ORC-1 One Room One Cable Kit shall consist of one (1) DXW-2 Wall Plate switcher, one (1) DXE-CAT-RX3-A HDBaseT Receiver

More information

Lighting Control Overview

Lighting Control Overview Overview Lighting Control Overview RTC Inbuilt real time clock Automatic daylight savings adjustment Atomic clock synchronisation (NTS). Triggers Inputs Schedules Network Conigurable inputs with dynamic

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically

More information

Operating instructions II / 2004

Operating instructions II / 2004 Operating instructions II / 2004 Light and presence sensor TOUCH DIM LS/PD LI OSRAM GmbH Costumer-Service-Center (CSC) Steinerne Furt 62 86167 Augsburg, Germany www.osram.com www.osram.de Tel. : (+49)

More information

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5 T5 TC-L PCA T5 BASIC lp Y II, 1 80 W BASIC T5 Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A1 BAT 1 Noise-free precise control via DSI signal,

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

ABB i-bus KNX Switch Actuators SA/S Product Information

ABB i-bus KNX Switch Actuators SA/S Product Information ABB i-bus KNX Switch Actuators SA/S Product Information ABB Stotz-Kontakt GmbH Your Partner with Know-How for Future-Oriented Electrical Installation Hugo Stotz, the company founder of ABB Stotz-Kontakt,

More information

DMX2PWM 9 Channel Dimmer Setup Manual

DMX2PWM 9 Channel Dimmer Setup Manual DMX2PWM 9 Channel Dimmer Setup Manual www.ecue.de DMX2PWM 9ch Dimmer - Setup Manual e:cue control GmbH An OSRAM Company Rev. 1.3_01/2010 DMX2PWM 9ch Dimmer - Setup Manual Table of Contents 1. Device Overview....................................4

More information

EQUIPMENT SPECIFICATIONS

EQUIPMENT SPECIFICATIONS EQUIPMENT SPECIFICATIONS IC-1600 Intelligent Controller The IC-1600 Intelligent Controller is a fully intelligent panel that has a complete database on board. It operates in conjunction with the Access

More information

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D 7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values

More information

Product Specifications Dialog System

Product Specifications Dialog System 1 1. PART 1 - General Product Specifications Dialog System 1.1 Overview Provide a complete low voltage lighting control system for the building as shown on the plans and specified herein. Lighting control

More information

Unica for KNX system 226

Unica for KNX system 226 Unica for KNX system 6 P117504 Greater flexibility and comfort, better energy efficiency with KNX More and more electronic appliances are needed for modern comfortable homes that contain everything from

More information

Setup guide. point to point wall plate extenders

Setup guide. point to point wall plate extenders SDS-1002/3 point to point wall plate extenders Setup guide For more information visit our website, or talk to one of our technical team tel: +44 (0) 1306 628264 www.smart-e.co.uk SDS-1002 & 1003 SETUP

More information

Inwall 4 Input / 4 Output Module

Inwall 4 Input / 4 Output Module Inwall 4 Input / 4 Output Module IO44C02KNX Product Handbook Product: Inwall 4 Input / 4 Output Module Order Code: IO44C02KNX 1/27 INDEX 1. General Introduction... 3 2. Technical data... 3 2.1 Wiring Diagram...

More information

ABB i-bus EIB / KNX DALI-Gateway DG/S 8.1

ABB i-bus EIB / KNX DALI-Gateway DG/S 8.1 Product manual ABB i-bus EIB / KNX DALI-Gateway DG/S 8.1 Intelligent Installation Systems This manual describes the function of the DALI-Gateway DG/S 8.1 with the application program Dim Slave Lightscenes

More information

Class 2 transformer (TBT) Low Tension Conform to EN 60742. A LED turns ON when the current exceeds 1 A at the 14V output connector

Class 2 transformer (TBT) Low Tension Conform to EN 60742. A LED turns ON when the current exceeds 1 A at the 14V output connector Technical notice TECHNICAL CHARACTERISTICS Power Class 2 transformer (TBT) Low Tension Conform to EN 60742 Rechargeable battery 16 Vac, 50-60Hz 50 Va min. 250 Va max 12 V, 7AH Protection A LED turns ON

More information

Niko Home Control. Installation Manual

Niko Home Control. Installation Manual Niko Home Control Installation Manual Niko Home Control: Table of contents Warnings regarding installation...2 Guarantee provisions...3 CE...4 Key of symbols...5 1. Installation preparations...6 2. Controller...8

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

EXTERNAL DIMENSIONS AND PARTS

EXTERNAL DIMENSIONS AND PARTS FX2N-4DA SPECIAL FUNCTION BLOCK USER S GUIDE JY992D65901A This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX2N-4DA special

More information

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation

More information

LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com

LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com Integrations LGAC-KNX V1.0 PROGRAMMING MANUAL Parque Tecnológico de Asturias, Parcela 50, 33428 Llanera Asturias - Spain Tel (+34) 985 118 859 Fax (+34) 984 283 560 ingeniumsl@ingeniumsl.com www.ingeniumsl.com

More information

ABB i-bus KNX DALI-Gateway DG/S 8.1

ABB i-bus KNX DALI-Gateway DG/S 8.1 Product manual ABB i-bus KNX DALI-Gateway DG/S 8.1 Intelligent Installation Systems This manual describes the function of the DALI-Gateway DG/S 8.1 with the application program Dim Slave Lightscenes Dynamic

More information

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling Electronics Ltd Presenting Power, Intelligence... with a sense of feeling By Appointment to Her Majesty The Queen Supplier of Fire Detection Equipment Kentec Electronics Ltd. Dartford Plug in slots K772

More information

Repeaters and Mimics Data Sheet

Repeaters and Mimics Data Sheet Repeaters and Mimics Data Sheet IDR series repeaters and mimics allow vital information from a Notifier fire system to be communicated to points around a building remote from the fire alarm control panel.

More information

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual 5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...

More information

GLPAC-DIMFLV Crestron Green Light Integrated Lighting System

GLPAC-DIMFLV Crestron Green Light Integrated Lighting System > > Up to 8 channels of 0-10 Volt dimming control > > Works in 100 to 277 VAC systems > > 16-Amp load rating per channel > > Built-in Control System with Cresnet and Ethernet port > > UL924 compliant emergency

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x.16.6.1, 2CDG 110 1xx R0011

ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x.16.6.1, 2CDG 110 1xx R0011 , 2CDG 110 1xx R0011 SA/S 8.16.6.1 2CDC 071 006 S0010 The 16/20 A Switch actuators are modular installation devices in Pro M Design for installation in the distribution board. The devices are especially

More information

PHASED OUT. Digital dimmable ballasts for fluorescent lamps EXCEL one4all series. PCA TCL EXCEL one4all, 18 80 W Compact and T5c fluorescent lamps

PHASED OUT. Digital dimmable ballasts for fluorescent lamps EXCEL one4all series. PCA TCL EXCEL one4all, 18 80 W Compact and T5c fluorescent lamps EXCEL oneall series Product description Noise-free precise control via DSI signal, switchdim, corridorfunction or DALI DALI-MEMORY Extended DALI commands CELMA energy class A1 1) Interfaces DALI DSI switchdim

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

KNX Powerline PL 110. KNX Association

KNX Powerline PL 110. KNX Association KNX Powerline PL 110 Table of Contents 1 Introduction...3 2 Standardisation...3 3 Transmission Process...4 3.1 Phase Coupling...5 3.2 Telegram Transmission...6 3.2.1 Training Sequence...6 3.2.2 Preamble

More information

Product Information Fire alarm panel 8000 C

Product Information Fire alarm panel 8000 C Product Information Fire alarm panel 8000 C Fire alarm panel 8000 C, basic configuration In common with all modern Esser panels, the 8000 C fire alarm panel is based on high-performance ringbus technology.

More information

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02 IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02 TABLE OF CONTENTS DESCRIPTION 2 MOUNTING INSTRUCTIONS 2 HOW TO CABLE THE IPX 2/3 POWER SUPPLY INSTALLATION 3 OPERATION 3 CARE

More information

Rack mounted telephone- and leased line modem for industrial applications

Rack mounted telephone- and leased line modem for industrial applications Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Technical Manual MDT Rain sensor

Technical Manual MDT Rain sensor 9/2012 Technical Manual MDT Rain sensor SCN-RS1R1.01 Technical Manual Rain sensor SCN RS1R1.01 1.1. Settings at the ETS Software Selection at the product database: Manufacturer: MDT Technologies Product

More information

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware Substation Automation Products Relion 670/650 series IEC and ANSI Hardware ABB Group 1MRG014097 October 2013 Relion 670/650 series hardware Contents Relion 670/650 series Relion Hardware Relion Common

More information

IntesisBox Modbus Server SAMSUNG Air Conditioners

IntesisBox Modbus Server SAMSUNG Air Conditioners IntesisBox Modbus Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung NASA compatible Air Conditioning Systems from any Modbus master device TCP or RTU (BMS, PLC, SCADA, HMI,

More information

Digidim 458/DIM8 8-Channel Dimmer Module. Installation and User Guide

Digidim 458/DIM8 8-Channel Dimmer Module. Installation and User Guide Digidim 458/DIM8 8-Channel Dimmer Module Installation and User Guide Introduction The 458/DIM8 is an 8-channel digital thyristor dimmer module, for leading-edge dimming of resistive and inductive loads.

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

3466 Building Energy Management Training Systems

3466 Building Energy Management Training Systems 3466 Building Energy Management Training Systems LabVolt Series Datasheet Festo Didactic en 120 V - 60 Hz 06/2015 Table of Contents General Description 3 Courseware 3 Topic Coverage 4 List of Available

More information

THE INPUT/OUTPUT SYSTEM. Key Points

THE INPUT/OUTPUT SYSTEM. Key Points M O D U L E T W O THE 2 INPUT/OUTPUT SYSTEM Key Points In the first module, you learned about the basic architecture and operation of the Allen-Bradley Micrologix 1000, including a brief introduction to

More information

ABB i-bus KNX Fan Coil Controller FC/S 1.1

ABB i-bus KNX Fan Coil Controller FC/S 1.1 Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Multi-Range Programmable DC Power Supplies 9115 Series

Multi-Range Programmable DC Power Supplies 9115 Series Data Sheet Multi-Range Programmable DC Power Supplies 1200 W / 3000 W Multi-Range DC Power Supplies Features & Benefits Any model can replace several supplies on your bench or in your rack. Unlike conventional

More information

EIB/KNX IP Interface with Power over Ethernet (PoE)

EIB/KNX IP Interface with Power over Ethernet (PoE) EIB/KNX IP Interface with Power over Ethernet (PoE) IP Interface between LAN and EIB/KNX bus (Quelle: EIBMARKT GmbH, Reference No.: N000401) Page 1 Application area The KNXnet/IP-Interface is used to connect

More information

Telephone- and leased line modem for industrial applications TD-36

Telephone- and leased line modem for industrial applications TD-36 Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased

More information

Voltage Regulator SPAU 341 C. Product Guide

Voltage Regulator SPAU 341 C. Product Guide Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6

Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6 Alarm over IP IRIS Touch Home Installation Manual Version 1.0 ENGLISH Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6 1. Introduction No more bulky batteries, just one sleek unit

More information

PS 29M DUAL CHANNEL BELTPACK IN METAL CASE

PS 29M DUAL CHANNEL BELTPACK IN METAL CASE PS 29M DUAL CHANNEL BELTPACK IN METAL CASE USER MANUAL October 2013 This product is designed and manufactured by: ASL Intercom BV Zonnebaan 42 3542 EG Utrecht The Netherlands Phone: +31 (0)30 2411901 Fax:

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

ComfortPoint Open Building Management System. For consultants and specifiers. The Simply Smart way to optimize building control and performance

ComfortPoint Open Building Management System. For consultants and specifiers. The Simply Smart way to optimize building control and performance ComfortPoint Open Building Management System For consultants and specifiers The Simply Smart way to optimize building control and performance ComfortPoint Open BMS. Simply Smart. The Honeywell ComfortPoint

More information

AXIS 262+ Network Video Recorder

AXIS 262+ Network Video Recorder 31433/EN/R4/0803 Complete Network Video Recording Solution Complete Network Video Recording Solution Picture this: A simple and reliable, plug-and-play video surveillance system for hotels, shops, banks,

More information

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.

More information

MINIMAT-EC-Servo Screwdriver Spindles

MINIMAT-EC-Servo Screwdriver Spindles Screwdriving technology Automation Air motors Air tools Screwdriver Spindles electric MINIMAT-EC-Servo Screwdriver Spindles Maximum Flexibility and process Control Straight Spindle Form - Torque range

More information

DALIX PROGRAMMING MANUAL. Gateway KNX-DALI V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com

DALIX PROGRAMMING MANUAL. Gateway KNX-DALI V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 tecnico@ingeniumsl.com Gateway KNX-DALI DALIX V1.0 PROGRAMMING MANUAL Parque Tecnológico de Asturias, Parcela 50, 33428 Llanera Asturias - Spain Tel (+34) 985 118 859 Fax (+34) 984 283 560 ingeniumsl@ingeniumsl.com www.ingeniumsl.com

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

Highly flexible the right KNX/DALI gateway for every requirement

Highly flexible the right KNX/DALI gateway for every requirement The worldwide standard for home and building control Highly flexible the right / gateway for every requirement Integrating lighting control into building control safely, efficiently and comfortably with

More information

Installation and operating instructions: Radio dimmer Type: DALI DM ADVANCED LI

Installation and operating instructions: Radio dimmer Type: DALI DM ADVANCED LI Installation and operating instructions: Radio dimmer Type: DALI DM ADVANCED LI OSRAM GmbH Hellabrunner Str. 1 D-81536 Munich Tel.: +49 (0) 89 6213 0 Fax: +49 (0) 89 6213 2020 Customer Service Center (KSC)

More information

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input

More information

IDDERO HCx-KNX TOUCH PANELS. Quick start guide. www.iddero.com 130125-02

IDDERO HCx-KNX TOUCH PANELS. Quick start guide. www.iddero.com 130125-02 IDDERO HCx-KNX TOUCH PANELS Quick start guide www.iddero.com 130125-02 TABLE OF CONTENTS 1 INTRODUCTION... 3 2 IDDERO CONFIGURATION SOFTWARE... 3 2.1 Installation and First Steps...3 3 TOUCH PANEL CONFIGURATION...

More information

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff

More information

Operating instructions IV / 2007

Operating instructions IV / 2007 General Operating instructions IV / 2007 Contents General Installation Application and function Application and function... 2 Safety information... 2 Design and dimensions... 3 Wiring diagram... 3 Installation

More information