INTRUSION DETECTION SYSTEM Section

Size: px
Start display at page:

Download "INTRUSION DETECTION SYSTEM Section 281600"

Transcription

1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 WORK INCLUDED A. Provide all labor, materials and equipment and services to perform operations required for the complete installation and related work as required in Contract Documents. 1.3 GENERAL DESCRIPTION A. Provide all equipment, accessories, programming, etc. for a complete electrically supervised intrusion detection system as described herein and as shown on the Contract Documents. Overall system engineering, layout and equipment installation shall be provided by an authorized representative of the equipment manufacturer. These specifications and associated drawings are intended to be used as a guideline. B. Equipment and accessories furnished under the terms of this Specification shall be the standard products of a single manufacturer where possible. The names of manufacturers and attendant model numbers are given to establish a standard of quality and performance. C. The main control panel shall be a microprocessor-based universal burglar, fire, hold-up supervisory control digital communicator. D. The systems shall be UL listed as follows: 1. UL 1635 Digital Burglar Alarm Communicator System. 2. NFPA 72 National Fire Alarm Code. 1.4 SYSTEM DESCRIPTION A. Provide a complete Intrusion Detection system with the performance criteria detailed in this specification. The system shall be inclusive of all necessary functions, monitoring, and control capability as detailed herein. System shall be monitored by Amherst Alarm (716) ; [email protected]. Project No

2 B. The system shall be capable of operation by 30 unique Personal Identification Number (PIN) codes with each code having one (1) of four user profiles Standard, Limited, Scheduled & Master. This allows for limitation of certain functions to authorized users. The operation of all keypads shall be limited to authorized users. The Control Communicator shall be capable of transmitting up to sixteen characters for the user s name to the central station receiver. C. This specification document describes the requirements for the programming, and configuration of an Intrusion Detection system. This system shall include, but not be limited to: 1. Control panel(s) 2. Integrated Network Communication 3. Integrated Wireless Receiver 4. Cellular Add-on Communication Modules (CDMA or HSPA+) 5. System cabinet 6. Power supplies 7. Digital Signaling Line Circuits (SLC) 8. Annunciator/keypad bus 9. Batteries 10. Wiring 11. Associated peripheral devices 12. Other relevant components and accessories required to furnish and install a complete and operational addressable reporting Intrusion Detection System. 1.5 SUBMITTALS A. Complete equipment list including quantities. Catalog descriptive literature for all equipment. Riser Wiring Diagram showing all devices, wire quantities and sizes. Typical Terminal Wiring Diagrams for each type of device. Terminal Wiring Diagram for the control panel. Calculations, including actual equipment loads used to derive battery backup amperehour rating. Submittals that fail to comply with the requirements described will be rejected. Project No

3 PART 2 - PRODUCTS 2.1 INTRUSION DETECTION CONTROLLER A. The intrusion detection controller system areas and zones shall be programmable, and the system shall store, log, display, and transmit specific custom designations for system areas, zones, and user names. B. The system shall support user interaction by way of a keypad, web browser, system software, key switch, or radio frequency wireless control, using integrated or auxiliary devices provided by the system manufacturer. C. The system shall support controller zone input connections, system keypads, system zone expansion modules, and wireless zone input modules, and must support zone input connection. The system shall offer a seamless integrated compatibility with hardwire and/ or wireless zone expansion equipment for at least 28 wireless zones and/ or a maximum of 30 hardwired zones. D. System relay outputs shall have the capability of being triggered as a result of a command from the user interface, changes in system status, changes in zone status, or by a programmable schedule. E. System relay output states shall be programmable for momentary, maintained, pulsed, or must follow the state of an associated system zone input. F. The system shall be completely programmable either locally from a keypad or remotely through a standard dial-up, and network connections by way of a LAN, WAN, and/or by way of the Internet. G. The control unit shall be completely programmable remotely using remote annunciators, and/ or using upload/ download software that communicates using dialup or IP Addressed data network. 2.2 CONTROL PANEL A. The Control panel shall be capable of expanding to a total of 30 user codes. B. Eight (8) independent door/keypad addresses, each with four zones. C. Event buffer of at least 100 events. D. A total of at least 4 programmable hardwired and 8 wireless output relays. Project No

4 E. Six (6) reporting areas. F. Built-in programmer. G. Virtual Keypad App for iphone, ipad, or Android Device for control of the security system. 2.3 KEYPADS A. The system shall support a maximum of eight (8) keypads with alphanumeric display. Each keypad shall be capable of arming and disarming any system area based on a pass code or Proximity key authorization. The keypad alphanumeric display shall provide complete prompt messages during all stages of operation and system programming and display all relevant operating and test data. B. Communication between the control panel and all keypads and zone expanders shall be multiplexed over a non-shielded multi-conductor cable, as recommended by the manufacturer. This cable shall also provide the power to all keypads, zone expanders, output expanders, and other power consuming detection devices. C. If at any time a keypad does not detect polling, the alphanumeric display shall indicate "SYSTEM TROUBLE". If at any time a keypad detects polling but not for its particular address, the alphanumeric display shall indicate "NON POLLED ADDR". The system shall display all system troubles at selected keypads with distinct alphanumeric messages. D. The keypad shall include self-test diagnostics enabling the installer to test all keypad functions: display test, key test, zone test, LED test, relay test, tone test, and address test. E. The keypad shall provide an easy-to-read English text display. The text shall exactly match the text seen in all software reports, keypad displays, and central station reports. F. The keypad user interface shall be a simple-to-use, menu-driven help system that is completely user friendly. G. The control panel shall support a keypad interface accessible on the World Wide Web in a browser window. The web-accessible keypad interface shall provide at least five (5) programmable hyperlinks for camera access or other use. Project No

5 2.4 INPUT/OUTPUT CAPACITY A. This system shall be capable of monitoring a maximum of 30 individual zones and controlling a maximum of 12 output relays. B. The control panel shall have, as an integral part of the assembly, four open collector outputs rated at 50mA each or 4 Form C relays, or 8 wireless relays. 2.5 COMPONENT ENCLOSURE A. Housings, power supply enclosures, terminal cabinets, control units, and other component housings, collectively referred to as enclosures shall be so formed and assembled as to be sturdy and rigid. If sheet steel is used in the fabrication of enclosures, it shall be not less than an 18-gauge door with a 20-gauge box frame. Where exposed pins, the hinges shall be of the tight pin type or the ends of hinge pins shall be tack welded to prevent ready removal. Doors having a latch edge length of less than 24 inches shall be provided with a single lock. 2.6 ELECTRONIC COMPONENTS A. All system electronic components shall be solid-state type, mounted on printed circuit boards. Light duty relays and similar switching devices shall be solid-state type or electromechanical. B. The panel shall have an over current notification LED that lights when devices connected to the Keypad Bus draw more current than the panel is rated for. When the over current LED lights, the Keypad bus shall shut down. 2.7 MAGNETIC DOOR CONTACTS A. Type 1 shall be a nominal 3/4 in. diameter concealed magnetic contact intended primarily for use in steel doors. Both switch and magnet shall be isolated from surrounding steel. Contacts shall be plated to prevent sticking and cold welding and to ensure reliability. Contacts shall be SPDT rated 3 watts maximum at 28 VDC. Make: Sentrol Model No. 1076CW or approved equivalent. B. Type 2 shall be overhead door type for mounting at top of door. Contacts shall be SPDT, and a range of gap distances shall be provided. Switch and magnet case shall be enclosed in an aluminum housing. Wiring shall be enclosed in armored cable. Make: Sentrol Model No. 2507A or approved equivalent. Project No

6 C. Type 3 shall be the same as Type 2 above, except installed on exterior hinged doors with heavy steel frames. Make: Sentrol Model No. 2507A or approved equivalent. 2.8 CONTROL UNIT A. Battery tests shall be automatically performed to test the integrity of the standby battery. The test shall disconnect the standby battery from the charging circuit and place a load on the battery. B. The control unit shall be capable of operating and supervising notification appliance devices as well as addressable initiating detection devices, integrated wireless receiver, integrated cellular communicator, and integrated network communications. C. Control unit must be Flash ROM updatable, and program must be held in non-volatile RAM. D. Control Panel shall have the ability for integrated built-in Network Communications, CDMA or HSPA+ Cellular Communication Add-on Modules, and two-way 900 MHz Spread Spectrum wireless communications to two-way wireless initiating devices. 2.9 POWER SUPPLIES A. Power supplies for the control unit shall operate from 120 VAC. Standby batteries shall be supplied to power the system in the event of a utility power failure. Batteries shall be sized to provide 100% capacity for eight hours. Standby batteries shall be sealed lead-acid. Power supplies shall be all Solid State. B. Controls shall be designed to maintain full battery charge when alternating current is available. Batteries shall be recharged to 85% capacity within 24 hours from battery use. The system shall be automatically transferred to battery power upon loss of alternating current power and return to alternating current power upon restoration. Intrusion alarms shall not be initiated during switch over; a signal shall be initiated upon failure of battery or alternating current power. C. Approved power supplies shall meet or exceed the following power supply model specifications: UL Listed, 12VDC 5 amp with transformer and enclosure. Project No

7 2.10 SOFTWARE A. The system shall interface with computer software with the capability to fully program the panel by connecting to the panel through: B. Standard phone line connection C. Ethernet network connection D. Network connection across the Internet E. The system shall interface with computer software capable of monitoring and logging all events. F. The system shall interface with computer software capable of exporting reports in the following file formats: Excel spreadsheet (.xls) Text (.txt) Rich Text (.rtf) Comma-separated (.csv) Windows Metafile (.wmf) HTML document (.htm) QuickReport (.qrp) G. The system shall interface with computer software capable of printing custom, filtered reports including: All Events, Opening/Closing Schedule Changes, Area Late to Close, User Code Changes, System Events, etc DESIGN MAKE A. DMP XLT Series Intrusion Detection Systems. PART 3 - EXECUTION 3.1 INSTALLATION - EQUIPMENT A. Installation shall be accomplished in a professional manner by qualified personnel regularly engaged in and experienced in this type of work. Installation shall conform to UL and FM requirements, and shall be in strict accordance with manufacturer's installation manuals. B. Install all wiring in accordance with manufacturer's recommendations. No ground loops can be tolerated. Ground only at one point as recommended by equipment manufacturer. Safes will be predrilled for wiring entrances. C. All wiring shall be stranded copper and installed as a separate and segregated system. No "tee-taps" are allowed. Project No

8 D. Minimum #18 AWG for initiating circuits, larger as recommended by equipment supplier. Minimum #14 AWG for signaling circuits. Utilize twisted shielded pair cables where recommended by equipment manufacturer. E. Arrange for a 120 volt, 20 ampere circuit to be brought to the Intrusion Detection Control Panel and other locations where required for proper system operation. Coordinate with Electrical Contractor. F. All 120 volt wiring shall be installed in separate conduit. G. Adjust the protection range or all sensing device so that an unprotected area from the floor level up to six inches above floor level is maintained. Also aim sensing devices to provide area coverage as required by Owner in the field. H. Detection and initiating equipment shall be listed by UL or FM. I. Intrusion Detection System equipment supplier shall provide complete wiring diagrams as part of the shop drawing submittal. An authorized representative of the manufacturer shall supervise the installation in order to insure a complete operating and trouble-free system. J. Coordinate with Owners monitoring service (Amherst Alarm) and provide communication cabling as per manufacturer and monitor service requirements. K. Provide 3 sets of all keys for all panels, stations, and devices. 3.2 PROGRAMMING A. Include in bid the cost to cover all system programming, including items particular to this project (such as custom zone descriptions, time delay settings, sensitivity settings, etc.) such that entire system is 100% complete and operating to the Owner's satisfaction. Coordinate all system programming with the Owner. Also, provide remote programming of the system a minimum of once during the guarantee period to allow for holiday schedule whereby all points will report to the receiver for a predetermined time period, and to provide changes requested by the Owner. Project No

9 3.3 TESTING A. Submit a written test report from an authorized representative of the equipment manufacturer that the system has been 100% tested and approved. Final test shall be witnessed by Owner, Engineer, Intrusion Detection Systems Contractor and performed by equipment supplier. Final test report must be received and acknowledged by the Owner prior to request for final payment. B. Provide a minimum of four hours of instruction to the Owner with regard to use and operation of system. C. Provide quarterly inspections during warranty period. 3.4 WARRANTY A. Entire system shall be warranted against equipment failure and installation defects for a period of one (1) year from the date of acknowledged Owner acceptance of final test. 3.5 RECORD DRAWINGS. A. Provide record drawings as specified in Section END OF SECTION Project No

INTEGRATED SECURITY SYSTEM PERFORMANCE SPECIFICATION FOR DMP MODEL XT SERIES CONTROL PANELS

INTEGRATED SECURITY SYSTEM PERFORMANCE SPECIFICATION FOR DMP MODEL XT SERIES CONTROL PANELS INTEGRATED SECURITY SYSTEM PERFORMANCE SPECIFICATION FOR DMP MODEL XT SERIES CONTROL PANELS 1.0 GENERAL 1.1 Manufacturer A. The manufacturer shall have at least thirty (30) years of experience in the role

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

Security Systems Intrusion Alarm

Security Systems Intrusion Alarm Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted

More information

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

The Pennsylvania State University ------------- Physical Security Office. Intrusion Alarm. Performance Specification

The Pennsylvania State University ------------- Physical Security Office. Intrusion Alarm. Performance Specification The Pennsylvania State University ------------- Physical Security Office Intrusion Alarm Performance Specification By PHYSICAL SECURITY OFFICE Group (Access Controls & Electronic Security Programs) and

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

Expansion Modules & Accessories

Expansion Modules & Accessories HONEYWELL SECURITY & CUSTOM ELECTRONICS Expansion Modules & Accessories Honeywell s wide range of expansion modules and accessories enable you to configure a system to meet any installation challenge and

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY SECTION 28 13 00 SECURITY AND ACCESS CONTROL SYSTEM

DIVISION 28 ELECTRONIC SAFETY AND SECURITY SECTION 28 13 00 SECURITY AND ACCESS CONTROL SYSTEM DIVISION 28 ELECTRONIC SAFETY AND SECURITY PART 1 GENERAL 1.01 DESCRIPTION A. Division 28 Contractor shall extend a complete Matrix Systems Access Control System as shown on the Drawings and as specified

More information

Invitation to Bid FIRE ALARM & DETECTION SYSTEM

Invitation to Bid FIRE ALARM & DETECTION SYSTEM Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066

More information

EQUIPMENT SPECIFICATIONS

EQUIPMENT SPECIFICATIONS EQUIPMENT SPECIFICATIONS IC-1600 Intelligent Controller The IC-1600 Intelligent Controller is a fully intelligent panel that has a complete database on board. It operates in conjunction with the Access

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS

DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS 1. Description and Phone Number Dialing: The dialer shall be a solid state component capable of dialing up to 16 telephone numbers, each up to 60 digits

More information

Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM

Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM Section TELEPHONE AUTOMATIC DIALER SYSTEM PART 1 GENERAL 1.01 SYSTEM DESCRIPTION A. Design Requirements: 1. Electronic monitoring system shall interface plant alarms to public telephone system or cellular

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

C. Conform to requirements of Americans with Disabilities Act (ADA).

C. Conform to requirements of Americans with Disabilities Act (ADA). SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National

More information

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT

More information

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit. Features. Description

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit. Features. Description INTELLIGENT FIRE ALARM CONTROL UNITS MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit Description Secutron s MMX-2017-12NDS Network Fire Alarm Control Unit offers modular components to meet a

More information

Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS

Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Fire alarm and smoke detection systems. 1.2 REFERENCES 1.3 NFPA 72 1.4 NFPA 101 1.5 REGULATORY REQUIREMENTS

More information

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1

More information

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's

More information

O C M III. Open Channel Flow Monitor

O C M III. Open Channel Flow Monitor O C M III Open Channel Flow Monitor Part 1. General 1.1 Scope A. This section describes the requirements for an ultrasonic flow transmitter with sensor and temperature compensation probe. B. Under this

More information

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-28 31 75.00 10 (November 2008) ----------------------------------- Preparing Activity: USACE Superseding UFGS-28 31 75.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

FIRE ALARM SYSTEM Section 16750 Page 1

FIRE ALARM SYSTEM Section 16750 Page 1 FIRE ALARM SYSTEM Section 16750 Page 1 PART 1 - GENERAL 1.1 REQUIREMENTS A. Provide a complete operational, stand-alone local protective signaling system in each defined building as indicated on the contract

More information

Talk-A-Phone Co. Model WEBS-MT/R OP5 Emergency Phone Tower Mount Architectural & Engineering Specification rev. 10/28/2011

Talk-A-Phone Co. Model WEBS-MT/R OP5 Emergency Phone Tower Mount Architectural & Engineering Specification rev. 10/28/2011 Talk-A-Phone Co. Model WEBS-MT/R OP5 Emergency Phone Tower Mount Architectural & Engineering Specification rev. 10/28/2011 1 General Description 2 Construction 1.1 The unit shall be a highly vandal-resistant

More information

Class 2 transformer (TBT) Low Tension Conform to EN 60742. A LED turns ON when the current exceeds 1 A at the 14V output connector

Class 2 transformer (TBT) Low Tension Conform to EN 60742. A LED turns ON when the current exceeds 1 A at the 14V output connector Technical notice TECHNICAL CHARACTERISTICS Power Class 2 transformer (TBT) Low Tension Conform to EN 60742 Rechargeable battery 16 Vac, 50-60Hz 50 Va min. 250 Va max 12 V, 7AH Protection A LED turns ON

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,

More information

ARCHITECT AND ENGINEER SPECIFICATION SECTION 13850 DETECTION AND ALARM SECURITY ACCESS AND SURVEILLANCE. DSC MAXSYS PC4020 V3.

ARCHITECT AND ENGINEER SPECIFICATION SECTION 13850 DETECTION AND ALARM SECURITY ACCESS AND SURVEILLANCE. DSC MAXSYS PC4020 V3. ARCHITECT AND ENGINEER SPECIFICATION SECTION 13850 DETECTION AND ALARM SECURITY ACCESS AND SURVEILLANCE DSC MAXSYS PC4020 V3.5 Rev0x2 Digital Security Controls 3301 Langstaff Rd., Concord, ON Canada L4K

More information

Using your LED Plus keypad

Using your LED Plus keypad Using your LED Plus keypad System 238 System 2316 System 238i System 2316i Part Number 5-051-372-00 Rev B Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced

More information

Life Alarm Fire Alarm Controls

Life Alarm Fire Alarm Controls FIRE SUPERVISORY SUPV SILENCED SILENCE AC POWER RESET UL, ULC Listed FM Approved MEA Approved* Life Alarm Fire Alarm Controls Fire Alarm Controls 4005 Series Fire Alarm Control Panels Eight through Thirty-Six

More information

Temperature & Humidity SMS Alert Controller

Temperature & Humidity SMS Alert Controller Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal

More information

GSM Alarm System User Manual

GSM Alarm System User Manual GSM Alarm System User Manual For a better understanding of this product, please read this user manual thoroughly before using it. Quick Guider After getting this alarm system, you need to do the following

More information

Utility Distribution Systems

Utility Distribution Systems Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

38. ACCESS CONTROL AND ELECTRONIC SECURITY SYSTEM

38. ACCESS CONTROL AND ELECTRONIC SECURITY SYSTEM 38. ACCESS CONTROL AND ELECTRONIC SECURITY SYSTEM 38.1 GENERAL Scope Modification and extension of the existing CDU Cardax security system and CCTV System including: Cardax (FT 3000 series) Access control

More information

Overview. Alarm console supports simultaneous viewing of both live and recorded video when alarm events are selected

Overview. Alarm console supports simultaneous viewing of both live and recorded video when alarm events are selected Niagara Security Overview Niagara Security by Tridium, is an open, web-based security management solution that allows you to manage and monitor your facility anytime, anywhere. Built on Tridium s Niagara

More information

Self Monitoring Power Supply (BPSM)

Self Monitoring Power Supply (BPSM) LIFETIME REPLACEMENT WARRANTY Self Monitoring Power Supply (BPSM) Application - When interfacing with a fire alarm system where the system s auxiliary relay cannot handle the full current potential of

More information

User manual Rev 1.3 Contents

User manual Rev 1.3 Contents User manual Rev 1.3 Contents 1. Introduction...4 2. System specifications...5 2.1.. General overview...5 2.2. Maximum capacity...6 2.3. Electrical specifications...6 2.4. Mechanical specifications...6

More information

ADDENDUM TO THE CONTRACT. for the. Bartlett Regional Hospital Server Room Cooling System Replacement. Contract No. E12-149

ADDENDUM TO THE CONTRACT. for the. Bartlett Regional Hospital Server Room Cooling System Replacement. Contract No. E12-149 ADDENDUM TO THE CONTRACT for the ENGINEERING DEPARTMENT Bartlett Regional Hospital Server Room Cooling System Replacement Contract No. E12-149 ADDENDUM NO.: TWO CURRENT DEADLINE FOR BIDS: January 20, 2012

More information

Talk-A-Phone Co. Model WEBS-MT/R Emergency Phone Tower Mount Architectural & Engineering Specification rev. 08/29/2011

Talk-A-Phone Co. Model WEBS-MT/R Emergency Phone Tower Mount Architectural & Engineering Specification rev. 08/29/2011 Talk-A-Phone Co. Model WEBS-MT/R Emergency Phone Tower Mount Architectural & Engineering Specification rev. 08/29/2011 1 General Description 2 Construction 1.1 The unit shall be a highly vandal-resistant

More information

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Phone: (866) 701-1146 Fax: (425) 216-7558 www.remotecontroltech.com Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Introduction... 2 Before Installation... 2 Receiver Installation...

More information

Specifications Control Features. User Interface. Communicator. Programmable Outputs. Access Control. System Response

Specifications Control Features. User Interface. Communicator. Programmable Outputs. Access Control. System Response Control/Communicators Specifications Control Features Eight programmable areas, each with perimeter/interior partitioning. Regular, master, associate, or shared option by area Real-time clock and test

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 25-POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1. DESCRIPTION: A. This section of the specification

More information

Automatic Door Openers and ADA Devices Rev. 0 Bid # 48240056. Scope of Work

Automatic Door Openers and ADA Devices Rev. 0 Bid # 48240056. Scope of Work Scope of Work I. Scope of Solicitation II. Instructions to Offerors III. Scope of Work / Specifications IV. Terms and Conditions - Special I. SCOPE OF SOLICITATION Clemson is seeking to initiate a turnkey

More information

DMP Network Monitoring

DMP Network Monitoring Contents Introduction... 1 The Monitoring Advantage.2 Savings... 2 Speed... 2 Quality of Service... 2 Security... 2 How to Further Minimize the Risk... 3 DMP Communication... 3 XT Series, XR100N, XR500N,

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719

More information

SECTION 16700 FIRE ALARM SYSTEM

SECTION 16700 FIRE ALARM SYSTEM SECTION 16700 FIRE ALARM SYSTEM PART ONE: GENERAL 1.1 GENERAL REQUIREMENTS A. Definition of Work : This section of the specification includes the furnishing, installation, connection and testing of the

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is

More information

APPLICATION NOTE. The DMP Software Family DMP COMPUTER SOFTWARE PROGRAMS

APPLICATION NOTE. The DMP Software Family DMP COMPUTER SOFTWARE PROGRAMS APPLICATION NOTE Contents The DMP Software Family... 1 Stand-Alone Link Software... 1 Add-on Modules for Link Software... 1 System Link End-User Panel Management Software... 2 Simple Registration and Activation...

More information

AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS

AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS AGRI-ALERT ALARM SYSTEMS Peace of Mind Agri-Alert is a complete alarm system for monitoring temperature, power, feed and watering systems, burglary,

More information

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02 IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02 TABLE OF CONTENTS DESCRIPTION 2 MOUNTING INSTRUCTIONS 2 HOW TO CABLE THE IPX 2/3 POWER SUPPLY INSTALLATION 3 OPERATION 3 CARE

More information

Versatility, reliability and expandability are the three main features that make the N-1000 one of the most popular access control panels ever.

Versatility, reliability and expandability are the three main features that make the N-1000 one of the most popular access control panels ever. Versatility, reliability and expandability are the three main features that make the N-1000 one of the most popular access control panels ever. Expandability is the most important feature of any access

More information

SILENT KNIGHT MODEL 5207

SILENT KNIGHT MODEL 5207 SILENT KNIGHT MODEL 5207 Fire Control / Communicator Installation, Programming, and Operation Manual Part Number 150865 Rev. C, 04/03 Contents Section 1 Introduction.......................................................................1-1

More information

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as

More information

CalMod Design-Build Electrification Services

CalMod Design-Build Electrification Services SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent

More information

Commander 2000 Control Panel

Commander 2000 Control Panel Commander 2000 Control Panel Interactive Technologies, Inc. File: Panels Overview Applications Features The Commander 2000 is an affordable wireless security system that is easy to install and easy to

More information

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The

More information

January 1, 2013. RE: TG-7FS Sole Path Cellular Alarm Communicator. To whom it may concern:

January 1, 2013. RE: TG-7FS Sole Path Cellular Alarm Communicator. To whom it may concern: January 1, 2013 RE: TG-7FS Sole Path Cellular Alarm Communicator To whom it may concern: In November 2009, the National Fire Protection Association (NFPA) released the newest addition to the NFPA 72, National

More information

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5 White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

FIREDEX 2200. Conventional Fire Panels

FIREDEX 2200. Conventional Fire Panels 68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class

More information

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling Electronics Ltd Presenting Power, Intelligence... with a sense of feeling By Appointment to Her Majesty The Queen Supplier of Fire Detection Equipment Kentec Electronics Ltd. Dartford Plug in slots K772

More information

SECTION 16620 FIRE ALARM SYSTEM

SECTION 16620 FIRE ALARM SYSTEM SECTION 16620 PART 1 GENERAL FIRE ALARM SYSTEM 1.01 SUMMARY A. Work included: Labor, materials and equipment necessary to complete the installation required for the item specified under this Division,

More information

2301.1 Scope: Communications and Electronic Systems addressed in this section include:

2301.1 Scope: Communications and Electronic Systems addressed in this section include: Chapter 23 COMMUNICATIONS / ELECTRONIC SYSTEMS SECTION 2301 - GENERAL 2301.1 Scope: Communications and Electronic Systems addressed in this section include: 1. Fire Alarm System 2. Telecommunication and

More information

Controller 5000GL Controller 5000GL provides flexible system architecture with options of GBUS and LOCAL BUS communications to field devices, to meet a wide range of site requirements. GGBUS L LOCAL BUS

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY

More information

Doc 10. UTM Standards: Card Access Security System

Doc 10. UTM Standards: Card Access Security System Doc 10 UTM Standards: Card Access Security System 1. GENERAL... 2 1.1. GENERAL REQUIREMENTS.... 2 1.2. SUMMARY OF WORK INCLUDED... 2 1.3. OVERVIEW... 2 1.4. MANDATORY REQUIREMENTS... 3 1.5. ACCESS CONTROL

More information

e-ask electronic Access Security Keyless-entry

e-ask electronic Access Security Keyless-entry e-ask electronic Access Security Keyless-entry e-fob Keyless-entry entry System Full-Function Function Installation Manual FCC ID: TV2EFOB1 (UM20 ~ 22793-02) Table of Contents Introduction... 1 e-fob Operation

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description

More information

Two-way communication, keep checking the commnunication between the panel and accessories, make sure the system safer.

Two-way communication, keep checking the commnunication between the panel and accessories, make sure the system safer. Innovative GSM & WIFI dual network operating platform. On WIFI network, the alarm system will work without any fee. If no WIFI, it will work on GSM automatically. With state-of-the-art WIFI network technology,

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information