tiastar TM Motor Control Center Catalog and Application Guide
Table of Contents Introduction tiastar MCC 4 Product Features and Benefits 6 tiastar Arc Resistant MCC 8 Key Innovations of Arc Resistant MCC 0 tiastar Smart MCC 2 General Information Codes and Standards 4 Estimated MCC Shipping Weight 5 NEMA Wire Classes and Types 6 MCC Heat Dissipation 8 Altitude Ratings 20 Structure and Bussing NEMA Enclosure Types 2 Paint and MCC Finish 22 Structure Design and Options 23 Bus Selection and Options 26 Wireways 29 Mains, Feeders, and Incoming Devices Incoming Line Termination & Cable Space 30 Main Lug Only (MLO) 32 Main Circuit Breaker (MCB) 34 Main Disconnect Switch (MDS) 36 Feeders 38 Bus Splice & Bus Duct 42 TPS3 Surge Protective Devices (SPD) 44
Units Plug-in Unit Features 46 Combination Starters 48 Compact High Density (HD) Combination Starters 56 Reduced Voltage Soft-Starter (RVSS) Units 57 Variable Frequency Drive (VFD) Units Micromaster 6 SINAMICS G20C 67 SINAMICS G20 70 Unit Options Overload 76 SIMOCODE 77 Terminal Blocks 79 Wiring Specifications 8 Pilot Devices 82 Control Transformer Sizes 84 Handle Auxiliary Switch 84 Nameplate 85 Programmable Logic Controller (PLCs) Units 86 Metering Units 87 Panelboard and Transformer Units 89 Standard MCC Catalog Items Feeder Circuit Breaker (FCB) Catalog Units 90 Full Voltage Non-Reversing (FVNR) Catalog Units 93 Common Modification Kits 94 Appendix Drawings and Dimensions 98 Motor Circuit Protector (MCP) Selection 0 Breaker Trip Settings Breaker Selection 2 Fuse Selection/UL Standard Fuse Classifications 3 Heater Tables 6 Typical Schematic 20 Aftermarket 30 Typical Specifications General MCC or Arc Resistant MCC 3 Smart MCC 36 MCC Training 43
Introduction Standard MCC tiastar MCC Motor Control Centers (MCC) have come a long way since they were introduced in 937 as a way to save floor space by placing several starters in a single cabinet. Ideally, the best-of the-best must also save installation time and money. Siemens has an installed base of Motor Control Centers dating back to 964. Our Siemens tiastar MCCs are designed as self-contained modular units which meets UL and NEMA standards. They come with rear-mounted, self-aligning copper stabs that firmly grasp onto the bus. Brackets guide the placement of units, further assuring positive engagement with the bus. From 22mm to 30mm pilot devices, from direct starters to world-class drives, the Siemens tiastar MCC has many features and options to meet your specific needs. UL 845 Labeling as applicable CSA C22.2 No. 254-05 Labeling as applicable when specified Heavy-Duty Construction with up to 00kA Bus Bracing 600V 50/60 Hz NEMA Wiring Plug-In Units (up to Size 5 Starters) Door/Unit Mounted Pilot Device Panel High Density Compact Units available to reduce footprint 4
Introduction Technical Specifications Summary tiastar MCC Bus and Electrical Ratings Horizontal Bus Ratings 600A, 800A, 200A, 600A, 2000A, 2500A Horizontal Bus Material Vertical Bus Ratings Vertical Bus Options Bus Bracing Max MCC Voltage Rating Copper with tin or silver plating, or Aluminum 2 with tin plating 300A, 600A, 800A Isolated (standard) Insulated and isolated (optional) Auto Shutters (optional) 42K AIC, 65K AIC, 00K AIC 600 V Enclosure Enclosure Type NEMA (standard), NEMA A, NEMA 2, NEMA 2, NEMA 3R (non walk-in) High Density 6 Units Option VFD, RVSS Units Back-to-Back Option Available Available Available Dimensions Section Depth 5, 20, 2 (back-to-back), 3 (double deep), 4 (double deep) Section Width 20, 24, 30, 40, 50, 60 NEMA only 2 for 600-200A, 65KA, 65 C 5
Introduction Standard MCC Product Features & Benefits Siemens tiastar Motor Control Centers (MCC) are composed of a number of vertical sections bolted together which allows for future addition of MCC vertical sections in case the customer requires expansion. Benefits Feature Easy accessibility for faster maintenance Entire horizontal bus assembly is in top 2 of the vertical section Easy visual inspection of horizontal bus Clear Lexan horizontal wireway barrier Ease of installation and movement of plug-in units Plug-in units with integrated racking handles 6
Introduction Benefits Feature Prevents arcing faults from propagating Isolated and insulated bus assembly (Optional) Improved service access to save time Dual location pilot device panel Clearly indicates equipment status (ON, TRIP, OFF) Industry s best unit operating handle 7
Introduction Arc Resistant MCC tiastar Arc Resistant MCC The Type 2 Arc Resistant low voltage motor control center is a new product offering that was tested in accordance to IEEE C37.20.7, which contains and channels internal arcing fault incident energy. It provides an additional degree of protection to the personnel performing normal operating duties in close proximity to the equipment while the equipment is operating under normal conditions. Type 2 accessibility means the MCC protects the operator in front, back and sides of the equipment. The Arc Resistant MCC is a state-of-art overarching technology. This means one can get an Arc Resistant MCC that can have various Smart components with communications, and/or High Density Compact Units. 8
Introduction Technical Specifications Summary tiastar Arc Resistant MCC Bus and Electrical Ratings Maximum Horizontal Bus Maximum Vertical Bus Maximum Short Circuit Withstand Rating Arc Flash Duration Maximum Voltage Rating Horizontal Bus Details Incoming 600 A 800 A 65KA 50ms (3 cycles) 600Vac Copper Only MLO, MCB/MDS 600 A max, splice to existing Enclosure Enclosure Type High Density Units Option VFD, RVSS Units Double Deep Option NEMA and A Only Available Available Available Dimensions Modified Pull Box Height 2 Minimum (standard), 8 and 24 (optional) Section Depth 20 Section Width 20 or 30 Total MCC Height 02 Minimum 2 Room Requirements 2 Minimum Ceiling Height (Total MCC Height + 0 ) 38 Minimum Aisle The Arc Resistant MCC should not be spliced to a Non-Arc Resistant MCC. 2 If the mounting channels are surface mounted then the minimum height is 03 (90 MCC height + mounting channels + 2 modified pull box). Also, note that the total MCC height will increase if standard modified pull box is not selected. 9
Introduction Arc Resistant MCC Key Innovations and Benefits of Arc Resistant Design REINFORCED DOORS Reinforced cabinet ensure the equipment can withstand and contain pressure from internal arcing faults. AUTOMATIC SHUTTERS The barrier automatically opens and closes to allow insertion or removal of units. It isolates the vertical bus to prevent inadvertent contact lowering the risk to personnel. BOLTED WIREWAY The wireway is bolted to ensure integrity of the MCC wireway is sustained during an arc flash incident. INSULATED BUS BAR Isolates energized components, prevents accidental contact, and keeps arcing faults from propagating. INTERNAL VENTING SYSTEM The vertical wireway is perforated with holes that channel the gasses to the back and out the top of the MCC. 0
Introduction DEFLECTORS The protection plate will allow MCCs to have vented doors, but will reduce the direct launching of arc flash by-products. MODIFIED PULL-BOX WITH PRESSURE FLAP The arc flash by-products will be prevented from launching due to the wire mesh, while the pressure flap will allow pressure release Figure 2. Closed Door View - Arc Resistant MCC Optional Features Dynamic Arc Flash Sentry (DAS) To complement the Arc Resistant MCC, the Dynamic Arc Flash Sentry (DAS) option is available. Dynamic Arc Flash Sentry (DAS) is a patented feature available in both Siemens MCCs and type WL Low Voltage Switchgear. The unique dual trip setting technology reduces the energy available in an arc flash event. For more information, please see the Dynamic Arc Flash Reduction System and its Application in Motor Control Centers white paper at www.usa.siemens.com/mcc
Introduction Smart MCC tiastar Smart MCC A Smart MCC is a networked NEMA compliant MCC that can communicate. It incorporates intelligent devices at the unit level to control and monitor motor operation, energy consumption, and power quality. It rapidly communicates with a PLC or process control system via a data network. Smart MCC Components Smart MCC is internally interconnected using PROFIBUS DP which incorporates intelligent devices such as SIMOCODE pro C and V motor management systems, SIRIUS 3RW44 soft starters, SIMATIC PLCs, Siemens VFDs, and other smart components. Major Benefits Reduces Wiring Connections Reduces Cost Improves Operational Diagnostics Simplifies Installation and Troubleshooting 2
Introduction tiastar Smart MCC Network Architecture Siemens Distributed Control System PCS7 Siemens Programmable Logic Controllers SIMATIC S7 PLCs Third Party PLC or DCS Systems PROFIBUS DP Options A Smart MCC has the option to externally talk to other networks such as DeviceNet, Modbus RTU, Modbus TCP/IP, EtherNet/IP, and PROFINET. VFD, RVSS Units High Density 6 Units Option Back-to-Back Option Available Not Available Available Double Deep Option Available 3
General Information Codes and Standards Siemens tiastar MCCs are manufactured to American National Standards Institute (ANSI) / Underwriters Laboratories (UL) 845 standard and contain the UL Listed label. Siemens tiastar MCCs complies with National Electrical Manufacturers Association (NEMA) ICS 8-200. Siemens tiastar MCCs also complies with Canadian Standards Association (CSA) C22.2 No. 254-05 standards. Siemens tiastar MCCs are American Bureau of Shipping (ABS) Type Approval Certificated. 4
General Information Estimated MCC Shipping Weight Dimensions in Inches (mm) Width Depth Type Weight per Section in lbs (Kg) for NEMA, 2, or 2 Weight per Section in lbs (Kg) for NEMA 3R 20 (508) 5 (38) Front Only 550 (250) 650 (295) 20 (508) 20 (508) Front Only 650 (295) 700 (38) 30 (762) 5 (38) Front Only 700 (38) 800 (363) 30 (762) 20 (508) Front Only 850 (386) 900 (409) 20 (508) 2 (533) Back-to-Back 670 (304) N/A 30 (762) 2 (533) Back-to-Back 880 (400) N/A Note: MCC shipping split maximum is 80 inches (for example, four 20-inch wide vertical sections). } Horizontal Bus Bars Vertical Bus Shipping Split # Shipping Split #2 Figure. Example of shipping split 5
General Information NEMA Wire Classes and Types Siemens MCCs are available as either Class I or Class II assemblies utilizing either Type A, Type B, or Type C wiring as defined in NEMA ICS8-200. Below are the NEMA class and type definitions: NEMA Classes Class I Independent Units Class I motor control centers shall consist of mechanical groupings of combination motor control units, feeder tap units, other units, and electrical devices arranged in a convenient assembly. The manufacturer shall furnish drawings that include: a. Overall dimensions of the motor control center, identification of units and their location in the motor control center, locations of incoming line terminals, mounting dimensions, available conduit entrance areas, and the location of the master terminal board if required (Type C wiring only). b. Manufacturer s standard diagrams for individual units and master terminal boards (Type C wiring only) consist of one or more drawing(s) that: Identify electrical devices Indicate electrical connections Indicate terminal numbering designations Note: When a combination schematic and / or wiring diagram for a unit is supplied showing optional devices, the manufacturer shall provide information to indicate which devices are actually furnished. Class II Interconnected Units Class II motor control centers shall be the same as Class I motor control centers with the addition of manufacturer furnished electrical interlocking and wiring between units as specified in overall control system diagrams supplied by the purchaser. In addition to the drawings furnished for Class I motor control centers, the manufacturer shall furnish drawings that indicate factory interconnections within the motor control center. Class I-S and II-S Motor Control Centers with Custom Drawing Requirements Class I-S and II-S motor control centers shall be the same as Class I and II except custom drawings shall be provided in lieu of standard drawings as specified by the user. Examples of custom drawings are Special identifications for electrical devices Special terminal numbering designations Special sizes of drawings The drawings supplied by the manufacturer shall convey the same information as drawings provided with Class I and II motor control centers, additionally modified as specified by the user. 6
General Information NEMA Types Type A User field wiring shall connect directly to device terminals internal to the unit and shall be provided only on Class I motor control centers. Figure 3. Class I, Type A Wiring Type B Type B user field load wiring for combination motor control units size 3 or smaller shall be designated as B-d or B-t, according to the following: B-d connects directly to the unit terminals, which are located immediately adjacent and readily accessible to the vertical wireway. B-t connects directly to a load terminal block in, or adjacent to, the unit. Figure 4. Class I, Type B-d Wiring Type B user field load wiring for combination motor control units larger than size 3, and for feeder tap units, shall connect directly to unit device terminals. Type B user field control wiring shall connect directly to unit terminal block(s) located in, or adjacent to, each combination motor control unit. Figure 5. Class I, Type B-t Wiring Type C User field control wiring shall connect directly to master terminal blocks mounted at the top or bottom of those vertical sections that contain combination motor control units or control assemblies which shall be factory wired to their master terminal blocks. User field load wiring for combination motor control units, size 3 or smaller, shall connect directly to master terminal blocks mounted at the top or bottom of vertical sections. Motor control unit load wiring shall be factory wired to the master terminal blocks. User field load wiring for combination motor control units larger than size 3, and for feeder tap units, shall connect directly to unit device terminals. Figure 6. Class I, Type C Wiring 7
General Information MCC Heat Dissipation The purpose of this section is to allow the reader to approximate the heat output of an MCC. This information is based on power loss data collected for the major heat producing components. The data presented here is based off the maximum rated current for each component. If the true loading current is known, then the estimate can be improved by multiplying the given power loss by the square of the true current divided by the square of the rated current: P actual = P max i 2 actual i 2 max The power losses can be multiplied by 3.42 to convert them from Watts to BTU/hr.. Combination Motor Starters Maximum Power Loss (3-Pole) [W] Size imax[a] Contactor Breaker Overload CPT Total 0 8 6 2 6 7 4 27 8 5 6 7 58 2 50 28 2 6 7 72 3 95 52 24 6 29 4 85 55 60 6 29 50 5 300 84 93 6 7 200 6 500 90 74 6 7 387 2. Circuit Breakers 3. Lighting Transformers 4. Reduced Voltage Soft Starters imax[a] Watts Loss (3-pole) KVA Watts Loss Family imax Power Loss (W) 3 5 6 300 X 7 4 5 8 30 60 20 9 400 0 542 5 658 3RW30 2X 34 9 3X 63 5 4X 98 2 00 36 20 76 2X 29 9 200 60 400 30 800 92 25 76 30 995 37.5 35 3RW40 3X 63 5 4X 98 2 5X 45 75 200 259 45 276 7X 385 65 600 46 75 928 2X 82 55 2000 720 3RW44 3X 45 95 4X 385 232 5X 850 270 6X 078 630 8
General Information MCC Heat Dissipation 5. Panel Boards Maximum Power Loss (3-Pole) [W] Main Branch Circuits Size imax[a] Bus Breaker 8 36 42 P 400 380 29 87 77 80 P2 600 420 26 99 97 09 P3 800 470 92 6 96 3 6. Variable Frequency Drives The power loss for a variable frequency drive is approximately 3.5% of the overall power: Power Loss= (HP of Motor). 746W. 3.5% HP Maximum Power Loss (3-Pole) [W] Horizontal (20 Section) Vertical (72 Section) imax[a] Aluminum Copper Copper 300 57 600 90 54 5 800 07 64 240 200 20 72 600 43 85 2000 66 2500 74 04 The data presented here is subject to change, without notice, owing to periodic updates and corrections. Please be advised that several assumptions had to be made in order to generate this and, accordingly, no representation or warranty is given with regard to its accuracy or completeness of the information as the same has been included for general purposes only and that, it should not be relied upon for any specific purpose. Siemens industry, inc. Or its affiliates, officers, employees or agents are neither responsible nor liable for inaccuracies, errors or omissions, or for any loss, damage or expense, including, without limitation, any loss of profit, indirect, special, incidental or consequential loss / damages, arising out of this data. 9
General Information Altitude Ratings Siemens tiastar Motor Control Centers are designed and built to operate up to 2000 meters above sea level (6,600 ft) without any modifications. Motor control centers are often installed in applications exceeding 000 meters (3300 ft) above sea level. Due to the lower air density and heat transfer capacity at elevated altitudes, the physical properties such as dielectric strength, load capacity of the motor control centers, conductors and motors, as well as the tripping characteristics of thermal relays may require modification to reflect these changes due to altitude. Paschen s Law describes the breakdown voltage of parallel plates in a gas, as a function of pressure and gap distance. In other words, at lower pressure (higher altitudes) it takes less voltage to cross a given distance increasing the chance for electrical arcs. To compensate for this, it is recommended that the operational voltage be de-rated for altitudes exceeding 2,000 meters according to Paschen s law. In addition, the rated thermal current should also be reduced because of the decreased thermal efficiency of lower density (high altitude) air. Siemens tiastar Motor Control Centers are designed and built to operate up to 2000 meters above sea level (6,600 ft) without any modifications. Siemens MCC components are designed and manufactured to provide excellent insulation and arc flash protection for bus components, in addition to having high thermal efficiency. Using creative design and engineering, Siemens MCC s can operate safely and reliably at altitudes up to 5,000 meters above sea level. Altitude (m) <2000 200-3000 300-4000 400-5000 De-Rating Voltage Current Voltage Current Voltage Current Voltage Current Motor Control Center Std. Aluminum & Copper 65 C rise horizontal bus Requires enhanced Copper 50 C rise horizontal bus Motor Control Center (MCC Bus & Enclosure) 600V 00% 480V 00% 480V 00% 480V 00% Breakers 600V 00% 480V 97% 480V 94% 480V 9% Starters Innova 600V 00% 480V 97% 480V 94% 480V 9% Sirius 600V 94% 600V 90% 480V 80% 480V 70% Soft Starters 3RW40 460V 89% 460V 75% 460V 70% 460V 63% 3RW44 460V 92% 460V 85% 460V 78% 460V 70% Drives MM440 frame (FXGX) 00% 00% 90% 90% 77% 85% MM440 frame (A-F) 00% 90% 90% 85% 77% 80% WL Breakers 600V 00% 480V 97% 480V 94% 445V 9% G20 (FSA...FMF) PM240 00% 92% 88% 86% 77% 80% G20 (FSGX) PM240 00% 00% 88% 92% 77% 85% The data presented here is subject to change, without notice, owing to periodic updates and corrections. ESP200 and/or the 3RB20 overloads are included in the ratings. For SIMOCODE, there is no de-rating required for 2000 meters. Usage is limited for applications above 2000 meters depending on ambient temperature. For more detail, please see the SIMOCODE Pro System Manual. 20
Structure & Bussing NEMA Enclosure Types Enclosure Types NEMA Standard NEMA A Gasketed Front, General Purpose Indoor or Outdoor Indoor Indoor Description This enclosure is primarily to prevent accidental contact by personnel with the enclosed equipment and for protection against falling dirt. NEMA 2 reset and handle mechanisms are standard for all enclosures. This enclosure has the same use as NEMA except the front of the enclosure is gasketed. The parts that are gasketed include: Unit separator angles, Right hand side of front of units, Bottom horizontal cross ties, Lip on top plate, Handle mechanism, and Bottom horizontal wireway cover plate. The whole front of structure is gasketed, except the hinged side of door. NEMA 2 Drip Proof NEMA 2 Dust tight, Industrial Use NEMA 3R Rainproof Indoor Indoor Outdoor (Non walk-in) This design is NEMA A front with a drip shield mounted on top of the enclosure. This enclosure is to protect equipment against falling noncorrosive liquids and dirt. It prevents the entrance of dripping liquid at a higher level than the lowest live part within the enclosure. The drip shield completely covers the top and extends 3 over the front and /2 over the sides of the basic structure. On front-only MCC s, the drip shield is flush to the rear. The drip shield is angled from front to rear and not flush with the top of the MCC. The drip shield mounts on the top of the structure. This enclosure is intended for indoor use in areas where fibers, lint, dust, dirt, and light splashing are prevalent. The NEMA 2 enclosure will provide a greater degree of protection than a NEMA A enclosure. The following additional parts are gasketed: Hinged side of doors, Pilot device panel, Top plates, Wireway end-covers, and Rear plates. Because of the divider side sheet assemblies, there is no gap between sections, allowing for much greater dust resistance. In addition, interconnection holes in the side sheet assemblies are sealed. Bottom plates are included when NEMA 2 is specified. This enclosure will prevent entrance of rain at a level higher than the lowest live part. The enclosure has provision for locking and drainage. This NEMA 3R enclosure entirely surrounds the motor control center for outdoor operation. Each non walk-in enclosure has a floor and a slanted roof. All doors are louvered and screened to promote air circulation and keep out pests. Motor control units can be racked in positive stop/test position with the outer enclosure doors closed. Additional structures may be added in the field without special bus splices. Rigid steel construction permits use from two sections up to any reasonable number of sections. Stainless steel hinge pins and door stops are standard. Pressure Sensitive Adhesive (PSA) Closed Cell Sponge Rubber door gasket forms a tight seal to keep the elements. Space heaters, fluorescent lights, fans, filters, blowers, and convenience outlets are available as options. NEMA 3R enclosures are designed to accommodate bottom cable entry and exit only. The enclosures are not dust, snow, or sleet (ice) proof. Attention: Variable Frequency Drives require special consideration, see Units chapter VFD section for further details. 2
Structure & Bussing Paint and MCC Finish The motor control finish is an electrostatically applied TGIC polyester powder, applied both manually and automatically in an environmentally controlled clean room, cured at 400 F for 20 minutes. All painted parts undergo a five-stage preparation process that includes an alkaline wash, water rinse, iron phosphate wash, water rinse and a nonchrome sealer. The minimum film thickness on external surfaces is 2.0 Mils and the finish passes a 600-hour salt spray test per ASTM B7-94 definitions. ANSI 6 Light Gray is the standard exterior color. Unit backplates and the rear of the vertical wireway are painted white for improved visibility. Custom color MCC s are available. 22
Structure & Bussing Structure Design and Options Sections Heavy 4 gauge steel side sheet assemblies are used for supporting the structure without additional bracing. The front of each side frame has a 80 bend to provide additional rigidity and a smooth edge. Cross channels tie the side frames together. A common sheet is used to provide isolation between adjacent sections. A shipping split will have two outer side sheet assemblies and an inside divider side sheet assembly between sections. Mounting Sills Full-length mounting sills are standard for each shipping split. The sills are 3 wide by /8 high and constructed of 7 gauge steel. They have four holes per section for use with /2 (max.) anchor bolts. The sills add additional structural rigidity. The mounting sills are an integral part of the structure and should not be removed. Structural Parts Divider Sheets Side Sheets Center Bottom Cross Ties Rear-Channel (FO) Channel Sills Center-Top Channel Vertical Bus Mounting Angles Lifting Angles Rear Covers Top Plates End Covers Separator Angles Shelf Brackets Unit Parts Top and Bottom Unit Barriers Back Pan Side Barrier Plate Angles Doors 4 ga. 4 ga. 2 ga. 3 ga. 7 ga. 3 ga. 4 ga. 7 ga. 6 ga. 3 ga. 6 ga. 2 ga. 0 ga. 4 ga. 3 ga. 4 ga. 8 ga. 4 ga. 3 ga. 4 ga. Note: Arc Resistant MCC metal thickness values will be different on some parts. 23
Structure & Bussing Structure Design and Options Lifting Angle A 7 gauge lifting angle is supplied with every shipping split regardless of length. The lifting angles are mounted atop the MCC structure. Side Sheets Side sheet assemblies on 20 deep units provide a 40.5 square inch wireway opening at the top and a 46 square inch wireway opening at the bottom to facilitate routing wires through the horizontal wireways between adjoining sections. 5 deep units provide a 40.5 square inch wireway opening at the top and a 30 square inch wireway opening at the bottom. 2 2 2 hr rti al S tions 24
Structure & Bussing Back-to-Back and Double Deep MCC Options Usually MCCs are front-mounted. However, for the customers who want to save space and cost, we offer our standard 2 deep back-to-back MCC design. We are the only manufacturer in the market that offers 2 deep back-to-back design with common horizontal and vertical buses. For customers that would like to have back-to-back configuration but with separate horizontal bus for both the front and rear, the options include 3 (double deep) and 4 (double deep). Pull Box (Top Hat) Options Pull boxes are generally used to provide additional cable bending space for incoming main feeds or bus duct connections. Pull boxes are shipped 2,8, or 24 high; 20 or 30 wide; 5 or 20 deep for customer field installation on top of centers. Each pull box has an open bottom with mounting holes Optional punched Pull in Box its front and rear flange. (Top After removing Hat) the top lifting angle and front conduit cover from the MCC, the pull box can be bolted to pretapped holes. The pull box has front, top, 2, 8, 24 and back removable covers. Stab-on Connections Stab Front-Mounted Unit Vertical Bus Pull boxes may also be supplied with incoming line bus extensions for mounting inverted main lugs only. This type of pull box assembly is referred to as a top hat. Front Unit Rear Unit Special Structures Back-to-Back Mounted Units Back-to-Back Mounting 30, 40, 50, and 60 wide sections are available for larger units such as large horsepower VFD, RVSS or special panels that may require it. 30 and wider structures may have horizontal bus, but are not supplied with vertical bus. 30 wide structures are available in 5 or 20 deep design and line up with standard 20 wide sections. 30 sections have full-width doors, while wider sections have two interposing doors. Dimensions for other special equipment such as transfer switches, NEMA 3R outdoor enclosures, or special service entrance enclosures will be provided on request. 25
Structure & Bussing Bus Selection and Options For additional strength, the horizontal bus, vertical bus, bus support angles, and bus bracing insulators form one unified assembly. Horizontal Bus The horizontal bus is a means of tapping power for distribution to the various units within a section. Siemens tiastar MCC s horizontal bus is always located on the top of the vertical section and never located behind unit space, allowing for easy maintenance and serviceability. Horizontal Bus Bars Horizontal Bus Specifications Horizontal Bus Current Ratings 600A, 800A, 200A, 600A, 2000A, 2500A only Horizontal Bus Material Options Copper with tin or silver plating, or Aluminum 2 with tin plating Vertical Bus The standard vertical bus is tin-plated copper 3/8 thick with rounded edges. The edges on the vertical bus are rounded to assist in units stabbing onto the bus. Vertical Bus Specifications Vertical Bus Current Ratings Vertical Bus Options Stab Plating Bus Bracing 300A, 600A, 800A Isolated (standard for 42kA or 65kA bus bracing) Insulated and isolated (optional for 42kA or 65kA bus bracing; standard for 00kA bus bracing and back-to-back) Auto Shutters (standard for the Arc Resistant MCC; optional for all other configurations) Tin (standard) Silver (optional) 42K AIC, 65K AIC, 00K AIC NEMA only 2 for 600-200A, 65KA 26
Structure & Bussing Vertical Bus (cont) Vertical buses are available in two designs: ) Isolated 2) Insulated and Isolated. Isolated vertical bus design is grounded sheet steel with stab openings and is the standard for front-only structures with 42kA or 65kA bus bracing.the vertical bus bars in this design are not physically insulated phase-to-phase. An optional insulated and isolated vertical bus design which prevents arcing faults from propagating is available for front only 42kA and 65kA bus bracing. The isolated and insulated vertical bus design is standard for 00kA bus bracing and all back-to-back structures. Bus Insulation Figure : Isolated vertical bus Figure 2: Insulated and Isolated vertical bus Auto Shutter (optional) mechanism automatically opens and closes to allow insertion or removal of units. It prevents inadvertent contact of the vertical bus; thus, lowering the risk to personnel. The Auto Shutters are standard for the Arc Resistant MCC. It is important to point out that the shutter mounting holes are not in the standard bus assembly and cannot be duplicated in the field. Therefore, retrofitting automatic shutters to MCC s that do not have them is not possible. The Auto Shutter mechanism cannot be retrofitted in the field Figure 3: Optional Auto Shutter is standard in Arc Resistant MCC 27
Structure & Bussing Bus Selection and Options Ground Bus A standard horizontal ground bus is typically mounted in the bottom 6 of the structure. An optional copper /4 x vertical ground bus can be connected to the horizontal bus. When a combination motor control unit is inserted into the MCC, the optional vertical ground bus is engaged before the vertical power bus. The vertical ground bus provides a means of assuring the plug-in unit is solidly grounded before the power stabs are engaged and remains grounded until the power stabs are disengaged. When vertical ground bus is specified on back-to-back structures, vertical and horizontal ground bus must be supplied in the front and rear of each section. The ground bus may be located in the top or bottom front of 5 or 20 deep MCCs or the top or bottom rear of back-toback structures under most situations. A ground lug is supplied on one end of the ground bus for one #6-300 MCM cable. If not otherwise specified, the lug will be located in the incoming line section. Vertical Ground Bus Horizontal H Ground Bus Ground Bus Horizontal (Bottom Mounted) (A) 300A 600A 600A Vertical (A)* 300A Cu *Available with motor ground terminations Cu Cu Al Neutral Bus A neutral connection is generally required for 3 phase 4 wire systems. A neutral pad is usually mounted in the incoming section only. Optionally, a neutral bus running the full length of the line-up can be provided. When full length neutral bus is specified, the neutral bus must be located in the bottom front of the MCC structure. Full length neutral bus requires that the ground bus be mounted in the top of the structure. In general, neutral bus capacity is sized at /2 main bus capacity. A two hole lug is supplied as standard when a service entrance label is not required. For service entry, a neutral lug and a bonding lug are supplied. All lugs used for ground or neutral are CU/AL type. Neutral Bus Neutral Bus (Bottom Mounted) (A) 600A 800A 200A 600A Cu Cu Cu Cu 28
Structure & Bussing Wireways Vertical Wireway The vertical wireway is 72 H x 4 W and has a cross sectional area of 38.25 square inches. An optional 8 W vertical wireway is available with an area of 76.5 square inches. A vertical wire-way door is supplied on each 20 and 24 wide section that does not contain a 72 tall unit. Vertical wireway doors are not supplied on any section that contains a 72 high unit or on 30 wide or wider structures or 20 wide units. Each vertical wireway is supplied with three wire form wire tie rods. 2 The top horizontal wireway is covered with a 2 high fullwidth door with a /4-turn latch. They are 2 high with a cross section of 90 square inches. Horizontal Wireways are located in the top and bottom of each section and run the full length of each line-up. The bottom horizontal wireway is 6 high with 45 square inch area. Figure : Wire tie rod Figure 2: Vertical and Horizontal wireways Rear Wireway The rear of the structure can be used as a wireway if the available bus support angles with 2 /2 grommeted holes are specified. Dimensions for rear wireways in front mounting 5 and 20 deep units are: 5 deep: /2 x 9 3/4 = 30 sq. in. cross sectional area. 20 deep: 9 x 9 3/4 = 78 sq. in. cross sectional area. 29
Mains, Feeders, and Incoming Devices Mains and Incoming Devices The incoming cables are terminated on lugs in an incoming compartment of the MCC. These lugs may be connected directly to the bus via Main Lug Only (MLO) or connected to a main disconnect device which may either be a Main Circuit Breaker (MCB) or Main Fusible Disconnect (MDS). It is important to know whether the incoming cables will be coming from the bottom or top of the MCC, as the required wire bending space may affect the compartment size. Note: All dimensions are shown in inches unless otherwise specified. Main Lugs: Top or Bottom Entry Main Lugs on Top, Top Entry Main Lugs on Bottom, Bottom Entry 30
Mains, Feeders, and Incoming Devices Main Lug Only (MLO) Top Feed Main Circuit Breaker (MCB) Top Feed 3
Mains, Feeders, and Incoming Devices Main Lug Only (MLO) Horizontal lugs are available with 600A, 42,000A symmetrical bracing only (see Figure 6 on next page). Special lugs such as Burndy crimp type can be accommodated. Consult Siemens for space requirements. Amp/Bracing (A/K) 600A/42K Location Top Incoming Cable size Qty = 2 #4-350MCM CU/AL Fig. ref. Next page Wire bending Space dim. A Total assembly Height dim. B 6 3 2 0 Required unit Space dim. C 600A/42K-65K Top Qty = 2 #2-600MCM CU/AL 7 6 24 2 600A/85-00K 600A/42K 600A/65K 800A/42K-65K 800A/85K-00K 800A/42K-65K 2 800A/42K-65K2 200A/42K-00K 600A/42K-00K 2000A/42K-00K 2000A/42K-00K Top Bottom Bottom Top Top Bottom Top Bottom Top Top Bottom Qty = 2 #2-600MCM CU/AL Qty = 2 #4-350MCM CU/AL Qty = 2 #4-350MCM CU/AL Qty = 2 #2-600MCM CU/AL Qty = 2 #2-600MCM CU/AL Qty = 2 #2-600MCM CU/AL Qty = 3 #2-600MCM CU/AL Qty = 3 #2-600MCM CU/AL Qty = 4 #2-600MCM CU/AL Qty = 6 #2-600MCM CU/AL Qty = 6 #2-600MCM CU/AL 8 20 30 8 9 3 8 2 9 3 24 8 7 6 24 2 8 20 30 8 20 8 30 24 8 20 30 8 20 8 30 24 8 20 30 8 2 29 48 36 22 46 72 72 Space behind structure not available. 2 Entire rear of structure not available. Optional lugs available. Contact factory for size and rating. 32
Mains, Feeders, and Incoming Devices Incoming line termination arrangements for Main Lug Only (MLO) Figure 6 Figure 7 Figure 8 Figure 9 Example: MLO Top Feed Figure 20 Figure 2 Figure 22 33
Mains, Feeders, and Incoming Devices Main Circuit Breaker (MCB) Molded Case Thermal Magnetic (80% rated) circuit breakers, Molded Case Solid State (80% rated) circuit breakers, and Insulated Case WL Power circuit breakers are used for mains in the MCC. Circuit Breaker Frame/Max Trip 25A/25A 25A/25A 250A/250A 250A/250A Location Top Bottom Top 400A/400 7 Top Bottom 400A/400 7 Bottom 600A/600A 7 600A/600A 7 800A/800A 800A/800A 2 6 200A/200A 200A/200A 2 3 6 600A/600A 3 600A/600A 3 2000A/2000A 3 2000A/2000A 3 600A/600A 4 600A/600A 4 2000A/2000A 4 2000A/2000A 4 Top Bottom Top Bottom Top Bottom Top Bottom Top Bottom Top Bottom Top Bottom Incoming Cable size Qty = 5 #3-3/0 CU/AL Qty = 5 #3-3/0 CU/AL Qty = #6-350MCM CU Qty = #6-350MCM CU Qty = #6-350MCM CU Qty = 2 3/0-500MCM CU Qty = 2 3/0-500MCM CU Qty = 2 3/0-500MCM CU Qty = 3 # - 500MCM CU/AL Qty = 3 # - 500MCM CU/AL Qty = 4 250-500MCM CU/AL Qty = 4 250-500MCM CU/AL Qty = 4 300-600MCM CU/AL Qty = 4 300-600MCM CU/AL Qty = 6 300-600MCM CU/AL Qty = 6 300-600MCM CU/AL Qty = 4 300-600MCM CU/AL Qty = 4 300-600MCM CU/AL Qty = 6 300-600MCM CU/AL Qty = 6 300-600MCM CU/AL Fig. ref. Next page Wire bending Space dim. A Total assembly Height dim. B Required unit Space dim. C 23 4 24 2 26 8 24 8 24 5 30 8 27 5 36 30 24 5 30 8 28 5 42 36 24 5 30 8 28 5 42 36 25 22 48 36 29 22 54 48 25 22 48 36 29 22 54 48 32 30 90 72 33 30 90 72 30 32 90 72 33 26 90 72 30 28 90 72 3 25 90 72 30 28 90 72 3 25 90 72 Space in rear of structure not available 2 Entire rear of structure not available 3 Molded case circuit breakers 4 WL power circuit breakers 5 5-25A lug size 2-0 AL, 4-0 CU; 30-00A, 0-/0 CU/AL 6 800A - 200A not available in back-to-back bottom mounting 7 Stab opening at bottom of unit not available in rear Optional lugs available. Contact factory for size and rating. 34
Mains, Feeders, and Incoming Devices Incoming line termination arrangements for Main Circuit Breaker (MCB) Figure 23 Figure 25 Figure 26 Figure 27 Figure 28 Figure 29 Figure 30 Figure 3 Figure 32 35
Mains, Feeders, and Incoming Devices Main Disconnect Switch (MDS) Main fusible switches consist of the following: 60 to 00A, Class R fuse clips 200 to 600A, Class R fuse holder 800 to 200A, Class L fuse holder Fusible disconnect Switch/clips Location Incoming Cable size Fig. ref. Next page Wire bending Space dim. A Total assembly Height dim. B Required unit Space dim. C 60A/30A or 60A Top Qty = #4 - #4 CU/AL 34 4 24 2 60A/30A or 60A Bottom Qty = #4 - #4 CU/AL 39 8 24 8 00A/00A Top Qty = #4 - #4 CU/AL 35 3 30 8 00A/00A Bottom Qty = #4 - #4 CU/AL 40 7 30 24 200A/200A Top Qty = #6-350MCM CU 36 6 42 30 200A/200A Bottom Qty = #6-350MCM CU 4 0 48 42 400A/400A Top Qty = 2 3/0-500MCM CU 37 4 48 36 400A/400A Bottom Qty = 2 3/0-500MCM CU 42 4 60 54 600A/600A Top Qty = 2 3/0-500MCM CU 37 4 48 36 600A/600A Bottom Qty = 2 3/0-500MCM CU 42 4 60 54 800A/800A Top Qty = 3 250-500MCM CU 44 22 90 72 800A/800A Bottom Qty = 3 250-500MCM CU 43 22 90 72 200A/200A Top Qty = 4 250-500MCM CU 44 22 90 72 200A/200A Bottom Qty = 4 250-500MCM CU 43 22 90 72 Space in rear of structure not available. Optional lugs available. Contact factory for size and rating. 36
Mains, Feeders, and Incoming Devices Incoming line termination arrangements for Main Disconnect Switches (MDS) Figure 35 Figure 36 Figure 37 Figure 39 Figure 40 Figure 4 Figure 43 Figure 44 37
Mains, Feeders, and Incoming Devices Feeders Example of Feeder Circuit Breaker (FCB) Example of Dual Feeder Disconnect Switch (DFDS) 38
Mains, Feeders, and Incoming Devices Feeder Circuit Breakers Space Requirements Frame Size (Amps) Max Trip Amps Unit Height (Inches) CB 2 CB 25 25 2 2 250 250 8 2 400 400 24 3,5 600 600 24 3,5 800 800 36 3 (Top) 800 800 48 3 (Bottom) 200 200 36 3 (Top) 200 200 48 3 (Bottom) Feeder Disconnect Switch Space Requirements Switch Rating (Amps) Fuse Clip Size (Amps) Unit Height (Inches) SW 2 SW 30 30 2 4 24 60 60 2 4 24 00 00 8 200 200 30 400 400 42 3,5 600 600 42 3,5 CED Current Limiting Breaker requires 8" 2 CFD Current Limiting Breaker requires 24" 3 Fixed mounted unit. 4 Requires load terminal blocks. 5 Stab opening at top of unit not available in rear. Feeders Disconnect Size Disconnect 2 Type Fuse Type Rating 30 MCS R,J 00KA 60 MCS R,J 00KA 00 MCS R,J 00KA 200 MCS R,J 00KA 400 JXDS R,J 00KA 600 LXDS R,J 00KA 800 MXDS L 00KA 200 NXDS L 00KA 39
Mains, Feeders, and Incoming Devices Feeders Ratings in KA Type Frame 240V 480V 600V ED6 25 65 25 8 HED4 25 00 42 CED6 25 00 00 00 HDG 50 00 65 20 FD6 250 65 35 22 HFD6 250 00 65 25 HHFD6 250 00 65 25 CFD6 250 00 00 00 HFG 250 00 65 20 JD6 400 65 35 25 HJD6 400 00 65 35 HHJD6 400 00 00 50 SCJD6 400 00 00 00 LD6 600 65 35 25 HLD6 600 00 65 35 HHLD6 600 00 00 50 SCLD6 600 00 00 00 MD6 800 65 50 25 HMD6 800 00 65 50 CMD6 800 00 00 65 SMD6 800 65 50 25 SHMD6 800 00 65 50 SCMD6 800 00 00 65 WLS208 800 65 65 65 WLL208 800 00 00 85 ND6 200 65 50 25 HND6 200 00 65 50 CND6 200 00 00 65 SND6 200 65 50 25 SHND6 200 00 65 50 SCND6 200 00 00 65 WLS22 200 65 65 65 WLL22 200 00 00 85 PD6 600 65 50 25 HPD6 600 00 65 50 CPD6 600 00 00 65 WLS26 600 65 65 65 WLL26 600 00 00 85 RD6 2000 65 50 25 HRD6 2000 00 65 50 WLS220 2000 65 65 65 WLL220 2000 00 00 85 40
Mains, Feeders, and Incoming Devices Standard Disconnects Standard fusible units use the following disconnects: Siemens Visible Blade 30-200A Siemens Molded Case Switch 400, 600A Example of 00A Disconnect Switch Example of 400A Molded Case Switch 4
Mains, Feeders, and Incoming Devices Bus Splice & Bus Duct Bus links are available for connection to existing tiastar/system 89 MCC. The following information is needed for each order: a. Style No. of existing MCC b. Left or right connection to new MCC order c. Ampacity of existing bus (example: 600A, 800A, etc.) d. Size of existing ground and neutral bus Note: For some MCCs (Model 90 and Model 95), a transition arrangement may be necessary. Bus duct connections are supplied on request. They may require a pull box or a special structure depending on the application. Complete bus stub dimensions, bus run drawings, and specification must be supplied. Splice Kits Note: For complete splice kit installation details, refer to instructions supplied with splice kits. Horizontal Bus Splice Splice Bar Adapter Bolts Belleville Washer Parallel Horizontal 42
Mains, Feeders, and Incoming Devices Splice Kits Parallel Horizontal Bus Bar (L2 & L3) Horizontal Bus Splice Bus Bar Clamp Figure 3. 200A, 600A L2 and L3 connection 200A, 600A neutral bus connection Belleville Washer Nut Belleville Washer Nut Horizontal Bus Splice Bus Bar Clamp Horizontal Bus Bar 43
Mains, Feeders, and Incoming Devices TPS3 Surge Protective Devices (SPD) Siemens Integral TPS3s are UL 449 3rd Edition, factory installed SPDs within our MCCs, utilizing optimal electrical system connections to minimize impedance losses. This results in the some of the industry s best installed Voltage Protection Ratings. This SPD has the following features: UL 449 3rd Edition and UL 283 UL Type (consult factory) or Type 4 tested as Type or 2 SPDs 20 ka In (most models) 00-300 ka per phase surge current capacity EMI/RFI filtering or Sine Wave tracking Standard 6 in units LED, Audible Alarm, Dry Contacts, and Ground Integrity Monitoring Diagnostics 200 ka SCCR (most models) UL96A Lightning Protection Master Label Compliant 44
Mains, Feeders, and Incoming Devices Notes 45
Units Plug-in Unit Features All plug-in unit of the same size are interchangeable and can be relocated elsewhere in the motor control center. Unit compartment heights may be modified in the field to accept different size units. Benefits Feature Ease in wiring and inspection Terminal blocks are mounted on a swing-out side barrier. Indicates that a plug-in unit is fully withdrawn from the vertical bus and prevents the unit from falling out of the structure during unit removal. A positive stop in the TEST position. 46
Units Benefits Feature Engages and grounds units at all times. Copper ground clip on plug-in unit. Easy unit access and removal. All doors swing open a minimum of 0. Allows lockout / tagout procedures to be implemented at the unit level. Safety lock capabilities. 47
Units Combination Starters Pilot Devices Motor Starter Molded Case Circuit Breaker Operating Handle A combination starter is the grouping of a motor starter with a fuse or circuit breaker disconnect. Plug-in units in a structure are connected to the vertical bus by a stab assembly on the back of the unit. The stab assembly is then wired to a disconnect device inside the plug-in unit. Power then flows through the circuit breaker, through the motor starter, and ultimately to the motor. NEMA Size Description 0-4 Siemens Heavy Duty NEMA Magnetic Starters and Contactors 5 6 Sirius NEMA Rated Contactors 4,5,6 Sirius Vacuum Contactors Stabs The power stabs engage the vertical power distribution bus when the units are installed in the structure. Plug-in tin plated copper (standard) unit stab assemblies include selfaligning stab clips with spring steel backup springs. Wires from the stab clips to the lineside of the circuit breaker or disconnect switch are contained in the stab housing and are isolated phase-to-phase until the wires enter the MCC. 48
Units Full Voltage Non-Reversing (FVNR) Unit and Full Voltage Reversing (FVR) with Fusible Switch or Circuit Breaker Example of FVNR Example of FVR 49
Units Full Voltage Non-Reversing (FVNR) Unit and Full Voltage Reversing (FVR) with Circuit Breaker or Fusible Switch Maximum Horsepower Rating Circuit Breaker Type NEMA Size 208V 230V 400V 480V 600V Standard Breaker Type MCP Frame Size (Amps) Dimensions in inches (mm) Unit Height W = Width, D = Depth FVNR FVR ka Interrupting Rating at 480V 2 2 7.5 0 7.5 5 0 25 0 25 0 25 25 2 (305) 2 (305) 8 (457) 24 (60) 3 25 30 50 50 50 8 (457) 30 (762) 4 40 50 75 00 00 MCP 25/250 24 (60) 36 (94) 5 75 00 50 200 200 250/400 36 (94) 48 (29) 42 (standard) / 00 (optional) 6 3 50 200 300 400 400 400/600/ 800 7 3 600 600 ND6 4 200 48 (29) 72 (829) 20W x 20D (508W x 508D) 72 (829) 30W (762W) N/A 42 / 65 Full Voltage Contactor (FVC) Unit with Circuit Breaker or Fusible Switch NEMA Size Maximum KW Resistance Heating Loads Circuit Breaker Type Fusible Type (For Maximum KW at 480V) 208V 230V 400V 480V 600V Circuit Breaker Frame Size (Amps) Dimensions in inches (mm) Unit Height 0.8.9 8.7 23.8 3 25 2 (305) ka Interrupting Rating at 480V 2 00 Fusible Switch / Fuse Clip (Amps) Dimensions in inches (mm) Unit Height W = Width, D = Depth 30 / 30 2 (305) 2 6.2 7.9 3.2 35.8 46.7 25 2 (305) 60 / 60 2 (305) 3 32 35 62 7 93 25 8 (457) 00 / 00 24 (60) 4 48 54 94 07 40 25 / 250 24 (60) 200 / 200 42 (067) 5 08 9 206 238 3 250 / 400 36 (94) 6 3 98 28 346 437 570 600 48 (29) 800 72 (829) 7 3 259 286 476 572 747 200 72 (829) 65 ) The addition of oversized CPTs, relays, timers, etc. may increase unit height. 2) For other available voltage ratings, consult Siemens 3) Fixed mounted units (not plug-in). JXD6 MCS / 400 LXD6 MCS / 600 MXD6 MCS / 800 NXD6 MCS / 200 60 (524) 72 (829) 72 (829) 30W (762W) 72 (829) 50W x 20D (270W x 508D) ka Interrupting Rating at 480V 2 00 50
Units Fusible Type (For Maximum HP at 480V), Type Fusible Switch/ Fuse Clip (Amps) Dimensions in inches (mm) Unit Height W = Width, D = Depth FVNR FVR ka Interrupting Rating at 480V 2 NEMA Size ) The addition of oversized CPTs, relays, timers, etc. may increase unit height. 2) For other available voltage ratings, consult Siemens 3) Fixed mounted units (not plug-in) 4) Thermal magnetic breaker (not MCP) 30 / 30 2 (305) 8 (457) 60 / 60 2 (305) 24 (60) 2 00 / 00 24 (60) 36 (94) 3 200 / 200 42 (067) 48 (29) 4 JD6 MCS / 400 60 (524) 60 (524) 00 5 MD6 MCS / 800 72 (829) ND6 MCS / 200 72 (829) 40W x 20D (06W x 508D) 72 (829) 30W (762W) 6 3 N/A 7 3 Dual Full Voltage Non-Reversing (DFVNR) Unit with Circuit Breaker Maximum Horsepower Rating Circuit Breaker Type NEMA Size 208V 230V 400V 480V 600V Standard Breaker Type MCP Frame Size Dimensions in inches (mm) Unit Height ka Interrupting Rating at 480V 2 7.5 7.5 0 0 0 MCP 25 8 (457) 00 ) The addition of oversized CPTs, relays, timers, etc. may increase unit height. 2) For other available voltage ratings, consult Siemens 5
Units Two Speed One Winding (2SW) and Two Speed Two Winding (2S2W) with Circuit Breaker or Fusible Switch Constant or Variable Torque Maximum Horsepower Rating NEMA Size 208V 230V 400V 480V 600V 7.5 7.5 0 0 0 Circuit Breaker Type Standard Breaker Type MCP Frame Size (Amps) Dimensions in inches (mm) Unit Height W=Width, D=Depth 2SW 2S2W 24 (60) 24 (60) 2 0 5 25 25 25 25 24 (60) 24 (60) 3 25 30 50 50 50 48 (29) 36 (94) 4 40 50 75 00 00 MCP 25 / 250 60 (524) 48 (29) 5 3 75 00 50 200 200 250 / 400 72 (829) 72 (829) 30W (762W) 30W (762W) 6 3 50 200 300 400 400 600 / 800 Consult 72 (829) Siemens 30W (762W) ) The addition of oversized CPTs, relays, timers, etc. may increase unit height. 2) For other available voltage ratings, consult Siemens 3) Fixed mounted units (not plug-in). ka Interrupting Rating at 480V 2 42 (standard) / 00 (optional) Constant Horsepower Maximum Horsepower Rating NEMA Size 208V 230V 400V 480V 600V 5 5 7.5 7.5 7.5 Circuit Breaker Type Standard Breaker Type MCP Frame Size (Amps) Dimensions in inches (mm) Unit Height W = Width, D = Depth 2SW 2S2W 24 (60) 24 (60) 2 7.5 0 20 20 20 25 24 (60) 24 (60) 3 20 25 40 40 40 36 (94) 30 (762) 4 30 40 50 75 75 MCP 25 / 250 48 (29) 36 (94) 5 3 60 75 00 50 50 250 / 400 6 3 00 50 200 300 300 400 / 600 72 (829) 30W (762W) Consult Siemens 72 (829) 30W (762W) 72 (829) 30W (762W) ka Interrupting Rating at 480V 42 (standard) / 00 (optional) ) The addition of oversized CPTs, relays, timers, etc. may increase unit height. 2) For other available voltage ratings, consult Siemens 3) Fixed mounted units (not plug-in). 52
Units Fusible Type (For Maximum HP at 480V) Fusible Switch/ Fuse Clip (Amps) Dimensions in inches (mm) Unit Height W = Width, D = Depth ka Interrupting Rating at 480V 2 NEMA Size 2SW 2S2W 30 / 30 24 (60) 24 (60) 60 / 60 24 (60) 24 (60) 2 00 / 00 36 (94) 30 (762) 3 200 / 200 48 (29) 36 (94) 00 4 JD6 72 (829) 72 (829) MCS / 400 30W (762W) 30W (762W) 5 3 MD6 Consult 72 (829) MCS / 800 Siemens 40W (06W) 6 3 Fusible Type (For Maximum HP at 480V) Fusible Switch / Fuse Clip (Amps) Dimensions in inches (mm) Unit Height W = Width, D = Depth 2SW 2S2W ka Interrupting Rating at 480V 2 NEMA Size 30 / 30 24 (60) 24 (60) 60 / 60 24 (60) 24 (60) 2 00 / 00 48 (29) 36 (94) 3 200 / 200 60 (524) 48 (29) 00 4 JD6 MCS / 72 (829) 72 (829) 400 30W (762W) 30W (762W) 5 3 MD6 MCS / Consult 72 (829) 800 Siemens 40W (06W) 6 3 53
Units Combination Starters Reduced Voltage Autotransformer (RVAT) Non-Reversing with Circuit Breaker or Fusible Switch Closed Transition Maximum Horsepower Rating NEMA Size 208V 230V 400V 480V 600V 2 0 5 25 25 25 Circuit Breaker Type Standard Breaker Type Dimensions in inches (mm) Unit Height W = Width, D = Depth 42 (067) ka Interrupting Rating at 480V 2 3 25 30 50 50 50 42 (067) 4 40 50 75 00 00 MCP 48 (29) 42 (standard) / 00 (optional) 5 3 75 00 50 200 200 72 (829), 30W (762W) 6 3 50 200 300 400 400 72 (829), 30W (762W) 7 3 600 600 ND6 4 Consult Siemens 42 / 65 ) The addition of oversized CPTs, relays, timers, etc. may increase unit height. 2) For other available voltage ratings, consult Siemens 3) Fixed mounted units (not plug-in) 4) Thermal magnetic breaker (not MCP) Reducing Voltage Wye Delta Closed (YDC) Transition and Reducing Voltage Wye Delta Open (YDO) Transition NEMA Size Maximum Horsepower Rating 208V 230V 400V 480V 600V 2 20 25 25 40 40 Circuit Breaker Type Standard Breaker Type Dimensions in inches (mm) Unit Height W = Width, D = Depth YDO YDC 30 (762) 42 (067) ka Interrupting Rating at 480V 2 3 25 30 50 75 75 36 (94) 48 (29) 4 60 60 75 50 50 MCP 36 (94) 48 (29) 5 3 50 50 50 300 300 72 (829) 30W (762W) 72 (829) 30W (762W) 42 (standard) / 00 (optional) ) The addition of oversized CPTs, relays, timers, etc. may increase unit height. 2) For other available voltage ratings, consult Siemens 3) Fixed mounted units (not plug-in) 54
Units Fusible Type (For Maximum HP at 480V) Fusible Switch / Fuse Clip (Amps) Dimensions in inches (mm) Unit Height W = Width, D = Depth ka Interrupting Rating at 480V 2 NEMA Size 60 / 60 42 (067) 2 00 / 00 48 (29) 3 200 / 200 60 (524) 4 00 JD6 MCS / 400 72 (829), 30W (762W) 5 3 MD6 MCS / 800 72 (829), 30W (762W) 6 3 ND6 MCS / 200 Consult Siemens 7 3 Fusible Type (For Maximum HP at 480V) Fusible Switch / Fuse Clip (Amps) Dimensions in inches (mm) Unit Height W = Width, D = Depth YDO YDC 00 / 00 36 (94) 48 (29) ka Interrupting Rating at 480V 2 NEMA Size 2 200 / 200 48 (29) 60 (524) 3 JD6 MCS / 400 72 (829) 72 (829) 00 4 LD6 MCS / 600 72 (829) 30W (762W) 72 (829) 30W (762W) 5 3 55
Units Compact High Density (HD) Combination Starters While meeting UL and NEMA standards, our Compact Modular High Density Units reduces unit size by 6 (up to 50%) for starters sizes -4; thus, reducing footprint and saving floor space. Full Voltage Non-Reversing (FVNR) Unit with Circuit Breaker Maximum Horsepower Rating NEMA Size 208V 230V 480V 7.5 7.5 0 Circuit Breaker Type Standard Breaker Type MCP Frame Size (Amps) Unit Height Dimensions in inches (mm) 6 (52) 2 0 5 25 25 MCP 3 25 30 50 2 (305) 4 40 50 00 25/250 8 (457) Full Voltage Contactor (FVC) Unit with Circuit Breaker Maximum KW Resistance Heating Loads NEMA Size 208V 230V 480V 9.7 0.7 22 Circuit Breaker Type Standard Breaker Type MCP Frame Size (Amps) Unit Height Dimensions in inches (mm) 6 (52) 2 6.2 7.9 37 25 MCP 3 32 35.8 74 2 (305) 4 48 54 2 25/250 8 (457) ka Interrupting Rating at 480V 00 ka Interrupting Rating at 480V 00 For other available voltage ratings contact Siemens 2 Only ESP 200 overload relays are available 3 Only 22mm pilot devices are available; maximum of 4 pilot devices may be used 56
Units Reduced Voltage Soft-Starter (RVSS) Units Siemens soft-start controllers and starters incorporate the latest in solid-state technology to provide precise control in the starting of AC induction motors. Solid state reduced voltage starting allows motor voltage to be gradually applied, reducing potentially damaging high inrush currents and starting torques. These controls are easy to set up, operate, troubleshoot and repair. They are fully adjustable for many applications and with voltage ramp capability, can handle varying loads. Soft-start controllers can lower operating costs by reducing downtime due to equipment maintenance and repair; and minimize product and drive system damage caused by hard physical starts or stops. Siemens Soft-Start controllers with the energy saving feature conserve energy during lightly loaded conditions by reducing the motor voltage and current Overview The advantages of the SIRIUS soft starters at a glance: Soft starting and soft stop Stepless starting Reduction of current peaks Avoidance of mains voltage fluctuations during starting Reduced load on the power supply network Reduction of the mechanical load in the operating mechanism Considerable space savings and reduced wiring compared with mechanical reduced voltage starters Maintenance-free switching Fits perfectly in the SIRIUS modular System 57
Units SIRIUS 3RW40 SIRIUS 3RW40 soft starters include soft start and soft stop, and internal bypass. At the same time they come with additional functions, i.e. selectable solid-state motor overload, intrinsic device protection and adjustable current limiting, as well as a new patented two-phase control method (Polarity Balancing) that is unique in this rating range. SIRIUS 3RW40 soft starters are part of the SIRIUS modular system. This results in advantages such as identical sizes and a uniform connection system. Thanks to their particularly compact design, SIRIUS 3RW40 soft starters are only half as big as comparable wye-delta starters. Hence they can be mounted in compact space requirements in the control cabinet. Configuring and installation are carried out quickly and easily thanks to the 3-wire connection. SIRIUS 3RW40 for three-phase motors Soft starters rated up to 300 Hp (at 460 V) for standard applications in three phase power systems. Extremely small sizes, low power losses and simple commissioning are just three of the many advantages of the SIRIUS 3RW40 soft starters. Application areas: Fans Pumps Building/construction machines Presses Escalators Transport systems Air conditioning systems Ventilators Assembly lines Operating mechanisms 58
Units SIRIUS 3RW44 In addition to soft starting and soft stopping, the solid-state SIRIUS 3RW44 soft starters provide numerous functions for higher-level requirements. They cover a rating range up to 900Hp at 460 V in the inline circuit. The SIRIUS 3RW44 soft starters are characterized by a compact design for space-saving and clearly arranged control cabinet layouts. For optimized motor starting and stopping, the innovative SIRIUS 3RW44 soft starters are an attractive alternative with considerable savings potential compared to applications with a frequency converter. The new torque control and adjustable current limiting enable these high feature soft starters to be used in nearly every conceivable task. They reliably mitigate the sudden torque applications and current peaks during motor starting and stopping. This creates savings potential when calculating the size of the control gear and when servicing the machinery installed. Be it for inline circuits or inside delta circuits the SIRIUS 3RW44 soft starter offers savings especially in terms of size and equipment costs. Combinations of various starting, operating and ramp-down possibilities ensure an optimum adaptation to the application specific requirements. Operating and commissioning can be performed by means of the user-friendly keypad and a menu prompted, multi-line graphic display with background lighting. The optimized motor ramp-up and ramp down can be effected by means of just a few settings with a previously selected language. Four-key operation and plain-text displays for each menu point guarantee full clarity at every moment of the parameterization and operation. Application areas Pumps Mills Ventilators Saws Compressors Crushers Water transport Mixers Conveying systems and lifts Centrifuges Hydraulics Industrial cooling and refrigerating systems 59
Units MCC Enclosures 480V Solid State Reduced Voltage NEMA MCC Enclosures Rating HP RVSS Type Rated Amperes 5 3RW40 9 0 3RW40 9 5 3RW40 24 20 3RW40 28 25 3RW40 34 30 3RW40 42 40 3RW40 58 50 3RW40 70 75 3RW40 7 00 3RW40 45 50 3RW40 205 Dimensions - In. (mm) Mounting Height 8 (457) 24 (60) 36 (94) 200 3RW40 35 48 (29) 300 3RW40 385 72 (829) 5 3RW44 26 20 3RW44 32 25 3RW44 42 30 3RW44 52 40 3RW44 68 50 3RW44 82 60 3RW44 00 75 3RW44 7 00 3RW44 45 25 3RW44 80 50 3RW44 25 200 3RW44 280 250 3RW44 385 400 3RW44 494 450 3RW44 562 500 3RW44 693 36 (94) 48 (29) 72 (829) Structure W x D 20 x 5 (508 x 38) 30 x 5 (762 x 38) ka Interrupting Rating 600 3RW44 850 65 750 3RW44 970 Consult Siemens 42 800 3RW44 076 Consult Siemens For other available voltage ratings, consult Siemens. For other enclosure types, consult Siemens. Ratings are based on CLASS 20 overloads and 6 starts per Hour. Consult Siemens for other applications. Dimensions shown are for circuit breaker or fusible disconnects. RVSS with bypass and / or isolation contactors require extra mounting space. Consult Siemens for further information. 3RW40 Units include line side isolation contactor Fixed mounted units (not plug-in). 00 60
Units Variable Frequency Drive (VFD) Units Micromaster 440 (MM440) Application The MICROMASTER 440 inverter is suitable for a variety of variable-speed drive applications. Its flexibility provides for a wide spectrum of applications. These also include cranes and hoisting gear, high-bay warehouses, production machines for food, beverages and tobacco, packaging machines etc.; i.e. applications which require the frequency inverter to have a higher functionality and dynamic response than usual. The inverter is especially characterized by its customer-oriented performance and ease of-use. Its large voltage range enables it to be used all over the world. 6
Units Micromaster 440 (MM440) Design The MICROMASTER 440 inverter has a modular design. The operator panels and modules can be easily exchanged. International standards The MICROMASTER 440 inverter complies with the requirements of the EU low voltage directive. The MICROMASTER 440 inverter has the marking acc. to and c certified c-tick Main characteristics Easy, guided start-up Modular construction allows maximum configuration flexibility Six programmable isolated digital inputs Two scalable analog inputs (0 V to 0 V, 0 ma to 20 ma) can also be used as a 7th/8th digital input Two programmable analog outputs (0 ma to 20 ma) Three programmable relay outputs (30 V DC/5 A resistive load; 250 V AC/2A inductive load) Low-noise motor operation thanks to high pulse frequencies, adjustable (observe derating if necessary) Complete protection for motor and inverter. Options (overview) EMC filter, Class A/B LC filter and sinusoidal filter Line commutating chokes Output chokes Gland plates Basic Operator Panel (BOP) for parameterizing the inverter Plain text Advanced Operator Panel (AOP) with multi-language display Communication modules PROFIBUS DeviceNet CANopen Pulse encoder evaluation module PC connection kits Mounting kits for installing the operator panels in the control cabinet doors PC start-up tools executable under Windows 98 and NT/2000/ME/XP Professional TIA integration with Drive ES 62
Units Micromaster 440 (MM440) MCC Enclosures 480V Variable Frequency Drives NEMA A MCC Enclosures 2 Dimensions - in. (mm) 4, 6 Rating HP 3 Drive Type Rated Amperes Mounting Height Structure W x D ka Interrupting Rating at 480V 2 4 8 (457) 5 0.2 7.5 6 24 (60) 0 8.4 5 26 36 (94) 20 32 25 38 48 (29) 7 30 45 40 MM440 62 48 (29) 5,7 50 76 60 (624) 7 60 90 75 0 20 x 5 (508 x 38) 25-65 (standard) / 00 (standard fusible, optional circuit breaker) 00 45 25 78 50 205 200 250 72 (829) 7 20 x 5 5 (508 x 38) 30 x 5 5 (762 x 38) For other available voltage rating, consult Siemens 2 For other enclosure types, consult Siemens 3 Ratings are for Variable Torque applications. Consult Siemens for other applications 4 Dimensions shown are for circuit breaker or fusible disconnects except as noted 5 Fusible disconnect unit is larger, consult Siemens 6 Drives with bypass and/or isolation contactors require extra mounting space. Consult Siemens for further information. 7 Fixed mounted units (not plug-in) 63
Units 600V Variable Frequency Drives NEMA A MCC Enclosures Rating HP 3 Drive Type Rated Amperes Dimensions - in. (mm) 3, 5 Mounting Height Structure W x D ka Interrupting Rating at 480V 2 2.7 5 6. 7.5 9 0 24 (60) 5 7 20 22 25 27 MM440 30 32 40 4 48 (29) 6 20 x 5 (508 x 38) 8-22 (standard) / 00 (standard fusible, optional circuit breaker) 50 52 60 62 60 (624) 6 75 77 00 99 72 (829) 6 20 x 5 4 25 25 For other enclosure types, consult Siemens 2 Ratings are for Variable Torque applications. Consult Siemens for other applications 3 Dimensions shown are for circuit breaker or fusible disconnects except as noted 4 Fusible disconnect unit is larger, consult Siemens 5 Drives with bypass and/or isolation contactors require extra mounting space. Consult Siemens for further information. 6 Fixed mounted units (not plug-in) 64
Units Micromaster Drives Technical Data MM440 - Technical Data Voltage and power ranges 200 240 V, ± 0%, 0.66 to 60 HP (CT / VT) 380 480 V, ± 0%, 0.5 to 50 HP (CT) 380 480 V, ± 0%, 0.5 to 200 HP (VT) 500 600 V, ± 0%,.0 to 00 HP (CT) 500 600 V, ± 0%,.0 to 25 HP (CT) Operating temperature 0 C to +40 C Process control Types of control Internal PID controller (autotuning) Vector control, FCC (Flux Current Control), multipoint characteristic (parameterizable V/f characteristic), V/f characteristic MM420 - Technical Data Voltage and power ranges Operating temperature 0 C to +50 C 200-240 V, ± 0%, 0.6 to 7.5 HP 380-480 V, ± 0%,, 0.5 to 5 HP Process control Types of control Inputs Outputs PID process controller V / Hz, Voltage Boost, Slip Compensation, FCC (Flux Current Control) 3 digital inputs, analog input analog output, relay output MM430 - Technical Data Voltage and power ranges 380-480 V, ± 0%, 0 to 25 HP Operating temperature 0 C to +40 C Process control Types of control Inputs Outputs PID process controller V / Hz, Voltage Boost, Slip Compensation, FCC (Flux Current Control) 6 digital inputs, 2 analog inputs, PTC/KTY input 2 analog outputs, 3 relay outputs 65
Units Factory Options Contactor Options Bypass Contactor (None/Automatic/Manual/Selectable) Input Isolation Contactor Output Isolation Contactor VFD Options Operator Panel (Basic/Advanced/None) Door Mounted Operator Panel (None/Single VFD/ Advanced Operator Panel (AOP) Communication Module (PROFIBUS, DeviceNet, CANopen, LON, etc.) Pulse Encoder Module PC to VFD connection kit Reactor, Filter, and Other Options Input/Output Reactor Passive harmonic filter RFI filter Output filter (DV/DT, sine wave) Pulse Resistor Braking Semiconductor Fuses Pollution Degree Ratings according to UL6800-5- MCCs containing VFDs should be installed in a Pollution Degree 2 environment in accordance with UL6800-5-. If an MCC with VFD is to be placed in a Pollution Degree 3 or higher environment, a NEMA2 rated MCC should be installed. Pollution Degree 2 3 4 Description No pollution or only dry, non-conductive pollution occurs. The pollution has no influence. Normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation is to be expected, when the VFD is out of operation. Conductive pollution or dry non-conductive pollution occurs, which becomes conductive due to condensation, which is to be expected. The pollution generates persistent conductivity caused, for example by conductive dust or rain or snow. 66
Units SINAMICS G20C SINAMICS G20C has been especially designed for an economic, space-saving and easy-to-operate frequency converter providing a multitude of functions. This device combines in particular compactness with superior power density and is characterized by fast installation and commissioning. Smallest size Compact design (integrated braking chopper) Fast mechanical installation (i.e. pluggable terminals) Easy to use Simple, optimized commissioning with the STARTER tool Effective, adequate parameter set (simple storing and cloning functions using IOP, BOP-2 or SD card) Usable with IOP or BOP-2 operator panels Leading edge technology Energy-efficient, encoder-less vector control - automatic flow reduction with V/F ECO Safety Integrated (Safe Torque Off) Communication PROFIBUS DP, PROFINET, CAN and USS/ Modbus RTU Application For industrial and commercial applications (secondary drive in production machines or generally for water/waste water, automotive). Application examples include Mixers, Extruders, Simple pumps, fans, compressors, Vibrator motors, Simple wire drawing machines. 67
Units SINAMICS G20C Design SINAMICS G20C is a compact inverter where the Control Unit (CU) and Power Module (PM) function units are combined in one device. SINAMICS G20C can be integrated into the widest range of applications, either using the integrated digital and analog inputs or via the integrated fieldbus interface (available in the USS/ Modbus RTU, PROFINET, PROFIBUS DP, CANopen versions). Especially the product versions with integrated PROFIBUS DP or Profinet interface make full integration into the Siemens TIA family possible, therefore allowing the advantages of the seamless TIA product family to be fully utilized. SINAMICS G20C devices are preset in the factory so that they can be immediately connected to PROFIBUS DP or Profinet fieldbuses and used without parameterization. G20C- Technical Data Output Ratings Dimensions - in. (mm) Frame Size LO-OL LO-OL HI-OL HI-OL Mounting A hp A hp Height A.4 0.5. 0.5 A.9 0.75.4 0.5 A 2.6.9 0.75 Structure W x D IR A 3.5 2 2.6 8 (457) A 4.8 2 3.5 2 A 6.2 3 4.8 2 A 7.5 3 6.2 3 20 x 5 (508 x 38) 65ka B 0.6 5 7.5 3 B 4.0 0 0.6 5 24 (60) C 2.3 5 4.0 0 C 26.4 5 2.3 5 30 (762) C 3.5 20 26.4 5 Circuit Breaker, Reactor (Line or Load) and Drive Included. Overload capability: High overload (HO): 200 % base load current IH for 3 s plus 50 % base load current IH for 57 s within a 300 s cycle time Light overload (LO): 50 % base load current IH for 3 s plus 0 % base load current IH for 57 s within a 300 s cycle time 68
Units SINAMICS G20C Factory Options Technical Data Voltage and power ranges 380 480 V, 0.5 to 20 HP (LO) 380 480 V, 0.5 to 5 HP (HO) Operating temperature 0 C to +40 C Process control Types of control Communications Internal PID controller (auto-tuning) Vector control, FCC (Flux Current Control), multipoint characteristic (parameterizable V/f characteristic), V/f characteristic PROFIBUS DP, PROFINET, CANopen and USS/ Modbus RTU For additional G20C information, please see the SINAMICS and Motors for Single-Axis Drives Catalog, Order No. E86060-K553-A0-A-7600. Contactor Options Bypass Contactor (None/Automatic/Manual/Selectable) Input Isolation Contactor Output Isolation Contactor VFD Options Operator Panel (BOP-2, IOP, none) Door Mounted Operator Panel PC Inverter Connection Kit 2 Reactor, Filter, and Other Options Input/Output Reactor Passive harmonic filter RFI filter Output filter (DV/DT, sine wave) Pulse Resistor Braking Semiconductor Fuses 69
Units SINAMICS G20 SINAMICS G20 is a modular drive inverter system that comprises various function units. These are essentially: Control Unit (CU) and Power Module (PM). The CU controls and monitors the PM and the connected motor in several operating modes that can be selected. It supports communication with a local or central controller and monitoring devices. With many innovative functions Safety Integrated for safety-relevant machines and systems, capable of regenerative feedback into the line supply for energy saving Fast commissioning STARTER tool and data backup using the BOP-2, IOP or MMC/SD card Efficient and consistent solutions via Totally Integrated Automation (TIA), consistency from SINAMICS through to the automation level Application Machines and plants in industrial and commercial applications (machinery construction, automotive, textiles, chemical industry, printing, steel). Application examples include: Pumps and fans, Compressors, Centrifuges, Conveyor systems. Design Application-oriented design of SINAMICS G20 SINAMICS G20 standard inverters are modular inverters for standard drives. Selection of the SINAMICS G20 is reduced to two or three steps thanks to the modular system used. 70
Units Selecting the Power Module PM240 Power Modules PM240 Power Modules are suitable for many applications. The PM240 has an integrated braking chopper in frame sizes FSA up to FSF and has the possibility of connecting a braking resistor. For frame size FSGX, an optional pluggable braking module can be ordered. PM250 Power Modules PM250 power modules are suitable for the same applications as the PM240, but they are specialized to address conveyor-related applications - where the braking energy is directly fed back into the line supply using the unique technology of Efficient Infeed Technology. This feature provides the ability to feed energy back into the supply system in the generator mode (electronic braking) so that the energy in not wasted in a braking resistor. 7
Units SINAMICS G20 Selecting the Control Unit The optimum Control Unit is selected, based on the number of I/Os and any additional functions required such as Safety Integrated or HVAC. The communication options are already integrated and do not have to be additionally ordered or plugged in. Three product series are available corresponding to the particular application. MCC Control Unit Options CU230P-2 HVAC CU240B-2 CU240E-2 CU250S-2 CU230P-2 DP CU240B-2 DP CU240E-2 DP CU250S-2 DP CU230P-2 CAN CU240E-2 F CU250S-2 PN CU230P-2 PN CU240E-2 DP-F CU250S-2 CAN CU240E-2 PN CU240E-2 PN-F Extended I/O configuration Vector and servo control Encoder feedback Basic and Extended Safety Functions USS, Modbus, PROFIBUS, PROFINET Basic I/O configuration USS, Modbus, PROFIBUS, PROFINET Standard I/O configuration STO as standard Optional Basic Safety Functions USS, Modbus, PROFIBUS, PROFINET Extended I/O configuration Vector and servo control Encoder feedback Basic and Extended Safety Functions USS, Modbus, PROFIBUS, PROFINET 72
Units Selecting the Control Unit (cont.) CU230 Control Units The CU230 Control Units have been specifically designed for pump, fan and compressor applications. CU240 Control Units The CU240 Control Units are suitable for a wide range of applications in a general machine construction, such as conveyor belts, mixers and extruders. CU250 Control Units The CU250 Control Unit is particularly suited for drives with high requirements in speed and torque accuracy. Selecting Optional System Components Intelligent Operator Panel IOP Graphic display with bar-type diagrams, e.g. for status values such as pressure or flow rate. Basic Operator Panel BOP-2 Menu navigation and 2-line display permit fast and user-friendly commissioning of the inverter. Simple basic commissioning by simultaneously displaying parameter value, as well as the option of filtering parameters. 73
Units SINAMICS G20 Technical Data Output Ratings Dimensions - in. (mm) PM240 PM250 Frame Size LO-OL LO-OL HI-OL HI-OL A hp A hp A.2 0.5.3 0.5 A.6 0.5.7 0.75 A 2.0 0.75 2.2 A 2.9 3..5 A 3.8 2 4. 2 B 5.5 3 5.9 3 B 7.2 3 7.7 5 B 9.5 5 0.2 5 C 6.7 0 3.2 7.5 C 23.3 5 9 0 C 29.8 20 26 5 D 35.3 25 32 20 D 4.9 30 38 25 D 55.8 40 45 30 E 69.8 50 60 40 E 83.7 60 75 50 F 02.3 75 90 60 F 34.9 00 0 75 F 65.5 25 45 00 F 90.7 50 78 25 F 240.0 50 200 50 Gx 264.3 200 250 200 Gx 323.8 250 302 250 Gx 47.4 350 370 300 D 35.3 25 32 20 D 4.9 30 38 25 D 55.8 40 45 30 E 69.8 50 60 40 E 83.7 60 75 50 F 02.3 75 90 60 F 34.9 00 0 75 F 65.5 25 45 00 Circuit Breaker, Reactor (Line or Load) and Drive Included. 2 Fixed Mounted Mounting Height 8 (457) 24 (60) 36 (94) 48 (29) 60 (624) 72 (829) 48 (29) 60 (624) 72 (829) Structure W x D 20 x 5 (508 x 38) 20 x 5 2 (508 x 38) 20 x 20 2 (508 x 508) 50 x 20 2 (270 x 508) 20 x 5 2 (508 x 38) 20 x 20 2 (508 x 508) IR 65ka Overload capability: High overload (HO): Up to 00 HP PM240 and all PM250 (HO): 2 base-load current IH (i. e. 200 % overload) for 3 s plus.5 base-load current IH (i. e. 50 % overload) for 57 s within a cycle time of 300 s From 25 HP PM240:.6 base-load current IH (i. e. 60 % overload) for 3 s plus.36 base-load current IH (i. e. 36 % overload) for 57 s within a cycle time of 300 s Light overload (LO): Up to 00 HP PM240 and all PM250 (LO):.5 base-load current IL (i. e. 50 % overload) for 3 s plus. base-load current IL (i. e. 0 % overload) for 57 s within a cycle time of 300 s From 25 HP PM240:.5 base-load current IL (i. e. 50 % overload) for s plus. base-load current IL (. e. 0 % overload) for 59 s within a cycle time of 300 s 74
Units Technical Data Voltage and power ranges 380 480 V, 0.5 to 350 HP (LO) 380 480 V, 0.5 to 300 HP (HO) Operating temperature 0 C to +40 C Process control Internal PID controller (autotuning) Types of control Factory Options Contactor Options Bypass Contactor (None/Automatic/Manual/Selectable) Input Isolation Contactor Output Isolation Contactor VFD Options Operator Panel (BOP-2, IOP, none) Door Mounted Operator Panel PC Inverter Connection Kit 2 Vector control, FCC (Flux Current Control), multipoint charac- teristic (parameterizable V/f characteristic), V/f characteristic Reactor, Filter, and Other Options Input/Output Reactor Passive harmonic filter RFI filter Output filter (DV/DT, Sinewave) Pulse Resistor Braking Semiconductor Fuses 8-pulse (for FSE and FSF) For additional G20 information, please see the SINAMICS and Motors for Single-Axis Drives Catalog, Order No. E86060-K553-A0-A-7600. Pollution Degree Ratings according to UL6800-5- MCCs containing VFDs should be installed in a Pollution Degree 2 environment in accordance with UL6800-5-. If an MCC with VFD is to be placed in a Pollution Degree 3 or higher environment, a NEMA2 rated MCC should be installed. Pollution Degree 2 3 4 Description No pollution or only dry, non-conductive pollution occurs. The pollution has no influence. Normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation is to be expected, when the VFD is out of operation. Conductive pollution or dry non-conductive pollution occurs, which becomes conductive due to condensation, which is to be expected. The pollution generates persistent conductivity caused, for example by conductive dust or rain or snow. 75
Units Unit Options Overload Options Overload Protection Thermal Bimetal Ambient Compensated Single Phase and Three Phase (Standard) ESP200 Solid State Overload Relay (Optional) SIMOCODE (Optional) Description Class 0 or Class 20 Protection +/- 5% Setting of nominal trip current Trip Class 5, 0, 20, or 30 can easily be set by two DIP switches Eliminates the need for heaters Solid State Overload Protection Class 5-40 Multifunctional, electronic full motor protection Detailed operating, service, and diagnostics data via PROFIBUS Bimetal Ambient Compensated Thermal Overload Bimetal ambient compensated overload relays protect both the motor and equipment by opening the control circuit when the motor experiences an overload condition. The bimetal overload relay may be set for either manual or automatic reset and can be supplied with standard Class 20 heater elements or optional Class 0 heater elements as required. An ambient compensated model of the bimetal overload is available. ESP 200 Solid State Overload Relay Building and improving on past successes, self-powered ESP200 overload relays are a revolution for both industrial and construction applications. These overload relays provide accuracy unmatched in the market. With repeat accuracy of greater than 99%, trips can beset to the most specific conditions, resulting in both longer motor life and cost savings. The ESP200 over-load relay is very simple to configure. Just set the FLA dial to match the FLA of the motor nameplate and set the DIP switches per the faceplate engraving. 76
Units SIMOCODE Smart MCC uses SIMOCODE in the units to give the customer a true motor management system. SIMOCODE pro is the flexible and modular motor control system for low-voltage motors. It can easily and directly be connected to automation systems via PROFIBUS and covers all functional requirements between the motor starter and the automation system including the fail-safe disconnection of motors. Further, SIMOCODE pro combines in just one compact system all required protection, monitoring, safety and control functions. The motor management system thus helps you to increase the process control quality and reduce costs at the same time from planning through installation right to operation or service of a plant or system. In the MCCs, SIMOCODE C and SIMCODE V are available. Benefits from SIMOCODE pro: Simple configuration Protects your flexibility with the aid of optional expansion modules Gain transparency throughout your system with extensive data provision SIMOCODE pro motor management is structured in functionally graded series: SIMOCODE pro C, as a compact system for direct-on-line starters and reversing starters or the actuation of a circuit breaker with PROFIBUS-interface SIMOCODE pro V, as a variable system with all control functions and with the possibility of expanding the inputs, outputs and other functions of the system using expansion modules. SIMOCODE Pro C SIMOCODE Pro V 77
Units SIMOCODE Expansion Expansion Possibilities SIMCODE pro C (Basic Unit ) SIMCODE pro V PB (Basic Unit 2) Operator panels X X Operator panel with display X Current measuring modules X X Current/voltage measuring module (Qty) X Decoupling module (Quantity) X Expansion modules (number): Digital modules 2 Fall Safe digital module 2 Analog module Ground fault module Temperature module X= available, - = not available ) When an operator panel with display and/or decoupling module is used, restrictions on the number of connection modules connectable per basic unit must be observed. 2) The fall-safe digital module can be used instead of one of the two digital modules. SIMOCODE Factory Programming When this selection is requested, functional unit programming per the unit wiring schematic will be provided after the customer supplies the proper information. For a list of standard programming blocks, please see the SIMOCODE Pro Control Reference Manual, E8700-A024-T004-A5-MCC. Commissioning / Integration / Process type programming is not part of this feature. 78
Units Terminal Blocks Control Terminal Blocks Screw-mounted stationary control terminals are standard for both type B and C units. All terminal blocks are located at the right front of the unit for access from the vertical wireway. Unit control terminal blocks are: White in color Box Type with Tang (wire clamped between tang and collar) Supplied with White Marking Strip Terminals supplied in groups of 3 for Stationary terminal blocks or groups of 4 for Pull- Apart terminal blocks as required for application. Standard terminal block mounting allows for a maximum of 2 Stationary or 20 Pull-Apart terminal points for control. Type Wire Range Amp Rating Voltage Stationary 22-8 ga. 40A 600V Pull-Apart 6-2 ga. 25A 600V Stationary Terminal Blocks Clamping the wire between a tang and a collar provides the following advantages: No twisted off strands. A constant locking torque keeps screws in position. Hardened stainless steel clamping collar eliminates stripped thread problems. Terminal blocks are also available with screw type terminals for ring tongue lugs. Pull-Apart Terminal Blocks Pull-apart terminal blocks are available. They have the same features as stationary blocks, except that they are pull-apart and interlock mechanically, providing a terminal block assembly in which individual groups are free to move to permit electrical separation while remaining coupled mechanically to the series. 79
Units Load Terminal Wire Ranges Starter Size Wire Range Starter Load Terminal Maximum* AWG Type Bd, Bt, & C Wiring Power Terminal Block Wire Range Stationary Optional Pull-Apart 0- #4 to #8 #8 #22 to #8 X X 2 #2 to #2 #6 #8 to #2 X X 3 #8 to #2/0 # #4 to #2/0 X 4 #6 to 250MCM 2/0 5 () #4 to 600MCM (2) #/0 to (2) 250MCM 350MCM 6 #2 to (2) 600MCM () 600MCM (2) 350 MCM *To maintain proper bending space for load cables direct to the starter do not exceed max. wire guage listed. Type C Wiring Terminal Blocks Type C wiring uses stationary type terminal blocks. Their standard location is in the top 2 horizontal wireway. C terminals may also be located in the bottom 6 horizontal wireway. Three rows of terminals for control and load may be mounted at the top. Space is available for 42 terminals per row for control and load. For each unit size 2, reduce 3 terminals per unit, due to larger load blocks. For each unit size 3, reduce 6 per unit. The bottom wireway is limited to one row of terminals only. C terminals cannot be located in the same area as incoming lines. C terminals for a section with incoming lines, whether connected to main lugs or main disconnect, will be located in an adjacent section C terminals will be restricted to two rows in a section with a print pocket. Ground or neutral bus should not be located in the same area as C terminals because of restricted conduit room and the number of C terminals that can be mounted. Master Terminal Block Location 80
Units Terminal Blocks Load Terminal Blocks If NEMA Type Bt wiring option is specified, load terminal blocks are supplied on units through Size 3 starters. Pull-apart load terminal blocks can be provided through Size 2. Size 3 starters will be supplied with stationary (non pull-apart) load terminal blocks. Load terminals are white in color. Wiring Specifications Control on Units Interconnection control wiring between Units Power wiring Sized to suit maximum HP rating of unit 6 ga. 9 strand bonded copper 05 C 600V 4 ga. 9 strand copper 05 C 600V 4 ga. to 2 ga. ga. to 500 MCM 9 strand copper 05 C 600V 9 strand to 00 strand copper 05 C 600V Standard Color Coding of Wires AC Control (all voltages) DC Control (all voltages) AC Power(all voltages) Line Side CPT Equipment Ground Current Carrying Neutral Interconnecting Control Wires Between Units Red Blue Black Black Green White Red 8
Units Pilot Devices Class 52 30mm Optional Oil Tight Transformer Type or LED NEMA Type 3, 4, 2 and 3 82
Units Pilot Device Options Option Description FVNR FVC FVR Start - Stop X X 2SW 2S2W Push Buttons Forward - Reverse - Stop X Fast - Slow - Stop X High - Low - Stop X Hand - Off - Auto X X Off - On X X Selector Switch Start - Stop X X Forward - Off - Reverse X Slow - Off - Fast X High - Off - Low X Pilot Device Housing Blank X X X X 4 Holes X X X X Pilot Lights Options Description FVNR FVC FVR Running X X 2SW / 2S2W Off X X X Running - Off X X On - Off X X Forward - Reverse X Forward - Reverse - Off X High - Low X High - Low - Off X 83
Units Standard Control Transformer Sizes in VA 2 Starter Size FVNR / FVR RVAT Wye Delta 2SW 2S2W 0 50 50 50 50 50 50 50 50 2 50 50 50 50 50 3 50 50 50 50 50 4 50 50 50 50 50 5 50 50 50 50 50 6 50 50 50 50 50 Starter supplied with interposing relay(s). 2 The CPT sizes will allow for the use of a pilot light. Excess Capacity CPT VA Rating FVNR Starter Standard Size VA Rating Starter Size FVNR Standard VA Rating Excess Capacity Above Starter Required VA Rating Required for 00 VA Extra Inrush Requirement VA Inrush Capacity of Standard Transformer 0 50 25 50 28 28 50 25 50 28 28 2 50 24 50 28 28 3 50 24 250 30 30 4 50 99 250 50 30 5 50 25 50 27 28 6 50 25 50 27 28 Starter supplied with interposing relay(s). Fuse Selection - Control Power Transformer Transformer VA Secondary Fuse Size Primary Fuse Size 24V 20V 240V 240V 480V 600V 50 3.2 0.6 0.3 0.5 0.3 50 0 2 3.5 250 2 3.2.6 5 2.5 2 Handle Auxiliary Switch A handle auxiliary switch is available on the disconnect operating handle for breakers and fusible switches. The standard switch has Form C contact, which is normally used to disconnect separate source voltage in the unit. 84
Units Standard Options Amp meter + CT CT Voltage monitor Vac. contactor Transducer Fuse Puller Bypass ASI Ground fault Elapse time meter Surge supression Under voltage CB Shunt Trip Ground stab Special paint Timer 4P relay Extra unit space Nameplate Nameplates for individual units are.25 tall by 3.56 wide and can have three (standard) or four engraving lines. Unit nameplates are fastened to the unit door with plastic rivets. Stainless screw mounted unit nameplates are available as an option. The standard color for unit nameplates is a black surface with a white text. Other unit nameplate colors, such as a white surface with a black text or dark gray surface with white text or light gray with black text or red with white text or yellow with black text or blue with white text, are available as options. Standard text size is 3/6, but /4, 3/8, and /2 are available as options. When dual units (starters or feeders) are supplied, two separate unit nameplates are supplied on each unit. An optional 2 tall by 6 wide or 2 tall by 8 wide master nameplate is available. Standard engraving on the master nameplate is three lines /2 tall characters. Optional 3/8 tall characters and various nameplate color options are available for the master nameplate. Unit Nameplate Engraving Character Limit Letter Height Line Line 2 Line 3 Line 4 3/6 Std. 25 8 25 3/6 25 8 8 25 /4 8 6 8 NA 3/8 6 6 NA NA /2 3 NA NA NA For ordering blank nameplate kits, please see the MCC Aftermarket Renewal Parts Catalog. 85
Units Programmable Logic Controller (PLCs) Units and Human-Machine Interface (HMI) Options A full line of Siemens PLC s (SIMATIC S7-300, S7-400, etc. ) can be mounted in the tiastar motor control center. Siemens has the flexibility and expertise to provide a wide variety of configurations to meet user specified requirements for programmable logic control applications. HMI can also be installed in the tiastar line. 86
Units Metering Units Advanced power monitoring devices are available for Siemens MCCs including SENTRON PAC300, SENTRON PAC3200, and SENTRON PAC4200. Siemens line of power meters provides market leading technology for power quality measurement. These products continually change to meet growing needs for power quality and energy monitoring. The PAC300 and PAC3200 are a powerful compact power monitoring device that is suitable for use in industrial, government and commercial applications, where basic metering and energy monitoring is required. The meter may be used as a stand alone device monitoring over 25 (PAC300) and over 50 (PAC3200) parameters or as part of an industrial control, building automation or global power monitoring system. Metering and monitoring applications range from simple analog volt and amp meter replacements to stand-alone sub-billing or cost allocation installation (PAC3200 offers this with multiple tariffs). PAC300 The PAC300 has many features not usually found in this price class of meters. A large graphical display supports multiple languages and easy to use menus that can be used to set up the meter. The meter also has built in Modbus RTU communications via a RS485 interface. The meter comes standard with two digital inputs and outputs. One output is suitable for pulse output for export/import real and reactive energy. The other output is controllable from an outside source by way of a Modbus register. 87
Units Metering Units PAC3200 The PAC3200 provides open communications using Modbus RTU/ TCP, PROFIBUS-DP, and PROFINET protocols for easy integration into any local or remote monitoring system. Simple configuration of the meter can be done from the front display. PAC4200 The PAC4200 is a feature packed power monitoring device that is suitable for use in industrial, government and commercial applications where basic to advanced metering, logging, and I/O is required. The meter may be used as a standalone device monitoring over 200 parameters or as part of an industrial control, building automation or global enterprise wide monitoring system. Advanced power quality monitoring and logging applications range from single low voltage breaker / building metering to sub-station main feeder monitoring, sub-billing or cost allocation installations with multiple tariffs. Whether your goal is to reduce operation cost, reduce your carbon footprint or to maintain your power assets, the PAC 4200 meter should be an important part of your power monitoring system. The PAC4200 provides open communication using the standard built-in Ethernet Modbus TCP and has the capability of communicating through Optional Modbus RTU, PROFIBUS-DP, and PROFINET protocol modules simultaneously. This allows for easy integration into any local or remote monitoring system. The gateway functionality of this device reduces installation cost by replacing other gateway devices and simplifying wiring. 88
Units Panelboards and Transformers Units A Motor Control Center is principally intended to house multiple combination starters for the control of electrical motors. It is often convenient to include a limited number of power distribution units such as lighting panels and transformer units. Lighting Panelboards Applied in MCCs Amp Rating Number of Circuits %, 3W 240/20 Main Lug Only/Main Circuit Breaker Height in Inches (mm) 3%, 4W 208Y/20 3%, 4W 277/480 8 30 (762) 30 (762) 30 (762) 25/250 30 36 (94) 36 (94) 36 (94) 42 42 (067) 42 (067) 42 (067) Distribution Transformers KVA Rating Phase Unit Height in Inches (mm).5 2 3 5 7.5 0 5 25 30 37.5 45 9 5 25 30 37.5 45 2 (305) 8 (457) 24 (60) 36 (94) 3 8 (457) 24 (60) Plate mounted. Transformer mounted on brackets 6 in. (52 mm) off sills. Requires 20 in. (508 mm) deep structure. 89
Standard MCC Catalog Items Feeder Circuit Breaker (FCB) Catalog Units Common tiastar FCB units are available as catalog numbers. Orders can be placed via Industry Mall or COMPAS. Units are 480V, 60Hz, NEMA 2. Units include: door, wiring diagram, and unit installation manual. FCB Catalog Numbering System 8 P G 2 B A 0 0 Class 8 P G tiastar MCC Unit Size Standard 2 High Density Compartment type 2 Plug-in units Overload Type None Product type B FCB Ratings and Unit Size at 480V A 65K 25A 6" B 65K 25A 2" C 65K 25A 8" D 65K 25A 24" E 65K 25A 36" F 65K 25A 48" G 65K 250A 8" H 65K 250A 24" I 65K 250A 36" J 65K 250A 48" K 65K 250A 60" L 00K 250A 24" M 00K 250A 36" N 00K 250A 48" P 00K 250A 60" Circuit Breaker Trip Amps 0 0 5 0 20 0 2 25 0 3 30 0 4 35 0 5 40 0 6 45 0 7 50 0 8 60 0 70 80 2 90 3 00 4 0 5 25 6 50 7 75 8 200 2 0 225 2 250 tiastar 6" FCB Catalog Unit tiastar 2" FCB Catalog Unit 90
Standard MCC Catalog Items FCB Catalog Numbers Product Description Catalog Number Product Description Catalog Number 480V 65K 25A 6 High Density 5A 20A 25A 30A 35A 40A 45A 50A 60A 70A 80A 90A 00A 0A 25A 8PG22-BA00 8PG22-BA0 8PG22-BA02 8PG22-BA03 8PG22-BA04 8PG22-BA05 8PG22-BA06 8PG22-BA07 8PG22-BA08 8PG22-BA0 8PG22-BA 8PG22-BA2 8PG22-BA3 8PG22-BA4 8PG22-BA5 480V 65K 25A 24 5A 20A 25A 30A 35A 40A 45A 50A 60A 70A 80A 90A 00A 0A 25A 8PG2-BD00 8PG2-BD0 8PG2-BD02 8PG2-BD03 8PG2-BD04 8PG2-BD05 8PG2-BD06 8PG2-BD07 8PG2-BD08 8PG2-BD0 8PG2-BD 8PG2-BD2 8PG2-BD3 8PG2-BD4 8PG2-BD5 480V 65K 25A 2 5A 20A 25A 30A 35A 40A 45A 50A 60A 70A 80A 90A 00A 0A 25A 8PG2-BB00 8PG2-BB0 8PG2-BB02 8PG2-BB03 8PG2-BB04 8PG2-BB05 8PG2-BB06 8PG2-BB07 8PG2-BB08 8PG2-BB0 8PG2-BB 8PG2-BB2 8PG2-BB3 8PG2-BB4 8PG2-BB5 480V 65K 25A 36 5A 20A 25A 30A 35A 40A 45A 50A 60A 70A 80A 90A 00A 0A 25A 8PG2-BE00 8PG2-BE0 8PG2-BE02 8PG2-BE03 8PG2-BE04 8PG2-BE05 8PG2-BE06 8PG2-BE07 8PG2-BE08 8PG2-BE0 8PG2-BE 8PG2-BE2 8PG2-BE3 8PG2-BE4 8PG2-BE5 480V 65K 25A 8 5A 20A 25A 30A 35A 40A 45A 50A 60A 70A 80A 90A 00A 0A 25A 8PG2-BC00 8PG2-BC0 8PG2-BC02 8PG2-BC03 8PG2-BC04 8PG2-BC05 8PG2-BC06 8PG2-BC07 8PG2-BC08 8PG2-BC0 8PG2-BC 8PG2-BC2 8PG2-BC3 8PG2-BC4 8PG2-BC5 480V 65K 25A 48 5A 20A 25A 30A 35A 40A 45A 50A 60A 70A 80A 90A 00A 0A 25A 8PG2-BF00 8PG2-BF0 8PG2-BF02 8PG2-BF03 8PG2-BF04 8PG2-BF05 8PG2-BF06 8PG2-BF07 8PG2-BF08 8PG2-BF0 8PG2-BF 8PG2-BF2 8PG2-BF3 8PG2-BF4 8PG2-BF5 9
Standard MCC Catalog Items FCB Catalog Numbers 480V 65K 250A 8 50A 75A 200A 225A 250A 8PG2-BG6 8PG2-BG7 8PG2-BG8 8PG2-BG20 8PG2-BG2 480V 00K 250A 24 50A 75A 200A 225A 250A 8PG2-BL6 8PG2-BL7 8PG2-BL8 8PG2-BL20 8PG2-BL2 480V 65K 250A 24 50A 75A 200A 225A 250A 8PG2-BH6 8PG2-BH7 8PG2-BH8 8PG2-BH20 8PG2-BH2 480V 00K 250A 36 50A 75A 200A 225A 250A 8PG2-BM6 8PG2-BM7 8PG2-BM8 8PG2-BM20 8PG2-BM2 480V 65K 250A 36 50A 75A 200A 225A 250A 8PG2-BI6 8PG2-BI7 8PG2-BI8 8PG2-BI20 8PG2-BI2 480V 00K 250A 48 50A 75A 200A 225A 250A 8PG2-BN6 8PG2-BN7 8PG2-BN8 8PG2-BN20 8PG2-BN2 480V 65K 250A 48 50A 75A 200A 225A 250A 8PG2-BJ6 8PG2-BJ7 8PG2-BJ8 8PG2-BJ20 8PG2-BJ2 480V 00K 250A 60 50A 75A 200A 225A 250A 8PG2-BP6 8PG2-BP7 8PG2-BP8 8PG2-BP20 8PG2-BP2 480V 65K 250A 60 50A 75A 200A 225A 250A 8PG2-BK6 8PG2-BK7 8PG2-BK8 8PG2-BK20 8PG2-BK2 92
Standard MCC Catalog Items Full Voltage Non-Reversing (FNVR) Catalog Units Common tiastar FNVR units are available as catalog numbers. Orders can be placed via Industry Mall or COMPAS. Units are 480V, 60Hz, NEMA 2, Type B-d Wiring, 00kAIC. Units include: N.O./ N.C. auxiliary contacts, pilot device housing for up to four 22 mm devices, door, wiring diagram, and unit installation manual. FVNR Catalog Numbering System 8 P G 2 A A 0 0 Class 8 P G tiastar MCC Unit Size Standard 2 High Density Compartment type 2 Plug-in units Overload type ESP200 2 SIMOCODE Pro C 2 3 SIMOCODE Pro V 2 Product type A FVNR Horsepower A 0 0 /4 A 0 /3 A 0 2 /2 A 0 3 3/4 A 0 4.5 A 0 5 2-3 A 0 6 4 A 0 7 5 A 0 8 7.5 0 A 0 5 20 A 25 A 2 30 A 3 40 50 A 4 60 75 A 5 00 tiastar 2" ESP FVNR Catalog Unit Includes Current Only Module 2 Not available with High Density 93
Standard MCC Catalog Items FVNR Catalog Numbers Product Description Catalog Number High Density ESP 200 Overload Units 6, /4 HP HD-FVNR SIZE, A ETI CB, ESP 200 0.25-A, CPT 8PG22-AA00 6, /3 HP HD-FVNR SIZE, 2A ETI CB, ESP 200 0.25-A, CPT 8PG22-AA0 6, /2 HP HD-FVNR SIZE, 3A ETI CB, ESP 200 0.75-3.4A, CPT 8PG22-AA02 6, 3/4 - HP HD-FVNR SIZE, 5A ETI CB, ESP 200 0.75-3.4A, CPT 8PG22-AA03 6,.5 HP HD-FVNR SIZE, 0A ETI CB, ESP 200 0.75-3.4A, CPT 8PG22-AA04 6, 2-3 HP HD-FVNR SIZE, 0A ETI CB, ESP 200 3-2A, CPT 8PG22-AA05 6, 4 HP HD-FVNR SIZE, 25A ETI CB, ESP 200 3-2A, CPT 8PG22-AA06 6, 5 HP HD-FVNR SIZE, 30A ETI CB, ESP 200 3-2A, CPT 8PG22-AA07 6, 7.5-0 HP HD-FVNR SIZE, 40A ETI CB, ESP 200 5.5-22A, CPT 8PG22-AA08 6, 5-20 HP HD-FVNR SIZE 2, 50A ETI CB, ESP 200 0-40A, CPT 8PG22-AA0 6, 25 HP HD-FVNR SIZE 2, 00A ETI CB, ESP 200 0-40A, CPT 8PG22-AA 2, 30 HP HD-FVNR SIZE 3, 00A ETI CB, ESP 200 25-00A, CPT 8PG22-AA2 2, 40-50 HP HD-FVNR SIZE 3, 25A ETI CB, ESP 200 25-00A, CPT 8PG22-AA3 ESP200 Overload Units 2, /4 HP FVNR SIZE, A ETI CB, ESP 200 0.25-A, CPT 8PG2-AA00 2, /3 HP FVNR SIZE, 2A ETI CB, ESP 200 0.25-A, CPT 8PG2-AA0 2, /2 HP FVNR SIZE, 3A ETI CB, ESP 200 0.75-3.4A, CPT 8PG2-AA02 2, 3/4 - HP FVNR SIZE, 5A ETI CB, ESP 200 0.75-3.4A, CPT 8PG2-AA03 2,.5 HP FVNR SIZE, 0A ETI CB, ESP 200 0.75-3.4A, CPT 8PG2-AA04 2, 2-3 HP FVNR SIZE, 0A ETI CB, ESP 200 3-2A, CPT 8PG2-AA05 2, 4 HP FVNR SIZE, 25A ETI CB, ESP 200 3-2A, CPT 8PG2-AA06 2, 5 HP FVNR SIZE, 30A ETI CB, ESP 200 3-2A, CPT 8PG2-AA07 2, 7.5-0 HP FVNR SIZE, 40A ETI CB, ESP 200 5.5-22A, CPT 8PG2-AA08 2, 5-20 HP FVNR SIZE 2, 50A ETI CB, ESP 200 3-52A, CPT 8PG2-AA0 2, 25 HP FVNR SIZE 2, 00A ETI CB, ESP 200 3-52A, CPT 8PG2-AA 8, 30 HP FVNR SIZE 3, 00A ETI CB, ESP 200 25-00A, CPT 8PG2-AA2 8, 40-50 HP FVNR SIZE 3, 25A ETI CB, ESP 200 25-00A, CPT 8PG2-AA3 24, 60-75 HP FVNR SIZE 4, 50A ETI CB, ESP 200 50-200A, CPT 8PG2-AA4 24, 00 HP FVNR SIZE 4, 250A ETI CB, ESP 200 50-200A, CPT 8PG2-AA5 94
Standard MCC Catalog Items FVNR Catalog Numbers Product Description Catalog Number SIMOCODE PRO C 2 2, /4 HP FVNR SIZE, A ETI CB, SIMOCODE PRO C 0.3-3 AMPS, CPT 8PG2-2AA00 2, /3 HP FVNR SIZE, 2A ETI CB, SIMOCODE PRO C 0.3-3 AMPS, CPT 8PG2-2AA0 2, /2 HP FVNR SIZE, 3A ETI CB, SIMOCODE PRO C 0.3-3 AMPS, CPT 8PG2-2AA02 2, 3/4 - HP FVNR SIZE, 5A ETI CB, SIMOCODE PRO C 0.3-3 AMPS, CPT 8PG2-2AA03 2,.5 HP FVNR SIZE, 0A ETI CB, SIMOCODE PRO C 2.4-25 AMPS, CPT 8PG2-2AA04 2, 2-3 HP FVNR SIZE, 0A ETI CB, SIMOCODE PRO C 2.4-25 AMPS, CPT 8PG2-2AA05 2, 4 HP FVNR SIZE, 25A ETI CB, SIMOCODE PRO C 2.4-25 AMPS, CPT 8PG2-2AA06 2, 5 HP FVNR SIZE, 30A ETI CB, SIMOCODE PRO C 2.4-25 AMPS, CPT 8PG2-2AA07 2, 7.5-0 HP FVNR SIZE, 40A ETI CB, SIMOCODE PRO C 2.4-25 AMPS, CPT 8PG2-2AA08 2, 5-20 HP FVNR SIZE 2, 50A ETI CB, SIMOCODE PRO C 0-00 AMPS, CPT 8PG2-2AA0 2, 25 HP FVNR SIZE 2, 00A ETI CB, SIMOCODE PRO C 0-00 AMPS, CPT 8PG2-2AA 8, 30 HP FVNR SIZE 3, 00A ETI CB, SIMOCODE PRO C 0-00 AMPS, CPT 8PG2-2AA2 8, 40-50 HP FVNR SIZE 3, 25A ETI CB, SIMOCODE PRO C 0-00 AMPS, CPT 8PG2-2AA3 24, 60-75 HP FVNR SIZE 4, 50A ETI CB, SIMOCODE PRO C 20-200 AMPS, CPT 8PG2-2AA4 24, 00 HP FVNR SIZE 4, 250A ETI CB, SIMOCODE PRO C 20-200 AMPS, CPT 8PG2-2AA5 SIMOCODE PRO V 2 2, /4 HP FVNR SIZE, A ETI CB, SIMOCODE PRO V 0.3-3 AMPS, CPT 8PG2-3AA00 2, /3 HP FVNR SIZE, 2A ETI CB, SIMOCODE PRO V 0.3-3 AMPS, CPT 8PG2-3AA0 2, /2 HP FVNR SIZE, 3A ETI CB, SIMOCODE PRO V 0.3-3 AMPS, CPT 8PG2-3AA02 2, 3/4 - HP FVNR SIZE, 5A ETI CB, SIMOCODE PRO V 0.3-3 AMPS, CPT 8PG2-3AA03 2,.5 HP FVNR SIZE, 0A ETI CB, SIMOCODE PRO V 2.4-25 AMPS, CPT 8PG2-3AA04 2, 2-3 HP FVNR SIZE, 0A ETI CB, SIMOCODE PRO V 2.4-25 AMPS, CPT 8PG2-3AA05 2, 4 HP FVNR SIZE, 25A ETI CB, SIMOCODE PRO V 2.4-25 AMPS, CPT 8PG2-3AA06 2, 5 HP FVNR SIZE, 30A ETI CB, SIMOCODE PRO V 2.4-25 AMPS, CPT 8PG2-3AA07 2, 7.5-0 HP FVNR SIZE, 40A ETI CB, SIMOCODE PRO V 2.4-25 AMPS, CPT 8PG2-3AA08 2, 5-20 HP FVNR SIZE 2, 50A ETI CB, SIMOCODE PRO V 0-00 AMPS, CPT 8PG2-3AA0 2, 25 HP FVNR SIZE 2, 00A ETI CB, SIMOCODE PRO V 0-00 AMPS, CPT 8PG2-3AA 8, 30 HP FVNR SIZE 3, 00A ETI CB, SIMOCODE PRO V 0-00 AMPS, CPT 8PG2-3AA2 8, 40-50 HP FVNR SIZE 3, 25A ETI CB, SIMOCODE PRO V 0-00 AMPS, CPT 8PG2-3AA3 24, 60-75 HP FVNR SIZE 4, 50A ETI CB, SIMOCODE PRO V 20-200 AMPS, CPT 8PG2-3AA4 24, 00 HP FVNR SIZE 4, 250A ETI CB, SIMOCODE PRO V 20-200 AMPS, CPT 8PG2-3AA5 Includes Current Only Module 2 Not available with High Density 95
Standard MCC Catalog Items Common Modification Kits Common modification kits includes pilot device(s), 6 gauge MTW wiring, wire tie, anchor, legend plate, wiring diagram, and installation guide. Pushbutton Kit Product Name Push Button 22MM Start - Stop Pushbutton Kit 22MM Emergency Stop Pushbutton Kit 30MM Start - Stop Pushbutton Kit 30MM Emergency Stop Pushbutton Kit Kit Type Product MLFB 8PG82-KA00 8PG82-KA0 8PG82-KA02 8PG82-KA03 Selector Switch 22MM Hand - Off - Auto Selector Switch Kit 22MM Start - Stop Selector Switch Kit 22MM Off - On Selector Switch Kit 30MM Hand - Off - Auto Selector Switch Kit 30MM Start - Stop Selector Switch Kit 30MM Off - On Selector Switch Kit Product MLFB 8PG82-KB00 8PG82-KB0 8PG82-KB02 8PG82-KB03 8PG82-KB04 8PG82-KB05 Selector Switch Kit Pilot Lights Product MLFB 22MM Off Pilot Light 20V Kit 8PG82-KC00 22MM On - Off Pilot Lights 20V Kit 8PG82-KC0 22MM Running - Off Pilot Lights 20V Kit 8PG82-KC02 22MM Running Pilot Light 20V Kit 8PG82-KC03 22MM Led Running Pilot Light 20V Kit 8PG82-KC04 22MM Led On - Off Pilot Lights 20V Kit 8PG82-KC05 22MM Push-To-Test On Pilot Light 20V Kit 8PG82-KC06 22MM Push-To-Test On - Off Pilot Lights 20V Kit 8PG82-KC07 22MM Led Push-To-Test On Pilot Light 20V Kit 8PG82-KC08 22MM Led Push-To-Test On - Off Pilot Lights 20V Kit 8PG82-KC0 30MM Off Pilot Light 20V Kit 8PG82-KC 30MM On - Off Pilot Lights 20V Kit 8PG82-KC2 30MM Running - Off Pilot Lights 20V Kit 8PG82-KC3 30MM Running Pilot Light 20V Kit 8PG82-KC4 30MM Led Running Pilot Light 20V Kit 8PG82-KC5 30MM Led On - Off Pilot Lights 20V Kit 8PG82-KC6 30MM Push-To-Test On Pilot Light 20V Kit 8PG82-KC7 30MM Push-To-Test On - Off Pilot Lights 20V Kit 8PG82-KC8 30MM Led Push-To-Test On Pilot Light 20V Kit 8PG82-KC20 30MM Led Push-To-Test On - Off Pilot Lights 20V Kit 8PG82-KC2 For an emergency stop device according to EN 48, please see the industrial controls catalog. Pilot Light Kit NOTE: Standard 30MM Nema Pilot Device Housing Kit (8PG92-DF06) and 30MM Nema 2 Pilot Device Housing Kit (8PG92-DF07) are available. 96
Standard MCC Catalog Items Other Modification Kits To order other parts for MCC modifications, refer to the "tiastar and legacy Motor Control Center Aftermarket Renewal Parts Catalog" which is literature order number MCCS-AFTMKT-063. Find information on ordering Splice kits, Drip Shield kits, Door Kits, Terminal Blocks, etc. Table of Contents tiastar TM and legacy Motor Control Center Aftermarket Renewal Parts Catalog MCC Identification Guide Ordering Processes 2-3 Section Parts Splice Kits 4 Drip Shield Kits 5 Structural Parts 6 Unit Parts Auxiliary Handle Switch Kits 7 Door Assembly Kits and Door Parts 8- Handle Operating Mechanism Kits 2-3 MCC Control Fuse Kits 4 MCC Control Part Kits 5 MCC Terminal Blocks 6 Nameplate Kits 6 Overload Reset Kits 6 Shutter Mechanism Kit 6 Miscellaneous 7 Splice Kit Section Parts Splice Kits Bus splice plate(s), mounting hardware, and installation guide are included in the Splice Kit. 50 C Horizontal Bus Silver Plated Kit Type 600A 800A 200A 600A 2000A 2500A 50 C Horizontal Bus Tin Plated Kit Type 600A 800A 200A 600A 2000A 2500A Neutral Bus Kit Type Ordering Number 8PG9-2KA00 8PG9-2KA0 8PG9-2KA02 8PG9-2KA03 8PG9-2KA04 8PG9-2KA05 Ordering Number 8PG9-2KB00 8PG9-2KB0 8PG9-2KB02 8PG9-2KB03 8PG9-2KB04 8PG9-2KB05 Ordering Number 600A, Silver Plated 8PG9-2KC00 800A, Silver Plated 8PG9-2KC0 600A, Tin Plated 8PG9-2KC02 800A, Tin Plated 8PG9-2KC03 Ground Bus Kit Type Ordering Number 300A, Top Mounted, Bare Copper 8PG9-2KD00 600A, Top Mounted, Bare Copper 8PG9-2KD0 300A, Bottom Mounted, Bare Copper 8PG9-2KD02 600A, Bottom Mounted, Bare Copper 8PG9-2KD03 300A, Top Mounted, Tin Plated 8PG9-2KD04 600A, Top Mounted, Tin Plated 8PG9-2KD05 300A, Bottom Mounted, Tin Plated 8PG9-2KD06 600A, Bottom Mounted, Tin Plated 8PG9-2KD07 65 C Horizontal Bus Silver Plated Kit Type 600A 800A 200A 65 C Horizontal Bus Tin Plated Kit Type 600A 800A Ordering Number 8PG9-2KE00 8PG9-2KE0 8PG9-2KE02 Ordering Number 8PG9-2KF00 8PG9-2KF0 Unit Parts Door Assembly Kits and Door Parts Model 95+ and System 89/tiastar Door, hinges, and mounting hardware included in the Model 95+ and System 89/tiastar Door Assembly Kit. Vertical Wireway Door Kit Type Ordering Number 4 Wide By 2 Tall 8PG92-DD00 4 Wide By 8 Tall 8PG92-DD0 4 Wide By 24 Tall 8PG92-DD02 4 Wide By 30 Tall 8PG92-DD03 4 Wide By 36 Tall 8PG92-DD04 4 Wide By 42 Tall 8PG92-DD05 4 Wide By 48 Tall 8PG92-DD06 4 Wide By 54 Tall 8PG92-DD07 4 Wide By 60 Tall 8PG92-DD08 4 Wide By 66 Tall 8PG92-DD0 4 Wide By 72 Tall 8PG92-DD 8 Wide By 2 Tall 8PG92-DD2 8 Wide By 8 Tall 8PG92-DD3 8 Wide By 24 Tall 8PG92-DD4 Blank Door Kit Door Kit Type Ordering Num 6 High Density Unit Door Kit 8PG92-DE 5 Wide By 6 Tall Filler Door 8PG92-DE 5 Wide By 2 Tall Blank Door 8PG92-DE 5 Wide By 8 Tall Blank Door 8PG92-DE 5 Wide By 24 Tall Blank Door 8PG92-DE 5 Wide By 30 Tall Blank Door 8PG92-DE 5 Wide By 36 Tall Blank Door 8PG92-DE 200A 8PG9-2KF02 97
Appendix Dimensions and Drawings Dimensions and Drawings Structures The standards structure is 90 in. (2286 mm) high, plus a.25 in. (29 mm) high channel sill. Front-only (FO) structures can be either 5 in. (38 mm) or 20 in. (508 mm) deep. Siemens provides a 2 in. (533mm) true back-to-back (BTB) design, consisting of a common horizontal and vertical bus structure, for applications where available footprint is limited. Moreover, we provide other back-to-back (BTB) mounted double deep structures which are 30.5 in. (775 mm) or 40.5 in. (029 mm) deep, and consist of two horizontal and vertical buses. This allows for correct bus phasing on the front or rear. The standards structure is 90 in. (2286 mm) high, plus a.25 in. (29 mm) high channel sill. Front-only (FO) structures can be either 5 in. (38 mm) or 20 in. (508 mm) deep. Structure Height NEMA, 2, or 2 9.25 in. (235mm) NEMA 3R 00 in (2540 mm) Front Mounted Only Structure (FO) Width 20 in. (508 mm). 24 in. (60 mm) 30 in. (762 mm) Depth 5 in. (38 mm) 20 in. (508 mm) Back-to-Back Structure Width 20 in. (508 mm) 30 in. (762 mm) Depth 2 in. (533 mm) Double Deep Structure Width 20 in. (508 mm) 30 in. (762 mm) Depth 30.5 in. (775 mm) 40.5 in. (029 mm) Vertical Wireway Height 72 in. (829 mm) Width Depth Cross Section 4 in. (02 mm) 9 (229mm) 36 sq. in. (94 sq. mm) Top Horizontal Wireway Height Depth 2 in. (305 mm) 7 in. (78 mm) Bottom Horizontal Wireway Height 6 in. (305 mm) Depth 5 in. (38 mm) 20 in. (508 mm) 30 in. (762 mm) Pull Box (Top Hat) Height 2 in. (305 mm) 8 in. (457 mm) 24 in. (60 mm) Width 20 in. (508 mm) 30 in. (762 mm) Depth 5 in. (38 mm) 20 in. (508 mm) 98
Appendix Bus Drawings Available Locations Of Ground And Full Length Neutral Section Neutral Ground Typical CD ABCD With Veritcal Ground Bus C AC Main Lug Only CD BCD Main Disconnect CD BCD Service Entrance C ABCD Note: a Location B and D is available on 2 back-to-back structures only. s When continuous (full length) neutral bus is specified, it must be located in the bottom of the structure. Full length neutral bus requires that the ground be located in the top of the structure. The standard location is C. Figure. Side View Figure 2. Mounting Dimensions 99
Appendix Dimensions and Drawings Bus Mounting Dimensions Figure 3: Stab-On Connection Bus Drawing Fi Qty./Phase AMP Size 50C 65C 600 () /4 x 2 /8 x 2 800 () 3/8 x 2 3/6 x 2 200 (2) /4 x 2 3/8 x 2 600 (2) 3/8 x 2 2000 (4) 3/8 x 2 2500* (4) 3/8 x 2 *2500A available in NEMA Enclosure only. Mounting of Single and Double Bus Bars Horizontal Bus Insulator Support Figure 5: Single and Double Bus Bars Spacer Section W/600A; 800A All dimensions are shown in inches unless otherwise specified. 00
Appendix Vertical Bus Dimensions and Availability Vertical Bus Available Structures Amp Rating Size 5 20 20 Back-to-Back 24 300 3/8 x 3/4 X X X 600 3/8 x /2 X X X X 800 3/8 x /2 X X X X Bus Bar Phase Figure 6: Front View Horizontal Bus Link For joining two sections in the field. Figure 7: Front View Figure 8: Front View All dimensions are shown in inches unless otherwise specified. 0
Appendix Dimensions and Drawings Wireway Dimensions Figure 9: Front and Right Side Views Figure 0: Back and Rigth Side Views All dimensions are shown in inches unless otherwise specified. 02
Appendix Blank Section Figure Note: For 30, 40, 50, 60 inch wide and 0, 20, 30, 40 inches to all width dimensions. Plug in Unit Dimensions Figure 2 03
Appendix Dimensions and Drawings Fixed Mounting Panel Dimensions Unit Space 20 A W B 30 A W B 40 A W B 50 A W B 60 A W B 2 9 7 7 /8 8 5 7 7 /8 24 2 7 7 /8 30 27 7 7 /8 36 33 7 7 /8 33 27½ 42 39 7 7 /8 48 45 7 7 /8 54 5 7 7 /8 60 57 7 7 /8 66 63 7 7 /8 72 69 7 7 /8 70 27½ 70 37½ 70 47½ 70 57½ 04
Appendix Conduit Entry and Transformer Mounting ) Figure 4: Top Conduit Entry 5:, 20:, and Back-to-Back Conduit should not extend more than 2 /2 inches above th floor surface. All dimensions are for reference and are subject to change. Not for use for construction. Figure 5: Bottom Conduit Entry 5:, 20:, and Back-to-Back Front, top, conduit space for 2000A and 2500A horizontal bus or for Insulated horizontal bus is 4 /8 05
Appendix Dimensions and Drawings Conduit Entry and Transformer Mounting Wireway Auto Transformer Mounting and Bottom Conduit Entry Restrictions Size 2-4 Reduced Voltage Auto Transformers FPO Figure 6: Size 2-4 Reduced Voltage Auto Transformers Size 5-6 Reduced Voltage Auto Transformers Figure 7: Size 5-6 Reduced Voltage Auto Transformers 06
Appendix Conduit Entry and Transformer Mounting Lighting Transformer Mounting and Conduit Entry Restrictions -5 KVA Single Phase Figure 8: -5 KVA Single Phase 7 /2 KVA Single Phase Figure 9: 7 /2 KVA Single Phase Conduit entry is not recommended below 20-45 KVA single phase and all 3 phase lighting transformers. 07
Appendix Dimensions and Drawings Conduit Entry and Transformer Mounting NEMA 3R Structure Dimensions Figure 20: NEMA 3R Structure A D Remarks 40 36 (2) 20 Sections 50 46 () 20 & () 30 Section 60 56 (3) 20 or (2) 30 Sections 80 (2) 36 (4) 20 Sections Note:. All dimensions given in inches. 2. Shaded areas indicate conduit entries. 3. Bottom mounted transformers will reduce conduit entry space 4. Vertical bus is 0 5/8 from bottom of base. 5. Bottom ground bus is 7/8 from bottom of base. 6. Drawings not for construction. For construction, obtain certified drawings from the factory 7. Not available for back-to-back structures. 08
Appendix Conduit Entry and Transformer Mounting Duplex Structure Floor Plan and Clearance Dimensions A B C D E F G H J Left- Handed Structure Width Right- Handed Structure Width Vertical Support (Mounting Angle Location) Panel Orientation Structure Depth Panel Surface to inside of Door Brace Panel Surface to inside of Door Left-Hand Door Opening Clearance Right-Hand Door Opening Clearance Total Opening Available (Door Brace Removed) Duplex Width Conduit Entry Space Conduit Entry Space Standard Standard 5 6.35 8.34 Standard Standard 20 6.35 8.34 Standard Inverted 5 8.85 0.93 Standard Inverted 20 8.25 0.93 Recessed Standard 5 9.25.20 Recessed Standard 20 4.25 6.20 Recessed Inverted 5.77 3.70 Recessed Inverted 20 6.75 8.70 20 8 8 38.88 40 7 7 30 8 8 48.88 50 7 27 3 0 28 28 58.88 60 7 27 Figure 2: Duplex Structure Floor Plan 09
Appendix Motor Circuit Protector (MCP) Selection Motor Circuit Protector (MCP) Selection Recommended MCP Type Selection: 30/60Hz Squirrel Cage Motors MCP Selection Unit Space 200V 60Hz 208V 60Hz 230V 60Hz 380V 50Hz 45V 50Hz 460V 60Hz 575V 60Hz HP Starter Size FLA MCP Starter Size FLA MCP Starter Size FLA MCP Starter Size FLA MCP Starter Size FLA MCP Starter Size FLA MCP Starter Size FLA MCP HP ½ 2.5 5 2.4 5 2.2 5.3 3 0.8 2. 3 0.9 2 ½ ¾ 3.7 0 3.5 0 3.2 0.8 5.2 3.6 5.3 3 ¾ 4.8 0 4.6 0 4.2 0 2.3 5 2 5 2. 5.7 5 ½ 0 0 0 6.9 25 6.6 25 6 25 0 3.3 0 0 2.5 5 0 3 0 0 2.4 5 ½ 2 7.8 30 7.5 30 6.8 25 4.3 0 3.5 0 3.4 0 2.7 5 2 3.0 40 0.6 40 9.6 30 6. 25 5 25 4.8 0 3.9 0 3 5 7.5 50 6.7 50 5.2 40 9.7 30 7.5 30 7.6 30 6. 25 5 7½ 25.3 50 24.2 50 22 50 4 40.0 40.0 40 9.0 30 7½ 0 2 32.2 00 2 30.8 00 28 50 8 50 4 40 4 40.0 30 0 2 5 48.3 25 46.2 25 42 00 27 50 2 50 2 50 7 50 5 20 3 62. 25 3 59.4 25 54 25 2 34 00 2 28 50 2 27 50 2 22 50 20 25 78.2 50 74.8 50 3 68 25 44 00 35 00 34 00 27 50 25 30 92 50 88 50 80 50 5 25 40 00 40 00 32 00 30 40 4 4 20 250 4 250 04 250 3 66 25 3 55 25 3 52 25 3 4 00 40 4 50 50 250 43 250 30 250 83 50 64 25 65 25 52 25 50 60 5 77 250 5 69 250 54 250 03 50 80 50 77 50 62 25 60 4 4 75 22 400 2 400 5 92 400 28 250 00 50 4 96 50 4 77 50 75 00 285 600 273 600 248 400 65 250 35 250 24 250 99 50 00 25 6 359 600 6 343 600 32 600 5 208 250 5 65 250 56 250 25 250 25 50 44 800 396 800 6 360 600 240 400 200 400 5 80 250 5 44 250 50 200 480 800 320 600 260 400 240 400 92 400 200 250 6 403 800 6 325 600 302 600 242 400 250 300 532 800 385 800 36 600 289 600 300 6 6 350 44 800 336 600 350 400 477 800 382 800 400 FLA per NEC 204 table 430.250. MCP size meets NEC requirements per article 430.0 5% FLA min. continuous amps. MCP trip ranges are selected to meet maximum settings per NEC table 430.52 and exception C, Art. 430.52. MSCP s are factory set at minimum and can be set to a maximum of 700% of motor FLA per NEC 430.52 for energy efficient motors. Above ratings will not exceed maximum size allowed to protect heater coil for energy efficient motor FLAs. Maximum ratings shown on heater coil selection charts are not to be exceeded. Do not use this chart for part winding starters. Use thermal magnetic breaker or fuse for short circuit protection. 0
Instananeous Trip (Motor Circuit Protectors) Appendix Instantaneous Trip (Motor Circuit Protectors) Siemens Sentron ETI Motor Circuit Protector Instantaneous Trip Breakers: Recommended Settings Max Settings HP 230V 460V 575V A Set A Set A Set ¼ 3 3 2 2 3 3 2 2 2 2 ½ 5 2 3 2 2 ¾ 0 5 3 2 0 2 5 2 5 ½ 25 0 5 2 2 25 2 0 5 2 3 30 0 2 0 2 5 40 2 30 25 7 ½ 50 40 30 0 50 2 40 2 30 2 5 00 2 50 50 20 25 50 2 50 25 25 2 00 50 2 30 50 3 00 00 40 250 2 25 00 2 50 250 3 25 2 25 60 250 5 50 3 25 2 75 400 2 50 5 50 3 00 400 5 250 3 50 5 25 600 3 250 3 250 3 50 600 4 250 7 250 4 200 800 4 400 4 400 2 250 600 3 400 4 300 600 4 600 2 350 800 2 600 4 400 800 4 800 2 A = Breaker Ampere Rating For maximum protection the trip position should be set as low as possible. Turn the adjustment screw counterclockwise to successively lower positions until the breaker trips on motor starting. After this position is determined, turn the adjustment screw clockwise to the next higher setting for normal operation. The adjustment screw is infinitely adjustable for customer convenience. If the breaker does not trip at the lowest setting leave the indicator at this setting. The instantaneous breaker is factory set at the LOW position. Trip Setting Positions LOW 2 3 4 5 6 7 HI 2.6 4.5 6 7.5 9 2 7 5 9 22 3 0 7 23 30 35 5 6 26 36 46 54 0 30 50 70 85 00 25 55 90 25 55 80 30 80 35 85 235 270 40 5 85 255 325 375 50 80 300 40 520 600 00 35 540 740 890 000 25 500 720 920 000 250 50 800 900 000 00 200 300 400 500 250 00 300 500 700 900 200 2300 2500 400 2000 2290 2570 2860 340 3430 370 4000 600 3000 3430 3800 4290 470 540 5570 6000 800 4000 4570 5740 580 7240 6850 7240 8000
Appendix Breaker Selection Thermal Magnetic Breaker Selection 3 Phase 60Hz Squirrel Cage Motors Unit Space 200V 60Hz 208V 60Hz 230V 60Hz 380V 50Hz 45V 50Hz 460V 60Hz 575V 60Hz Unit Space HP Starter Size FLA CB Trip Starter Size FLA CB Trip Starter Size FLA CB Trip Starter Size FLA CB Trip Starter Size FLA CB Trip Starter Size FLA CB Trip Starter Size FLA CB Trip HP ½ 2.5 5 2.4 5 2.2 5.3 5 0.8 5. 5 0.9 5 ½ ¾ 3.7 5 3.5 5 3.2 5.8 5.2 5.6 5.3 5 ¾ 4.8 5 4.6 5 4.2 5 2.3 5 2 5 2. 5.7 5 0 0 0 ½ 6.9 5 6.6 5 6 5 0 3.3 5 0 2.5 5 0 3 5 0 2.4 5 ½ 2 7.8 5 7.5 5 6.8 5 4.3 5 3.5 5 3.4 5 2.7 5 2 3.0 20 0.6 20 9.6 20 6. 5 5 5 4.8 5 3.9 5 3 5 7.5 30 6.7 30 5.2 25 9.7 20 7.5 5 7.6 5 6. 5 5 7½ 25.3 45 24.2 40 22 40 4 25.0 20.0 20 9.0 5 7½ 0 2 32.2 60 2 30.8 50 28 45 8 30 4 25 4 25.0 20 0 2 5 48.3 80 46.2 80 42 70 27 45 2 35 2 35 7 30 5 20 3 62. 00 3 59.4 00 54 90 2 34 60 2 28 50 2 27 45 2 22 40 20 25 78.2 50 74.8 25 3 68 0 44 80 35 60 34 60 27 50 25 30 92 50 88 50 80 50 5 90 40 70 40 70 32 60 30 4 4 40 20 200 4 200 04 75 3 66 0 3 55 90 3 52 90 3 4 70 40 4 50 50 250 43 250 30 225 83 50 64 0 65 0 52 90 50 60 5 77 300 5 69 300 54 250 03 75 80 50 77 25 62 00 60 4 4 75 22 400 2 350 5 92 350 28 225 00 75 4 96 75 4 77 25 75 00 285 500 273 450 248 400 65 300 35 225 24 200 99 75 00 25 6 359 600 6 343 600 32 500 5 208 350 5 65 300 56 250 25 200 25 50 44 700 396 700 6 360 600 240 400 200 350 5 80 300 5 44 250 50 200 480 800 320 600 260 450 240 400 92 350 200 6 250 403 700 6 325 600 302 500 242 400 250 300 385 700 36 600 289 500 300 6 6 350 44 700 336 600 350 400 477 800 382 700 400 Circuit breaker trip ratings are selected in accordance with NEC 204 article 430.52 and table 430.52 assuming motors with locked rotor KVA Code B thru E. Lower trip ratings may be required for motors with Code A. FLA per NEC 204 table 430.250. Do not use to size heater coils. Use motor NP data. Maximum ratings shown on Heater Coil selection charts are not to be exceeded. Special applications on motor may require different rating, refer to proper section of NEC to size. Do not use this chart for part winding starters - Maximum breaker size to be limited to 200% FLA or less, 50% for FLA greater than 00A. 2
Fuse Selection Appendix Fuse Selection UL Standard Fuse Classifications K K5 K9 RK RK5 J L Amp Rating Range Interrupting Rating RMS Amps 0-600 0-600 0-600 0-600 0-600 0-600 60-6000 200,000 200,000 200,000 200,000 200,000 200,000 200,000 Voltage 250 or 600 250 or 600 250 or 600 250 or 600 250 or 600 600 600 Current Limiting Characteristics Dual Element Time Delay Generic Names Rejection Type Manufacturer Designations High Moderate Fair High Moderate High High No Yes Yes No Yes No Yes 3 Current Limiting No Bussman KTN Bussman KTS Current Limiting Time Delay No Bussman FRN Bussman FRS Current Limiting Time Delay NO Current Limiting Yes Bussman LPN-RK Bussman KTS-R Mersen A2D Mersen A6D Current Limiting Time Delay Yes Bussman LPN-RK Bussman KTS-R Mersen A2D Mersen A6D Current Limiting Inherent Bussman JKS Mersen A4J Current Limiting Inherent Bussman KTU Mersen A4Bt UL does not permit fuses to be marked current limiting due to lack of rejection feature. 2 Class J smaller the NEC Code specifications; Class L requires bolt-on fuse blocks. Inherent rejection feature of unique fuse dimensions allows UL marking of current limiting features. 3 Class L fuses may be marked Time Delay although UL does not investigate Time Delay characteristics of such fuses. 3
Appendix Fuse Selection/UL Standard Fuse Classifications Fuse Selection 3 Phase 60Hz Squirrel Cage Motors Fuse sizes are selected in accordance with NEC 204 article 430.52 & 57 and table 430.52. 200V 60Hz 208V 60Hz 230V 60Hz 380V 50Hz HP Starter Size FLA Time Delay Non Delay Starter Size FLA Time Delay Non Delay Starter Size FLA Time Delay Non Delay Starter Size FLA Time Delay Non Delay. ½ 2.5 4 5 2.4 4 5 2.2 3.5 4.5.3 2 2.8 ¾ 3.7 5.6 8 3.5 5.6 7 3.2 5 7.8 2.8 3.5 4.8 8 0 4.6 7 0 4.2 7 9 2.3 3.5 5 0 0 0 ½ 6.9 0 5 6.6 0 5 6 9 2 0 3.3 5.6 7 2 7.8 2 7.5 7.5 2 5 6.8 0 5 4.3 7 9 3.0 7.5 25 0.6 5 20 9.6 5 20 6. 0 5 5 7.5 30 40 6.7 25 30 5.2 25 30 9.7 5 20 7½ 25.3 40 50 24.2 40 50 22 35 45 4 25 30 0 2 32.2 45 60 2 30.8 45 60 28 45 60 8 30 30 2 5 48.3 80 00 46.2 70 90 42 60 90 27 40 60 20 3 62. 00 25 3 59.4 90 0 54 80 00 2 34 60 70 25 78.2 25 75 74.8 0 50 3 68 00 25 44 70 90 30 92 50 200 88 50 75 80 25 75 5 80 00 4 4 40 20 200 225 4 75 225 04 75 200 3 66 00 25 4 50 50 225 300 43 225 300 30 200 250 83 50 75 60 5 77 300 400 5 69 300 350 54 250 350 03 50 200 4 75 22 350 400 2 350 400 5 92 300 400 28 200 200 00 285 450 600 273 450 600 248 400 400 65 250 350 25 6 359 600 600 6 343 600 600 32 500 600 5 208 300 400 50 44 650 800 396 650 800 6 360 600 700 240 400 400 200 480 800 800 320 500 600 250 6 403 600 800 300 532 800 800 350 400 Fuse sizes are selected in accordance with NEC 204 article 430.52 & 57 and table 430.52. 4
Fuse Selection/UL Standard Fuse Classifications Appendix 45V 50Hz 460V 60Hz 575V 60Hz Starter Size FLA Time Delay Non Delay Starter Size FLA Time Delay Non Delay Starter Size FLA Time Delay Non Delay HP 0.8.25.8..8 2.25 0.9.4.8 ½.2 2 2.8.6 2.5 3.2.3 2 2.8 ¾ 2 3 4 2. 3.2 4.5.7 2.8 3.5 0 2.5 4 5.6 0 3 4.5 6 0 2.4 4 5 ½ 3.5 5 7 3.4 5 7 2.7 4 5.6 2 5 8 2 4.8 8 0 3.9 6 8 3 2 7.5 2 5 7.6 2 5 6. 9 2 5.0 7.5 25.0 7.5 25 9.0 5 20 7½ 4 25 30 4 20 30.0 7.5 25 0 2 35 45 2 35 40 7 25 35 5 28 45 60 2 27 40 60 2 22 35 45 20 35 60 60 34 50 60 27 40 60 25 40 60 80 40 60 80 32 50 70 30 3 4 5 55 80 00 3 52 80 00 3 4 60 80 40 64 00 25 65 00 25 52 80 00 50 80 25 75 77 25 75 62 00 25 60 00 50 200 4 96 50 200 4 77 25 75 75 35 200 300 24 200 225 99 50 200 00 65 250 350 56 250 350 25 200 250 25 200 300 400 5 80 300 400 5 44 225 300 50 6 260 400 600 240 400 400 92 300 400 200 325 500 600 302 450 600 242 400 500 250 385 600 800 36 600 700 289 450 600 300 6 6 44 650 800 336 500 600 350 477 800 800 382 600 700 400 Size fuses, time delay or non-time delay, in accordance with the NEC permitted fuse size as noted below: Starter Maximum Fuse Size Size Class R Class J Class L 0 30 60-60 20-2 00 200-3 200 400-4 200 400-5 400 800-6 600 800 800 If the calculated rating is between standard sizes, the next larger size may be used. Fuse size may not exceed switch size. Minimum switch size per NEC 430.0 must be 5% of FLA of motor. Do not use this chart for part winding motors. Size as follows: maximum fuse size limited to 50% FLA for dual element fuses and 200% for non-delay type fuses. 5
Appendix Heater Tables Heater Tables E Standard Trip Heater Elements for Ambient Temp. Comp. Bimetal Relays Full Load Max. Rat. Full Load Max. Rat. Heater Heater Motor Amps of Prot. Motor Amps of Prot. Code No. CodeNo. Min Max Device * Min Max Device * Size 0 & Size 3/4 0.67 0.72 E4 2.27 2.54 E34 3 0.73 0.80 E6 2 2.55 2.69 E36 5 0.73 0.80 E6 2 2.70 2.88 E37 5 2.08 2.26 E33 3 2.89 3.4 E38 5 2.27 2.54 E34 3 3.5 3.40 E39 5 2.55 2.69 E36 5 3.4 3.8 E4 5 2.70 2.88 E37 5 3.82 4.25 E42 5 2.89 3.4 E38 5 4.26 4.62 E44 7 3.5 3.40 E39 5 4.63 5.09 E46 0 3.4 3.8 E4 5 5.0 5.6 E47 0 3.82 4.26 E42 5 5.62 5.9 E48 0 4.27 4.62 E44 7 5.92 6.5 E49 0 4.63 5.09 E46 0 6.6 6.70 E50 0 5.0 5.6 E47 0 6.7 7.54 E5 0 2.08 2.26 E33 3 7.55 8.29 E52 25 2.27 2.54 E34 3 8.30 8.99 E53 25 2.55 2.69 E36 5 9.00 9.85 E54 25 2.70 2.88 E37 5 9.86 0.4 E55 25 2.89 3.4 E38 5 0.5 2.0 E56 25 3.5 3.40 E39 5 2. 3.6 E57 25 3.4 3.8 E4 5 3.7 5.6 E60 30 3.82 4.26 E42 5 5.7 7.0 E6 30 4.27 4.62 E44 7 7. 9.4 E62 30 4.63 5.09 E46 0 9.5 20.9 E65 30 5.0 5.6 E47 0 2.0 22.2 E66 40 5.62 5.9 E48 0 22.3 25.3 E67 40 5.92 6.5 E49 0 25.4 26.9 E69 40 6.6 6.70 E50 0 27.0 30.2 E70 40 6.7 7.54 E5 25 30.3 33.3 E72 40 7.55 8.29 E52 25 Size 2 & 2 /2 8.30 8.99 E53 25 0.5 2.0 E56 50 9.00 9.85 E54 25 2. 3.6 E57 50 9.86 0.4 E55 25 3.7 5.6 E60 50 0.5 2.0 E56 25 5.7 7. E6 50 2. 3.6 E57 25 7.2 9.4 E62 50 3.7 5.6 E60 30 9.5 20.9 E65 50 5.7 7.0 E6 30 2.0 22.2 E66 50 7. 9.4 E62 30 22.3 25.3 E67 50 8.5 9.4 E65 30 25.4 26.9 E69 50 9.5 20.9 E65 30 27.0 30.2 E70 50 2.4 24.4 E67 40 30.3 33.3 E72 50 24.5 25.9 E69 40 33.4 35.3 E73 50 26.0 26.0 E70 40 35.4 4.5 E74 50 4.6 45.0 E76 00 45. 52.3 E77 00 52.4 55.7 E78 00 6
Heater Tables Appendix FullLoad Max.Rat. FullLoad Heater Heater MotorAmps of Prot. MotorAmps CodeNo. CodeNo. Min Max Device * Min Max Size3&3/2 Size4/2&5 Max.Rat. of Prot. Device * 30.0 33.5 E69 00 88.0 98.0 E27 400 33.6 36.4 E70 00 98. 08 E28 400 36.5 39.6 E7 00 09 4 E29 400 39.7 43.6 E73 00 5 22 E3 400 43.7 46.5 E73A 00 23 30 E32 400 46.6 5.6 E74 00 3 40 E33 400 5.7 54.4 E76 00 4 55 E34 400 54.5 58.0 E77 00 56 66 E36 400 58. 63.0 E78 00 67 77 E37 400 63. 67.7 E79 00 78 93 E38 400 67.8 72.4 E80 00 94 209 E39 400 72.5 80.0 E94 00 20 233 E4 400 80. 88. E96 50 234 248 E42 400 88.2 9.5 E97 50 Size6 9.6 96.8 E98 50 66 95 E27 600 96.9 99.0 E99 50 96 27 E28 600 99. 08 E0 50 28 229 E29 600 Size4 230 245 E3 600 56.9 60.9 E89 250 246 26 E32 600 6.0 63.9 E9 250 262 28 E33 600 64.0 67.7 E92 250 282 3 E34 600 67.8 72.4 E93 250 32 33 E36 600 72.5 77.7 E94 250 332 355 E37 600 77.8 85.9 E96 250 356 387 E38 600 86.0 9.9 E97 250 388 49 E39 600 92.0 96.7 E98 250 420 467 E4 600 96.8 05 E99 250 468 500 E42 600 06 5 E03 250 6 30 E04 250 Heaters shown in the table provide a maximum trip rating of 25% of the motor name plate amperes, which is suitable for 40 C motors. For all other motors select heaters one code number lower than specified in the table, which give a maximum trip rating of approximately 5%. The tripping current of any heater in a 40 C ambient is 25% greater than the lower value of motor amperes shown in the table. Starters do not provide protection from short circuits. A protective device should be provided in accordance with the NEC (CEC in Canada) and not exceed the values shown in the table. Note: If the rating specified is not a standard size for the circuit breaker manufacturer, use the next largest size. * Ratings specified are for instantaneous trip circuit breakers. Maximum current rating for thermal magnetic circuit breakers is 250% of maximum heater FLA. Maximum current rating of fuses is: a. 50% of maximum heater FLA for Class R, K, or L (time delay). b. 250% of maximum heater FLA for Class K or L (non-time delay). c. 300% of maximum heater FLA for Class J (nontime delay). If the calculated rating is between standard sizes, the next larger size may be used. Fuse size may not exceed switch size. Wye-delta starters: If the motor nameplate shows the full load delta line current only, divide this value by.73 or multiply by.58 to select the proper heater rating 7
Appendix Heater Tables Part Winding Starter Heater Selection WYE NEMA connected dual voltage motor or SPECIAL 6 lead DELTA connected part winding motor. DELTA NEMA connected dual voltage motor. Select overload heaters from table in both starters (M and M2) based on ½ motor nameplate full load current. Example: Motor Full Load Current of 5 Amperes, Select Heaters from Table for 7.5 Amperes. Consult factory Give complete motor data and application. Bimetal Overload Relays Size 0 through /2 & 4 /2 through 6 Size 3 through 4 INC. NOM. DEC. +5% -5% Figure 22 Man Trip Adjustment Reset Position Auto Reset Position MAIN RESET AUTO RESET Formulas For Obtaining Full Load Amps Of Other Motors 208V Full Load Amp 230V current X 0% 2 Phase FLA 0.866 X the 3 phase FLA 2 Phase, 3 wire current in common wire.4 X that in the other 2 lines. 50 Hz, multiply 60 Hz value X.20 25 Hz, 500 RPM., amps amps of 60 Hz, 3600 RPM. 25 Hz 750 RPM., amps amps of 60 Hz 800 RPM. Service factor.0 amps X 0.9. 50º 55ºC motor amps X 0.9. Single Phase Motor FLA The single phase full load amps of the same horsepower, voltage and speed vary over wide ranges. The following table conforms with table 430-248 of the NEC. When possible the motor full load amps from the motor nameplate should always be used when selecting heater code numbers. Single Phase HP Amperes - 60 Hz 5V 230V 6 4.4 2.5 ¼ 5.8 3.3 3 7.2 4. ½ 9.8 5.6 ¾ 3.8 7.9 6. 9.2 ½ 20..5 2 24. 3.8 3 34. 9.6 5 56. 32.2 7½ 80. 46. 0 00. 57.5 To maintain overcurrent, short circuit, and ground fault protection, the manufacturers instructions for selection of the current elements and setting of the instantaneous trip circuit breaker must be followed. Operating starter sizes 4 through 6 without the heater elements installed will damage the Current Transformers. 8
Approximate AC Motor Amps Appendix Approximate AC Motor Amps Use only When Motor Full Load Current is Not Known Motor Amps will vary depending on the type and manufacture of the motor. These average values, usually for T frame motors with service factor of.5 are to be used only as a guide. The formulas on the previous page may be used to obtain approximate amps for other motors. NOTE: Actual Motor Amps may be higher or lower than the values listed below for a particular motor. For more reliable motor protection, NEC requires selection of heater elements by using the motor nameplate data. Motor nameplate data must be checked to determine proper size of heater coil before motor is energized. 3 Phase 200V 208V 230V 380V 45V 460V 575V KW HP FLA FLA FLA (50Hz) FLA (50Hz) FLA FLA FLA 0.25(¼).39.2 0.6 0.84 0.33( 3).69.46 0.73 0.58 0.37 0.5 2.5 2.4 2.3.8..9 0.55 0.75 3.7 3.5 3.2.8.2.6.3 0.75 4.8 4.6 4.2 2.3 2 2..7..5 6.9 6.6 6.0 3.3 2.5 3 2.4.5 2 7.8 7.5 6.8 4.3 3.5 3.4 2.7 2.2 3 0.6 9.6 6. 5 4.8 3.9 3.7 5 7.5 6.7 5.2 9.7 7.5 7.6 6. 5.5 7.5 25.3 24.2 22 4 9 7.5 0 32.2 30.8 28 8 4 4 5 48.3 46.2 42 27 2 2 7 5 20 62. 59.4 54 34 28 27 22 8.5 25 78.2 74.8 68 44 35 34 27 22 30 92 88 80 5 40 40 32 30 40 20 4 04 66 55 52 4 37 50 50 43 30 83 64 65 52 45 60 77 69 54 03 80 77 62 55 75 22 2 92 28 00 96 77 75 00 285 273 248 65 35 24 99 90 25 359 343 32 208 65 56 25 0 50 44 396 360 240 200 80 44 47 200 552 528 480 320 260 240 92 85 250 403 325 302 242 220 300 532 385 36 289 257 350 620 450 44 336 295 400 709 500 477 382 335 450 797 728 55 42 375 500 886 809 590 472 445 600 656 523 700 76 57 800 775 68 9
Appendix Typical Schematic Typical Schematic Full Voltage Non Reversing (FVNR) Unit NOTE: Rear-Mounted units on Back-to-Back MCC s have reversed phase sequence. Connect motor leads for proper rotation. Figure 23 Full Voltage Non Reversing (FVNR) High Density Unit NOTE: Rear-Mounted units on Back-to-Back MCC s have reversed phase sequence. Connect motor leads for proper rotation. Figure 24 20
Typical Schematic Appendix Typical Schematic Dual Full Voltage Non Reversing (FVNR) Unit NOTE: Rear-Mounted units on Back-to-Back MCC s have reversed phase sequence. Connect motor leads for proper rotation. Figure 25 2
Appendix Typical Schematic Typical Schematic Full Voltage Contactor (FVC) Unit L ELEMENTARY DIAGRAM LI M T L2 L3 CKT. BKR. OR FUSED DISC. L2 L3 T2 T3 7 8 5 6 AUX SW. NOTE F FU () (H) H3 * H2 2FU (4) (H4) NOTE A (XF) 3FU X X2 CPT 2 3 JUMPER M 9 0 A STOP 2 START 3 (V) OFF MS L2 (W) X2 4 5 6 ~ 9 M 0 OFF X2 ~ M 3 L PUSH TO TEST INDICATING LIGHT OPTION (PTT) L2 L ~ ~ 22
Typical Schematic Appendix Typical Schematic Full Voltage Reversing (FVR) Unit NOTE: Rear-Mounted units on Back-to-Back MCC s have reversed phase sequence. Connect motor leads for proper rotation. Figure 27 23
Appendix Typical Schematic Typical Schematic Two Speed - Two Winding (2S2W) Unit NOTE: Rear-Mounted units on Back-to-Back MCC s have reversed phase sequence. Connect motor leads for proper rotation. Figure 28 24
Typical Schematic Appendix Typical Schematic Reduced Voltage Auto-Transformer (RVAT) Unit NOTE: Rear-Mounted units on Back-to-Back MCC s have reversed phase sequence. Connect motor leads for proper rotation. Figure 30 25
Appendix Typical Schematic Reduced Voltage Wye Delta Closed (YDC) Transition NOTE: Rear-Mounted units on Back-to-Back MCC s have reversed phase sequence. Connect motor leads for proper rotation. 26
Typical Schematic Appendix Typical Schematic Reduced Voltage Wye Delta Open (YDO) Transition NOTE: Rear-Mounted units on Back-to-Back MCC s have reversed phase sequence. Connect motor leads for proper rotation. Figure 32 27
SEK SES SAW LMB SEK SES SAW LMB SEK SES SAW LMB NEMA NEMA 2 SEK SES SAW LMB SEK SES SAW LMB SEK SES SAW LMB NEMA NEMA 2 Appendix Typical Schematic Typical Schematic Reduced Voltage Soft-Starter Unit (with SIRIUS 3RW40) Reduced Voltage Soft-Starter Unit (with SIRIUS 3RW44) 3 PHASE L L2 L3 ELEMENTARY DIAGRAM 3 PHASE L L2 L3 ELEMENTARY DIAGRAM 00 0 02 L L2 L3 CIRCUIT BREAKER OR DISCONNECT (FUSED OR NON FUSED) 3M- 2L (L) M (2T) T 00 0 02 L L2 L3 CIRCUIT BREAKER OR DISCONNECT (FUSED OR NON FUSED) (L) (2T) T 03 3M-2 2L2 (3L2) (4T2) T2 MTR 03 M 04 3M-3 2L3 (5L3) (6T3) T3 04 (3L2) (4T2) T2 MTR 05 3RW40 05 (5L3) (6T3) 3RW44 (PE) T3 06 06 07 08 09 0 2 3 4 JUMPER NOTE D 4 (A) FU (H) () M 3FU X (+) 80 8 M CR 24 Volt DC Connections on 3RW405, 407 BLUE WIRE (4/24) (3) M (23) (IN) H M X X2 CR 75 H4 H3 H2 CPT CONNECTIONS FOR OPTIONAL DEVICES X2 2 3 2 2FU (4) (H4) NOTE D SEE TRANSFORMER NAMEPLATE FOR WIRING CONNECTIONS REQUIRED. 3 9 C CR 3M C (96) M_FLT (A2) M (95) 8 CR 0-230 Volt Connections on 3RW402, 403, 404 X2 () M 07 08 09 0 2 3 4 (A) JUMPER M 4 M 2FU (H4) (4) SEE NOTE C FU (H) () SEE NOTE C FU XA (L+) M 76 77 CR Reset 24 Volt DC Connections on 3RW44 BLUE WIRE (3) (4) (23) (24) M 3PB 78 (IN) M (IN4) M (33) (34) M H X 2 3 2 CR H4 H3 H2 CPT X2 SEE TRANSFORMER NAMEPLATE FOR WIRING CONNECTIONS REQUIRED. X2 (A2) M 3 9 (96) (95) C CR M_FLT X2 5 4 2 3 5 CONNECTIONS FOR OPTIONAL DEVICES 6 7 8 9 20 2 22 23 24 25 26 27 28 4 HAND X STOP PB HAND OFF AUTO 4 * SS START 2 3 2PB HAND OFF AUTO START 4 2 3 * 2PB AUTO CONTACT 6 * SS 6 * OFF ON 4 3 * SS FIELD WIRING OFF/STOP 0 0 X2 CR 2LT 0 0 CR 2LT OFF AUTO SS 3 AUTO CONTACT LEGEND: M-CONTROLLER 3M-ISOLATION CONTACTOR ETM-ELAPSED TIME METER *CR-RELAY X 8 PTT OFF/STOP 6 X2 STOP PB CR AUX. CONTACTS OR CONTROL RELAY. WIRE CONTACTS STARTING WITH N.O. 27 29 3 33 (3) 2CR (9) AUTO CONTACT START 2PB NO FAN FOR 3RW402,403,404 (FAN QTY. FOR MCC) AMP SOFTSTART 26-68 77-45 72-25 246-385 494-780 30" WIDE 494-780 50" WIDE FAN X2 C FAN 2 28 30 32 34 -TERMINAL BLOCK POINT (#) -TERMINAL ON CONTROLLER (M) C 0 2 2 2 2 X2 OPTIONAL DEVICES ARE FURNISHED PER CONTRACT DOCUMENTS (4/24) M-UTV 3 9 C ETM RUN/ON/ RUNNING 3 9 LT PTT RUN/ON/ RUNNING 3 9 LT POWER ON X2 3LT UP TO VOLTAGE (4/24) (23) 5 X2 M-UTV 5LT OL TRIPPED 6LT OL TRIPPED 6LT 9A 9A X2 NOTES: A. FOR TYPE A WIRING, JUMPER BETWEEN AND 4. B. WHEN REMOTE CONTROL DEVICES ARE REQUIRED, REMOVE JUMPER BETWEEN AND 4. C. WHEN USING CONTACTORS GROUND CONTACTOR CASE TO MOUNTING PANEL.(AS NEEDED) D. CONTROL DEVICES, LIGHTS, AUX. INTERLOCKS, SURGE SUPRESSER, ETM, CR, CONT. TERMS, PRIMARY FUSES, AND LOAD TERMINALS ARE FURNISHED PER CONTRACT DOCUMENTS. UP TO (23) VOLTAGE 5 X2 5LT (98) (98) M_Flt (95) M_Flt (95) X2 X2 6 7 8 9 20 2 22 23 24 25 26 27 28 29 30 4 76 76 76 4 HAND STOP PB HAND OFF AUTO START 4 2 3 * 2PB AUTO CONTACT 6 * * HAND OFF AUTO 4 * * X X X SS * OFF AUTO X SS 2 6 START 2 3 2PB 3 X AUTO CONTACT OFF ON 4 3 * SS FIELD WIRING 2 (IN3) M 8 (IN3) M MANUAL OPERATION LOCAL (PROFIBUS MODULE) 2 (IN3) X SS M MANUAL OPERATION LOCAL (PROFIBUS MODULE) STOP PB 6 AUX. CONTACTS OR CONTROL RELAY. WIRE CONTACTS STARTING WITH N.O. 27 29 3 33 (3) 2CR (9) 2 AUTO CONTACT CR 26-68 77-45 72-25 246-385 494-850 30" WIDE 494-850 50" WIDE 970-076 28 30 START 2PB MANUAL OPERATION LOCAL (PROFIBUS MODULE) FAN X2 C FAN 2 C (FAN QTY. FOR MCC) AMP SOFTSTART 32 0 2 2 34 2 2 2 2 3 X2 OL TRIPPED 6LT OL TRIPPED 6LT OFF/STOP 0 X2 CR 2LT PTT OFF/STOP 0 CR 2LT 3 9 C ETM RUN/ON/ RUNNING 3 9 LT PTT RUN/ON/ RUNNING 3 9 LT 9A POWER ON X2 3LT 9A (98) X2 (98) M_Flt (95) M_Flt (95) UP TO VOLTAGE (23) (24) 5 X2 M-UTV 5LT X2 X2 X2 UP TO VOLTAGE (23) (24) 5 X2 5LT M-UTV OPTIONAL DEVICES ARE FURNISHED PER CONTRACT DOCUMENTS Figure 33 LEGEND: M- CONTROLLER *CR-RELAY -TERMINAL BLOCK POINT (#) -TERMINAL ON CONTROLLER (M) NOTES: A. FOR TYPE A WIRING, JUMPER BETWEEN AND 4. B. WHEN REMOTE CONTROL DEVICES ARE REQUIRED, REMOVE JUMPER BETWEEN AND 4. C. FUSE PROVIDED PER CONTRACT DOCUMENTS. Figure 34 28
SEK SES SAW LMB SEK SES SAW LMB SEK SES SAW LMB SEK SES SAW LMB SEK SES SAW LMB Typical Schematic Appendix Typical Schematic Variable Frequency Drive Unit (with Micromaster 440) 22 X2 C ETM RUN\ON\RUNNING 22 X2 LT PTT RUN/ON/ RUNNING 22 X2 LT L L2 CIRCUIT BREAKER OR FUSED DISCONNECT L L2 L3 L3 AUX. SW. NOTE C 28 30 29 3 CONNECTION DIAGRAM 2FU H4 L2 L H FU CPT * 3FU XF X2 X2 X2 5 5A 28 29 00 0 02 03 3 PHASE L L2 CIRCUIT BREAKER OR FUSED DISCONNECT L L3 AUX. SW. NOTE C 28 30 29 3 ELEMENTARY DIAGRAM (L) (U) T SPEED POT 2 3 OFF\STOP 45 X2 2LT PTT OFF\STOP 45 X2 2LT FAULT RESET (9) (8) 9 8 3PB COAST STOP (9) (7) 9 7 4PB (9) (9) 2 3 4 START 46 48 2PB STOP 9 46 PB FWD OFF REV 9 5 (4) () (3) (2) HAND OFF AUTO 9 5 5 (5) * SS 5A * (6) * 6 (5) BLUE TWISTED WIRE POWER SUPPLY FOR ANALOG ANALOG INPUT INPUT (6) 6 * SS OFF ON (9) (5) 9 5 AUX. CONTACTS OR * SS RELAY. WIRE CONTACTS STARTING WITH N.O. X2 22 32 34 36 38 C FAN X2 CR C 2FAN DOOR MOUNTED X2 33 35 37 39 0V SUP 0V DIGITAL INPUTS 2 3 4 5 6 7 8 9 0 2 3 4 5 6 7 8 9 20 L L2 45 BLUE TWISTED WIRE L3 GND BUS OR CLIP SUP ANALOG INPUT PE 48 2CR X2 48 46 ANALOG OUTPUT B+ DC+ MOTOR TEMP PROT. U DIGITAL INPUTS V W GND RELAY OUTPUTS 2 22 23 24 NOTES: A. CONTROL DEVICES, LIGHTS, AUX. INTERLOCKS, ETM, CONTROL RELAY, CONTROL TERMINAL, AND LOAD TERMINALS ARE FURNISHED PER CONTRACT DOCUMENTS. B. * CONNECT TRANSFORMER FOR VOLTAGE SPECIFIED PER NAMEPLATE. C. AUX. SWITCH IS MOUNTED ON HANDLE OR INTERNAL TO CIRCUIT BREAKER PER CONTRACT DOCUMENTS. FOR INTERNAL SWITCH, TERMINAL 28 IS COMMON WITH TERMINAL 30. (*) -TERMINAL POINT ON VFD * -TERMINAL BLOCK POINT 25 BLUE TWISTED WIRE DC- AIN+ AIN- DIN DIN2 DIN3 DIN4 ISO 24V AIN2+ AIN2- AOUT+ AOUT- PTCA PTCB DIN5 DIN6 RL RL RL RL2 RL2 RL3 RL3 RL3 AUOT2+ AOUT2- ISO 0V P+ N- 8 2 4 3 4 5 9 6 6 9 7 22 MM440 ONLY MM440 ONLY R+ B- 9 5 T T2 T3 GND ANALOG OUTPUT 26 27 28 SHIELDED WIRE RS485 29 30 30 3 32 33 34 35 36 37 38 39 40 T T2 T3 GND 04 05 06 07 08 09 0 2 3 4 5 6 7 8 9 20 2 22 L2 L3 BLUE TWISTED WIRE P0700=2 OFF ON (9) 9 5 (5) * SS FAULT RESET (9) (8) 9 8 3PB P0704=9 P0700=2 COAST STOP (9) (7) 9 7 4PB P0703=3 P0700=2 2FU (H4) (4) FU (H) () 3FU X (2) RUN (22) VFD P0732=52.2 45 CR (2) RUN VFD P0732=52.2 BLUE TWISTED WIRE (2) (4) (3) () 4 4 3 2 3 2 SLOW SPEED POT 5KOHM P000=2 FAST (22) X H3 22 X2 C ETM H2 X2 () (2) (3) (4) BLACK RED WHITE GREEN () (2) (3) KEYPAD ON DOOR (4) CPT GND BUS OR CLIP (L2) PE (V) MM430/MM440 VFD (L3) (W) GND SEE TRANSFORMER NAMEPLATE FOR WIRING CONNECTIONS REQUIRED. (9) HAND OFF AUTO 9 5 * SS 5A * * BLUE TWISTED WIRE 5 (5) AUTO 6 (6) P0705[0]=99 P0705[]=99 P000[0]=2 P000[]=7 P080=722.4 2FAN C X2 C FAN SUP 22 CR CR X2 RUN\ON\RUNNING 22 X2 LT PTT RUN/ON/ RUNNING 22 X2 LT PTT OFF\STOP 45 X2 2LT OFF\STOP 45 X2 2LT P0700=2 X2 T2 T3 MTR A FRAME DRIVE UNITS DO NOT REQUIRE ANY FAN 2FAN ONLY USED FOR NEMA 2 C FRAME UNITS AND 50HP CT AND 200HP VT UNITS. FWD OFF BLUE TWISTED REV WIRE (9) 9 5 (5) P0700=2 P0702=2 (6) 6 * SS START STOP SUP 9 46 48 X2 CR PB 2PB 2CR BLUE 46 48 TWISTED 2CR WIRE FAULT P0700=2 (9) (20) (9) 9 5 (5) VFD 2CR Figure 35 29
Appendix Aftermarket Aftermarket Siemens is committed to serving our customers and supporting a full line of replacement components, renewal parts, and aftermarket units to maintain the value and use of existing tiastar and previous generation motor control centers. Renewal Parts Renewal parts for tiastar and legacy MCC are now available via Industry Mall and COMPAS. These kits represent the most requested renewal parts for field retrofit installations. Please use the MCC Aftermarket Renewal Parts Catalog, MCCS-AFTMKT-063, which is available at www.usa.siemens.com/mccaftermarket to select the ordering items required. tiastar TM and legacy Motor Control Center Aftermarket Renewal Parts Catalog MCC Aftermarket Request Form For an MCC aftermarket quote, please visit http://www.usa.siemens.com/ mccaftermarket and fill out the online request form. Your request will be processed by a representative who will follow-up with you. For assistance in identifying the MCC, please use the MCC Identification Guide: CCBR-MCCAR-083. Motor Control Centers (MCC) Identification Guide 30
Typical Specification Appendix GENERAL SECTION [26 24 9] [6443] LOW VOLTAGE MOTOR CONTROL CENTERS, ARC RESISTANT SCOPE The requirements of the contract, Division [26] [6] applies to work in this section. Motor Control Centers as specified and as shown on the contract drawings shall be furnished and installed by the contractor. RELATED DOCUMENTS [Related sections include the following: Section [26 29 23] [6269] Variable-Frequency Motor Controllers Section [26 29 3.6] [6420] Reduced Voltage Motor Controllers Section [26 36 23] [645] Automatic Transfer Switches Section [26 43 3] [6289] - Transient Voltage Suppression for Low-Voltage Electrical Power Circuits] Section [26 09 3.xx.xx] [6290] Electrical Power Monitoring and Control Section [2622 9 ] [646] Control and Signal Transformers Section [26 24 6] [6442] - Panelboards Section [2628 6] [640] Enclosed Switches and Circuit Breakers] SUBMITTALS Product Data: Submit manufacturer s printed product data. Drawings: Submit shop drawings for approval. Drawings shall include all dimensions, weights, electrical ratings, wiring diagrams and required clearances. RELATED STANDARDS The Motor Control Center shall be manufactured and tested according to the latest applicable standards of the following agencies: UL 845 Motor Control Centers UL 489 Molded Case Circuit Breakers NEMA ICS 8-200 Motor Control Centers NEMA ICS -200 Industrial Control and Systems: General Requirements NFPA 70 ANSI/IEEE C37.20.7-2007 Guide for Testing Metal-Enclosed Switchgear Rated up to 38kV for Internal Arcing Faults. [Manufacturer Seismic Qualification: The low voltage motor control center(s) shall meet and be certified to seismic requirements specified in the [IBC 2009 International Building Code] [CBC 200 California Building Code] [ASCE American Society of Civil Engineers 7-0]. The low voltage motor control center(s) shall be complaint with IBC 2009 parameters: Building Occupancy Category (as defined in Table. from ASCE 2005): [I] [II] [III] [IV] Seismic Design Category: [A] [B] [C] [D] [E] [F] Site Class: [A Hard Rock] [B - Rock] [C Very dense soil and soft rock] [D Stiff soil profile] as defined in IBC 2006 Table 63.5.2 Site Class Definitions Ip Importance Factor: [.5 Components must function after an earthquake for life safety purposes (Building Occupancy Code IV)] [.25 - Buildings and structures that represent a substantial hazard to human life in the event of failure or that can cause substantial economic impact or mass disruption of day-to-day civilian life (Building Occupancy Code III)] [.0 Non-essential buildings. Function not life critical. (Building Occupancy Code I and II)] Ss Mapped Spectral Accelerations for Short Periods at 0.2 seconds 300%g Sds 5% Damped Design Spectral Response Accelerations for Short Periods at 0.2 seconds 2.0 z/h Height factor ratio: [ ] Note: Ratio is a calculated value equal to the floor the gear is installed on divided by 2. A 6th floor installation is a 0.5 value. A basement or ground floor installation is a 0.0 value. 3
Appendix Typical Specification LOW VOLTAGE MOTOR CONTROL CENTERS, ARC RESISTANT (cont.) Equipment shall be designed to be located in a concrete and steel, moment-resisting frame building not exceeding 2 stories in height with a minimum story height of 0 feet.] QUALITY ASSURANCE Manufacturer: For equipment required for the work of this section, provide products which are the responsibility of one manufacturer. Manufacturer shall have had produced similar electrical equipment for a minimum of 5 years. Manufacturer shall be ISO 900 certified. DELIVERY, STORAGE AND HANDLING Handle and store equipment in accordance with manufacturer s Installation and Maintenance Manual. One () copy of this document shall be provided with the equipment at the time of shipment. PRODUCTS MANUFACTURERS [The low voltage arc resistant motor control center shall be manufactured by Siemens, Type tiastar TM Low Voltage Arc Resistant Motor Control Center or pre-approved equal. Approved manufacturers are as follows: Siemens - Type tiastar Low Voltage Arc Resistant Motor Control Center.] RATINGS System Configuration: Motor Control Center suitable for application in three-phase, [60 Hz] [50 Hz], [3 wire] [4 wire] [grounded-neutral] [3 wire ungrounded] [3 wire high-impedance grounded] system. Electrical Ratings: Nominal System Voltage: [600 V] [480 V] [240 V] [208 V] [Other (specify)]. Maximum Design Voltage: 600V Short-Circuit Current: [42] [65] ka Main-Bus Continuous Current: [600] [800] [200] [600] A. Accessibility Type: 2 Internal Arcing Short-Circuit Current: 65 ka Arcing Duration: 50 msec GENERAL REQUIREMENTS STRUCTURES The enclosure shall be NEMA Type [], [-with gasketed doors]. Vertical sections shall be constructed with steel divider sheet assemblies formed or otherwise fabricated to eliminate open framework between adjacent sections or full-length bolted-on side sheet assemblies at the ends of the MCC(s). Vertical sections shall be 02 high excluding mounting sills and including a 2 modified pull-box or top-hat with pressure flaps installed throughout the MCC for Arc Resistant purposes, 20 wide and 20 deep for front mounting of units. The width of the vertical section may be increased for special oversize units that cannot be accommodated in the standard 20 wide structure up to 30. Vertical structures shall be divided into six (6) full space factors (2 ) and shall accommodate up to six (6) NEMA size or 2 Full Voltage Non Reversing FVNR combination starters. MCC unit sizes shall be multiples of /2 space factor (6 ). The vertical structures shall accommodate up to twelve (2) 6 high density units. The vertical structures shall accommodate up to six (6) 2 units with dual mounted feeders, for a total of up to twelve (2) 25 AF feeders. Each standard 20 wide structure shall be supplied with a 4 wide vertical wireway. Wireways shall be completely isolated from all power busses. The rear surface of the vertical wireway shall be painted white and include openings for pressure release in case of an Arc Flash event. A minimum of three (3) formed wire cable supports, extending the full depth of the vertical wireway shall be supplied in each vertical section. A separate hinged door shall cover the vertical wireway. 32
Typical Specification Appendix Each standard structure shall be supplied with a 2 inch top and six (6) inch bottom horizontal wireway that are continuous for the entire length of the MCC. The minimum horizontal wireway opening between sections is 40 square inches for the top and 30 square inches for the bottom horizontal wireway. A hinged door shall be supplied to cover the top horizontal wireway. Unit doors shall be hinged on the left and vertical wireway doors on the right for unobstructed access to the units and associated vertical wireway. All doors shall be mounted on removable pin-type hinges and secured with steel quarter-turn, into a secured support tested to withstand an Arc Flash event, indicating type fasteners. Wireways shall be completely isolated from bus compartments by suitable barriers. Sliding barriers between the horizontal bus and top horizontal wireway are not acceptable. Removable top cover plates shall be provided for conduit entry to the top horizontal wireway and shall provide a minimum of 6 square inches of area for conduit location. Top cover plates shall be fabricated from 3 gauge steel. All MCC structures shall be supplied with -/8 high X 3 wide base channel sills that are continuous for the entire length of the shipping split. The base channel sills shall be fabricated of 7 gauge steel and shall be suitable for grouting the base channel sills in place, welding to leveling plates or securing to the floor with /2 anchor bolts. MCC structures shall be supplied with reversible bottom end cover plates to cover the bottom horizontal wireway and ends of the base channel sills. The bottom end cover plates shall be factory installed to cover the ends of the base channel sills to prevent entrance of dirt and rodents into the MCC when installed flush on the floor and shall be removable to expose the ends of the base channel sills if they are to be grouted into the floor. A removable, full length lifting angle shall be provided for each shipping split of each MCC. The lifting angle shall be bolted to each side sheet or divider sheet of the shipping split to evenly distribute the weight of the MCC during lifting. MCC s shall be assembled in such a manner that it is not necessary to have rear accessibility to remove any internal devices or components. The main horizontal bus shall be (Pick a. or b. Delete the other. If a. is selected, then make decisions within the paragraph.) [[Tin] [Silver] plated copper rated at [600] [800] [200] [600] amperes with a conductivity rating of 00% AICS. The horizontal bus bars shall be fully sized to carry 00% of the rated current the entire length of the MCC. Horizontal bus bars shall be mounted edge wise and located at the top of the MCC. Tapered horizontal bus is not acceptable.] All power bus shall be braced to withstand a fault current of 65,000 RMS symmetrical amperes.] [The entire horizontal bus assembly must be located behind the top horizontal wireway at any amperage. Horizontal bus bars located behind usable unit space are not acceptable.] The horizontal bus shall be isolated from the top horizontal wireway by a clear, flexible, polycarbonate, Lexan, barrier allowing visual inspection of the horizontal bus without removing any hardware. The vertical bus: Shall be rated [300] [600] amperes. Vertical bus bars shall be fabricated of [tin] [silver] plated solid copper bars with a conductivity rating of 00% AICS. The vertical bus barrier support shall be designed as to effectively enclose each vertical bus bar, providing both isolation and insulation. Automatic shutter mechanisms shall be provided to close off all unused stab openings when a plug-in unit is moved to the TEST position or removed from the structure. Unused stab openings shall be covered with snap-in covers All bus ratings are to be based on a maximum temperature rise of 50ºC over a 40ºC ambient temperature. Horizontal to vertical bus and horizontal bus splice connections shall be made with two (2) 3/8 grade 5 bolts and Belleville-type conical washers at each connection point. All connecting hardware shall be designed to be tightened from the front of the MCC without applying any tools to the rear of the connection. The horizontal ground bus shall be rated [300 amp copper] [600 amp copper]. UNITS Plug-in units shall connect to the vertical bus by means of self-aligning, tin plated copper stab-on connectors provided with spring steel back-up springs to insure positive connection to the vertical bus. When vertical ground bus is specified, plug-in units shall include a ground stab which engages the vertical ground bus before the power stabs engage the vertical bus when the unit is inserted into the structure. When the plug-in unit is withdrawn from the vertical bus, the vertical ground stab shall release after the power stabs. The interior of all MCC units shall be painted white, including unit top and bottom plates or isolation barriers. All plug-in units 30 tall and larger will be secured to the structure in four (4) points to withstand an Arc Flash event. 33
Appendix Typical Specification LOW VOLTAGE MOTOR CONTROL CENTERS, ARC RESISTANT (cont.) All plug-in units 2 tall and larger will include two (2) auxiliary handles to aid in installation, removal and transporting plug-in units. All plug-in units will include a racking mechanism to assure full engagement with the stab-on connectors with the vertical bus. Plug-in units shall be provided with interference type draw-out to prevent complete removal of the plug-in unit from the structure in one motion. The interference mechanism shall also provide clear indication when the plugin unit has been withdrawn to the TEST position. A mechanical interlock shall be supplied on all plug-in units to prevent insertion of removal of a unit from the structure when the unit operator handle is in the ON position. This interlock may not be defeated. Each 2 tall and larger plug-in unit shall be secured in the structure by two (2) readily accessible devices, one of which is tool operated. These devices shall be located at the front of the unit. Plug-in units with NEMA Type B or C wiring shall be supplied with unit terminal block mounted on the right hand side of the unit, adjacent to the vertical wireway. The terminal blocks shall be mounted on a movable bracket that maintains the terminals inside the unit structure for normal operation and pivots into the vertical wireway exposing the terminals for wiring, test and maintenance. All plug-in units shall include a positive means of grounding the unit to the structure at all times. All units that need ventilation (VFD units, RVSS units) shall have a protective plate in front of the louvers to deflect material exiting the unit in case of an Arc Flash event. The MCC unit disconnect operator for 600 ampere maximum units shall operate in a vertical, up-down, plane. High density units shall have horizontal motion. All unit disconnects shall remain engaged with the disconnect device at all times, regardless of the unit door position. The operating handles shall be interlocked with the unit door so that the door can neither be opened with the disconnect device in the ON position, nor can the disconnect device be turned ON with the unit door open except by operation of a defeater mechanism. Indication of the disconnect device shall be clearly indicated by the position of the operating handle. When applied with circuit breaker devices, the handle shall also provide clear indication of a circuit breaker trip. When pilot lights, push buttons or sector switches are specified. The devices shall be mounted in a formed metal device panel that is capable of accepting four (4) such devices in any combination. The device panel shall be secured to the unit door for normal operation, or mounted on the plug-in unit as required for unit removal and bench testing. Pilot devices shall be [22 mm in diameter, rated for NEMA 4 (IP 67) applications. Connections to 22 mm pilot devices shall be made to touch resistant screw type terminations. Pilot device contacts shall be rated at 0A, 600 VAC (NEMA A600).] [heavy duty, oil tight 30mm devices with a NEMA 4 rating. Pilot device contacts shall be rated at 0A, 600 VAC (NEMA A600). The pilot device bodies shall be fabricated from metal.] Unit identification nameplate shall be provided for each unit. Nameplates shall be a black surface with white core. Engraving shall cut through the gray surface exposing white lettering of the unit designation. Nameplates shall be tall by 3 /2 wide. Adhesives or glues are not an acceptable means of mounting unit nameplates. WIRING The wiring shall be NEMA Class [] [2], Type [A] [B] [C]. COMBINATION MOTOR STARTERS The combination starters shall be full voltage, non-reversing and provided with a Siemens [magnetic only circuit breaker] [fused disconnect], unless noted otherwise on the drawings. Starters and disconnects shall be rated equal to or greater than the AIC rating of the gear. Overload Protection The overload protection shall be: Control Power Each starter unit shall be provided with an encapsulated control power transformer of sufficient size to accommodate the contactor coil burden plus all specified auxiliary devices. 34
Typical Specification Appendix FEEDERS Feeder disconnects shall be Siemens [thermal-magnetic circuit breaker] [fused disconnect]. [METERING EQUIPMENT Provide a multi-function, high accuracy digital power metering instrumentation module equipped with LCD display. The power metering module shall provide simultaneous measurements for current, voltage and power parameters. Power meter shall be Siemens type [PAC 300] [PAC 3200] [PAC4200] [9340] [9360] [950] [950ADR/RTU] [960] equipped with a communications port for standard RS-485 connection.] [ARC FLASH Labeling [Delete one or both of the next 2 sentences on arc flash.] [Apply in the field, the factory supplied arc flash warning label to all motor control centers that are in other than dwelling occupancies and are likely to require examination, adjustment, servicing, or maintenance while energized to warn qualified persons of potential electrical arc flash hazards.] [Provide a complete arc flash study of the entire electrical system from the point of incoming service to all panelboards. Labels shall include the arc flash boundary in feet, hazard category and a list of appropriate PPE. When dynamic arc flash sentry is provided, (see below) then perform the study with both the dynamic arc flash sentry on and off. Label the gear for both settings.]] [Dynamic Arc Flash Sentry [OPTIONAL] The TIASTAR motor control center shall come with Dynamic Arc Flash Sentry to reduce the duration of an arc flash event. The main circuit breaker shall be a Siemens WL equipped with an ETU776 trip unit, programmed with two trip curves. One curve shall be set to the levels determined by a coordination study. The second setting shall be set with instantaneous set down to a minimum acceptable level to trip the main rapidly on an arc flash event. The settings shall be adjusted via: [A SIGUARD motion sensor. The sensor shall be mounted approximately 3 feet off of the ground to sense motion in the room and automatically turn on and off the Dynamic Arc Flash Sentry. A blue light will illuminate on the front of the MCC to denote Dynamic Arc Flash Sentry is on.] [A 2 position selector switch. A blue light will illuminate on the front of the MCC to denote Dynamic Arc Flash Sentry is on.]] EXECUTION INSTALLATION Install per manufacturer s recommendations and contract documents. Coordinate installation with adjacent work to ensure proper sequence of construction, clearances and support. ADJUSTMENTS AND CLEANING [Insert your firms requirements] TESTING Perform factory and installation tests in accordance with applicable NEC, NEMA and UL requirements. WARRANTY Equipment manufacturer warrants that all goods supplied are free of non-conformities in workmanship and materials for one year from date of initial operation, but not more than eighteen months from date of shipment. FIELD TESTS Check tightness of all accessible mechanical and electrical connections to assure they are torqued to the minimum acceptable manufacturer s recommendations. 35
Appendix Typical Specification GENERAL SCOPE The requirements of the contract, Division [26] [6] applies to work in this section. Motor Control Centers as specified and as shown on the contract drawings shall be furnished and installed by the contractor. RELATED DOCUMENTS [Related sections include the following: Section [26 29 23] [6269] Variable-Frequency Motor Controllers Section [26 29 3.6] [6420] Reduced Voltage Motor Controllers Section [26 36 23] [645] Automatic Transfer Switches Section [26 43 3] [6289] - Transient Voltage Suppression for Low-Voltage Electrical Power Circuits] Section [26 09 3.xx.xx] [6290] Electrical Power Monitoring and Control Section [2622 9 ] [646] Control and Signal Transformers Section [26 24 6] [6442] - Panelboards Section [2628 6] [640] Enclosed Switches and Circuit Breakers SUBMITTALS Product Data: Submit manufacturer s printed product data. Drawings: Submit shop drawings for approval. Drawings shall include all dimensions, weights, electrical ratings, wiring diagrams and required clearances. RELATED STANDARDS The Motor Control Center shall be manufactured and tested according to the latest applicable standards of the following agencies: UL 845 Motor Control Centers UL 489 Molded Case Circuit Breakers NEMA ICS 8-200 Motor Control Centers NEMA ICS -200 Industrial Control and Systems: General Requirements NFPA 70 [Manufacturer Seismic Qualification: The low voltage motor control center(s) shall meet and be certified to seismic requirements specified in the [IBC 2009 International Building Code] [CBC 200 California Building Code] [ASCE American Society of Civil Engineers 7-0]. The low voltage motor control center(s) shall be complaint with IBC 2009 parameters: Building Occupancy Category (as defined in Table. from ASCE 200): [I] [II] [III] [IV] Seismic Design Category: [A] [B] [C] [D] [E] [F] Site Class: [A Hard Rock] [B - Rock] [C Very dense soil and soft rock] [D Stiff soil profile] as defined in IBC 2006 Table 63.5.2 Site Class Definitions Ip Importance Factor: [.5 Components must function after an earthquake for life safety purposes (Building Occupancy Code IV)] [.25 - Buildings and structures that represent a substantial hazard to human life in the event of failure or that can cause substantial economic impact or mass disruption of day-to-day civilian life (Building Occupancy Code III)] [.0 Non-essential buildings. Function not life critical. (Building Occupancy Code I and II)] Ss Mapped Spectral Accelerations for Short Periods at 0.2 seconds 300%g Sds 5% Damped Design Spectral Response Accelerations for Short Periods at 0.2 seconds 2.0 z/h Height factor ratio: [ ] Note: Ratio is a calculated value equal to the floor the gear is installed on divided by 2. A 6th floor installation is a 0.5 value. A basement or ground floor installation is a 0.0 value. Equipment shall be designed to be located in a concrete and steel, moment-resisting frame building not exceeding 2 stories in height with a minimum story height of 0 feet.] QUALITY ASSURANCE 36
Typical Specification Appendix Manufacturer: For equipment required for the work of this section, provide products which are the responsibility of one manufacturer. Manufacturer shall have had produced similar electrical equipment for a minimum of 5 years. Manufacturer shall be ISO 900 certified. DELIVERY, STORAGE AND HANDLING Handle and store equipment in accordance with manufacturer s Installation and Maintenance Manual. One () copy of this document shall be provided with the equipment at the time of shipment. PRODUCTS MANUFACTURERS [The motor control centers shall be TIASTAR by Siemens or pre-approved equal. Approved manufacturers are as follows: Siemens.] GENERAL REQUIREMENTS STRUCTURES [The enclosure shall be NEMA Type [], [-with gasketed doors], [2], [2], [3R non-walk-in]. Vertical sections shall be constructed with steel divider sheet assemblies formed or otherwise fabricated to eliminate open framework between adjacent sections or full-length bolted-on side sheet assemblies at the ends of the MCC(s).] [Vertical sections shall be 90 high excluding mounting sills, 20 wide and [5 ] [20 ] deep for front mounting of units. Where indicated that arrangement is to accommodate front & rear mounting of units, the structure depth shall not exceed 2. The width of the vertical section may be increased for special oversize units that cannot be accommodated in the standard 20 side structure. ] Vertical structures shall be divided into six (6) 2 space factors and shall accommodate six (6) full size NEMA size or 2 Full Voltage Non Reversing FVNR combination starters. MCC unit sizes shall be multiples of /2 space factor (6 ). The vertical structures shall accommodate 6 high density and dual mounted units. Back-to-Back, front and rear unit mounting, structures shall be 2 deep maximum and shall accommodate 2 full size NEMA size or 2 Full Voltage Non Reversing FVNR combination starters per section. Each standard 20 and 24 wide structure shall be supplied with a vertical wireway. 4 wide wireways shall be installed on 20 wide structures and 8 wide wireways on 24 wide structures. Wireways shall be completely isolated from all power busses. The rear surface of the vertical wireway shall be painted white. A minimum of three (3) formed wire cable supports, extending the full depth of the vertical wireway shall be supplied in each vertical section. A separate hinged door shall cover the vertical wireway. Each standard structure shall be supplied with a 2 inch top and six (6) inch bottom horizontal wireway that are continuous for the entire length of the MCC. The minimum horizontal wireway opening between sections is 40 square inches for the top and 30 square inches for the bottom horizontal wireway. A hinged door shall be supplied to cover the top horizontal wireway. Doors are to be hinged in a manner that allows for the removal of individual doors without the removal of any door above or below. Unit doors shall be hinged on the left and vertical wireway doors on the right for unobstructed access to the units and associated vertical wireway. All doors shall be mounted on removable pin-type hinges and secured with steel quarter-turn, indicating type fasteners. Wireways shall be completely isolated from bus compartments by suitable barriers. Sliding barriers between the horizontal bus and top horizontal wireway are not acceptable. Removable top cover plates shall be provided for conduit entry to the top horizontal wireway and shall provide a minimum of 6 square inches of area for conduit location. Top cover plates shall be fabricated from 3 gauge steel. All MCC structures shall be supplied with -/8 high X 3 wide base channel sills that are continuous for the entire length of the shipping split. The base channel sills shall be fabricated of 7 gauge steel and shall be suitable for grouting the base channel sills in place, welding to leveling plates or securing to the floor with /2 anchor bolts. MCC structures shall be supplied with reversible bottom end cover plates to cover the bottom horizontal wireway and ends of the base channel sills. The bottom end cover plates shall be factory installed to cover the ends of the base channel sills to prevent entrance of dirt and rodents into the MCC when installed flush on the floor and shall be removable to expose the ends of the base channel sills if they are to be grouted into the floor. 37
Appendix Typical Specification A removable, full length lifting angle shall be provided for each shipping split of each MCC. The lifting angle shall be bolted to each side sheet or divider sheet of the shipping split to evenly distribute the weight of the MCC during lifting. MCC s shall be assembled in such a manner that it is not necessary to have rear accessibility to remove any internal devices or components. BUSSING The main horizontal bus shall be (Pick a. or b.) [[Tin] [Silver] plated copper rated at [600] [800] [200] [600] [2000] amperes with a conductivity rating of 00% AICS. The horizontal bus bars shall be fully sized to carry 00% of the rated current the entire length of the MCC. Horizontal bus bars shall be mounted edge wise and located at the top of the MCC. Tapered horizontal bus is not acceptable.] All power bus shall be braced to withstand a fault current of [42,000] [65,000] [00,000] RMS symmetrical amperes.] [Tin plated aluminum rated at [600] [800] [200] amperes. All power bus shall be braced to withstand a fault current of [42,000] [65,000] RMS symmetrical amperes.] The entire horizontal bus assembly must be located behind the top horizontal wireway at any amperage. Horizontal bus bars located behind usable unit space are not acceptable. The horizontal bus shall be isolated from the top horizontal wireway by a clear, flexible, polycarbonate, Lexan, barrier allowing visual inspection of the horizontal bus without removing any hardware. The vertical bus: Shall be rated [300] [600] amperes. Vertical bus bars shall be fabricated of [tin] [silver] plated solid copper bars with a conductivity rating of 00% AICS. [Pick one of the following 4; delete the other 3.] [The vertical bus assembly shall be isolated from the unit mounting space by means of a full height steel barrier. Provisions shall be made to close off unused unit stab openings in the vertical bus barrier with removable covers.] [The vertical bus assembly shall be isolated from the unit mounting space by means of a full height steel barrier. Automatic shutter mechanisms shall be provided to close off all unused stab openings when a plug-in unit is moved to the TEST position or removed from the structure. Unused stab openings shall be covered with snap-in covers.] [The vertical bus barrier support shall be designed as to effectively enclose each vertical bus bar. Provisions shall be made to close off unused unit stab openings in the vertical bus barrier with removable covers.] [The vertical bus barrier support shall be designed as to effectively enclose each vertical bus bar. Automatic shutter mechanisms shall be provided to close off all unused stab openings when a plug-in unit is moved to the TEST position or removed from the structure. Unused stab openings shall be covered with snap-in covers.] All bus ratings are to be based on a maximum temperature rise of [50ºC] [65ºC] over a 40ºC ambient temperature. Horizontal to vertical bus and horizontal bus splice connections shall be made with two (2) 3/8 grade 5 bolts and Belleville-type conical washers at each connection point. All connecting hardware shall be designed to be tightened from the front of the MCC without applying any tools to the rear of the connection. The horizontal ground bus shall be rated [300 amp copper] [600 amp copper] [600 amp aluminum]. UNITS Plug-in units shall connect to the vertical bus by means of self-aligning, tin plated copper stab-on connectors provided with spring steel back-up springs to insure positive connection to the vertical bus. When vertical ground bus is specified, plug-in units shall include a ground stab which engages the vertical ground bus before the power stabs engage the vertical bus when the unit is inserted into the structure. When the plug-in unit is withdrawn from the vertical bus, the vertical ground stab shall release after the power stabs. The interior of all MCC units shall be painted white, including unit top and bottom plates or isolation barriers. All plug-in units 2 tall and larger will include two (2) auxiliary handles to aid in installation, removal and transporting plug-in units. All plug-in units will include a racking mechanism to assure full engagement with the stab-on connectors with the vertical bus. 38
Typical Specification Appendix Plug-in units shall be provided with interference type draw-out to prevent complete removal of the plug-in unit from the structure in one motion. The interference mechanism shall also provide clear indication when the plugin unit has been withdrawn to the TEST position. A mechanical interlock shall be supplied on all plug-in units to prevent insertion of removal of a unit from the structure when the unit operator handle is in the ON position. This interlock may not be defeated. Each 2 tall and larger plug-in unit shall be secured in the structure by two (2) readily accessible devices, one of which is tool operated. These devices shall be located at the front of the unit. Plug-in units with NEMA Type B or C wiring shall be supplied with unit terminal block mounted on the right hand side of the unit, adjacent to the vertical wireway. The terminal blocks shall be mounted on a movable bracket that maintains the terminals inside the unit structure for normal operation and pivots into the vertical wireway exposing the terminals for wiring, test and maintenance. All plug-in units shall include a positive means of grounding the unit to the structure at all times. The MCC unit disconnect operator for 600 ampere maximum units shall operate in a vertical, up-down, plane. High density units shall have horizontal motion. All unit disconnects shall remain engaged with the disconnect device at all times, regardless of the unit door position. The operating handles shall be interlocked with the unit door so that the door can neither be opened with the disconnect device in the ON position, nor can the disconnect device be turned ON with the unit door open except by operation of a defeater mechanism. Indication of the disconnect device shall be clearly indicated by the position of the operating handle. When applied with circuit breaker devices, the handle shall also provide clear indication of a circuit breaker trip. When pilot lights, push buttons or sector switches are specified. The devices shall be mounted in a formed metal device panel that is capable of accepting four (4) such devices in any combination. The device panel shall be secured to the unit door for normal operation, or mounted on the plug-in unit as required for unit removal and bench testing. Pilot devices [shall be 22 mm in diameter, rated for NEMA 4 (IP 67) applications. Connections to 22 mm pilot devices shall be made to touch resistant screw type terminations. Pilot device contacts shall be rated at 0A, 600 VAC (NEMA A600).] [Pilot devices shall be heavy duty, oil tight 30mm devices with a NEMA 4 rating. Pilot device contacts shall be rated at 0A, 600 VAC (NEMA A600). The pilot device bodies shall be fabricated from metal.] Unit identification nameplate shall be provided for each unit. Nameplates shall be a black surface with white core. Engraving shall cut through the gray surface exposing white lettering of the unit designation. Nameplates shall be tall by 3 /2 wide. Adhesives or glues are not an acceptable means of mounting unit nameplates. WIRING The wiring shall be NEMA Class [] [2], Type [A] [B] [C]. COMBINATION MOTOR STARTERS The combination starters shall be full voltage, non-reversing and provided with a Siemens [magnetic only circuit breaker] [fused disconnect], unless noted otherwise on the drawings. Starters and disconnects shall be rated equal to or greater than the AIC rating of the gear. Overload Protection The overload protection shall be:.) [Bi-Metal Ambient compensated overload.] 2) [Self power ESP solid state overload relay with NEMA Class [0] [20] [30] trip curve.] Control Power Each starter unit shall be provided with an encapsulated control power transformer of sufficient size to accommodate the contactor coil burden plus all specified auxiliary devices. FEEDERS Feeder disconnects shall be Siemens [thermal-magnetic circuit breaker] [fused disconnect]. [ARC FLASH Labeling [DELETE ONE OR BOTH OF THE NEXT 2 SENTENCES ON ARC FLASH] [Apply in the field, the factory supplied arc flash warning label to all motor control centers that are in other than dwelling occupancies and are likely to require examination, adjustment, servicing, or maintenance while energized to warn qualified persons of potential electrical arc flash hazards.] [Provide a complete arc flash study of the entire electrical system from the point of incoming service to all panelboards. Labels shall include the arc flash boundary in feet, hazard category and a list of appropriate PPE. When dynamic arc flash sentry is provided (see below), then perform the study with both the dynamic arc flash sentry on and off. Label the gear for both settings.]] 39
Appendix Typical Specification [Dynamic Arc Flash Sentry [OPTIONAL] The TIASTAR motor control center shall come with Dynamic Arc Flash Sentry to reduce the duration of an arc flash event. The main circuit breaker shall be a Siemens WL equiped with an ETU776 trip unit, programmed with two trip curves. One curve shall be set to the levels determined by a coordination study. The second setting shall be set with instantaneous set down to a minimum acceptable level to trip the main rapidly on an arc flash event. The settings shall be adjusted via: ) [A SIGUARD motion sensor. The sensor shall be mounted approximately 3 feet off of the ground to sense motion in the room and automatically turn on and off the Dynamic Arc Flash Sentry. A blue light will illuminate on the front of the MCC to denote Dynamic Arc Flash Sentry is on.] 2) [A 2 position selector switch. A blue light will illuminate on the front of the MCC to denote Dynamic Arc Flash Sentry is on.]] SMART MOTOR STARTER Motor starter units shall include a microprocessor based protective and control device that provides NEMA class 5,0,5, 20, 25, 30, 35 or 40 thermal overload trip characteristics, phase asymmetry (phase imbalance & phase loss) protection, stalled rotor protection, instantaneous over current (jam) and under current protection and provisions for connecting one thermistor. Upper and lower current limits are adjustable for tripping and monitoring.. The device should provide an option of voltage and power monitoring as well as monitoring of power factor (cos-phi or loss of load) protection. Device shall have internal and external ground fault monitoring capabilities to an exacting 0.3 amp equipment protection. Additionally the device shall have an option of monitoring three RTD s (PT00 or PT000) temperature sensors or three NTC thermistor sensors. [The device shall have two analog inputs and one analog output with a [0 to 20m amp] [4 to 20m amp] signal.] All protective functions shall be programmable to initiate a fault (trip) or warning. The device shall have the ability to designate its inputs as external fault inputs for hardwiring into upstream or downstream parts of the application. Running status of the connected load shall be determined by monitoring motor current to give a true indication of running status. The device shall provide monitoring of operating hours, downtime hours, number of starts, overload trips and have permissible starting capabilities. The device shall contain four digital inputs and three relay output points for use in controlling the motor starter. [There shall be two additional digital modules with 4I/2O, and they shall have [bi-stable] [mono-stable] output contacts.] Output relays shall be programmable to either turn off or retain their status in the event of a control voltage loss or network failure. The device shall also include on board logic elements including up to a total of six 3I/O truth tables, two 2I/O truth tables, and one 5I/2O truth table. The device shall have up to four signal conditioners and four non-volatile elements with adjustable (edge rising with memory, edge falling with memory, inverting and non-inverting) conditions. Additional elements shall include up to four timers with adjustable (with closing delay, closing delay with memory, with off delay, with fleeting closing) conditions and four limit monitors for overshoots and undershoots of any of its analog signals. The device shall communicate via PROFIBUS-DP to a central master controller and provide motor current, in percent of the motor full load amps, input and output data, status messages ON, OFF, under and over current warning and trip on a continuous cyclical basis. The user shall have the ability to remotely monitor and program all programmable parameters, diagnostic data and operating data. The device shall communicate at a maximum of.5mbit Profibus communication speed, and shall be auto baud rate sensing. The device shall be able to send 244 bytes per telegram and 64 bytes of diagnostics. In the event of a communication network failure or PLC failure, the device shall operate as a stand-alone device. Upon restoration of the PROFIBUS network, the device shall resume communication with the network. 40
Typical Specification Appendix NETWORK [The Siemens Intelligent Motor Control Center shall be connected to the customer s existing system via the Profibus network scanner located in the customer s PLC. These network scanners shall provide full Profibus network connectivity.] [The Siemens Intelligent Motor Control Center shall be connected to the customer s existing system via a Network Gateway. The network gateway shall provide restricted Profibus network connectivity.] [The Siemens Intelligent Motor Control Center shall be a stand alone system.] Siemens TIASTAR Intelligent Motor Control Center is supplied with [Profibus DP] [AS-Interface]. These networks shall be installed at the factory to provide simplify commissioning on site. [Select either 2.4.B. or 2.4.B.2. Delete the other section] [AS-Interface AS-Interface networking shall be used for the passing of low level binary information to and from TIASTAR Intelligent Motor Control Center devices. Maximum electrical cable length is 00m with a 5ms cycle time. Each AS-Interface network must consist of AS-Interface Master Unit and may connect up to 3 AS- Interface module slaves located within the TIASTAR Intelligent Motor Control Center units. There may be as many AS-Interface networks as the higher level operating system can control. The AS-Interface network is connected throughout the TIASTAR Intelligent MCC via a copper two wire twisted pair daisy chained from the master unit to each subsequent unit. These wires terminate into pull-apart terminals at each unit to keep network integrity if the unit is withdrawn from the vertical section. The AS-Interface Master provides all AS-I network support functions and also the data transfer to Profibus DP. The AS-Interface Power Supply generates the AS-interface slave control power as well as the data decoupling feature to send both power and data over the same two wires. The AS-Interface Master Unit must contain both the Master and Power Supply. Each AS-Interface Master Unit and its connected network devices shall be considered a single Profibus DP slave within a TIASTAR Intelligent Motor Control Center.] [Profibus DP Profibus DP networking shall be used for the passing of binary and analog data to and from TIASTAR Intelligent Motor Control Center devices. Maximum electrical cable length 400m at 500kbps; 200m at.5mbps. Distances of 3000m are possible with the use of fiber optic cable. Each Profibus DP network shall connect to up to 26 nodes. The Profibus DP network may have up to 0 segments with up to 30 nodes in each. Profibus segments are connected via the Profibus Repeater. There shall be as many Profibus DP networks as the higher level operating system can control. The Profibus DP network shall connect throughout the TIASTAR Intelligent MCC via copper RS485 shielded twisted two wire Profibus cable daisy chained from unit to unit. These cables terminate into Profibus Connectors at each unit with a Profibus communication port. Cables terminated within the Profibus Connector shall maintain network connectivity when the unit is withdrawn from the vertical section. Profibus Repeater units shall provide data signal amplification and bus segment connection. Standard active termination shall be provided through the Profibus Connector with Termination Resistor. Each connector shall have a switch located on its spine that turns the terminating resistor on and off. [OPTIONAL Active Profibus Terminator units shall provide consistent Profibus DP network termination that does not rely on node control power or connector switch position].] METERING Multifunction Digital-Metering Monitors shall be UL-listed or recognized, microprocessor-based unit suitable for three or four wire systems. Units shall communicate via: [Profibus DP module] (SIEMENS Prefered method) [ModBus TCP port] [ModBus RTU expansion module]. The meter shall mounted on the door and shall meter [at the Main Lugs] [at the Main Breaker] [as shown on the drawings]. [Metering Equipment Provide a multi-function, high accuracy digital power metering instrumentation module equipped with LCD display. The power metering module shall provide simultaneous measurements for current, voltage and power parameters. Power meter shall be Siemens type [PAC 300] [PAC 3200] [PAC4200] [9340] [9360] equipped with a communications port for standard RS-485 connection. 4
Appendix Typical Specification EXECUTION INSTALLATION Install per manufacturer s recommendations and contract documents. Coordinate installation with adjacent work to ensure proper sequence of construction, clearances and support. ADJUSTMENTS AND CLEANING [Insert your firms requirements] TESTING Perform factory and installation tests in accordance with applicable NEC, NEMA and UL requirements. WARRANTY Equipment manufacturer warrants that all goods supplied are free of non-conformities in workmanship and materials for one year from date of initial operation, but not more than eighteen months from date of shipment. FIELD TESTS Check tightness of all accessible mechanical and electrical connections to assure they are torqued to the minimum acceptable manufacturer s recommendations. END OF SECTION 42
Appendix MCC Training Those who are new to the industrial technologies might find the STEP (Siemens Technical Education Program) web site and the MCC course helpful. The link to the MCC Online Training Course can be found here: www.usa.siemens.com/step 43