1 SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132 Covers & Doors 133 Compartments / Incoming / Cable / Outgoing 134 Form of Internal Separation 135 Protection & Finish 20 Electrical Characteristic 30 Testing & Certification 31 Tests according to BSEN Full Type Tests & Routine Tests according to Clause 8 2 & Test According To Other Standards 40 Instructions For Installation, Operation & Maintenance GENERAL CHARACTERISTICS 11 STANDARDS All Low-Voltage switchboards shall comply with Standard BS EN , DIN VDE 0660 T500 section 83, and all their electrical and operating characteristics shall be expressed in accordance to these standards 12 GENERAL OPERATIONAL CONDITIONS The switchboards shall be for indoor installation, in environmental conditions showing a pollution degree 3 according to BS EN The reference ambient temperature shall be 35ºC Relative humidity shall not exceed 50% at the reference ambient temperature
2 13 GENERAL DESCRIPTION OF THE SWITCHBOARDS 131 Structure The panel structure shall be made of steel Partition steel plates, fastened to the structure, shall divide the switchboard into compartments The position of the partition steel plates shall be adjustable to easily adapt the height of the compartments in steps of 25mm Each compartment shall be closed by an individual practicable steel door on the front, and by independent steel covers on the sides and back Fully independent compartments shall be provided for: - Incoming section - Main Busbar - Cabling - Switch-gear - Metering and protections Extensions of the switchboard, by addition of similar structures, shall be possible both to the right and to the left of the initial structure 132 Covers and doors All accessible parts of the switchboard shall be conveniently earthed by their assembly means, and shall not require any supplementary specific Earthing lead When installed, covers and doors shall ensure a minimum IP30 degree of protection according to Standard BS EN Side- and back-covers Side- and back-covers shall be flush-mounted on the structure by means of spacers and self-tapping screws, which shall ensure the Earthing of the covers For ease of maintenance, the covers shall be interchangeable and re-usable on any compartment of the same height Doors The doors shall be provided with internal hinges, ensuring the Earthing of the door The minimum opening angle of the door shall be 130 to 180 degrees The doors shall be pre-punched to accommodate at any time: - Door locks - Meters - Plates for auxiliary components - Louvers for ventilation Doors for switchgear compartments shall be provided with an interlock, avoiding the opening of the door without previously switching-off the voltage supply to the compartment Doors for Busbar, cable and meter compartments shall be equipped with a lock, to avoid unauthorised access to the compartments 133 Compartments The different compartments formed by the partition plates, shall comply with the following conditions: Incoming and Busbar compartments - The incoming and the busbar compartments shall be separated from the other compartments by moulded plastic finger-proof shrouds - The main Busbar compartment shall be located at the rear of the switchboard, in a top or middle position - The Busbar compartment shall contain all phase and Neutral conductors, duly marked L1, L2, L3, and N - Protective conductors shall be located in a separate compartment, and shall be duly marked PE or PEN - The Busbar shall be made of flat copper bars, of the same cross-section over the whole width of the switchboard, and allow extensions of the switchboard both left and right - All fixed connections shall be maintenance-free - Separation links to adjacent columns shall be accessible from the front of the switchboard - The Busbar shall be supported by insulators, made of flameproof and leakage-proof material - For rated currents of 630A and above, flat copper bars shall be used, both for the Busbar and for the in-coming and out-going feeders
3 Cable compartment - The cable compartment shall contain the out-going terminals for main and control circuits - The cable compartment shall be located to the right of the switchboard - The cable compartment shall be separated from the other compartments by metallic shutters providing a degree of protection of minimum IP20 according to Standard BS EN 60529, to avoid the accidental downfall of parts from upper compartments - Out-going feeders shall have a degree of protection of minimum IP20 according to Standard BS EN 60529, to avoid accidental contacts - For out-going feeders of 630A and above, copper bars shall be provided as terminals, to allow the connection of several cables in parallel - All connection terminals and cables shall be mounted in such a way as to avoid any traction or compression forces being exerted on them - The bars and cable supports shall be designed to withstand the presumed shortcircuit current - Incoming and outgoing cables shall enter the compartment by the top and the bottom, with front and rear access provided to the connections Switch-gear and metering compartments - Switch-gear and metering compartments shall be equipped with universal fixing plates, with holes in fixed steps allowing for the mounting of the different switch-gear and metering and protection components - Suitable incoming devices using breaker or fuse-switch technology with corresponding ratings and breaking capacity shall protect each switchgear compartment out-going feeder - Meters and signal lamps shall be mounted on the hinged door of the compartment, which shall be pre-punched to accommodate standard instruments and signalling lamps and push buttons 134 Form of internal separation Switchgear and metering compartments shall be separated from each other by finger-proof partitions Busbar and cable compartments shall be separated from the switchgear and metering compartments by finger-proof partitions The manufacturer shall indicate the Form of separation of the compartments according to informative Annex D of Standard BS EN 60439, Form 4b being the minimum required 135 Protection and finish Protection against corrosion - A zinc coating, providing protection against corrosion according to Standard EN 10142, shall protect all steel parts forming the structure - All ferrous parts eg hinges, mounting parts, shall be protected by an electrogalvanic zinc coating Protection shall be verified in accordance with Standard BS EN Following tests shall be made: - Wet heat, 6 cycle 24hours with 95% relative humidity at 40ºC, according to Standard IEC Salt fork, 2 cycle 24hours at 35ºC, according to Standard IEC Finish - Covers and doors shall be made of 2mm steel sheet to ensure stability - All edges shall be bent-over to avoid sharp edges - All external doors and covers shall be flush-mounted to the structure - No hinges, fixing screws or bolts shall be visible from the front of the switchboard - All external parts shall show a uniform colour, preferably RAL 7035, applied through an epoxy powder painting of minimum 75 thickness
4 2 ELECTRICAL CHARACTERISTICS Switchboards shall be designed according to the following electrical characteristics: Rated operational voltage Ue: 690V ac Rated insulation voltage Ui: 1000V Impulse withstand voltage: 8kV 12/50s Rated frequency: 40-60Hz Minimum Rated short time withstand current Icw For Busbars phase conductors with: - Rated currents up to 1000A: 50kA 1s - Rated current 1250A: 65kA 1s - Rated currents 1600A up to 4000A: 80kA 1s Minimum Peak withstand current Ipk For Busbar phase conductors with: - Rated currents up to 1000A: 105kA pk - Rated current 1250A: 143kA pk - Rated currents 1600A up to 4000A: 176kA pk Minimum Cross-sections for Neutral conductor: Busbars with phase conductors with rated currents: - Up to 1250A: 300mm A & 2000A: 400mm A & 3200A: 800mm A: 1200mm 2 Minimum Cross-sections for PE or PEN conductors: Busbars with phase conductors with rated currents: - Up to 1000A 300mm 2 - Over 1000A 400mm 2 3 TESTING AND CERTIFICATION Upon delivery, the manufacturer of the switchboard shall carry out tests with the fully equipped switchboard, according to the relevant Standards indicated below For each of the tests, the manufacturer, indicating the results of the tests, shall provide a valid certification 31 TESTS ACCORDING TO BS EN Type tests made according to clause 82 Verification of temperature-rise limits (clause 821) Maximum temperature-rise with fully loaded compartments shall not exceed the values indicated in Table 2 of BS EN Verification of the dielectric properties (clause 822) Test Voltage for main circuits shall be 3500V ac rms Test voltage for auxiliary circuits shall be 1500V ac rms Test voltage for the Impulse voltage withstand test shall be 8kV 12/50s Clearance and creepage distances shall be in accordance with Tables 14 & 16 of Standard BS EN There shall be no unintentional disruptive discharge during the tests Verification of short-circuit withstand strength (clause 823) Test current for short-circuit withstand current Icw shall be at least; For Busbars phase conductors with: - Rated currents up to 1000A: 50kA rms 1s - Rated current 1250A: 65kA rms 1s - Rated currents 1600A up to 4000A: 80kA rms 1s Test current for impulse withstand current Ipk for shall be at least, For Busbar phase conductors with: - Rated currents up to 1000A: 105kA pk - Rated current 1250A: 143kA pk - Rated currents 1600A up to 4000A: 176kA pk
5 During the tests for short-circuit withstand strength, we have verified: - That Busbar-compartment doors and covers remained closed during the test, - That full arc containment is achieved An accredited laboratory shall provide the certificate for the results of these tests Verification of the effectiveness of the protective circuit (clause 824) All parts of the switchgear combinations shall be effectively connected to the protective conductor, and this connection shall show a resistance below 01Ohm After the test for the verification of short-circuit withstand strength of the protective circuit, the protective conductor shall not be impaired Verification of clearance and creepage distances (clause 825) It shall be verified that clearance and creepage distances are in accordance with Tables 14 & 16 of Standards BS EN , considering a pollution degree 3 Minimum values for creepage and clearances combinations shall be used when dielectric properties are tested Withdrawable assemblies, if any, shall additionally endure dielectric tests in their test and disconnected positions Verification of Mechanical operation (clause 826) A minimum of 50 mechanical operations shall be made on the mechanical functions of individual components and groups after installation into the assembly At the same time, the operation of the functions of coupled & interlocking devices and mechanisms shall be checked After the testing is complete the apparatus, interlocks, etc, shall operate properly and practically the same as before the test Verification of the degree of protection (clause 827) The degree of protection shall be verified according to BS EN EMC tests (clause 828) Only components complying with EMC requirements shall be used within the assembly If exceptionally required, the manufacturer shall provide a CE Declaration of Conformity, no further testing being required 311 Routine tests (clause 83) For the fully assembled and installed switchboard, the following routine tests shall be carried out: Checking of Assembly, wiring & electrical operations (clause 831) Dielectric test (clause 832) Checking of protective measures & electrical circuits clause 833) Verification of insulation resistance (clause 834) Before commissioning the switchboard, the manufacturer, or the installer acting on his behalf, shall issue a compliance certificate stating all these routine tests having been made with positive results 32 TESTS ACCORDING TO OTHER STANDARDS Where required, for specific functions or components built into the switchboard, specific compliance certificates may be required from the manufacturer In particular, compliance to the following Standards may be required: BS EN Electrical equipment for industrial machines BS EN Preventive Measures BS EN Ingress Protection BS EN Isolation Co-ordination BS EN Motor Starters with Co-ordinated Short Circuit Protection, with voltage ranges & product ratings to VDE 0106 T100 (BGV A2) Type 2 coordinated 4 INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE The manufacturer shall specify in his documents or catalogues the conditions for the installation, operation and maintenance of the assembled switchboard and the equipment therein These documents may also include the recommended extent and frequency of maintenance, and a list of recommended spares for the switchboard and equipment therein
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA
MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,
SIVACON The Versatile Low-Voltage Switchboard
s SIVACON The Versatile Low-Voltage Switchboard Type-Tested Power Distribution Board 8PT The Obvious Solution for Global Challenges SIVACON Type testing in low-voltage switchgear is increasingly becoming
Industrial Process Plants. Residential & Commercial Buildings. Roads & Tunnels. Airports & Seaports
APPLICATION TYPE TEST Industrial Process Plants ANT-V: Reliable, safety switchgear Hundreds of ANT s Switchboards have been supplied to industrial factories. ANT-V siwtchboards are designed, fabricated
IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
xl 3 configurable assemblies IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES XL 3 configurable assemblies guide to migration from IEC 60439 to IEC 61439
Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy
Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility
Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon
Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
MNS is Switchgear System Technical Overview
Switchgear System Technical Overview Innovative Design ABB s innovative MNS is concept combines the long term experience, energy efficiency, grid reliability and industrial productivity of the well-known
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket
The power distribution board that sets new standards
SIVACON The power distribution board that sets new standards SIVACON S4 safe, cost-efficient and flexible Answers for infrastructure. Contents We support you with system 04 05 Maximum safety is our top
Securing your electrical installations Prisma,
Securing your electrical installations Prisma, an optimised solution for type tested low voltage switchboards up to 3200 A Table of contents Developing installation safety 4 Prisma P * Electrical switchboards
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component
Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125
Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated
IEC specifications for LV assembly switchboards
Technical set IEC specifications for LV assembly switchboards In conformity with IEC 61439-1&2 standard Specifier Guide Introduction Within the IEC 61439 series of standards for low-voltage switchgear
COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR
COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR Copyright Material IEEE Paper No. PCIC 2003-13 Eddie Wilkie Eaton Cutler-Hammer 3990 Old Tasso Road NE Cleveland, TN 37312 USA Abstract
P System Cubicles. Certified for more safety
P System Cubicles Prisma Plus LV Switchboards Certified for more safety Prisma Plus, an offer thought out for greater professionalism With the Prisma Plus P system, Schneider Electric proposes high-performance
Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
Low Voltage Switchboards The Best Technical Solution for Your Ship
The Best Technical Solution for Your Ship Wärtsilä SAM Electronics Optimal Power Distribution The uninterrupted supply of power to systems and consumers onboard modern ships is an extremly important matter.
Automation Products. Low Voltage Switchgear MNS System Overview
Automation Products Low Voltage Switchgear MNS System Overview Inroduction to the MNS System ABB is the global leader for production of a wide range of low voltage energy systems. In 1992 ABB started operations
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Sample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
GE Power Controls. MiniFORM Switchboards
GE Power Controls MiniFORM Switchboards MiniFORM MiniFORM MiniFORM switchboards Arrangement Modules Arrangement modules 1-6 6 Arrangement modules 7-12 7 Arrangement modules 12-14 8 Arrangement modules
TriLine ASSEMBLY System PowerModules
04 2012 TriLine ASSEMBLY System PowerModules TriLine ASSEMBLY system Contents Introduction The new modular system intelligence 2 Delivery formats 8 EDS PowerCon configuration software 10 Technical specifications
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services
Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole)
Overcurrentswitch,6A,2p,D-Char,AC Partno. FAZ-D6/2 Articleno. 278777 CatalogNo. FAZ-D6/2 Similar to illustration Deliveryprogramme Basic function Miniature circuit breakers Pole 2 pole Tripping characteristic
SIVACON Low Voltage Switchboard
SIVACON Low Voltage Switchboard s Industrial Solutions and Services Your Success is Our Goal Versatile with Safety Type tested Components for Power Distribution The SIVACON low voltage switchgear board
The easy way to build switchgear and controlgear assemblies in compliance with the regulations
The easy way to build switchgear and controlgear assemblies in compliance with the regulations A guide for partially type-tested switchgear and controlgear assemblies in compliance with EN 60 439 What
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact
Technical Application Papers No.11 Guidelines to the construction of a low-voltage assembly complying with the Standards IEC 61439 Part 1 and Part 2
Technical Application Papers No.11 Guidelines to the construction of a low-voltage assembly complying with the Standards IEC 61439 Part 1 and Part 2 Technical Application Papers Index Introduction...
KAM 25-32 A Lighting Busbar System KAP 40-63 A Plug-in Busbar Distribution System
2-32 A Lighting Busbar System 4-63 A Plug-in Busbar Distribution System / E-LINE KX Compact Busbar Distribution System 63...63 A E-LINE KB Compact Busbar Distribution System 8...63 A E-LINE KO Plug-in
Providing Consulting Engineers and Switchboard Builders the BUILDING BLOCKS for advanced & cost effective solutions TECHNO MODULAR SWITCHBOARD SYSTEM
TECHNO MODULAR SWITCHBOARD SYSTEM Features: - A fully modular switchboard system that complies with the new IEC61439-1 & 2 design verification standards.. - User friendly Estimation & Design software.
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
MNS Low Voltage Switchgear System Guide
MNS Low Voltage Switchgear System Guide 2 MNS is a registered trademark. Product names of other products are registered trademarks of their manufacturers or owners. Technical descriptions relate to MNS
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
IEC 61439-1 & 2 standard. The reference for safe and reliable LV switchboards
IEC 61439-1 & 2 standard The reference for safe and reliable LV switchboards IEC61439-1 & 2 The power of a standard adapted to your needs IEC standards are today legal or market references. The new IEC
Switchboard system. NorLine 800
Switchboard system NorLine 800 NorLine 800 SWITCHBOARD SYSTEM 2 NorLine 800 Switchboard system Table of contents Subject Page Table of contents 2 Overview 2-3 NorLine 800 technical specifications 4 Structural
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
MEDIUM VOLTAGE SWITCHGEAR AND CONTROLGEAR MODEL MS-E. IEC 62271-200 7.2 /12 /15 kv 25, 31.5, 40 ka
SWITCHGEAR AND CONTROLGEAR MODEL MS-E IEC 6227- /2 /5 kv,, ka The MS-E conforms to IEC 6227- standard and is designed and manufactured utilising Mitsubishi Electric state-of-the-art technology, fully taking
R.C.C.B. s two-pole LEXIC
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
Heavy Duty Solenoid Controlled Access Lock. User Manual - Original Language Version
OLYM-S24D-C24D The Olympus 4HD is a heavy duty solenoid controlled access lock available with either a stainless steel tongue actuator or a heavy duty handle. The Olympus 4HD is capable of supporting Category
Modis 25/32. Modular Switchboard Solution
Modis 25/32 Modular Switchboard Solution Dorman Smith Switchgear Limited With over 130 years of experience in switchgear design and production Dorman Smith Switchgear Limited continues to provide high
Comparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
Installation, Operation and Maintenance Instructions. Uniflex ABB PTMV
Installation, Operation and Maintenance Instructions Uniflex ABB PTMV SAFETY FIRST! For safe and correct usage note the following recommendations: Only install switchgear and switchboards in enclosed rooms
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
DEVICES OF PROTECTION AND COMMAND
COMPLEMENT Doc: 702-CRC-007-E Page: 1/24 Elaborated by: Laercio Santos Checked by: Karen Carolina Martins Rodrigo Omori Douglas Ferreira Nelson Coelho Approved by: Nelson Coelho Approval date: 14/07/2014
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
NDQ5 Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD
Shanghai Liangxin Electrical CO.,LTD Address: No. 668 Heng An Road, Pu Dong New District, Shanghai Zip: 200137 Tel: 86-21-5012789 Fax: 86-21-58675966 E-mail: [email protected] LINE 1 LINE 3 LINE 5
Masterclad Medium Voltage Passive Arc-Resistant Switchgear
Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
Vario-Series Accessories
Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Distribution Boards & Consumer Units
Distribution Boards & Consumer Units Enclosures for system pro M compact Distribution Boards & Consumer Units Contents General 2/ Distribution Boards Mini Center compact Mounting kits for compact accessories
SURGE PROTECTIVE DEVICES
SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood
Standard-compliant switchgear and controlgear production
Rittal technology library 1 2013 Standard-compliant switchgear and controlgear production Application of IEC 61439 2 The new standard IEC 61439 A new standard. A new opportunity. IEC 61439 is the new standard
More than just OK. Okken: Low voltage switchboard for electrical distribution and motor control
More than just OK Okken: Low voltage switchboard for electrical distribution and motor control 2 Safe, reliable, efficient, easy to maintain, durable, open-ended. 3 A question of balance Low voltage equipment
Electronic ballasts for fluorescent lamps Products for special applications. PC BASIC, 4 28 W Electronic ballast for system output < 25 W
T5 TC-DEL TC-SEL TC-TEL TC-DD PC BASIC, 4 28 W Electronic ballast for system output < 25 W Product description CELMA Energy Efficiency Index A2 / A3 Nominal life time up to 50,000 h (at ta 50 C with a
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels
How To Build A Low Voltage Capacitor Lvcp
Low Voltage Capacitor LVCP The new choice for Power Factor Correction LVCP : the new choice for Power Factor Correction The LVCP is a compact and powerful capacitor. It offers high modularity, unmatched
5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH
Amphenol C 091 A/B/D Circular Connectors Amphenol-Tuchel Electronics GmbH C 091 A Main Features Metal threaded coupling acc. to IEC. Number of contacts are 2 to 8, 12 and 14. Internal metal strain relief
Linkeo 19" freestanding cabinets
87045 LIMOGES Cedex France Telephone: (+33) 05 55 06 87 87 - Fax: (+33) 05 55 06 88 88 Linkeo 19" freestanding cabinets Page 1. General characteristics....1 2. Range....2 3. Technical characteristics...3
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273
Multi-cubicle type switchboard systems. NorPower 5000
Multi-cubicle type switchboard systems NorPower 5000 NorPower 5000 (EHKE) MULTI-CUBICLE TYPE SWITCHBOARD SYSTEMS NorPower 5000 (EHKE) Multi-cubicle type switchboard systems Table of contents Page Table
Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
Medium Voltage Switchgear
Uniswitch Medium Voltage Switchgear 12 kv, 17.5 kv, 24 kv 630 A and 1250 A Operation and TABLE OF CONTENTS 1 Summary...1 1.1 General...1 1.2 Standards and specifications...2 1.3 Service conditions...3
Product and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
Thermal-Magnetic Circuit Breaker 3120-...-M1-..
Thermal-Magnetic Circuit Breaker -...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic tripping
Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
Nothing s BetterThan the Original MODAN Power Distribution Systems
MODAN www.eaton.com Nothing s BetterThan the Original MODAN Power Distribution Systems Modan Modular switchboard system Controlling and Distributing Power Safely Thinking further. Questioning the well-established
ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-85366 MOOSBURG TEL. +49 87 61 6 81-0 FAX +49 87 61 68 12 30
40 DRIESCHER - Low voltage fusedswitch-disconnector system 40 Rated current upto 445 A 40 84 40 40 ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D-8566 MOOSBURG TEL. +49 87 6 6 8-0 FAX +49 87 6
CAS 36 Ring Main Unit
Power distribution networks Ring Main Unit Catalogue 2008 A new path for achieving your electrical installations A comprehensive offer The range is part of a comprehensive offer of products that are perfectly
High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv
High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage
Components for System Solutions E9/5. Ex d Enclosure System Made of Light Metal or Stainless Steel, "Flameproof Enclosure" Series 8264. www.stahl.
> Installation chamber can be fully used > Up to three mounting levels can be used > Saving of weight > Compact > Easy to combine > 26 enclosure versions > 15 window versions www.stahl.de 10303E00 The
Emergency lighting units EM powerled
M BASIC 1 W Combined emergency lighting Driver 1 4 W Product description Emergency lighting Driver for manual testing SEV for output voltage < 60 V DC ow-profile casing (21 x 30 mm cross-section) 5-year
SENTRON Switching and Protection Devices Air Circuit Breakers
Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General
08. SEK IDC CONNECTORS
. IDC CONNECTORS connectors for flat cables enable simple and, cost-optimized device configuration. connectors are preferably used for connection within the device. HARTING offers a broad range of these
Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U 02. 01. Technical characteristics types D and E... 02.
Directory chapter 02 - () Types D, E, F, FM, 2F, F9, interface connectors I/U Page Technical characteristics types D and E.............................. 02.10 Type D connectors.................... 02.11
know-how Giant in distributing electricity for industry Prisma GK
Prisma GK Giant know-how in distributing electricity for industry Installation system up to 630A for electrical power distribution and circuit control. Prisma GK: technology and innovation for an IP55
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
Engineers Edge, LLC PDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior
E-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide
1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
Series 8146/5-V37 and Series 8150/5-V37
www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
ADS8 IP54 Direct-On-Line Starter Technical Focus. Replaces ADS7 Rated up to 9kW
ADS8 IP54 Direct-On-Line Starter Technical Focus Replaces ADS7 Rated up to 9kW New ADS8 Motor Starter The new ADS8 range of motor starters replaces the successful ADS7 range which was introduced 20 years
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT User Manual SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 - e-mail: [email protected]
Engineering Specification
Engineering Specification Electrical 33KV AC INDOOR SWITCHGEAR NON-WITHDRAWABLE Owner: Approved by: Chief Engineer, Electrical Neal Hook Chief Engineer Electrical Authorised by: Version 2.1 Issued May
Manual Motor Starter MS 116 up to 16 A Technical Data
Manual Motor Starter MS 116 up to 16 A Technical Data Type MS 116 Standards: Major International IEC 60 947-4-1 / IEC 60 947-2 and European Standards EN 60 947-4-1 / EN 60 947-2 Approvals, Certificates
HIGH VOLTAGE SHORE CONNECTION
Guide for High Voltage Shore Connection GUIDE FOR HIGH VOLTAGE SHORE CONNECTION NOVEMBER 2011 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 Copyright 2011
MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of