1 COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear

2 PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice. This Practice is subject to revision at any time. (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas PIP Member Companies and Subscribers may copy this Practice for their internal use. Changes or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP. Authorized Users may attach addenda or overlays to clearly indicate modifications or exceptions to specific sections of PIP Practices. Authorized Users may provide their clients, suppliers and contractors with copies of the Practice solely for Authorized Users purposes. These purposes include but are not limited to the procurement process (e.g., as attachments to requests for quotation/ purchase orders or requests for proposals/contracts) and preparation and issue of design engineering deliverables for use on a specific project by Authorized User s client. PIP s copyright notices must be clearly indicated and unequivocally incorporated in documents where an Authorized User desires to provide any third party with copies of the Practice. PRINTING HISTORY September 1997 Issued October 2004 Complete Revision October 2010 Complete Revision Not printed with State funds

3 COMPLETE REVISION October 2010 Electrical Table of Contents PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear 1. Introduction Purpose Scope References Industry Codes and Standards Definitions Requirements Service Conditions Switchgear Assembly Additional Requirements for Arc- Resistant Switchgear Power Circuit Breakers Bus Work Voltage Transformers Control Power Transformers Current Transformers Control Devices, Indicating Lights and Metering Protective Relaying Breaker Interlocking and Transfer Schemes Space Heaters Wiring and Terminations Bus Ducts and Cable Bus Nameplates Finish Secondary System Grounding Accessories Shipping Inspection and Testing Documentation Conflict Resolution Page 1 of 25

4 PIP ELSSG01 COMPLETE REVISION Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear October Introduction 1.1 Purpose This Practice provides requirements for design, fabrication, and testing of metal-enclosed, low-voltage AC power circuit breaker switchgear assemblies. 1.2 Scope 2. References This Practice describes the requirements for metal-enclosed power switchgear assemblies employed in three-phase AC electrical systems having a voltage not greater than 1000 volts and located in a nonclassified area. Applicable parts of the following Practices and industry codes and standards shall be considered an integral part of this Practice. The edition in effect on the date of contract award shall be used, except as otherwise noted. Short titles are used herein where appropriate. 2.1 (PIP) PIP ELSBD01 - Design and Fabrication of Metal-Enclosed Nonsegregated-Phase Bus Duct Assemblies PIP ELSBD01D - Data Sheet for Design and Fabrication of Metal-Enclosed Nonsegregated-Phase Bus Duct Assemblies PIP ELSGS01 - Design and Fabrication of High-Resistance Grounding System (600 Volts or below) PIP ELSGS01D - Data Sheet for Design and Fabrication of High-Resistance Grounding System (600 Volts or below) PIP ELSSG01D - Data Sheet for Design and Fabrication of Low-Voltage Metal- Enclosed AC Power Circuit Breaker Switchgear PIP ELSSG12 - Design and Fabrication of Outdoor Enclosures for Motor Controllers and Switchgear 2.2 Industry Codes and Standards American National Standards Institute, Inc. (ANSI) ANSI C Low-Voltage Power Circuit Breakers and AC Power Circuit Protectors Preferred Ratings, Related Requirements, and Application Recommendations ANSI C Trip Devices for AC and General Purpose DC Low-Voltage Power Circuit Breakers ANSI C Switchgear - Low-Voltage AC Power Circuit Breakers Used in Enclosures - Test Procedures ANSI Z American National Standard for Product Safety Signs and Labels American Society for Testing Materials (ASTM) ASTM D Standard Practice for Specifying Code by the Munsell System Page 2 of 25

5 COMPLETE REVISION PIP ELSSG01 October 2010 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear 3. Definitions International Code Council (ICC) IBC - International Building Code Institute of Electrical and Electronic Engineers (IEEE) IEEE C Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures IEEE C Standard for Metal-Enclosed Low-Voltage Power Circuit-Breaker Switchgear IEEE C IEEE Guide for Testing Metal-Enclosed Switchgear Rated Up to 38 kv for Internal Arcing Faults IEEE C Standard for Control Switchboards Underwriters Laboratories (UL) UL Standard for Safety Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear arc resistant accessibility Type 1: Equipment with arc-resistant designs or features at the freely accessible front of the equipment only arc resistant accessibility Type 1B: Equipment with arc-resistant designs or features at the freely accessible front of the equipment only, and the additional requirements of ANSI C Annex A, for equipment if normal operation of the equipment involves opening the door or cover of compartments specifically identified as Low Voltage Control or Instrumentation compartments arc resistant accessibility Type 1C: Equipment with arc-resistant designs or features at the freely accessible front of the equipment only, and the additional requirements of ANSI C Annex A, which are intended to reduce the collateral damage to adjacent compartments and equipment, and should not be interpreted to indicate any additional degree of protection for personnel arc resistant accessibility Type 2: Equipment with arc-resistant designs or features at the freely accessible exterior (i.e., front, back, and sides) of the equipment only Arc resistant accessibility Type 2B: Equipment with arc-resistant designs or features at the freely accessible exterior (i.e., front, back, and sides) of the equipment only, and the additional requirements of ANSI C Annex A, for equipment if normal operation of the equipment involves opening the door or cover of compartments specifically identified as Low Voltage Control or Instrumentation compartments arc resistant accessibility Type 2C: Equipment with arc-resistant designs or features at the freely accessible exterior (i.e., front, back, and sides) of the equipment only, and the additional requirements of ANSI C Annex A, which are intended to reduce the collateral damage to adjacent compartments and equipment, and should not be interpreted to indicate any additional degree of protection for personnel arc resistant equipment: Equipment designed to withstand the effects of an internal arcing fault, in accordance with the test requirements of ANSI C Page 3 of 25

6 PIP ELSSG01 COMPLETE REVISION Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear October 2010 internal arcing fault: An unintentional discharge of electrical energy in air within the confines of an electrical equipment enclosure owner: The party who owns the facility wherein the low voltage metal-enclosed switchgear will be used purchaser: The party who awards the contract to the supplier. The purchaser may be the owner or the owner s authorized agent. purchaser s inspector: The purchaser s authorized representative with authority to act in the interest of, and on behalf of, the purchaser in all quality assurance matters supplier: The party responsible for furnishing the low-voltage metal-enclosed AC power circuit breaker switchgear 4. Requirements 4.1 Service Conditions Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, equipment shall be designed to perform satisfactorily under the following ambient conditions: a. Ambient conditions within the limits of -30 C (-18 F) and 40 C (104 F) b. Altitude of installation does not exceed 1000 m (3300 feet) c. Humidity within the limits of 0-95% non-condensing Seismic requirements shall be as specified on the purchaser s PIP ELSSG01D Data Sheet. If specified on the purchaser s PIP ELSSG01D Data Sheet, the manufacturer shall provide a certificate of compliance and anchoring recommendations for all equipment. 4.2 Switchgear Assembly The switchgear assembly shall consist of metal-enclosed freestanding selfventilated vertical steel structures containing power buses, a ground bus, lowvoltage power circuit breakers, and auxiliary control devices in accordance with the attached purchaser s PIP ELSSG01D Data Sheet and one-line diagram(s) The switchgear shall be designed such that the breakers can be tripped and closed and the breaker position can be viewed with the doors closed. Refer to section for breaker operation All enclosures shall be fabricated from freestanding steel frames, steel panels, and doors to provide a strong and rigid structure. The design shall allow the switchgear to be rolled across a floor on pipes or other means without causing the structure to deform or otherwise be damaged Enclosure panel and doors shall be 14-gage minimum thickness Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, enclosures shall be NEMA Enclosures for outdoor service shall be in accordance with PIP ELSSG12. Page 4 of 25

7 COMPLETE REVISION PIP ELSSG01 October 2010 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear Maximum number of feeder circuit breakers in each vertical section shall be as indicated in the purchaser s PIP ELSSG01D Data Sheet All bolted doors and removable panels shall be secured with captive slotted fasteners or machine screws or machine bolts engaging captive nuts or tapped holes in structural members. All fasteners shall employ vibration-resistant devices. Self-tapping sheet metal screws shall not be permitted Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, rear access to cable compartments shall be by removable panels. Any removable panels weighing more than 50 pounds (23 kg) shall have two lifting handles When rear access doors are specified on the purchaser s PIP ELSSG01D Data Sheet, they shall be either full height or split, hinged, and bolted. All rear access doors shall have provisions for padlocking All doors shall have hinges. The hinges may be either continuous or separate. If separate hinges are used, a minimum of three hinges shall be provided on fullheight doors Provisions shall be made for the addition of vertical sections with future breakers at open ends of the line-up. This shall include removable plates or side sheets furnished on the end of vertical sections Breaker compartment doors shall have door handle latches and shall remain closed when racking the breaker to any of three positions: disconnected, test or connected. Breaker compartment doors shall not have ventilation louvers Breaker compartments shall be furnished with a mechanism which will move the breaker between the connected, test and disconnected positions. The mechanism shall be designed so that the breakers will be self-aligning and will be held rigidly in the operating position without the necessity of locking bars or bolts From the disconnect position the breaker shall be easily removable from the compartment without further disassembly or the use of special tools other than a breaker lift device Provisions shall be made for padlocking breakers in the test and disconnected positions. Padlocking shall not interfere with removal or operation of the breaker or its mechanism In double-ended switchgear, each main and tie breaker shall be in separate vertical sections. Comment: This does not preclude metering, auxiliary equipment, or a feeder breaker being in the same vertical section with the main breaker or tie breaker The purchaser shall be notified of any breaker-derating factors caused by ambient conditions and the cumulative circuit loads in the vertical sections with multiple breakers in accordance with IEEE C , Section When specified on the purchaser s PIP ELSSG01D Data Sheet, an interlock shall be provided to prevent opening of the breaker compartment door unless the breaker is in the disconnect position. This interlock shall have an override mechanism for authorized entry. Page 5 of 25

8 PIP ELSSG01 COMPLETE REVISION Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear October Interlocks shall prevent moving the breaker to or from the operating position unless its main contacts are in the open position. As a further safety precaution, the operating springs shall be discharged automatically when a breaker is rolled fully into the compartment or is moved into the disconnect position Spaces shall be provided for future use as specified on the one-line diagram. Spaces shall be of three types: equipped, unequipped, and blank. Spaces shall be configured as follows: a. Equipped spaces shall be capable of being modified to add future circuit breakers of the same ampere rating without shutdown of the switchgear. b. Equipped spaces shall be furnished with all hardware, wiring, doors, and miscellaneous equipment including current transformers and monitoring devices required to permit completion of the unit by the addition of only a circuit breaker. c. Unequipped spaces shall be provided with doors but without other equipment for future use except the power stabs. Unequipped spaces shall not be used for mounting control switches and other auxiliary equipment. d. Power stabs (both line and load side) shall be provided with covers to prevent accidental contact with live parts when door is opened. e. Blank spaces shall be completely empty cubicles with doors but without power stabs or other equipment Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, shutters shall be provided to automatically isolate the primary line and load disconnects as the breaker is removed from the connected position. Shutters shall be nonmetallic. The line and load shutters shall operate by movement of the circuit breaker truck or racking mechanism. The shutters shall also be capable of being operated by hand with the breaker removed from the cell If uninsulated buses are specified on the purchaser s PIP ELSSG01D Data Sheet, removable vertical barriers shall be provided in the rear cable compartments to prevent accidental contact of personnel with all energized buses. The barriers shall not cover load connections Sheet steel barriers shall be provided between power and control compartments Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, full height and depth barriers shall be provided between adjacent vertical sections in the rear load terminal compartments If specified on the purchaser s PIP ELSSG01D Data Sheet, sheet steel barriers shall be provided between breaker compartments in vertical sections Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, enclosure vent openings shall be provided with stainless steel screens having a maximum opening size of 1/16 inch (1.6 mm) Breaker control power shall be as specified on the purchaser s PIP ELSSG01D Data Sheet Indicator lights shall have replaceable cluster-type LED lamps and colored lens. Page 6 of 25

9 COMPLETE REVISION PIP ELSSG01 October 2010 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear Switchgear shall be provided with removable lifting eyes or angles for handling during installation If specified on the purchaser s PIP ELSSG01D Data Sheet, a remote racking device to electrically rack the breaker shall be provided and shall include a minimum of 25 feet (7.6 m) of heavy duty umbilical cord. Means shall be provided to shut off the remote racking device when breaker is in the connected position If specified on the purchaser s PIP ELSSG01D Data Sheet, thermography windows shall be provided. Location of windows shall be as specified on the purchaser s PIP ELSSG01D Data Sheet If specified on the purchaser s PIP ELSSG01D Data Sheet, the switchgear assembly shall be UL labeled. 4.3 Additional Requirements for Arc-Resistant Switchgear If specified on the purchaser s PIP ELSSG01D Data Sheet, the switchgear shall be arc-resistant design as described below Switchgear shall be tested in accordance with IEEE C Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, Switchgear shall be arc-resistant construction Type 2 (switchgear with arcresistant construction at front, rear, and sides) A written certificate of successful type testing, including all the parameters used in the testing, shall be submitted to the purchaser. Testing shall be based on prospective current of the highest rated circuit breaker without insertion of any current limiting device in the test circuit Switchgear shall be designed for closed door racking. Arc-resistant integrity shall be maintained during closed door racking Instrument compartment door(s) shall be designed and tested to allow the compartment door to be opened without affecting the arc-resistant rating of the switchgear The front and rear compartment doors shall be designed to withstand the effects of an internal arcing fault Instrument compartment shall have steel hinged doors that are in accordance with IEEE C testing requirements The design of openings shall pass the requirements of IEEE C , with respect to the emission of arc/flash products Openings intended to close on initiation of a fault to preserve arc-resistant construction shall be provided with the necessary guards on top and sides to prevent dropping of any foreign material that can prevent openings from closing Design and construction of the switchgear shall prevent effects of any fault in the circuit breaker and bus compartments from entering the instrument compartment All opening cover plates provided to preserve arc-resistant construction shall be accessible for inspection. Page 7 of 25

10 PIP ELSSG01 COMPLETE REVISION Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear October Means to manually trip the breaker without requiring opening the door and compromising the integrity of arc-resistant construction shall be provided Provisions for closed door manual racking of the circuit breaker while maintaining the integrity of arc-resistant construction shall be provided A single-handle latch system with position labeling and provision for padlocking shall be provided on each door such that arc-resistant integrity is maintained when the latch is in closed position. Additional tie down bolts are acceptable on the doors to maintain arc resistant construction Personnel shall be protected from arc products and noise expelled from the switchgear enclosure. Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, a plenum system shall be provided as described below: a. Plenum system shall exhaust arc products from the switchgear room. b. Exhaust outlet shall be weatherproof and directed to an area that minimizes personnel exposure. c. Plenum minimum volume shall be tested and certified in accordance with IEEE C d. Plenum shall be separate from other plenum systems. If a combined plenum system is desired, manufacturer(s) shall analyze and certify the combined plenum system design. 4.4 Power Circuit Breakers Low-voltage power circuit breakers shall be air break type and shall be designed, rated, manufactured, and tested in accordance with IEEE C37.13, ANSI C37.16, ANSI C37.17, and ANSI C Breakers shall be of the stored-energy type with standard draw-out construction for both power and control circuits. Breakers shall be three-pole and complete with necessary operating mechanisms Breakers shall be operated electrically or manually as specified on the purchaser s PIP ELSSG01D Data Sheet. Electrically operated breakers shall also be capable of manual operation Circuit breakers shall have continuous current ratings as specified on the purchaser s PIP ELSSG01D Data Sheet or one line diagram(s). Ratings stated are those when installed and working under the specified service conditions. Ratings shall not be dependent upon the use of cooling fans Circuit breaker shall have a maximum interrupting time of 5 cycles, excluding sensing mechanism time Closing and tripping circuits shall be individually protected within each breaker compartment by fuses. When specified on the purchaser s PIP ELSSG01D Data Sheet other control and indication circuits (such as breaker trip indication) shall be individually protected within each breaker compartment by fuses. Page 8 of 25

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

PIP ELSSG02 Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv

PIP ELSSG02 Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv Electrical Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv Table of Contents 1. Introduction...2 1.1 Purpose... 2 1.2 Scope... 2 2. References...2 2.1... 2 2.2 Industry

More information

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY

More information

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com

More information

Power-Zone 4 Arc Resistant Low Voltage Switchgear

Power-Zone 4 Arc Resistant Low Voltage Switchgear Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior

More information

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Masterclad Medium Voltage Passive Arc-Resistant Switchgear Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. 1.02 RELATED

More information

Enhancing Personnel Safety with Arc Resistant Equipment

Enhancing Personnel Safety with Arc Resistant Equipment Enhancing Personnel Safety with Arc Resistant Equipment Carl Christian Power LV Offer Marketing Nashville, TN Sponsored by the Water Wastewater Competency Center 1 Enhancing Personnel Safety 5-10 Five

More information

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR MEDIUM VOLTAGE METAL CLAD SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, connection and testing of the medium voltage switchgear. 1.2 SWITCHGEAR FEATURES

More information

Medium Voltage Motor Control Assemblies

Medium Voltage Motor Control Assemblies Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................

More information

SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR

SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

LVA Take Offs in Bid Manager

LVA Take Offs in Bid Manager Electrical Sales and Distributor Training Low Voltage Assemblies (LVA) LVA Take Offs in Bid Manager This job aid helps to define some of the common selection questions that are encountered when configuring

More information

Extend the Life of Existing Switchgear

Extend the Life of Existing Switchgear Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...

More information

Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125

Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125 Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated

More information

Low Voltage Switchgear

Low Voltage Switchgear Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

SECTION 16426C ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE

SECTION 16426C ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install, where indicated on the drawings, a deadfront type, arc resistant

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

MCC Ratings. Voltage Rating

MCC Ratings. Voltage Rating MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,

More information

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock.

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock. Arc Flash Hazards Dan Neeser Field Application Engineer DanRNeeser@Eaton.com Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of

More information

This section applies to the design and installation of transformers.

This section applies to the design and installation of transformers. ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies

More information

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR Copyright Material IEEE Paper No. PCIC 2003-13 Eddie Wilkie Eaton Cutler-Hammer 3990 Old Tasso Road NE Cleveland, TN 37312 USA Abstract

More information

Choosing the Best Solution for Reducing Arc Energy

Choosing the Best Solution for Reducing Arc Energy CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors

More information

Switchgear Capabilities. NexGear is a Division of PowerSecure NASDAQ: POWR

Switchgear Capabilities. NexGear is a Division of PowerSecure NASDAQ: POWR Switchgear Capabilities NexGear is a Division of PowerSecure NASDAQ: POWR Discussion Points Introducing PowerSecure Introducing NexGear Solutions Offered Scope of Services Examples of Work Q & A NexGear,

More information

Bypass transfer switch mechanisms

Bypass transfer switch mechanisms Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee

More information

Type GM-SG-AR 5 kv and 15 kv arc-resistant metal-clad switchgear instruction manual. Answers for energy.

Type GM-SG-AR 5 kv and 15 kv arc-resistant metal-clad switchgear instruction manual. Answers for energy. Type GM-SG-AR 5 kv and 15 kv arc-resistant metal-clad switchgear instruction manual Installation operation maintenance E50001-F710-A254-X-4A00 Answers for energy. Hazardous voltages and high speed moving

More information

Instructions for Eaton 7.2kV AMPGARD Arc Resistant Motor Control Centers

Instructions for Eaton 7.2kV AMPGARD Arc Resistant Motor Control Centers Contents Description Page 1. Introduction............................ 2 2. Receiving, Handling, and Storing........... 4 3. Installation............................ 5 4. Plenum and Duct Installation.............

More information

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY 2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings

More information

Installation, Operation and Maintenance Instructions. Uniflex ABB PTMV

Installation, Operation and Maintenance Instructions. Uniflex ABB PTMV Installation, Operation and Maintenance Instructions Uniflex ABB PTMV SAFETY FIRST! For safe and correct usage note the following recommendations: Only install switchgear and switchboards in enclosed rooms

More information

How to reduce exposure to arc flash hazards

How to reduce exposure to arc flash hazards GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not

More information

Fusible Disconnect Switch

Fusible Disconnect Switch Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

Top Commercial / Residential Electrical Requirements *

Top Commercial / Residential Electrical Requirements * Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial

More information

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to: PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront

More information

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12 Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Cleaveland/Price Type TP-C2 Motor Operator

More information

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR

More information

Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear

Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear Class 6055 Instruction Bulletin 6055-62 06/2012 Retain for future use. Hazard Categories and Special Symbols Read these instructions carefully

More information

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009 A Comparison of Contemporary Electrical Distribution Equipment Standards San Francisco IEEE Industry Applications Society May 26, 2009 What are Standards? Clearly defined performance characteristics Based

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

Cooktop Low-Profile Ventilation Hoods

Cooktop Low-Profile Ventilation Hoods INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............

More information

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number

More information

Addendum #2 Contract UK-11-13

Addendum #2 Contract UK-11-13 Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

How To Build A Germany Power Plant

How To Build A Germany Power Plant Medium Voltage Air Insulated Motor Control Featuring AdvanceTM Technology. Medium Voltage Motor Control Center Product Description Contemporary Design Advance TM medium voltage motor control center (MVMCC)

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

42U/45U 28" Wide Rack Installation & Service Guide

42U/45U 28 Wide Rack Installation & Service Guide 42U/45U 28" Wide Rack Installation & Service Guide 96-00171-005 Rev B Important Information Information in this document is subject to change without notice and does not represent a commitment on the part

More information

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C 41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers

More information

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Installation Instructions For Slider Casement Air Conditioners

Installation Instructions For Slider Casement Air Conditioners Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT

More information

GEK-90214B. GE Lift Truck. User s Guide 144D2933G1 144D2912G1 144D2911G5

GEK-90214B. GE Lift Truck. User s Guide 144D2933G1 144D2912G1 144D2911G5 g GEK-90214B GE Lift Truck User s Guide 144D2933G1 144D2912G1 144D2911G5 GE LIFT TRUCK EACH USER HAS THE RESPONSIBILITY TO INSTRUCT ALL PERSONNEL ASSOCIATED WITH THIS EQUIPMENT ON ALL SAFETY PRECAUTIONS

More information

DCF Optimized Rack System

DCF Optimized Rack System Integrated Cabinet Solutions For Business-Critical Continuity DCF Optimized Rack System User Manual IMPORTANT SAFETY GUIDELINES SAVE THESE INSTRUCTIONS This manual contains important instructions that

More information

PS6500 Storage Arrays Rack Mount Instructions

PS6500 Storage Arrays Rack Mount Instructions PS6500 Storage Arrays Rack Mount Instructions Part Number: R724M Rev. A01 Copyright 2010 Dell, Inc. All rights reserved. Dell is a trademark of Dell, Inc. EqualLogic is a registered trademark. All trademarks

More information

1997 ELECTRIC UTILITY CONFERENCE SUBJECT VII-I APPLICATION OF ARC-RESISTANT METAL-CLAD SWITCHGEAR IN POWER DISTRIBUTION CENTERS

1997 ELECTRIC UTILITY CONFERENCE SUBJECT VII-I APPLICATION OF ARC-RESISTANT METAL-CLAD SWITCHGEAR IN POWER DISTRIBUTION CENTERS 1997 ELECTRIC UTILITY CONFERENCE SUBJECT VII-I APPLICATION OF ARC-RESISTANT METAL-CLAD SWITCHGEAR IN POWER DISTRIBUTION CENTERS Robert A. Patten Manager of Product Development Distribution Systems Division

More information

Questions and Answers for Heating and A/C Contractors

Questions and Answers for Heating and A/C Contractors 1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded

More information

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC

More information

DOCUMENT 009102 - ADDENDUM NO. 2. Issued to all Bidders: Date: February 3, 2015. Contract Name: 13,800-Volt and 480-Volt Switchgear

DOCUMENT 009102 - ADDENDUM NO. 2. Issued to all Bidders: Date: February 3, 2015. Contract Name: 13,800-Volt and 480-Volt Switchgear DOCUMENT 009102 - ADDENDUM NO. 2 Issued to all Bidders: Date: February 3, 2015 Contract Name: 13,800-Volt and 480-Volt Switchgear SUA Bid No.: #21-14/15 This addendum forms a part of the Bid described

More information

Power Plant Electrical Distribution Systems

Power Plant Electrical Distribution Systems PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will

More information

Contents. Description. Product Selection Guide

Contents. Description. Product Selection Guide .1 Medium Voltage Switchgear Introduction Indoor Type VCP-W Metal-Clad Switchgear Assembly (5/15 kv shown) Product Selection Guide Product Offering Chart Metal-Enclosed Contents Description Notes Additional

More information

Section 10 Electric Switchboards: 0 Through 600 Volts

Section 10 Electric Switchboards: 0 Through 600 Volts Section 10 Electric Switchboards: 0 Through 600 Volts 10.1. Scope This section provides specific dimensions and details for service and meter equipment that is assembled by the manufacturer in freestanding,

More information

Installation Instructions

Installation Instructions READ BEFORE INSTALLING UNIT For Slider Casement Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:

More information

SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR

SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Introduction. Upon completion of Basics of Switchboards you should be able to: Explain the role of switchboards in a distribution system

Introduction. Upon completion of Basics of Switchboards you should be able to: Explain the role of switchboards in a distribution system Table of Contents Introduction... 2 Distribution Systems... 4 Switchboard Definition... 9 Switchboard Construction... 12 Service Entrance Equipment... 18 Service Section... 20 Switchboard Grounding...

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in

More information

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch

More information

CENTERLINE 2100 Low Voltage Motor Control Centers

CENTERLINE 2100 Low Voltage Motor Control Centers Installation Instructions CENTERLINE 2100 Low Voltage Motor Control Centers Catalog Numbers 2100 Important User Information Read this document and the documents listed in the additional resources section

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac

New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges

More information

Atlanta Chapter IEEE Industry Applications Society

Atlanta Chapter IEEE Industry Applications Society Atlanta Chapter IEEE Industry Applications Society Electrical Equipment Room Design Considerations presented at the Sheraton Buckhead Hotel Atlanta, Georgia November 20, 2006 Outline 1. Definitions 2.

More information

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,

More information

Instructions for Magnum DS T

Instructions for Magnum DS T Instructions for Magnum DS T Contents Description Page 1: Introduction............................ 3 2: Receiving, Handling, and Storage........... 4 3: Equipment Description................... 8 4: Installation............................

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information