1 COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear
2 PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice. This Practice is subject to revision at any time. (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas PIP Member Companies and Subscribers may copy this Practice for their internal use. Changes or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP. Authorized Users may attach addenda or overlays to clearly indicate modifications or exceptions to specific sections of PIP Practices. Authorized Users may provide their clients, suppliers and contractors with copies of the Practice solely for Authorized Users purposes. These purposes include but are not limited to the procurement process (e.g., as attachments to requests for quotation/ purchase orders or requests for proposals/contracts) and preparation and issue of design engineering deliverables for use on a specific project by Authorized User s client. PIP s copyright notices must be clearly indicated and unequivocally incorporated in documents where an Authorized User desires to provide any third party with copies of the Practice. PRINTING HISTORY September 1997 Issued October 2004 Complete Revision October 2010 Complete Revision Not printed with State funds
3 COMPLETE REVISION October 2010 Electrical Table of Contents PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear 1. Introduction Purpose Scope References Industry Codes and Standards Definitions Requirements Service Conditions Switchgear Assembly Additional Requirements for Arc- Resistant Switchgear Power Circuit Breakers Bus Work Voltage Transformers Control Power Transformers Current Transformers Control Devices, Indicating Lights and Metering Protective Relaying Breaker Interlocking and Transfer Schemes Space Heaters Wiring and Terminations Bus Ducts and Cable Bus Nameplates Finish Secondary System Grounding Accessories Shipping Inspection and Testing Documentation Conflict Resolution Page 1 of 25
4 PIP ELSSG01 COMPLETE REVISION Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear October Introduction 1.1 Purpose This Practice provides requirements for design, fabrication, and testing of metal-enclosed, low-voltage AC power circuit breaker switchgear assemblies. 1.2 Scope 2. References This Practice describes the requirements for metal-enclosed power switchgear assemblies employed in three-phase AC electrical systems having a voltage not greater than 1000 volts and located in a nonclassified area. Applicable parts of the following Practices and industry codes and standards shall be considered an integral part of this Practice. The edition in effect on the date of contract award shall be used, except as otherwise noted. Short titles are used herein where appropriate. 2.1 (PIP) PIP ELSBD01 - Design and Fabrication of Metal-Enclosed Nonsegregated-Phase Bus Duct Assemblies PIP ELSBD01D - Data Sheet for Design and Fabrication of Metal-Enclosed Nonsegregated-Phase Bus Duct Assemblies PIP ELSGS01 - Design and Fabrication of High-Resistance Grounding System (600 Volts or below) PIP ELSGS01D - Data Sheet for Design and Fabrication of High-Resistance Grounding System (600 Volts or below) PIP ELSSG01D - Data Sheet for Design and Fabrication of Low-Voltage Metal- Enclosed AC Power Circuit Breaker Switchgear PIP ELSSG12 - Design and Fabrication of Outdoor Enclosures for Motor Controllers and Switchgear 2.2 Industry Codes and Standards American National Standards Institute, Inc. (ANSI) ANSI C Low-Voltage Power Circuit Breakers and AC Power Circuit Protectors Preferred Ratings, Related Requirements, and Application Recommendations ANSI C Trip Devices for AC and General Purpose DC Low-Voltage Power Circuit Breakers ANSI C Switchgear - Low-Voltage AC Power Circuit Breakers Used in Enclosures - Test Procedures ANSI Z American National Standard for Product Safety Signs and Labels American Society for Testing Materials (ASTM) ASTM D Standard Practice for Specifying Code by the Munsell System Page 2 of 25
5 COMPLETE REVISION PIP ELSSG01 October 2010 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear 3. Definitions International Code Council (ICC) IBC - International Building Code Institute of Electrical and Electronic Engineers (IEEE) IEEE C Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures IEEE C Standard for Metal-Enclosed Low-Voltage Power Circuit-Breaker Switchgear IEEE C IEEE Guide for Testing Metal-Enclosed Switchgear Rated Up to 38 kv for Internal Arcing Faults IEEE C Standard for Control Switchboards Underwriters Laboratories (UL) UL Standard for Safety Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear arc resistant accessibility Type 1: Equipment with arc-resistant designs or features at the freely accessible front of the equipment only arc resistant accessibility Type 1B: Equipment with arc-resistant designs or features at the freely accessible front of the equipment only, and the additional requirements of ANSI C Annex A, for equipment if normal operation of the equipment involves opening the door or cover of compartments specifically identified as Low Voltage Control or Instrumentation compartments arc resistant accessibility Type 1C: Equipment with arc-resistant designs or features at the freely accessible front of the equipment only, and the additional requirements of ANSI C Annex A, which are intended to reduce the collateral damage to adjacent compartments and equipment, and should not be interpreted to indicate any additional degree of protection for personnel arc resistant accessibility Type 2: Equipment with arc-resistant designs or features at the freely accessible exterior (i.e., front, back, and sides) of the equipment only Arc resistant accessibility Type 2B: Equipment with arc-resistant designs or features at the freely accessible exterior (i.e., front, back, and sides) of the equipment only, and the additional requirements of ANSI C Annex A, for equipment if normal operation of the equipment involves opening the door or cover of compartments specifically identified as Low Voltage Control or Instrumentation compartments arc resistant accessibility Type 2C: Equipment with arc-resistant designs or features at the freely accessible exterior (i.e., front, back, and sides) of the equipment only, and the additional requirements of ANSI C Annex A, which are intended to reduce the collateral damage to adjacent compartments and equipment, and should not be interpreted to indicate any additional degree of protection for personnel arc resistant equipment: Equipment designed to withstand the effects of an internal arcing fault, in accordance with the test requirements of ANSI C Page 3 of 25
6 PIP ELSSG01 COMPLETE REVISION Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear October 2010 internal arcing fault: An unintentional discharge of electrical energy in air within the confines of an electrical equipment enclosure owner: The party who owns the facility wherein the low voltage metal-enclosed switchgear will be used purchaser: The party who awards the contract to the supplier. The purchaser may be the owner or the owner s authorized agent. purchaser s inspector: The purchaser s authorized representative with authority to act in the interest of, and on behalf of, the purchaser in all quality assurance matters supplier: The party responsible for furnishing the low-voltage metal-enclosed AC power circuit breaker switchgear 4. Requirements 4.1 Service Conditions Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, equipment shall be designed to perform satisfactorily under the following ambient conditions: a. Ambient conditions within the limits of -30 C (-18 F) and 40 C (104 F) b. Altitude of installation does not exceed 1000 m (3300 feet) c. Humidity within the limits of 0-95% non-condensing Seismic requirements shall be as specified on the purchaser s PIP ELSSG01D Data Sheet. If specified on the purchaser s PIP ELSSG01D Data Sheet, the manufacturer shall provide a certificate of compliance and anchoring recommendations for all equipment. 4.2 Switchgear Assembly The switchgear assembly shall consist of metal-enclosed freestanding selfventilated vertical steel structures containing power buses, a ground bus, lowvoltage power circuit breakers, and auxiliary control devices in accordance with the attached purchaser s PIP ELSSG01D Data Sheet and one-line diagram(s) The switchgear shall be designed such that the breakers can be tripped and closed and the breaker position can be viewed with the doors closed. Refer to section for breaker operation All enclosures shall be fabricated from freestanding steel frames, steel panels, and doors to provide a strong and rigid structure. The design shall allow the switchgear to be rolled across a floor on pipes or other means without causing the structure to deform or otherwise be damaged Enclosure panel and doors shall be 14-gage minimum thickness Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, enclosures shall be NEMA Enclosures for outdoor service shall be in accordance with PIP ELSSG12. Page 4 of 25
7 COMPLETE REVISION PIP ELSSG01 October 2010 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear Maximum number of feeder circuit breakers in each vertical section shall be as indicated in the purchaser s PIP ELSSG01D Data Sheet All bolted doors and removable panels shall be secured with captive slotted fasteners or machine screws or machine bolts engaging captive nuts or tapped holes in structural members. All fasteners shall employ vibration-resistant devices. Self-tapping sheet metal screws shall not be permitted Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, rear access to cable compartments shall be by removable panels. Any removable panels weighing more than 50 pounds (23 kg) shall have two lifting handles When rear access doors are specified on the purchaser s PIP ELSSG01D Data Sheet, they shall be either full height or split, hinged, and bolted. All rear access doors shall have provisions for padlocking All doors shall have hinges. The hinges may be either continuous or separate. If separate hinges are used, a minimum of three hinges shall be provided on fullheight doors Provisions shall be made for the addition of vertical sections with future breakers at open ends of the line-up. This shall include removable plates or side sheets furnished on the end of vertical sections Breaker compartment doors shall have door handle latches and shall remain closed when racking the breaker to any of three positions: disconnected, test or connected. Breaker compartment doors shall not have ventilation louvers Breaker compartments shall be furnished with a mechanism which will move the breaker between the connected, test and disconnected positions. The mechanism shall be designed so that the breakers will be self-aligning and will be held rigidly in the operating position without the necessity of locking bars or bolts From the disconnect position the breaker shall be easily removable from the compartment without further disassembly or the use of special tools other than a breaker lift device Provisions shall be made for padlocking breakers in the test and disconnected positions. Padlocking shall not interfere with removal or operation of the breaker or its mechanism In double-ended switchgear, each main and tie breaker shall be in separate vertical sections. Comment: This does not preclude metering, auxiliary equipment, or a feeder breaker being in the same vertical section with the main breaker or tie breaker The purchaser shall be notified of any breaker-derating factors caused by ambient conditions and the cumulative circuit loads in the vertical sections with multiple breakers in accordance with IEEE C , Section When specified on the purchaser s PIP ELSSG01D Data Sheet, an interlock shall be provided to prevent opening of the breaker compartment door unless the breaker is in the disconnect position. This interlock shall have an override mechanism for authorized entry. Page 5 of 25
8 PIP ELSSG01 COMPLETE REVISION Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear October Interlocks shall prevent moving the breaker to or from the operating position unless its main contacts are in the open position. As a further safety precaution, the operating springs shall be discharged automatically when a breaker is rolled fully into the compartment or is moved into the disconnect position Spaces shall be provided for future use as specified on the one-line diagram. Spaces shall be of three types: equipped, unequipped, and blank. Spaces shall be configured as follows: a. Equipped spaces shall be capable of being modified to add future circuit breakers of the same ampere rating without shutdown of the switchgear. b. Equipped spaces shall be furnished with all hardware, wiring, doors, and miscellaneous equipment including current transformers and monitoring devices required to permit completion of the unit by the addition of only a circuit breaker. c. Unequipped spaces shall be provided with doors but without other equipment for future use except the power stabs. Unequipped spaces shall not be used for mounting control switches and other auxiliary equipment. d. Power stabs (both line and load side) shall be provided with covers to prevent accidental contact with live parts when door is opened. e. Blank spaces shall be completely empty cubicles with doors but without power stabs or other equipment Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, shutters shall be provided to automatically isolate the primary line and load disconnects as the breaker is removed from the connected position. Shutters shall be nonmetallic. The line and load shutters shall operate by movement of the circuit breaker truck or racking mechanism. The shutters shall also be capable of being operated by hand with the breaker removed from the cell If uninsulated buses are specified on the purchaser s PIP ELSSG01D Data Sheet, removable vertical barriers shall be provided in the rear cable compartments to prevent accidental contact of personnel with all energized buses. The barriers shall not cover load connections Sheet steel barriers shall be provided between power and control compartments Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, full height and depth barriers shall be provided between adjacent vertical sections in the rear load terminal compartments If specified on the purchaser s PIP ELSSG01D Data Sheet, sheet steel barriers shall be provided between breaker compartments in vertical sections Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, enclosure vent openings shall be provided with stainless steel screens having a maximum opening size of 1/16 inch (1.6 mm) Breaker control power shall be as specified on the purchaser s PIP ELSSG01D Data Sheet Indicator lights shall have replaceable cluster-type LED lamps and colored lens. Page 6 of 25
9 COMPLETE REVISION PIP ELSSG01 October 2010 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear Switchgear shall be provided with removable lifting eyes or angles for handling during installation If specified on the purchaser s PIP ELSSG01D Data Sheet, a remote racking device to electrically rack the breaker shall be provided and shall include a minimum of 25 feet (7.6 m) of heavy duty umbilical cord. Means shall be provided to shut off the remote racking device when breaker is in the connected position If specified on the purchaser s PIP ELSSG01D Data Sheet, thermography windows shall be provided. Location of windows shall be as specified on the purchaser s PIP ELSSG01D Data Sheet If specified on the purchaser s PIP ELSSG01D Data Sheet, the switchgear assembly shall be UL labeled. 4.3 Additional Requirements for Arc-Resistant Switchgear If specified on the purchaser s PIP ELSSG01D Data Sheet, the switchgear shall be arc-resistant design as described below Switchgear shall be tested in accordance with IEEE C Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, Switchgear shall be arc-resistant construction Type 2 (switchgear with arcresistant construction at front, rear, and sides) A written certificate of successful type testing, including all the parameters used in the testing, shall be submitted to the purchaser. Testing shall be based on prospective current of the highest rated circuit breaker without insertion of any current limiting device in the test circuit Switchgear shall be designed for closed door racking. Arc-resistant integrity shall be maintained during closed door racking Instrument compartment door(s) shall be designed and tested to allow the compartment door to be opened without affecting the arc-resistant rating of the switchgear The front and rear compartment doors shall be designed to withstand the effects of an internal arcing fault Instrument compartment shall have steel hinged doors that are in accordance with IEEE C testing requirements The design of openings shall pass the requirements of IEEE C , with respect to the emission of arc/flash products Openings intended to close on initiation of a fault to preserve arc-resistant construction shall be provided with the necessary guards on top and sides to prevent dropping of any foreign material that can prevent openings from closing Design and construction of the switchgear shall prevent effects of any fault in the circuit breaker and bus compartments from entering the instrument compartment All opening cover plates provided to preserve arc-resistant construction shall be accessible for inspection. Page 7 of 25
10 PIP ELSSG01 COMPLETE REVISION Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear October Means to manually trip the breaker without requiring opening the door and compromising the integrity of arc-resistant construction shall be provided Provisions for closed door manual racking of the circuit breaker while maintaining the integrity of arc-resistant construction shall be provided A single-handle latch system with position labeling and provision for padlocking shall be provided on each door such that arc-resistant integrity is maintained when the latch is in closed position. Additional tie down bolts are acceptable on the doors to maintain arc resistant construction Personnel shall be protected from arc products and noise expelled from the switchgear enclosure. Unless otherwise specified on the purchaser s PIP ELSSG01D Data Sheet, a plenum system shall be provided as described below: a. Plenum system shall exhaust arc products from the switchgear room. b. Exhaust outlet shall be weatherproof and directed to an area that minimizes personnel exposure. c. Plenum minimum volume shall be tested and certified in accordance with IEEE C d. Plenum shall be separate from other plenum systems. If a combined plenum system is desired, manufacturer(s) shall analyze and certify the combined plenum system design. 4.4 Power Circuit Breakers Low-voltage power circuit breakers shall be air break type and shall be designed, rated, manufactured, and tested in accordance with IEEE C37.13, ANSI C37.16, ANSI C37.17, and ANSI C Breakers shall be of the stored-energy type with standard draw-out construction for both power and control circuits. Breakers shall be three-pole and complete with necessary operating mechanisms Breakers shall be operated electrically or manually as specified on the purchaser s PIP ELSSG01D Data Sheet. Electrically operated breakers shall also be capable of manual operation Circuit breakers shall have continuous current ratings as specified on the purchaser s PIP ELSSG01D Data Sheet or one line diagram(s). Ratings stated are those when installed and working under the specified service conditions. Ratings shall not be dependent upon the use of cooling fans Circuit breaker shall have a maximum interrupting time of 5 cycles, excluding sensing mechanism time Closing and tripping circuits shall be individually protected within each breaker compartment by fuses. When specified on the purchaser s PIP ELSSG01D Data Sheet other control and indication circuits (such as breaker trip indication) shall be individually protected within each breaker compartment by fuses. Page 8 of 25
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationMEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
More informationPIP ELSSG02 Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv
Electrical Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv Table of Contents 1. Introduction...2 1.1 Purpose... 2 1.2 Scope... 2 2. References...2 2.1... 2 2.2 Industry
More informationThe following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationSpecification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationSWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
More informationSWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
More informationFFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
More information01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety
PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com
More informationPower-Zone 4 Arc Resistant Low Voltage Switchgear
Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions
More informationSwitchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
More informationEngineers Edge, LLC PDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior
More informationMasterclad Medium Voltage Passive Arc-Resistant Switchgear
Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand
More informationSecondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationSECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR
METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. 1.02 RELATED
More informationEnhancing Personnel Safety with Arc Resistant Equipment
Enhancing Personnel Safety with Arc Resistant Equipment Carl Christian Power LV Offer Marketing Nashville, TN Sponsored by the Water Wastewater Competency Center 1 Enhancing Personnel Safety 5-10 Five
More informationMEDIUM VOLTAGE METAL CLAD SWITCHGEAR
MEDIUM VOLTAGE METAL CLAD SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, connection and testing of the medium voltage switchgear. 1.2 SWITCHGEAR FEATURES
More informationMedium Voltage Motor Control Assemblies
Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................
More informationSECTION 16341 MEDIUM VOLTAGE SWITCHGEAR
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed
More informationPrimary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
More informationLVA Take Offs in Bid Manager
Electrical Sales and Distributor Training Low Voltage Assemblies (LVA) LVA Take Offs in Bid Manager This job aid helps to define some of the common selection questions that are encountered when configuring
More informationExtend the Life of Existing Switchgear
Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...
More informationVoltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125
Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated
More informationLow Voltage Switchgear
Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering
More informationMedium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
More informationSECTION 16426C ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE
ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install, where indicated on the drawings, a deadfront type, arc resistant
More informationMETAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component
More informationBERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
More informationELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
More informationMCC Ratings. Voltage Rating
MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationCAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
More informationSection 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,
More informationArc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer DanRNeeser@Eaton.com Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
More informationThis section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
More informationCOMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR
COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR Copyright Material IEEE Paper No. PCIC 2003-13 Eddie Wilkie Eaton Cutler-Hammer 3990 Old Tasso Road NE Cleveland, TN 37312 USA Abstract
More informationChoosing the Best Solution for Reducing Arc Energy
CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors
More informationSwitchgear Capabilities. NexGear is a Division of PowerSecure NASDAQ: POWR
Switchgear Capabilities NexGear is a Division of PowerSecure NASDAQ: POWR Discussion Points Introducing PowerSecure Introducing NexGear Solutions Offered Scope of Services Examples of Work Q & A NexGear,
More informationBypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationArc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
More informationELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC
ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee
More informationType GM-SG-AR 5 kv and 15 kv arc-resistant metal-clad switchgear instruction manual. Answers for energy.
Type GM-SG-AR 5 kv and 15 kv arc-resistant metal-clad switchgear instruction manual Installation operation maintenance E50001-F710-A254-X-4A00 Answers for energy. Hazardous voltages and high speed moving
More informationInstructions for Eaton 7.2kV AMPGARD Arc Resistant Motor Control Centers
Contents Description Page 1. Introduction............................ 2 2. Receiving, Handling, and Storing........... 4 3. Installation............................ 5 4. Plenum and Duct Installation.............
More information2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium
More informationNATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
More informationQUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings
More informationInstallation, Operation and Maintenance Instructions. Uniflex ABB PTMV
Installation, Operation and Maintenance Instructions Uniflex ABB PTMV SAFETY FIRST! For safe and correct usage note the following recommendations: Only install switchgear and switchboards in enclosed rooms
More informationHow to reduce exposure to arc flash hazards
GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not
More informationFusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
More informationMETER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
More informationTop Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
More informationPREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront
More informationBRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety
More informationALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
More informationTP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12
Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Cleaveland/Price Type TP-C2 Motor Operator
More informationCONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
More informationMasterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear
Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear Class 6055 Instruction Bulletin 6055-62 06/2012 Retain for future use. Hazard Categories and Special Symbols Read these instructions carefully
More informationA Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009
A Comparison of Contemporary Electrical Distribution Equipment Standards San Francisco IEEE Industry Applications Society May 26, 2009 What are Standards? Clearly defined performance characteristics Based
More informationCircuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
More informationCooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
More informationMaintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number
More informationAddendum #2 Contract UK-11-13
Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)
More informationFAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
More informationHow To Build A Germany Power Plant
Medium Voltage Air Insulated Motor Control Featuring AdvanceTM Technology. Medium Voltage Motor Control Center Product Description Contemporary Design Advance TM medium voltage motor control center (MVMCC)
More informationSECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
More information42U/45U 28" Wide Rack Installation & Service Guide
42U/45U 28" Wide Rack Installation & Service Guide 96-00171-005 Rev B Important Information Information in this document is subject to change without notice and does not represent a commitment on the part
More information3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C
41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers
More informationSECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
More informationIRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
More informationInstallation Instructions For Slider Casement Air Conditioners
Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT
More informationGEK-90214B. GE Lift Truck. User s Guide 144D2933G1 144D2912G1 144D2911G5
g GEK-90214B GE Lift Truck User s Guide 144D2933G1 144D2912G1 144D2911G5 GE LIFT TRUCK EACH USER HAS THE RESPONSIBILITY TO INSTRUCT ALL PERSONNEL ASSOCIATED WITH THIS EQUIPMENT ON ALL SAFETY PRECAUTIONS
More informationDCF Optimized Rack System
Integrated Cabinet Solutions For Business-Critical Continuity DCF Optimized Rack System User Manual IMPORTANT SAFETY GUIDELINES SAVE THESE INSTRUCTIONS This manual contains important instructions that
More informationPS6500 Storage Arrays Rack Mount Instructions
PS6500 Storage Arrays Rack Mount Instructions Part Number: R724M Rev. A01 Copyright 2010 Dell, Inc. All rights reserved. Dell is a trademark of Dell, Inc. EqualLogic is a registered trademark. All trademarks
More information1997 ELECTRIC UTILITY CONFERENCE SUBJECT VII-I APPLICATION OF ARC-RESISTANT METAL-CLAD SWITCHGEAR IN POWER DISTRIBUTION CENTERS
1997 ELECTRIC UTILITY CONFERENCE SUBJECT VII-I APPLICATION OF ARC-RESISTANT METAL-CLAD SWITCHGEAR IN POWER DISTRIBUTION CENTERS Robert A. Patten Manager of Product Development Distribution Systems Division
More informationQuestions and Answers for Heating and A/C Contractors
1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded
More informationBT300 HVAC Drives Conventional Bypass (C-Bypass) Options
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC
More informationDOCUMENT 009102 - ADDENDUM NO. 2. Issued to all Bidders: Date: February 3, 2015. Contract Name: 13,800-Volt and 480-Volt Switchgear
DOCUMENT 009102 - ADDENDUM NO. 2 Issued to all Bidders: Date: February 3, 2015 Contract Name: 13,800-Volt and 480-Volt Switchgear SUA Bid No.: #21-14/15 This addendum forms a part of the Bid described
More informationPower Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
More informationSECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
More informationType-Tested Power Distribution Board 8PT with Rear Busbars. sivacon
Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will
More informationContents. Description. Product Selection Guide
.1 Medium Voltage Switchgear Introduction Indoor Type VCP-W Metal-Clad Switchgear Assembly (5/15 kv shown) Product Selection Guide Product Offering Chart Metal-Enclosed Contents Description Notes Additional
More informationSection 10 Electric Switchboards: 0 Through 600 Volts
Section 10 Electric Switchboards: 0 Through 600 Volts 10.1. Scope This section provides specific dimensions and details for service and meter equipment that is assembled by the manufacturer in freestanding,
More informationInstallation Instructions
READ BEFORE INSTALLING UNIT For Slider Casement Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:
More informationSECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationIntroduction. Upon completion of Basics of Switchboards you should be able to: Explain the role of switchboards in a distribution system
Table of Contents Introduction... 2 Distribution Systems... 4 Switchboard Definition... 9 Switchboard Construction... 12 Service Entrance Equipment... 18 Service Section... 20 Switchboard Grounding...
More informationHyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
More informationSuitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
More informationIndustrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
More informationCENTERLINE 2100 Low Voltage Motor Control Centers
Installation Instructions CENTERLINE 2100 Low Voltage Motor Control Centers Catalog Numbers 2100 Important User Information Read this document and the documents listed in the additional resources section
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationNew Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac
New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges
More informationAtlanta Chapter IEEE Industry Applications Society
Atlanta Chapter IEEE Industry Applications Society Electrical Equipment Room Design Considerations presented at the Sheraton Buckhead Hotel Atlanta, Georgia November 20, 2006 Outline 1. Definitions 2.
More informationIntegrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,
More informationInstructions for Magnum DS T
Instructions for Magnum DS T Contents Description Page 1: Introduction............................ 3 2: Receiving, Handling, and Storage........... 4 3: Equipment Description................... 8 4: Installation............................
More informationPRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors
PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2
More information