1 PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors
2 Table of Contents 1 Overview Introduction Features History Technology Applications Design and Test Standards Contactor Features ( Amperes) Features Control Voltage Settings Drop-out Time Settings Altitude Designations Ordering Information Contactor Sizes Motor Ratings Catalogue Number Selection Chart Accessory Kits ( Amperes) Electrical Connections Diagrams Features (800 Amperes) Catalogue Number Selection Guide Factory Modifications Contactor Components Identification SL Series ( Amperes) Control Terminal Strip Coil Control Board Dip Switches Technical Information Type SL Vacuum Contactor Ratings Ampere Frame Type SL Vacuum Contactor Ratings Ampere Frame Type SL Vacuum Contactor Ratings Ampere Frame Type SL Vacuum Contactor Ratings Ampere Frame Type SL Vacuum Contactor Ratings Ampere Frame Dimensions and Weights Front and Rear View ( Amperes) Dimensional Drawings ( Amperes) Front and Rear View (800 Amperes) Dimensional Drawings (800 Amperes) Dimensions and Weights Lug Terminal Drawings and Information Label Identification Fuse Coordination Information Fuse Application Table for SL Contactors
3 2 Overview Introduction The SL contactor family creates a new era for Medium Voltage Control. This new addition allows a single source for all medium voltage control needs. B The Ampgard MV Starter line is well known as a market leader. Now, with complete families of medium voltage breakers, fuses and contactors, customers now have the ability to align themselves with a leader in medium voltage products and technology for all their needs. Features The new SL contactor ratings Voltages of 2200 through 7200 volts. Amperages from 160 to 800 amperes. Interrupting ratings as high as 8500 amperes➀. Control Voltages (Field Adjustable)➀ 110, Hz VAC 120, Hz VAC 125 VDC Drop-out Time (Field Adjustable)➀ ms 50 ms 50 ms 70 ms 1 ms 170 ms 210 ms 250 ms C A Global Acceptability IEC NEMA ANSI Third-Party Verification KEMA CSA UL Easy-to-install Option Kits (Field Addition)➀ Up to 6 extra auxiliary contacts Mechanical latch many coil voltages. Long Life Guarantees High Quality➀ 1 Million Electrical Operations 2.5 Million Mechanical Operations History In 1982, introduced its first vacuum contactor. Used to replace popular air-break contactors of its day, the SJ Medium Voltage Contactor was designed into the Ampgard product and quickly revolutionized the world of Medium Voltage Control. Since that time, vacuum contactors have become the standard of the industry and, a market leader. The Ampgard name has become a trademark for excellence in assembled medium voltage starters. Now that same quality and durability is available in a stand-alone, component form, the SL Contactor. Technology The SL contactor family incorporates world-class Vacuum Interrupters. Vacuum Interrupters provide: Increased safety, reliability, and production. Improved performance, especially in dusty and corrosive environments. Reduce maintenance, downtime, and unit weight. Quiet Operation Less wattage loss High quality and long life. Applications SL Medium Voltage Contactors starting applications: Squirrel-Cage Induction Motors Synchronous Motors Wound-Rotor Fully applicable to: Full Voltage Starting Reduced Voltage Starting The perfect choice for harsh duty applications: Mining Pulp and Paper HVAC Petro-Chemical Automotive Many Others Design and Test Standards IEC #60470 CSA T.I.L. D-21, File #LR28548 ANSI/NEMA ICS 3, Part 2 UL347, File #E63257 ➀ Information may vary for 800 ampere units. Please see page 7 for details.
4 Contactor Features ( Amperes) 3 SL Series Amperes Features➀ A single family of contactors for any medium voltage control application. Voltage range of 2200 to 7200 volts. Amperage ratings from 160 through 400 amperes with Induction Motor Horsepower ranges from 600 to 4500 horsepower. Three Different Altitude Versions. Contactor Leading-Edge Vacuum Technology Fully complies with global standards. Third-party qualified by KEMA, CSA, UL. Long Life 1 Million electrical and over 2 million mechanical. Mounting Flexibility Panel or Pedestal mounting provisions are standard. Unit can be mounted in horizontal or vertical position. Field Selectable Settings for coil voltage, AC/DC, and coil drop-out time. Field Kits available for Auxiliary Contacts and Mechanical latch. Accessories are common for all sizes. Special ordering allows unit to be factory pre-set to customer specification, including field kit installation. Highest Quality Available All contactors manufactured within state-of-the-art ISO-Certified facilities. 100% Made in America. SL Medium Voltage Table 1 Control Voltage Settings➀ Voltage Switch Number /50 On On Off Off Off 120/60 Off On On Off Off 125 VDC Off Off On On Off 220/50 On On Off Off On 240/60 Off On On Off On Note: Stock units pre-set to 120/60 VAC. Table 2 Drop-out Time Settings➀ Voltage Switch Number 5 (On) 6 (On) 7 (On) 8 (On) 110/50 ms 50 ms 1 ms 250 ms 120/60 ms 50 ms 1 ms 250 ms 125 VDC 40 ms 60 ms 170 ms 220 ms 220/50 50 ms 70 ms 1 ms 210 ms 240/60 50 ms 70 ms 1 ms 210 ms Note: Only one drop-out switch should be on at a time. Table 3 Altitude Designations➀ Altitude Low Standard High Meters to to to Feet - 11,483 to to to +13,123 ➀ Information may vary for 800 ampere units. Please see page 7 for details.
5 4 Ordering Information Catalogue Number Selection Chart Contactor Size Voltage Ratings Capacitor Catalogue Numbers Switching Motor Type KW (Amperes)➀ Utilized Operating Elevation➁ Standard Low High 160 Ampere 200 Ampere 360 Ampere 2200 to 2500 Induction SLC011S5A-220 SLC011L5A-220 SLC011H5A-220 Synchronous (0.8 PF) 450 Synchronous (1.0 PF) to 3600 Induction 675 Synchronous (0.8 PF) 675 Synchronous (1.0 PF) to 4800 Induction 900 Synchronous (0.8 PF) 900 Synchronous (1.0 PF) to 6900 Induction 1350 Synchronous (0.8 PF) 1350 Synchronous (1.0 PF) to 2500 Induction SLC012S5A-220 SLC012L5A-220 SLC012H5A-220 Synchronous (0.8 PF) 600 Synchronous (1.0 PF) to 3600 Induction 825 Synchronous (0.8 PF) 825 Synchronous (1.0 PF) to 4800 Induction 1100 Synchronous (0.8 PF) 1100 Synchronous (1.0 PF) to 6900 Induction 1675 Synchronous (0.8 PF) 1675 Synchronous (1.0 PF) to 2500 Induction SLC013S5A-220 SLC013L5A-220 SLC013H5A-220 Synchronous (0.8 PF) 1100 Synchronous (1.0 PF) to 3600 Induction 1500 Synchronous (0.8 PF) 1500 Synchronous (1.0 PF) to 4800 Induction 1850 Synchronous (0.8 PF) 1850 Synchronous (1.0 PF) to 6900 Induction 00 Synchronous (0.8 PF) 00 Synchronous (1.0 PF) 3750 Notes: Stock amperes units are set to 120 VAC coil and -50 ms drop-out time, with 2 NO and 2 NC auxiliary contacts installed. Coil voltage and drop-out time settings are field selectable. Additional auxiliary contacts and mechanical latch are available in kit form. Units may be ordered with special settings and kits. See page 8-9 for details. ➀ Ratings not applicable for back-to-back switching. Consult factory for back-to-back switching applications. ➁ Refer to Table 3 on page 3. Information may vary for 800 ampere units. See page 7 for details.
6 Ordering Information 5 Catalogue Number Selection Chart, Continued Contactor Size Voltage Ratings Capacitor Catalogue Numbers Switching Motor Type KW (Amperes)➀ Utilized Operating Elevation➁ Standard Low High 400 Ampere 800 Ampere 2200 to 2500 Induction SLC014S5A-220 SLC014L5A-220 SLC014H5A-220 Synchronous (0.8 PF) 10 Synchronous (1.0 PF) to 3600 Induction 1675 Synchronous (0.8 PF) 1675 Synchronous (1.0 PF) to 4800 Induction 2250 Synchronous (0.8 PF) 2250 Synchronous (1.0 PF) to 6900 Induction 3350 Synchronous (0.8 PF) 3350 Synchronous (1.0 PF) to 2500 Induction SLN018S1A-220 N/A SLN018H1A-220 Synchronous (0.8 PF) 2250 Synchronous (1.0 PF) to 3600 Induction 00 Synchronous (0.8 PF) 00 Synchronous (1.0 PF) to 4800 Induction 3750 Synchronous (0.8 PF) 3750 Synchronous (1.0 PF) to 6900 Induction 6000 Synchronous (0.8 PF) 6000 Synchronous (1.0 PF) 7500 Notes: Stock amperes units are set to 120 VAC coil and -50 ms drop-out time, with 2 NO and 2 NC auxiliary contacts installed. Coil voltage and drop-out time settings are field selectable. Additional auxiliary contacts and mechanical latch are available in kit form. Units may be ordered with special settings and kits. See page 8-9 for details. ➀ Ratings not applicable for back-to-back switching. Consult factory for back-to-back switching applications. ➁ Refer to Table 3 on page 3. Information may vary for 800 ampere units. See page 7 for details.
7 6 Ordering Information SL Series Accessory Kits Amperes Mechanical Latch Kit SL Vacuum Contactor Sizes Amperes Field Mount to amperes SL Vacuum Contactor. Coil voltages available in a wide range of AC and DC selections. Easy to install on new and existing units. Mechanical Latch Kit Ordering Information Mechanical Latch Kit Amperes Coil Voltage Catalogue Number Auxiliary Contact Kit SL Vacuum Contactor Sizes Amperes Field Mount auxiliary contact kits for amperes SL Vacuum Contactor. Contact kits are available in many configurations of NO-NC. Auxiliary Contact Kit Ordering Information Auxiliary Contact Kit Amperes Description Catalogue Number Mechanical Interlock Kit SL Vacuum Contactor Sizes Amperes Field Mount mechanical interlock kits for amperes SL Vacuum Contactor. Mechanical Interlock Kit Ordering Information Mechanical Interlock Kit Amperes Description AVAILABILITY TO BE ANNOUNCED Catalogue Number 24 VDC 32 VDC 48 VDC 110/50, 120/60, 125 DC (Selectable) 220/50, 240/60 (Selectable) SLA-ML24 SLA-ML32 SLA-ML48 SLA-ML120 SLA-ML240 3NO 3NC Additional 6NO Additional 6NC Additional 5NO 1NC Additional 4NO 2NC Additional 2NO 4NC Additional 1NO 5NC Additional SLA-AS33 SLA-AS60 SLA-AS06 SLA-AS51 SLA-AS42 SLA-AS24 SLA-AS15 Vertical Arrangement Horizontal Arrangement SLA-MIV SLA-MIH Electrical Connections Diagrams 8 (+) Control Voltage (On/Off) White Black DC Coil 1 White Black DC Coil 2 Jumper (Factory Installed) Control Voltage (Open) M M ( ) DC Latch Coil White Black DC Coil 1 White Black DC Coil 2 Connection for Magnetically Held Contactor 3 Control Voltage (Close) 2 1 Jumper (Factory Installed) Connections for Mechanically Latched Contactor
8 Ordering Information 7 SL Series Accessory Options 800 Amperes Mechanical Latch Option SL Vacuum Contactor Size 800 Ampere Factory installed for 800 Ampere SL Vacuum Contactor. Coil voltages available in a wide range of AC and DC selections. Dual Solenoid Latch also available. Mechanical Latch Coil Voltages Coil Voltage 24 VDC 48 VDC VDC 110/50, 120/60 220/50, 240/60 Double Solenoid Latch also Available. Consult factory for details. Features SL Vacuum Contactor Size 800 Ampere Table 1 Altitude Designations Altitude Low Standard High Meters N/A to to Feet N/A to +11, ,811 to +16,076 Table 2 Contactor Application Ratings Mechanical Latch Assembly 800 Ampere Rated Current Open Enclosed Maximum Interrupting Short Time Current (1 Second) Impulse Withstand 800A 720A 13,200A 10,800A 60kV Table 3 Coil Settings/Drop-out Times Factory Settings Coil Voltages Drop-out Time 110/50, 120/60 220/50, 240/ VDC ms ms
9 8 Ordering Information Catalogue Number Selection Guide SL C 01 2 S 5 U SL Contactor Series Design Ampere 800 Ampere C = IEC N = NEMA N = NEMA Mechanical Latch Ampere (Coil Voltage) 0 = None 1 = 24 VDC 2 = 32 VDC 3 = 48 VDC 4 = 110/50,120/60, or 125 VDC 5 = 220/50, 240/ Ampere (Coil Voltage) 0 = None 1 = 24 VDC 3 = 48 VDC 4 = 110 (50/60) 5 = 220 (50/60) 6 = VDC Type 01 = Open Contactor Auxiliary Contacts Ampere 800 Ampere Ampere Rating 1 = = = = = = 2 NO, 2 NC 28 = 2 NO, 8 NC 37 = 3 NO, 7 NC 46 = 4 NO, 6 NC 55 = 5 NO, 5 NC 64 = 6 NO, 4 NC 73 = 7 NO, 3 NC 82 = 8 NO, 2 NC 22 = 2 NO, 2 NC Altitude Ampere 800 Ampere S = Standard (-1000 to M) L = Low (-3500 to 1000 M) H = High (+2000 to M) S = Standard (-1000 to M) H = High (+3600 to M) Coil Voltage Ampere➀ 800 Ampere A = 120/60 B = 240/60 S = 125 VDC U = 110/50 W = 220/50 A = 110/50, 120/60 B = 220/50, 240/60 S = 125 VDC Coil Drop-Out Time Ampere➀ 800 Ampere 5 = -50 ms 6 = ms 7 = ms 8 = ms 1 = ms 2 = ms ➀ Field Selectable.
10 Ordering Information 9 SL Series Factory Modified When Ordering Specify Refer to Catalogue Number Selection Guide. Select Option Codes required. Select Base Unit Price. Add Pricing for Options Required. Design and Test Standards IEC #60470 ( A Only) CSA T.I.L. D-21, File #LR28548 ANSI/NEMA ICS 3, Part 2 UL347, File #E63257 Ordering Information Factory Modified Description Option Code List Price Addition (US Dollars) Base Price 160 Ampere SL Contactor 200 Ampere SL Contactor 360 Ampere SL Contactor 400 Ampere SL Contactor 800 Ampere SL Contactor Enclosure $ 3, , , , , Open 01 Standard Coil Voltage 110/50, 120/60 AC 220/50, 240/60 AC 125 VDC Coil Drop-Out Time➀ -50 ms ( Amperes Only) ms ( Amperes Only) -170 ms ( Amperes Only) ms ( Amperes Only) ms (800 Ampere Only) ms (800 Ampere Only) Auxiliary Contacts 2 NO 2 NC 2 NO 8 NC ( Amperes Only) 3 NO 7 NC ( Amperes Only) 4 NO 6 NC ( Amperes Only) 5 NO 5 NC ( Amperes Only) 6 NO 4 NC ( Amperes Only) 7 NO 3 NC ( Amperes Only) 8 NO 2 NC ( Amperes Only) Mechanical Latch➀ None 24 VDC Coil 32 VDC Coil ( Amperes Only) 48 VDC Coil VDC Coil (800 Ampere Only) 110/50, 120/60 Coil 125 VDC Coil ( Amperes Only) 220/50, 240/60, Coil A, U B, W S Standard Standard Standard Standard Standard ➀ Information for 800 ampere units may vary. Please see page 7 for details.
11 10 Contactor Component Identification SL Series Amperes Panel-Mount Provisions Panel-Mount Provisions Vacuum Interrupters Panel-Mount Provisions Actuator Assembly Control Terminal Strip Contactor Nameplate Auxiliary Contact Blocks Auxiliary Contact Blocks Pedestal-Mount Provisions Pedestal-Mount Provisions Coil Control Board (Behind Control Terminal Strip) Magnet Coil Mechanical Latch Provision Control Settings Coil Control Board Dip Switches Control Terminal Strip
12 Technical Information 11 SL Series Ratings Type SL Vacuum Contactor Ratings 160 Ampere Frame Rated Utilization Voltage Interrupting Rating Application Table Transformer Capacitor (Amperes)➀ Unfused Fused Induction Motor Synchronous Motor (KW) (KW) (0.8 PF) (1.0 PF) Maximum Insulation Voltage 2200 to to to to kva 800 kva 1000 kva 1600 kva Specifications Maximum Interrupting Current (3 Operations) Amperes Rated Current Amperes Enclosed IEC Make-Break Capability-AC4 Make Amperes Break Amperes Short Time Current Second Amperes 1 Second Amperes 8.7 ms (0.5 Cycle) ka Peak Normal Service Altitude to meters Mechanical Life Million Electrical Life AC Million Operations AC ,000 Operations Impulse Withstand kv (1.2 x 50 Microseconds) Dielectric Strength kv RMS (1 Minute) Closing Time Milliseconds (Energization to Contact Touch) Opening Times Milliseconds (2 Cycles) Selectable➁ Milliseconds (4 Cycles) Milliseconds (8 Cycles) Milliseconds (15 Cycles) Arcing Time ms (0.75 Cycle) or Less Pickup Voltage % Rated Coil Voltage Dropout Voltage % Rated Coil Voltage Control Voltages AC/Hz /50, 120/60, 220/50, 240/60 DC Control Circuit Burden Closing (AC)/(DC) VA Holding (AC)/(DC) VA Auxiliary Contact Rating Voltage (Maximum) Volts Continuous Current Amperes Making Capacity (AC) VA (DC) VA Breaking Capacity (AC) VA (DC) VA Latch (when Specified) Mechanical Life ,000 Operations Trip Voltage (DC) Volts (DC) Volts (AC) /120 Volts Minimum Trip Voltage % Rated Coil Voltage Trip Burden (24 VDC) VA (48 VDC and 125 VDC) VA (110 VAC and 120 VAC) VA Trip Time Milliseconds (2 cycles) Weight kg ➀ Ratings not applicable for back-to-back switching. Consult factory for back-to-back switching applications. ➁ Approximate values. Refer to Table 2, page 3 for specific ranges.
13 12 Technical Information SL Series Ratings, Continued Type SL Vacuum Contactor Ratings 200 Ampere Frame Rated Utilization Voltage Interrupting Rating Application Table Transformer Capacitor (Amperes)➀ Unfused Fused Induction Motor Synchronous Motor (KW) (KW) (0.8 PF) (1.0 PF) Maximum Insulation Voltage 2200 to to to to kva 1000 kva 1250 kva 2000 kva Specifications Maximum Interrupting Current (3 Operations) Amperes Rated Current Amperes Enclosed IEC Make-Break Capability-AC4 Make Amperes Break Amperes Short Time Current Second Amperes 1 Second Amperes 8.7 ms (0.5 Cycle) ka Peak Normal Service Altitude to meters Mechanical Life Million Electrical Life AC Million Operations AC ,000 Operations Impulse Withstand kv (1.2 x 50 Microseconds) Dielectric Strength kv RMS (1 Minute) Closing Time Milliseconds (Energization to Contact Touch) Opening Times Milliseconds (2 Cycles) Selectable➁ Milliseconds (4 Cycles) Milliseconds (8 Cycles) Milliseconds (15 Cycles) Arcing Time ms (0.75 Cycle) or Less Pickup Voltage % Rated Coil Voltage Dropout Voltage % Rated Coil Voltage Control Voltages AC/Hz /50, 120/60, 220/50, 240/60 DC Control Circuit Burden Closing (AC)/(DC) VA Holding (AC)/(DC) VA Auxiliary Contact Rating Voltage (Maximum) Volts Continuous Current Amperes Making Capacity (AC) VA (DC) VA Breaking Capacity (AC) VA (DC) VA Latch (when Specified) Mechanical Life ,000 Operations Trip Voltage (DC) Volts (DC) Volts (AC) /120 Volts Minimum Trip Voltage % Rated Coil Voltage Trip Burden (24 VDC) VA (48 VDC and 125 VDC) VA (110 VAC and 120 VAC) VA Trip Time Milliseconds (2 cycles) Weight kg ➀ Ratings not applicable for back-to-back switching. Consult factory for back-to-back switching applications. ➁ Approximate values. Refer to Table 2, page 3 for specific ranges.
14 Technical Information 13 SL Series Ratings, Continued Type SL Vacuum Contactor Ratings 360 Ampere Frame Rated Utilization Voltage Interrupting Rating Application Table Transformer Capacitor (Amperes)➀ Unfused Fused Induction Motor Synchronous Motor (KW) (KW) (0.8 PF) (1.0 PF) Maximum Insulation Voltage 2200 to to to to kva 1600 kva 2000 kva 3200 kva Specifications Maximum Interrupting Current (3 Operations) Amperes Rated Current Amperes Enclosed IEC Make-Break Capability-AC4 Make Amperes Break Amperes Short Time Current Second Amperes 1 Second Amperes 8.7 ms (0.5 Cycle) ka Peak Normal Service Altitude to meters Mechanical Life Million Electrical Life AC Million Operations AC ,000 Operations Impulse Withstand kv (1.2 x 50 Microseconds) Dielectric Strength kv RMS (1 Minute) Closing Time Milliseconds (Energization to Contact Touch) Opening Times Milliseconds (2 Cycles) Selectable➁ Milliseconds (4 Cycles) Milliseconds (8 Cycles) Milliseconds (15 Cycles) Arcing Time ms (0.75 Cycle) or Less Pickup Voltage % Rated Coil Voltage Dropout Voltage % Rated Coil Voltage Control Voltages AC/Hz /50, 120/60, 220/50, 240/60 DC Control Circuit Burden Closing (AC)/(DC) VA Holding (AC)/(DC) VA Auxiliary Contact Rating Voltage (Maximum) Volts Continuous Current Amperes Making Capacity (AC) VA (DC) VA Breaking Capacity (AC) VA (DC) VA Latch (when Specified) Mechanical Life ,000 Operations Trip Voltage (DC) Volts (DC) Volts (AC) /120 Volts Minimum Trip Voltage % Rated Coil Voltage Trip Burden (24 VDC) VA (48 VDC and 125 VDC) VA (110 VAC and 120 VAC) VA Trip Time Milliseconds (2 cycles) Weight kg ➀ Ratings not applicable for back-to-back switching. Consult factory for back-to-back switching applications. ➁ Approximate values. Refer to Table 2, page 3 for specific ranges.
15 14 Technical Information SL Series Ratings, Continued Type SL Vacuum Contactor Ratings 400 Ampere Frame Rated Utilization Voltage Interrupting Rating Application Table Transformer Capacitor (Amperes)➀ Unfused Fused Induction Motor Synchronous Motor (KW) (KW) (0.8 PF) (1.0 PF) Maximum Insulation Voltage 2200 to to to to ka 8.5 ka 8.5 ka 8.5 ka kva 2000 kva 2500 kva 4000 kva Specifications Maximum Interrupting Current (3 Operations) Amperes Rated Current Amperes Enclosed IEC Make-Break Capability-AC4 Make Amperes Break Amperes Short Time Current Second Amperes 1 Second Amperes 8.7 ms (0.5 Cycle) ka Peak Normal Service Altitude to meters Mechanical Life Million Electrical Life AC Million Operations AC ,000 Operations Impulse Withstand kv (1.2 x 50 Microseconds) Dielectric Strength kv RMS (1 Minute) Closing Time Milliseconds (Energization to Contact Touch) Opening Times Milliseconds (2 Cycles) Selectable➁ Milliseconds (4 Cycles) Milliseconds (8 Cycles) Milliseconds (15 Cycles) Arcing Time ms (0.75 Cycle) or Less Pickup Voltage % Rated Coil Voltage Dropout Voltage % Rated Coil Voltage Control Voltages AC/Hz /50, 120/60, 220/50, 240/60 DC Control Circuit Burden Closing (AC)/(DC) VA Holding (AC)/(DC) VA Auxiliary Contact Rating Voltage (Maximum) Volts Continuous Current Amperes Making Capacity (AC) VA (DC) VA Breaking Capacity (AC) VA (DC) VA Latch (when Specified) Mechanical Life ,000 Operations Trip Voltage (DC) Volts (DC) Volts (AC) /120 Volts Minimum Trip Voltage % Rated Coil Voltage Trip Burden (24 VDC) VA (48 VDC and 125 VDC) VA (110 VAC and 120 VAC) VA Trip Time Milliseconds (2 cycles) Weight kg ➀ Ratings not applicable for back-to-back switching. Consult factory for back-to-back switching applications. ➁ Approximate values. Refer to Table 2, page 3 for specific ranges.
16 Technical Information 15 SL Series Ratings, Continued Type SL Vacuum Contactor Ratings 800 Ampere Frame Rated Utilization Voltage Interrupting Rating Application Table Transformer Capacitor (Amperes)➀ Unfused Fused Induction Motor Synchronous Motor (KW) (KW) (0.8 PF) (1.0 PF) Maximum Insulation Voltage 2200 to to to to ka (50 MVA) 13.2 ka (50 MVA) 13.2 ka (75 MVA) 13.2 ka (100 MVA) (200 MVA at 20V) (285 MVA at 30V) (400 MVA at 4600V) (570 MVA at 6600V) kva 3500 kva 4500 kva 6000 kva Specifications Maximum Interrupting Current (3 Operations) Amperes Rated Current Amperes Enclosed Amperes Open IEC Make-Break Capability-AC4 Make Amperes Break Amperes Short Time Current Second Amperes 1 Second Amperes 8.7 ms (0.5 Cycle) ka Peak Normal Service Altitude to meters Mechanical Life Million Electrical Life AC ,000 Operations AC ,000 Operations Impulse Withstand kv (1.2 x 50 Microseconds) Dielectric Strength kv RMS (1 Minute) Closing Time Energization to Contact Touch Milliseconds (3.0 Cycles) Opening Times Deenergization to Full Open➁ Milliseconds (8.0 Cycles) Milliseconds (12.0 Cycles) Arcing Time ms (0.75 Cycle) or Less Pickup Voltage % Rated Coil Voltage Dropout Voltage % Rated Coil Voltage Control Voltages AC/Hz /50, 120/60 VAC DC VDC Control Circuit Burden Closing (AC)/(DC) VA/00 VA Holding (AC)/(DC) VA/28 VA Auxiliary Contact Rating Voltage (Maximum) Volts Continuous Current Amperes Making Capacity (AC) VA (DC) VA Breaking Capacity (AC) VA (DC) VA Latch (when Specified) Mechanical Life ,000 Operations Trip Voltage (DC) , 48, 96 Volts (AC) /120, 220/240 Volts 50/60 Hz Minimum Trip Voltage % Rated Coil Voltage Trip Burden (24 VDC) VA (48 VDC and 96 VDC) VA (110 VAC and 220 VAC) VA Trip Time Milliseconds (2 cycles) Weight kg ➀ Ratings not applicable for back-to-back switching. Consult factory for back-to-back switching applications. ➁ Approximate values. Refer to Table 2, page 3 for specific ranges.
17 16 Dimensions and Weights SL Series Amperes Front and Rear View Amperes Front View Amperes Dimensional Drawings Amperes (mm) Rear View Amperes Upper Terminals Lower Terminals Rear Dimensions Amperes Front Dimensions Amperes Rear Mounting (8 DIA) 10 DIA (6) Front Mounting (8 DIA) Front Front 8 DIA Base Plate Dimensions Amperes Side Dimensions Amperes
18 Dimensions and Weights 17 SL Series 800 Ampere Front and Rear View 800 Ampere Front View 800 Ampere Rear View 800 Ampere Dimensional Drawings 800 Ampere (mm) Latch Trip Target (When Used) DIA Bolt Hole (6) Places 13 DIA Mounting Hole (4) Places Intl k Intl k Optional 12 Point Plug square shaft with the axis vertical when the contactor is closed. Rotates 3.8 counterclockwise to open Front Dimensions 800 Ampere Top Dimensions 800 Ampere Latch (When Used) 33 Plug (When Used) Line Terminals Latch Trip Target (When Used) 7.62 Travel Required to Trip When Latch is Used. Optional 12 Point Plug Load Terminals Side Dimensions 800 Ampere
19 18 Dimensions and Weights SL Series Dimensions and Weights Ampere Size Mounting Length (A) Width (B) Depth (C) Weight mm Inches mm Inches mm Inches kg Lbs. 160 Panel or Pedestal 200 Panel or Pedestal 360 Panel or Pedestal 400 Panel or Pedestal 800 Pedestal A B C Lug Terminal Dimensions Lug Terminal Contactor Ampere Rating Upper Terminal Lower Terminal Width (mm) Depth (mm) Hardware (Bolt Diameter in mm) Width Depth Hardware Diameter
20 19 Label Identification Catalogue Number Amperage/Frame Size Altitude Rating Voltage Class MEDIUM VOLTAGE VACUUM CONTACTOR SLC014S7U-220 MODEL A MAXIMUM CONTINUOUS 400A CURRENT SHORT CIRCUIT INTERRUPTING CAPACITY ALTITUDE -1000m to +2000m RATED RATED VOLTAGE 7.2 kv FREQUENCY 8.5kA RATED MAKING AND BREAKING CAPACITY CONTROL VOLTAGE 110V 50Hz 50/60Hz STANDARD IEC Pub AC4 Series Interrupt Rating Control Voltage Coil Burden ARDEN, NC USA (G.O.# ) N.P. 7875A41H02 100% Made in USA Frequency Rating Contactor Label Quantity Frame Size Altitude Rating Design Type Qty.1 Pc. SLC014S7U Ampere 110V 50Hz Coil Medium Voltage Vacuum Contactor Altitude Rating -1000m to +2000m IEC Rated Model A Catalogue Number Coil Burden Series Factory Number G.O.# 4A36634H01 Carton Label
21 20 Fuse Coordination Information SL Series Fuses Fuse Application Table for SL Contactors Motor FLA Voltage Suggested Fuse➀ SL SL ➁ SL ➁ D597G01 449D597G02 449D597G03 449D597G04 449D597G05 449D597G06 151D933G01 151D933G D963G01 151D963G02 151D963G03 151D963G04 151D963G05 151D963G06 151D963G D597G01 449D597G02 449D597G03 449D597G04 449D597G05 449D597G06 151D933G01 151D933G D963G01 151D963G02 151D963G03 151D963G04 151D963G05 151D963G06 151D963G D597G01 449D597G02 449D597G03 449D597G04 449D597G05 449D597G06 151D933G01 151D933G02 151D933G02 N/A D963G01 151D963G02 151D963G03 151D963G04 151D963G05 151D963G06 151D963G07 N/A Rating Minimum Opening Time -1R 70-2R 100-3R 1-4R 150-5R 170-6R 200-9R 2-12R 70-2R 100-3R 1-4R 150-5R 170-6R 200-9R 2-12R -1R 70-2R 100-3R 1-4R 150-5R 170-6R 200-9R 2-12R 70-2R 100-3R 1-4R 150-5R 170-6R 200-9R 2-12R -1R 70-2R 100-3R 1-4R 150-5R 170-6R 200-9R 2-12R 2-12R 70-2R 100-3R 1-4R 150-5R 170-6R 200-9R 2-12R Motor FLA Voltage Suggested Fuse➀ SL ➂ SL-800➃ D597G01 449D597G02 449D597G03 449D597G04 449D597G05 449D597G06 151D933G01 151D933G02 151D933G03 151D933G04 151D933G D963G01 151D963G02 151D963G03 151D963G04 151D963G05 151D963G06 151D963G07 151D963G10 151D963G Consult Factory Consult Factory Consult Factory Consult Factory Consult Factory Consult Factory Note: Fuse selections based on LRC = FLA x 6, acceleration time of 10 seconds except where noted. Copyright Inc., All Rights Reserved. Rating Minimum Opening Time -1R 70-2R 100-3R 1-4R 150-5R 170-6R 200-9R 2-12R R R R 70-2R 100-3R 1-4R 150-5R 170-6R 200-9R 2-12R R R R R R R R R ➀ ANSI/NEMA fuses. Special mounting configuration. Consult factory for information. ➁ For FLA>180, Maximum Acceleration Time = 4.5 seconds. ➂ For FLA>360, Maximum Acceleration Time = 6 seconds. ➃ Based on Ampgard Fuse Clip design. Consult factory for field application.
22 , a part of Eaton Corporation, is a worldwide leader providing customer-driven solutions. From power distribution and electrical control products to industrial automation, utilizes advanced product development, world-class manufacturing, and offers global engineering service and support. For more information on products, call or , for engineering services call or visit our website at PG48C01TU Pittsburgh, Pennsylvania Publication No. March, 2000 Printed in U.S.A. / Z00117
7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units
Automotive Powering business worldwide Aerospace Eaton delivers the hundreds of power distribution products that are answering the demands of today s fast changing world. We help our customers worldwide
More informationMedium Voltage Motor Control Assemblies
Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................
More informationHow To Build A Germany Power Plant
Medium Voltage Air Insulated Motor Control Featuring AdvanceTM Technology. Medium Voltage Motor Control Center Product Description Contemporary Design Advance TM medium voltage motor control center (MVMCC)
More informationCatalog January. Heavy industrial power applications Motor contactors and starters
Catalog January Heavy industrial power applications Motor contactors and starters 2006 General contents 0 Heavy Industrial Power Applications Motor Contactors and Starters 1 Contactors and Starters, Type
More informationBulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
More informationBussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1
How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module
More informationCATALOG #250 WWW.DANAHERSPECIALTYPRODUCTS.COM
CATALOG #250 WWW.DANAHERSPECIALTYPRODUCTS.COM TABLE OF CONTENTS Vacuum Control... Low Voltage, Medium Voltage... A NEMA Control - Heavy Duty... TM, 5000... B NEMA Control - General Duty... HP... C Pilot
More informationSubmit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationTmax MCCBs. Molded case circuit breakers. Tmax
Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high
More informationAF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationOverview Brochure Integrated Power Distribution. Medium Voltage Assembly Solutions
Overview Brochure Integrated Power Distribution Medium Voltage Assembly Solutions Medium voltage assembly solutions Eaton, a premier leader in manufacturing power distribution and power protection equipment
More informationCAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
More informationBulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
More informationSecondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
More information3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C
41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers
More informationIEC style contactors - long electrical and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide
- long al and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide range coils +0% to -30% Finger safe terminals Four-pole versions available NO + NC and
More informationNF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.
More informationDead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
More informationElectronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
More informationElectronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
More informationMagnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast
More informationHPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
More informationElectronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
More informationType: DILM9 10(24VDC) Article No.: 276705
Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50
More information3AH5 Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG 11.05 2010
Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.05 2010 Answers for energy. R-HG11-172.tif 2 Siemens HG 11.05 2010 Contents Contents Page 3AH5 Vacuum Circuit-Breakers Medium-Voltage
More informationGTEC transfer switch open transition
GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility
More informationType: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
More informationSIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.
The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved
More informationGuide. Hi-TECH UCA CONTACTORS & HUBBELL SPECIAL PURPOSE CONTACTORS. Ordering. Hubbell Contactor Range SECTION 2 HUBBELL CONTACTOR RANGE
Hubbell Contactor Range SECTION 2 HUBBELL CONTACTOR RANGE HiTECH UCA CONTACTORS & HUBBELL SPECIAL PURPOSE CONTACTORS HiTech Contactors up to 110kW Fully comply with BS EN 6094741 5 sizes up to 110kW Designed
More informationType: DILM32 10(24V50HZ) Article No.: 277247
Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,
More informationPROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B
WHITE PAPER PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS BULLETIN 1497, 1497A, AND 1497B CONTROL CIRCUIT TRANSFORMERS The proper selection of the control circuit transformers is important for suitable
More informationIndustrial Control Power Transformers
Class MT Features Epoxy-encapsulated (50 5000); Completely seals the transformer coils against moisture, dust, dirt and industrial contaminants for maximum protection in hostile and industrial environments
More informationRISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
More informationHow To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply
GTEC Transfer switch open transition 40 2000 amp Description GTEC transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator
More informationMotor Control V12-T13-2 V12-T13-72 V12-T13-76 V12-T13-87
Motor Control Motor Control............................. Adjustable Frequency AC Drives............................. Synchronous............................................ Starters (Medium Voltage)..................................
More informationMTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
More informationAuxiliary Relay. Type P8n, PQ8n, PN8n
Auxiliary Relay Type P8n, PQ8n, PN8n ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering
More informationSMC -3 Specifications
Technical Data SMC -3 Specifications Bulletin Number 150 Topic Page Product Overview 2 Standards Compliance and Certifications 2 Features 3 Catalog Number Explanation 4 Wiring Diagrams 6 General Specifications
More informationCatalog. Modular DIN rail components Installation contactors
Catalog Modular DIN rail components Installation contactors 0 CDC00C00 Installation contactors Benefits and features Overview Ordering details ESB installation contactors ESB0 ESB ESB0 ESB 7 EN installation
More informationGeneral Purpose Relays Types K, R, N, and C
General Purpose Relays s K, R, N, and C Catalog 0CT00R/0 00 Class 0 CONTENTS Description............................................. Page R Miniature Plug-in Relays.............................. K Plug-in
More informationPLUGS & RECEPTACLES. INNOVATIVE EXPLOSION PROTECTION by R. STAHL 1-800-782-4357
Series Features: Color coding and pin configuration makes it physically impossible to mate plugs and receptacles of different voltages and current ratings (per IEC 60 309-2). Interlocked switch mechanism
More informationTechnical catalogue. Modular DIN rail components Installation contactors
Technical catalogue Modular DIN rail components Installation contactors Installation Contactors Overview... ESB Installation Contactors 0 A / AC-/AC-7a ESB0...4 4 A / AC-/AC-7a ESB4...5 40 A / AC-/AC-7a
More informationUS Breaker Brand 3 Pole AC Contactors (Square D Telemecanique LC1 Replacements)
4 NC1 D09-D18 NC1 -D32 US Breaker Brand 3 Pole AC Contactors (Square D Telemecanique LC1 Replacements) Standards: UL508, CSA C22.2, IEC 60947, and CE Marked Integral DIN Rail & Base Mounting in One Compact
More informationBolted contact switches. Pringle switches
Bolted contact switches Pringle switches Eaton s Pringle bolted contact switches History Eaton s PringleT switches have helped pioneer the development of high-quality electrical products for commercial
More informationBreakers and Switches. Switches Switch-disconnectors OT, OETL, OTDC and OTM
Breakers and Switches Switches Switch-disconnectors OT, OETL, OTDC and OTM Switch-disconnectors OT 16...2500, OETL 3150, OTDC16...32 and OTM160...2500 Contents 4 Product overview, features 8 Technical
More informationCircuit Breakers. NRC Series. NRC Series. 900 www.idec.com
Switches & Pilot Lights Display Lights NRC series circuit breakers offer circuit protection which is far superior to using fuses in applications containing relay circuits, motor circuits, heater circuits,
More informationType: DILM50(230V50HZ,240V60HZ) Article No.: 277830
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase
More information48 SERIES Relay interface modules 10 A
48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply
More informationDATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen
More informationEVER EFFICIENT. EVER RELIABLE. EVER PROFITABLE.
EVER EFFICIENT. EVER RELIABLE. EVER PROFITABLE. A Regal Brand EVERGREEN SOLUTIONS Powered by ECM Technology Upgrade/Replace PSC motors with Evergreen IM Residential/Light Commercial HVAC Systems Reduce
More informationType MG-6 Multi-Contact Auxiliary Relay
Type MG-6 Multi-Contact Auxiliary Relay Instruction Leaflet: 41-753.1 N Effective: August 2008 Supersedes 41-753.1 M, Dated December 1999 ( ) Denotes Change Since Previous Issue Device Number: 94X, Y,
More information0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N
55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils
More informationUniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
More informationData Sheet. Electro-mechanical counters Hengstler 800 series
Data Pack D Issued March 00 504897 Data Sheet Electro-mechanical counters Hengstler 800 series The 800 series totalising and predetermining batch counters, manufactured by Hengstler, is available from
More informationMCC Ratings. Voltage Rating
MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control
More informationSUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
More information38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
More informationDecision-Maker Paralleling System. Power Distribution Switchboards and Circuit Breakers. Standard Features
Decision-Maker Paralleling System Power Distribution Switchboards and Circuit Breakers Power Distribution Switchboards and Circuit Breakers The generator paralleling circuit breakers for the Kohler Decision-Maker
More informationPanel Meters and Controllers Modular Panel Meter Type EDM 35
Panel Meters and Controllers Modular Panel Meter Type EDM 35 Modular digital panel meter, 3 1/2-digit Indicating or controlling current, voltage, resistance, temperature, tacho or frequency. Easy programming
More informationRotary Disconnect Switch Specifications
Technical Data Rotary Disconnect Switch Specifications Bulletin Number 194R Topic Page Product Line Overview 2 General Specifications Fuse Description 12 Approximate Dimensions 14 Additional Resources
More informationManual motor starter MS116
Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and
More informationSolid State Timers Type F
Solid State Timers Type F Class 9050 CATALOG CONTENTS Description.....................................................Page Product Descriptions............................................. 3 Application
More informationSUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
More information48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.
48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according
More informationTemperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)
Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,
More informationLow Voltage Fuses For Motor Protection
Code Requirements The NEC or CEC requires that motor branch circuits be protected against overloads and short circuits. Overload protection may be provided by fuses, overload relays or motor thermal protectors.
More information38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
More informationManual Motor Starter MS 116 up to 16 A Technical Data
Manual Motor Starter MS 116 up to 16 A Technical Data Type MS 116 Standards: Major International IEC 60 947-4-1 / IEC 60 947-2 and European Standards EN 60 947-4-1 / EN 60 947-2 Approvals, Certificates
More information8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
More informationSpeed Control Relays SX2
SX2 File 850 CONENS Description.....................................................Page General Information................................................ 2-3 SX2DV General Information...........................................
More informationLow Voltage Products. Switches Automatic Transfer Switches
Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,
More informationCircuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
More information60 Series - General purpose relays 6-10 A. Features 60.12 60.13
Features 60.12 60.13 Plug-in mount 10 A General purpose relay 2 & 3 pole changeover contacts Cadmium Free contacts (preferred version) AC coils & DC coils UL Listing (certain relay/socket combinations)
More informationMedium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
More informationDORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
More informationConnecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations
Connecting the Power of the Sun DC Disconnects for Solar Photovoltaic Installations DC disconnects for solar photovoltaic installations Solar energy is heating up Interest in renewable energy sources has
More informationType Contact material Contact form Construction Model General purpose AgCdO SPDT Semi-sealed G2R-1
Power PCB Relay G2R Creepage distance of 8.0 mm (0.31) min. between coil and contact. Dual-winding latching type available. Plug-in and quick-connect terminals available. High sensitivity (360 mw) and
More informationSpecification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
More informationBETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview
BETA Switching Siemens AG 200 5TT5 Insta contactors, AC technology Overview The 5TT5 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary
More informationSENTRON Switching and Protection Devices Air Circuit Breakers
Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General
More informationBuck - Boost Transformers
Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single
More informationThermal-Magnetic / Magnetic Only Molded Case Circuit Breakers
Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Catalog 2004 Class 601 CONTENTS Description..............................................Page INTRODUCTION.............................................
More informationInstallation Contactors. Technical Catalogue. Type ESB. abb. ABB STOTZ-KONTAKT GmbH 1 2CDC 103002 C0201
Technical Catalogue Installation Contactors Type ESB abb ABB STOTZ-KONTAKT GmbH 1 CDC 10300 C001 ABB STOTZ-KONTAKT GmbH CDC 10300 C001 Low Voltage Products and Systems We ensure safety and comfort for
More informationBimetallic Overload Relay Specifications
Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions
More informationHVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
More informationOVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B
OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B The OVR-3SP three-phase recloser style guide aids in the proper selection of your OVR-3SP style number. The OVR-3SP
More informationTP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12
Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Cleaveland/Price Type TP-C2 Motor Operator
More information49 Series - Relay interface modules 8-10 - 16 A. Features
Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole
More informationSAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content
More informationPS6500 Storage Arrays Rack Mount Instructions
PS6500 Storage Arrays Rack Mount Instructions Part Number: R724M Rev. A01 Copyright 2010 Dell, Inc. All rights reserved. Dell is a trademark of Dell, Inc. EqualLogic is a registered trademark. All trademarks
More informationNATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
More informationSeries 427. 1/16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS
Series 427 1/16 DIN Multi-Mode Bar Graph Display Timer PRODUCT HIGHLIGHTS Digital Setting with 0.1% Accuracy Unique LED Bargraph Indicates Time Cycle in 20% Increments 8 Field Selectable Modes of Operation
More informationMini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear
Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC
More informationThyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
More informationDimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)
9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity
More informationCircuit Breakers. Next Generation of Protection Capabilities
Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationFusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
More information