Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF (10/2011) LF24 Standard

Size: px
Start display at page:

Download "Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard"

Transcription

1 LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled with controls factory installed and wired. Each unit is test operated at the factory to ensure proper operation and dependability. Installer has only to locate unit, make unit gas supply, electrical connections and mount thermostat to complete the installation. Units may be vented horizontally or vertically. pprovals Unit certified by CS International. Listed by California Energy Commission (CEC) Units are certified for natural or LPG/Propane gas ISO 900 Registered Manufacturing Quality System Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form LF (0/0) Thermal Efficiency - up to 80.% Input - 00,000 to 390,000 Btuh Warranty Heat exchanger stainless steel - fifteen year limited warranty, aluminized steel - ten year limited warranty. ll other covered components have a limited warranty of one year. Refer to the Equipment Limited Warranty certificate included with the equipment for details. Cabinet Constructed of heavy gauge painted steel. Inside cabinet insulation keep outer cabinet surface temperatures low. djustable louvers are furnished on cabinet for control of air flow direction. Wiring junction box is conveniently located on outside of cabinet for easy access. Box contains all electrical and safety controls. Terminal strip provided for thermostat connections. 3/8" x 6 rivet nuts are located on the top of cabinet for suspending unit. See dimension drawing.

2 Identification Unit Type LF = Unit Heater LF - 00 Heating System volt redundant combination gas control valve combines a manual main shutoff valve, pressure regulation and automatic electric valve (dual) into one compact combination control. Solid-state electronic direct spark ignition control provides positive main burner ignition. Spark is intermittent and occurs only when required. Heat Exchanger Type = luminized Steel S = Stainless Steel Nominal Gas Heat Input 00 = 00,000 Btuh =,000 Btuh =,000 Btuh 7 = 7,00 Btuh 00 = 9,000 Btuh 30 = 30,000 Btuh 0 = 0,000 Btuh 300 = 300,000 Btuh 3 = 3,000 Btuh 00 = 390,000 Btuh Separate electronic flame sensor control assures safe and reliable operation. Should loss of flame occur, flame sensor controls will initiate 3 attempts at re-ignition before locking out unit operation. Combustion air inducer prepurges heat exchanger and safely vents flue products. Pressure switch proves inducer operation before allowing gas valve to open. Combustion air inducer operates only during heating cycle. Tubular luminized or Stainless Steel Heat Exchanger Tubular heat exchanger is constructed of aluminized or stainless steel for superior resistance to corrosion and oxidation. Curving design of heat exchanger allows complete exposure of heating surfaces to supply air stream. Round tube surfaces create minimum air resistance and allow air to surround all surfaces for excellent heat transfer. Compact design reduces space requirements in unit cabinet. Heat exchanger has been laboratory life cycle tested. Inshot Burners luminized steel inshot burners provide efficient trouble free operation. Burner venturi mixes air and gas in correct proportion for proper combustion. Burner assembly is removable from the unit as a single component for ease of service and each burner may be removed individually. Limit Control Factory installed and accurately located. Limit control has fixed temperature setting and protects heating system from abnormal operating conditions. Combustion ir Inducer Prepurges heat exchanger and safely vents combustion products. Blower motor has sleeve bearings and is thermally protected. Pressure switch prevents unit operation in case of blockage of combustion air inlet or flue outlet. Combustion air inducer on LF-00,,, and units may be rotated 90º to left or right of vertical to facilitate installation. Venting Units may be vented horizontally or vertically. Vertical Venting - LF units are approved for installation with single wall and type B- double wall vent pipe. Horizontal Venting - LF units are approved for installation with single wall or Lennox-approved stainless steel vent kits. - Page -

3 Controls Includes: volt main gas valve with 00% safety shutoff, main shutoff valve, gas pressure regulation (natural & LPG/propane gas models), limit control, transformer and combination ignition/fan timer control board. Combination Direct Spark Ignition/Fan Timer Control Solid-state control board contains all necessary controls and relays to operate unit. Includes: Fan timer control - fan on seconds (fixed), fan off 0 seconds (fixed), terminal strip for thermostat connections, diagnostic LED for troubleshooting, continuous fan operation. Transformer 0V/V transformer furnished as standard. Direct Drive Fan ll models are equipped with efficient and quiet operating direct drive fan. Options Discharge Nozzles To direct discharge air from unit heater. vailable in 30º, º, 60º and 90º style. Fully assembled from heavy-gauge steel. Paint finish matches unit heater. See Dimension Drawings. Hanging Bracket Used to suspend unit heaters on two pipe hangers. contains two brackets and all necessary hardware. Pipe hangers (3/ in.) are not furnished and must be field provided. Horizontal Vent s and Elbow Required for Horizontal Venting pplications Unit Heater Vent Diameter (in.) Upslope Vent Catalog Downslope Vent Catalog º Elbow Catalog 90º Elbow Catalog Minimum Vent Length (ft.) LF-00 LF- LF- LF-7 LF-00 LF-30 LF-0 LF-300 LF-3 LF-00 CVENTKU 7W63 CVENTKD 7W67 CVENTKU 7W6 CVENTKD 7W68 6 CVENT6KU 7W6 CVENT6KD 7W69 CVENTE (Optional) CVENTE (Required) CVENT6E (Required) 87W80 87W8 87W8 CVENTE (Optional) CVENTE (Required) CVENT6E (Required) 7W7 7W7 7W73 Length does not include termination (or elbow where applicable) NOTE: Elbow is required where shown to facilitate connection of horizontal vent kit to flue outlet. Straight Vent Pipe - For Horizontal Venting Unit Heater Vent Diameter (in.) Length (in.) Catalog LF-00 LF- LF- LF-7, LF-00 LF-30, LF-0 LF-300 LF-3 LF-00 CVENTP6 6 7W77 CVENTP 7W78 CVENTP W79 CVENTP6 6 7W80 CVENTP 7W78 CVENTP W8 CVENT6P 6 7W83 CVENT6P W8 - Page 3 -

4 Specifications - LF-00 to LF-30 Gas Heating Perf. - Stainless Steel - luminized Steel Heating Capacity Input - Btuh Heating Capacity Output - Btuh Steady State Efficiency LF -00S LF ,000 80,00 80.% LF -S LF -,000 9,000 LF - S LF -,000 6,000 LF - 7S LF - 7 7,00 38,000 LF - 00S LF ,000 6,000 LF - 30S LF ,000 8,000 Connections - in. Flue size (round) - Vertical Venting Gas Piping Size / / / / / 3/ Fan Data ir Volume -cfm of fans Fan Diameter - in. of blades of motors Motor Output - hp RPM / / / / / /8 07 Weight Data Net Weight - lbs Shipping - Weight - lbs ELECTRICL DT Line Voltage Data - 60 HZ Motor amps Total Unit amps... volts - phase OPTIONL CCESSORIES - MUST BE ORDERED EXTR... Discharge Nozzel Hanging Bracket 3 High ltitude Pressure Switch LPG/Propane 30-9K9 9K9 9K96-9K98 9K99 9K L8 6L9 6L L96 L97 L W L8 63J6 0L07 63J7 -/8 x in. diameter adaptor is furnished with unit for flue connection. -/ x -3/ in. rectangle to in. round adaptor is furnished with unit for flue connection. 3 LF-00 through - models - Combustion air inducer pressure switch must be replaced at altitudes over 00 ft. LF-7 model - Combustion air inducer pressure switch must be replaced at altitudes over 00 ft. - Page -

5 Specifications - LF-0 to LF-00 Gas Heating Performance - Stainless Steel - luminized Steel Heating Capacity Input - Btuh Heating Capacity Output - Btuh Steady State Efficiency LF -0S LF - 0 0,000 0,0 80.% LF - 300S LF ,000,00 80.% LF - 3S LF - 3 3,000 76,000 LF - 00S LF ,000 3,000 Connections - in. Flue size (round) - Vertical venting Gas Piping Size 3/ 3/ 6 3/ 6 3/ Fan Data ir Volume -cfm of fans Fan Diameter - in. of blades of motors Motor Output - hp RPM 00 6 / / / /8 07 Weight Data Net Weight - lbs Shipping Weight - lbs ELECTRICL DT Line Voltage Data - 60 HZ Motor amps Total Unit amps.. volts - phase.. OPTIONL CCESSORIES - MUST BE ORDERED EXTR Discharge Nozzel 30-9K96-9K L L98 Hanging Bracket 8777 LPG/Propane L88 63J7 0L06 -/ x -3/ in. rectangular to in. round adapter is furnished with unit for flue connection. -/ x -3/ in. rectangular to 6 in. round adaptor is furnished with unit for flue connection. Throw Data ir Volume cfm Effective Throw feet LF - 00,, LF - 7, LF LF - 30, LF - 0 LF - 300, LF - 3 LF NOTE - djustable horizontal louvers on unit allow a variation in throw and spread. Throw terminates where velocity reaches 0 ft. per minute. - Page - Maximum Mounting Height Feet LF - 00, 6 LF -, LF - 7 LF - 00 LF - 30, LF - 0 LF - 300, LF - 3 LF Recommended maximum mounting height from floor to bottom of unit. t heights greater than shown air throw distance and air temperature at floor level is affected.

6 High ltitude Information ll units may be fired at full input up to 000 feet above sea level. bove 000 feet, manifold pressure must be adjusted on some units. djust pressure regulator to pressure shown in tables. If unit is installed at an altitude greater than 700 feet, unit must be derated by percent for each additional 000 feet above 700 feet. In Canada, certification for installation at altitudes over 00 feet above sea level is the jurisdiction of the local authorities. Note - This is the only permissible derate for the units. Natural Gas Manifold Pressure - in. w.c ft ft ft ft ft ft ft. LF - 00 LF - LF LF LF - 7 LF - 30,, LF - 00 LF - 0 LF - 3 LF LF - 7 Combustion air inducer pressure switch must be replaced at altitudes from ft. Order 36W9 pressure switch. LF-00 through - models - Combination air inducer pressure switch must be replaced at altitudes over 00 ft. Order pressure switch 36W9 LPG/Propane Manifold Pressure - in. w.c ft ft ft ft ft ft ft. LF - 00 LF - LF LF LF - 7 LF - 30,, LF - 00 LF - 0 LF - 3 LF LF - 7 Combustion air inducer pressure switch must be replaced at altitudes from ft. Order 36W9 pressure switch. LF - 00 through - models - Combination air inducer pressure switch must be replaced at altitudes over 00 ft. Order 36W9 pressure switch. - Page 6 -

7 Installation Clearances Top Sides Rear Bottom Flue 6 inches 6 inches 8 inches 0 inches 6 inches NOTE - Provide adequate clearance for servicing. See Installation Instructions for further installation considerations. Dimensions - in inches Note -Single fan model shown. LF-00,,,7 and 00. LF-30, 0, 300, 3 and 00 models have two fans. Note -Two rivet nuts are furnished on LF-00,,, 7 and 00 models. Four rivet nuts are furnished on LF-30, 0, 300, 3 and 00 models. Maximum Horizontal Vent Lengths of Elbows LF-00,,, 7, 00 LF-30, 0, 300 LF-3 LF Furnished on LF-30, LF-0, LF-300, LF-3 and LF-00 s Only. *7-/8 / / C TOP VIEW 3-/6 B E 3/8-6 RIVETNUTS FOR UNIT SUSPENSION FLUE OUTLET ELECTRICL INLETS F D 3-3/6 DJUSTBLE LOUVERS IR FLOW COMBUSTION IR INDUCER DIRECT DRIVE FN FRONT VIEW HET EXCHNGER SIDE VIEW GS VLVE B C D E F LF - 00 LF - LF - LF - 7 LF - 00 LF - 30 LF - 0 LF LF - 3 LF /6 -/ 9-/6-3/ 3-/ 7-7/8 3-/8 -/ -/ 8-/ 3-/ 8-/6 -/8 3-/ / 3-/ 8-/6 -/8 3-/6 0 7-/ 3-/ 9-3/6 - Page 7 -

8 ccessory Dimensions in inches. Usage LF - 00 LF - LF - LF - 7 LF - 00 LF - 30 LF - 0 LF LF - 3 "" Dimension in inches 8-/ -/ 39-/ -3/6 30 o _ Discharge Nozzle 30 deg 60_ o Discharge Nozzle 3-/ 8-/ 7-7/8-3/6 _ o Discharge Nozzle 8 deg 90_ o Discharge Nozzle 30-7/8 8-/8 LF /6 60 deg 8-3/ -3/6 3-3/ Vent s and ccessories HORIZONTL VENT KITS (UPSLOPE) 3 ND 6 INCH HORIZONTL VENT KITS (DOWNSLOPE) ELBOW (Typical) 90 ELBOW (Typical) STRIGHT PIPE (Typical) Form LF (0/0) 0 llied ir Enterprises LLC, a Lennox International Inc. Company Printed in the U.S.. Phone: (803) Page 8 -

Commercial Gas Furnace Upflow

Commercial Gas Furnace Upflow Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted

More information

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially

More information

XV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE

XV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE UPF/HORIZONTAL 2-, VARIABLE SPEED GAS-FIRED FURNACE XV80 MODELS TUD2B060A9V3VB, TUD2B080A9V3VB TUD2C080A9V4VB, TUD2C080B9V4VB TUD2B00A9V3VB, TUD2C00A9V5VB TUD2C00B9V5VB, TUD2DA9V5VB TUD2DB9V5VB, TUD2DA9V5VB

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air

More information

G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS

G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating

More information

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S NATURAL GAS 40-130 MBH INPUT Due to continuous product improvement, specifications are subject to change

More information

ELITE SERIES Up Flow / Horizontal Precision Speed Blower

ELITE SERIES Up Flow / Horizontal Precision Speed Blower G S F U R N C E S G50UHi ELITE SERIES Up Flow / Horizontal Precision Speed Blower E N G I N E E R I N G D T Bulletin No. 210380 ugust 2005 Supersedes May 2004 FUE 80% Input 66,000 to 132,000 Btuh Nominal

More information

XV 95. Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace PUB. NO.

XV 95. Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace PUB. NO. Upflow/ Horizontal Left, Downflow/ Horizontal Right Speed Two Stage Condensing Gas-Fired Furnace XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB Direct Vent

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in cooling California NOx

More information

F9MXE. Product Specifications

F9MXE. Product Specifications 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Select models earn the ENERGY STAR (See below, indicated with check mark.) Xtra SEER ECM blower motor Supports

More information

TECHNICAL MANUAL GDS8 & GHS8

TECHNICAL MANUAL GDS8 & GHS8 TECHNICAL MANUAL AL GDS8 & GHS8 33-3/8" 80% Gas Furnace Units Refer to Service Manual RS6610004 for installation, operation, and troubleshooting information. All safety information must be followed as

More information

CB29M Bulletin #490071 February 1996

CB29M Bulletin #490071 February 1996 ENGINEERING DT MTCHED REMOTE SYSTEMS 50hz S LOWER UNITS 50hz ELITE 10 MULTI POSITION LOWER UNITS 20 100 to 49 00 tuh (5.9 to 14.4 kw) Cooling Capacity 19 700 to 49 100 tuh (5.8 to 14.4 kw) Heat Pump Heating

More information

High efficiency, cast-iron gas boiler

High efficiency, cast-iron gas boiler SENTRY High efficiency, cast-iron gas boiler LOWER PROFILE MAKES PROBLEM INSTALLATIONS EASY SENTRY High efficiency, cast-iron gas boiler A smarter choice for informed The boiler you choose for your home

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters CYCLONE Mxi MODULATING MODULATING BURNER ADVANCES THE CYCLONE TO HIGHER LEVELS OF EFFICIENCY The full line of A. O. Smith Cyclone Mxi condensing water heaters has been designed to provide years of dependable

More information

HEAVY DUTY STORAGE GAS

HEAVY DUTY STORAGE GAS Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters POWERED BURNER MODELS LARGE-VOLUME POWERED BURNER FEATURES The large-volume powered burner line includes the largest, most powerful A. O. Smith tanktype gas water heaters. With tank capacities up to 600

More information

Owner Retain this manual in a safe place to provide your serviceman information if it becomes necessary.

Owner Retain this manual in a safe place to provide your serviceman information if it becomes necessary. INSTALLATION, OPERATING AND SERVICE MANUAL FOR EASY RADIANT WORKS HEATWAVE MODEL GH-25-40 GAS FIRED, VENTED INFRARED TUBE HEATER FOR RESIDENTIAL & COMMERCIAL / INDUSTRIAL APPLICATIONS. For Your Safety

More information

UDSA - UDSBD unit heater

UDSA - UDSBD unit heater APPLICATIONS Heating >> FACTORIES >> WAREHOUSES >> HALLS >> SHOWROOMS >> GREENHOUSES >> RETAIL >>... UDSA - UDSBD unit heater www.reznor.eu V3 gas fired unit heater Reznor V3 unit heaters are one of the

More information

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters FEATURES ULTRA-LOW NOx CONDENSING TECHNOLOGY PROVIDES UNPRECEDENTED 0.95 ENERGY FACTOR DURABLE HEAT EXCHANGER Primary Heat Exchanger

More information

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH Centauri Condensing Fire Tube Water Boiler 399 to 1000 MBH Pre-mix surface burner with up to a 7-to-1 turndown NOx levels as low a 5 ppm at full rate Operates on 4" gas pressure shown with optional gauges

More information

NAVIEN AMERICA INC. 17855 FITCH AVENUE

NAVIEN AMERICA INC. 17855 FITCH AVENUE Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

G9MXE. Product Specifications

G9MXE. Product Specifications Up to 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL Up to 96% AFUE, all models all positions California NOx approved Select models earn the ENERGY STAR (See below, indicated with check mark.)

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...

More information

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The

More information

Commercial Gas Water Heater

Commercial Gas Water Heater Commercial Gas Water Heater 3-Year Limited Tank/1-Year Limited Parts Warranty* The Polaris has a high grade 444 stainless steel tank with brass connections for years of dependable, trouble-free service

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

GCS16 GCS20 WARNING CAUTION

GCS16 GCS20 WARNING CAUTION Service Literature Corp. 0110 L6 Revised 12 2004 GCS16/GCS20 SERIES UNITS GCS16 GCS20 2 to 5 Ton GCS16/20 series units in the 2 to 5 ton (7.0 to 17.0 kw) cooling size are packaged combination gas heat

More information

Explosion-Proof Electric Unit Heaters

Explosion-Proof Electric Unit Heaters Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters UP TO 96% THERMAL EFFICIENCY, DIRECT-VENT FEATURES TM BTH-120 through BTH-500 The A. O. Smith Cyclone Xi family of products represents the industry s most technologically advanced commercial water heaters.

More information

Basic Selection & Proper Application of Overhead Air Distribution Devices

Basic Selection & Proper Application of Overhead Air Distribution Devices Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return

More information

FIRE DAMPER APPLICATION GUIDE

FIRE DAMPER APPLICATION GUIDE FIRE AND CEILING RADIATION DAMPERS FIRE DAMPER APPLICATION GUIDE Use this application guide to help determine what type of fire damper best suits the application. Below are listed the ten Metal-Fab fire

More information

Originators of the Flexible Water Tube design

Originators of the Flexible Water Tube design BRYAN FLEXIBLE WATER TUBE AB SERIES STEAM AND WATER BOILER 900,000 TO 3,000,000 BTUH FORCED DRAFT GAS, OIL OR DUAL FUEL FIRED Water Boiler AB120-W-FDGO Steam Boiler AB250-S-150-FDG Originators of the Flexible

More information

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS Electronic thermostatically controlled Low power consumption Compact space saving size Short heat-up times Dehumidification of the cabin Quiet when running Combustion

More information

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Introduction SRU s (Sulfur Recovery Units) are critical pieces of equipment in refineries and gas plants. SRUs remove sulfur compounds from certain

More information

C26 Bulletin #210061 November 1997 Supersedes January 1997 (Coil/Furnace Match Up Charts)

C26 Bulletin #210061 November 1997 Supersedes January 1997 (Coil/Furnace Match Up Charts) NGINRING T loset Installation With Pulse21 Furnace and lectronic ir leaner Typical pplications UNS N FULL S UP- VPORTOR OILS IR-ONITIONING N HT PUMP 2 To 5 Ton (7.0 To 17.6 kw) Nominal Size OILS LOWR OILS

More information

GCS16-024-030-036-048-060

GCS16-024-030-036-048-060 Packaged Unit & Gas Heat 2-5 Ton Capacity 50,000-120,000 Btuh Input Heating Capacity GCS16-024-030-036-048-060 FEATURES Designed for outdoor rooftop or ground level installations Down-flow or horizontal

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

ARMSTRONG AIR HEAT PUMPS www.armstrongair.com

ARMSTRONG AIR HEAT PUMPS www.armstrongair.com INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional

More information

Figure 22: Typical Individual Venting. Figure 21: Single Water Heater Venting

Figure 22: Typical Individual Venting. Figure 21: Single Water Heater Venting ING THE WATER HEATER The purpose of venting a gas or oil-fired water heater is to completely remove all products of combustion and to vent gasses to the outside air without condensation in the vent or

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

MODEL TF, RF & SF GAS-FIRED TUBULAR UNIT HEATERS

MODEL TF, RF & SF GAS-FIRED TUBULAR UNIT HEATERS CATALOG NO.: TFPC-8 SUPERCEDES: TFPC-4 MODEL TF, RF & SF GAS-FIRED TUBULAR UNIT HEATERS REPLACEMENT PARTS CATALOG INDEX WARRANTY INFORMATION RETURN GOODS...2 CONVERSION KITS...3 SF-30/75 SEPARATED COMBUSTION

More information

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

80UHG. Service Literature

80UHG. Service Literature Service Literature Corp. 9728 L12 Revised 01 2002 80UHG 80UHG series units are mid efficiency gas furnaces used for upflow or horizontal applications only, manufactured with tubular heat exchangers formed

More information

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES.

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES. QUIET-ONE Environmental Products 2000 Kickspace Heater Series Models: KS 2004, KS 2006 KS 2008, KS 2010 INSTALLATION OPERATING MAINTENANCE Please read these instructions thoroughly before beginning your

More information

CEILING CASSETTE FAN COIL UNIT

CEILING CASSETTE FAN COIL UNIT CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and

More information

MODEL BRT GAS-FIRED TUBULAR UNIT HEATERS

MODEL BRT GAS-FIRED TUBULAR UNIT HEATERS CATALOG NO.: BRTPC-3 GAS-FIRED UNIT HEATERS MODEL BRT GAS-FIRED TUBULAR UNIT HEATERS CATALOG INDEX WARRANTY INFORMATION RETURN GOODS...2 BRT-30/120...3, 4, 5 OPTIONAL PARTS...6 CONVERSION KITS...7 TERMS...8

More information

ASX7-4-IOM-7 J30-08579

ASX7-4-IOM-7 J30-08579 INSTALLATION INSTRUCTIONS 4" COMBUSTION AIR INLET KIT TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION For 30,000 to 75,000 BTU/HR SUPPLEMENT

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

TB-A028-06 - A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION

TB-A028-06 - A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION 1 2 3 4 5 Inadequate or no earth ground sensed by the Intelli-Vent control. Power supply to Intelli-Vent control has reversed polarity. Pressure switch circuit remaining closed for more than 5 seconds

More information

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

TANKLESS WATER HEATER INSTALLATION DIAGRAMS TANKLESS WATER HEATER INSTALLATION DIAGRAMS Installation Diagrams Tankless Installation / Optional Return Small 10-15 Gallon Point-of-Use Water Single and Optional Return : One single, small capacity water

More information

Low Profile Unit Cooler

Low Profile Unit Cooler Super-Flo Now available with EC Motors High Efficiency / High Reliability Low Profile Unit Cooler Publication No. 411.4 November, 2008 S A N I T A T I O N F O U N D A T I O N A L N A T I O N Air Defrost

More information

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI). SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........

More information

Model 1210C Battery Powered Pump Shown. Description

Model 1210C Battery Powered Pump Shown. Description 12 Volt DC Rotary Vane Pump Series 1200C Model 1210C Battery Powered Pump Shown Description of Included Models Model Number FR1205C FR1210C FR1211C FR2410C FR2411C Description Basic 12 volt DC pump with

More information

Cooktop Low-Profile Ventilation Hoods

Cooktop Low-Profile Ventilation Hoods INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html APPLY POWER TO APPLIANCE FIELD WIRING CORRECT? DPLAY ERROR CODE 1 OR 2 Intelli-Vent TM Sequence of Operation REQUEST FOR HEAT PRESENT?

More information

Gas Stoves. H15-10 Direct Vent Gas Stove. Model H15-NG10 H15-LP10. Approved Venting Systems

Gas Stoves. H15-10 Direct Vent Gas Stove. Model H15-NG10 H15-LP10. Approved Venting Systems H15-10 Direct Vent Gas Stove Model H15-NG10 H15-LP10 Fuel Type Natural Gas Propane Minimum Supply Pressure 5.0 W.C. (1.25 kpa) 12.0 W.C. (3.00 kpa) Manifold Pressure - High 3.8 W.C. (0.95 kpa) 11 W.C.

More information

Air Conditioning Sign-Off Sheet

Air Conditioning Sign-Off Sheet Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate

More information

Light Duty Commercial Electric Water Heater

Light Duty Commercial Electric Water Heater Features Heavy Duty Construction Hydrastone cement lining provides longer tank life Copper-silicon tappings cannot rust or corrode High impact composite jacket eliminates damage during installation and

More information

OIL FURNACES CLASSIC PREMIUM CLASS UPFLOW OIL FURNACES. ROBD- SERIES Heating Capacities 56,000 to 151,200 BTU/HR [16.41 to 44.

OIL FURNACES CLASSIC PREMIUM CLASS UPFLOW OIL FURNACES. ROBD- SERIES Heating Capacities 56,000 to 151,200 BTU/HR [16.41 to 44. FORM NO. O11-608 REV. 2 Supersedes Form No. O11-608 Rev. 1 OIL FURNACES CLASSIC PREMIUM CLASS UPF OIL FURNACES ROBD- SERIES Heating Capacities 56,000 to 151,200 BTU/HR [16.41 to 44.30 kw] The Rheem Classic

More information

EFFECTIVE OCTOBER 2005. Atwood Furnaces. and Digital Thermostats

EFFECTIVE OCTOBER 2005. Atwood Furnaces. and Digital Thermostats EFFECTIVE OCTOBER 2005 Atwood Furnaces and Digital Thermostats Unique 2-Stage System Set the temperature, turn the thermostat on automatic and let the furnace take over! During cold start-ups, the furnace

More information

12288 Side Road 22, Wainfleet, Ontario Canada L0S 1V0 Phone: 905-899-3473 www.easyradiantworks.com Fax: 905-899-2262

12288 Side Road 22, Wainfleet, Ontario Canada L0S 1V0 Phone: 905-899-3473 www.easyradiantworks.com Fax: 905-899-2262 12288 Side Road 22, Wainfleet, Ontario Canada L0S 1V0 Phone: 905-899-373 www.easyradiantworks.com Fax: 905-899-2262 Installation & Operating Instructions For EASY RADIANT EZ, EZU, SH & SHU Radiant Tube

More information

Installation Manual CLIFC Fan & Coil Variable Speed

Installation Manual CLIFC Fan & Coil Variable Speed Installation Manual CLIFC Fan & Coil Variable Speed General Description GENERAL DESCRIPTION FANS EQUIPMENT Totally Factory assembled within the unit all piping, wiring, and required controls for operation

More information

High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR

High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR The heat transfer innovators. THE RELIANCE COPPER FINNED TUBE HYDRONIC BOILER FEATURES Copper Fin-Tube Heat Exchanger Up to 88% Thermal

More information

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water 2 to 15 tons Water-Cooled and Chilled Water Unique Solutions for Challenging HVAC Projects Your Choice for Limited Space Applications Water-Cooled Chilled Water The VertiCool Space Saver allows installation

More information

OIL FURNACES. Clean, Comfortable Oil Heat From

OIL FURNACES. Clean, Comfortable Oil Heat From OIL FURNACES Clean, Comfortable Oil Heat From Features 3 1 2 5 10 9 7 6 8 4 1 Foil-faced high density fi berglass insulation gives durable, insulating heat and sound protection. 2 Heavy-duty 14 gauge steel

More information

Series GM. Peerless Boilers. Residential/Commercial Gas Boilers

Series GM. Peerless Boilers. Residential/Commercial Gas Boilers Peerless Boilers Series GM Residential/Commercial Gas Boilers The Series GM cast iron, hot water boiler is ideal for use in large residences or commercial applications. This gas-fired, atmospheric boiler

More information

Frequently Asked Questions. Air Top Diesel Heaters. 2000STC, Evo 40 & Evo 55

Frequently Asked Questions. Air Top Diesel Heaters. 2000STC, Evo 40 & Evo 55 Frequently Asked Questions Air Top Diesel Heaters 2000STC, Evo 40 & Evo 55 Question 1 What power outputs are the heaters available in? There are 3 models 2kW, 4kW and 5.5kW Question 2 What voltage are

More information

ASME Packaged Indirect Fired Water Heater

ASME Packaged Indirect Fired Water Heater Utilizes Or HTHW To Heat Domestic Water, Semi-Instantaneous or Storage Type Model BW Features Reliable Only high grade materials used in construction to ensure long operating life Hydrastone cement lining

More information

GTS. New! Plus: PR0DUCT CATALOG. Vapor-logic 4 controller with: and LonTalk. New models GTS-500 and GTS-700. Gas-to-Steam Humidification System

GTS. New! Plus: PR0DUCT CATALOG. Vapor-logic 4 controller with: and LonTalk. New models GTS-500 and GTS-700. Gas-to-Steam Humidification System GTS Gas-to-Steam Humidification System PR0DUCT CATALOG New! Vapor-logic 4 controller with: and LonTalk Plus: New models GTS-500 and GTS-700 Gas has lowest energy operating costs The industry s first and

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions

More information

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................

More information

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling 405_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT 48/50E-4SB 48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT GAS HEAT ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS

PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS OVENS MANUFACTURED BY: EARTHSTONE OVENS-6717 SAN FERNANDO RD GLENDALE CA 91201 TELEPHONE: 800-840-4915 818-553-1134 FAX: 818-553-1133

More information

CITYPLEX TOWERS BOILER INSTALLATION ORU RFP-1138

CITYPLEX TOWERS BOILER INSTALLATION ORU RFP-1138 ALTERNATE No. 2 BFS LOCATION: Locate BFS North of B-3 on new house-keeping pad. HOUSE KEEPING PAD and DRAIN CONNECTIONS: Furnish house-keeping pad for new boilers B-2 and B-3 including trench drains to

More information

WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013

WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013 Bulletin 30-34 / March 2013 INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES General The information on the following pages is to provide the installer the necessary information to properly install the

More information

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners M/MR Modulating Valves design certified For Atmospheric, Infrared, and Direct Fired urners TALE OF CONTENTS Description/Specifications... 1 Introduction... 2 Direct Fired Applications (Negative Pressure)...

More information

COMMERCIAL TYPE B GAS VENT MODEL E/V 10" 30"

COMMERCIAL TYPE B GAS VENT MODEL E/V 10 30 OMMERIL TYPE GS VENT MODEL E/V 10" 30" www.eccomfg.com GS VENT 10" 30" EO INDEX DESRIPTION... 90 E/V PIPE ND FITTINGS 10" Model... 91 12" Model... 91 92 14" Model... 92 16" Model... 93 18" Model... 93

More information

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER Certified to / Certifié à CGA 2.14 M2000 Conforms to / Conforme à ANSI std Z83.7 2000 Suitable for indoor or outdoor installation / Unvented / Unattended Type

More information

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS Electronic thermostatically controlled Low power consumption Compact space saving size Short heat-up times Dehumidification of the cabin Quiet when running Combustion

More information

Fossil fuel heating equipment

Fossil fuel heating equipment Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating

More information

Tankless water heaters

Tankless water heaters imagine RHEEM TANKLESS WATER HEATERS never running out of hot water again Tankless water heaters Continuous hot water continuoushot water from Rheem 1-2 RTG-64 Series RTG-64DV, RTG-64X Natural or LP Gas.

More information

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size

More information

ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL

ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER INSTALLATION USE & CARE MANUAL ALL WEATHER W-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER TABLE OF CONTENTS: INSTALLATION USE & CARE MANUAL IMPORTANT INFORMATION Assembly Instructions 2 Wiring Instructions 2 Outdoor Installation

More information

CATTURA TM DOWNDRAFT MODELS D49M30SB, D49M36SB, D49M48SB

CATTURA TM DOWNDRAFT MODELS D49M30SB, D49M36SB, D49M48SB SPECIFICATIONS CATTURA TM DOWNDRAFT MODELS D49M30SB, D49M36SB, D49M48SB Page 1 Powerful VERTEX TM Complete Capture Design rivals the finest island hoods. Compact design allows the choice of many cooktop

More information

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000

More information

AIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency

AIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency FORM NO. H11-52 REV. 3 Supersedes Form H11-52 Rev. 2 AIR HANDLERS AIR HANDLERS RHLA- Efficiency featuring R-22 Refrigerant RHLL- Efficiency featuring Earth-Friendly R-10A Refrigerant earth friendly refrigerant

More information

LH and GH/GL Series UNIT COOLERS. Technical Bulletin: LHGH_001_071015. Products that provide lasting solutions.

LH and GH/GL Series UNIT COOLERS. Technical Bulletin: LHGH_001_071015. Products that provide lasting solutions. LH and GH/GL Series UNIT COOLERS Technical Bulletin: LHGH_001_07101 Products that provide lasting solutions. LH Series Unit Coolers Dual Discharge Low Hite Series At 9 1/ maximum height, the LH Series

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex

More information

Watts Spacemaker. Sa f e t y Wa t e r He a t e r. Enclosures Stands Restraints

Watts Spacemaker. Sa f e t y Wa t e r He a t e r. Enclosures Stands Restraints Watts Spacemaker Sa f e t y Wa t e r He a t e r Installation Products Enclosures Stands Restraints Ta b l e o f Co n t e n t s / In t r o d u c t i o n / Seismic Zo n e s Table of Contents Seismic Zones

More information

DRYER VENTING SPECIFICATIONS DRYER SAFETY

DRYER VENTING SPECIFICATIONS DRYER SAFETY DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting

More information

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural

More information