KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE



Similar documents
Section kv Power Cables

KNOW YOUR OPTIONS: 230 KV POWER CABLES

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G

EDS KV TRIPLEX CABLE

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities

XLPE Land Cable Systems User s Guide. Rev 5

HIGH VOLTAGE XLPE CABLE SYSTEMS. Technical User Guide

High Voltage Systems. Today. The history of cables

Industrial Cable Solutions for Variable Frequency Drives

Gulf Cable & Electrical Ind. Co.

100% EMI Emission Containment

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

UGVCL/SP/591/11KV HT AB CABLE

Network Standard Advice No. 1420C 9/6/2011

MEDIUM VOLTAGE CABLES Up to and including 36 KV

3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables /15 kv XLPE insulated cables /20 kv XLPE insulated cables 35

Exane 125 Drilling Rig and Commercial Marine Cable

Removal of EP SP High Voltage Cable

TFC/U-JIN Coaxial Cable Product Information Sheet Type: TU6T60-JVB

Underground Cable Temperature Monitoring in the Real World

APPLICATION ORIENTED DESIGN OF CABLES

Uptown Campus, Primary Electric Master Plan - Program Study State University of New York At Albany, SUCF Project No V.

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES

MEDIUM VOLTAGE POWER CABLES

Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables

Cables, Cable Laying & Accessories Manual

Fault location on power cables. Fault location on power cables

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

Gexol. Gexol. The Global Cable Solutions Company. Designed for safe, reliable performance in the harshest oil and gas operating environments

VIPERFLEX ELECTRIC CABLE

WIRE AND CABLE ENGINEERING GUIDE

Session Five: Modern XLPE Materials for Extruded Energy Cable Systems

MV CABLE TYPE C

CONFLEX ELECTRIC CABLE

Communication, Signal & Data Cables

FIELD AGING OF ETHYLENE-PROPYLENE-RUBBER (EPR) CABLES UNDER NORMAL AND ACCELERATED VOLTAGE STRESS AT MEMPHIS LIGHT, GAS AND WATER DIVISION

SECTION SIGNAL WIRE AND CABLE

345 kv Underground Report

High Voltage Cable Systems

Instrumentation Cable Power Cable Assembly Solutions...32

COAX Cables Radio Frequency Cables

PROFIBUS cable. for PROFIBUS-PA and -DP 10/ EN

Outside Telephone Cable

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

Specification SFTP CAT6 Network Cable 23AWG CU

Tri-Rated Flexible PVC Equipment Wire

FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR

SECTION MEDIUM VOLTAGE CABLE

Commercial Coaxial Cable

6-36kV Medium Voltage Underground Power Cables. XLPE insulated cables

WIRE AND CABLE ENGINEERING GUIDE

PROFIBUS cable. PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications

Cable Tray Selection-

CABLES FOR PHOTOVOLTAIC SOLAR ENERGY INSTALLATIONS FOR CLEAN ENERGY

Least Cost Cable System. Strategies to Reduce Cable and Infrastructure Costs When Transitioning to an All Conduit Systems

6 ELECTRICAL PARAMETERS

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

General Calculations. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE

INTERNATIONAL STANDARD

OFFICE OF CIVIL ENGINEERING UNITED STATES COAST GUARD WASHINGTON, D.C. APRIL 1996 MARINE CABLE, POWER AND CONTROL SPECIFICATION NO.

LOW VOLTAGE POWER CABLES

CABLE ACCESSORIES kv

International Electrotechnical Commission Standards

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide

ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION

MICROCABLES. A complete vision of your connectivity needs. Catalogue

VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials

Flexible cables for submersible products

Radial Distribution Test Feeders

M. GELDON Brugg Kabel CZ. Ing. D. RÚŽEK PREdistribuce. Switzerland Czech Rep. Czech Rep. Czech Rep., Switzerland Germany

Contents. All Rights Reserved

3M Scotchcast Mine and Portable Cable Splice Kit

Installation and Application Guide. for 600V Conductors

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 BASEC APPROVED PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

Fire Resistant Cables

XLPE рower cables. 2 Modern solutions for power cables I Estralin HVC

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

The Quality Connection. Cable Solutions for Mobile Networks Business Unit Telecom

RoHS DATA, COAXIAL AND ELECTRONIC M.R. D A TA, C O A X I A L, ECOLGICAL Telecom Cables A N D EL E CTRON I C. Cables

How To Monitor Water Penetration In A Cable Screen

Temperature Permissible ambient temperature. Weather Resistance to severe weather conditions. Impacts Cable mechanical resistance to impacts

Cable Guide. Cables, Connectors & Tools for installation of quality networks. TRIAX - your ultimate connection

Standards Affecting a Premise T-1 Installation

The Instrumentation Cable Experts

Standard Buccaneer - Ethernet

with coloured cores and overall copper screen UL/CSA... 17

Type XHHW-2 or RHH/RHW-2/USE-2 GenFree II LSZH XLPO Single Conductor

6000 Series Buccaneer

superconductors, while also working on integrating the new 2nd generation superconductors based on Y(RE)Ba 2 Cu 3 O X Ca 2

Cable Installation Notes

Offshore Transformer Platform. Technical Standard. Energinet.dk. HV, MV, LV and Signal Cables and Cable Routing

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

Global cable expertise for rolling stock

MESSENGERS FOR AERIAL CABLE

Copper wire figures. AWG Table

ScottishPower Distribution Cables & Equipment. Metal Theft

CIR. Index. Gexol. Standard CIR UL Listed Type TC-ER. Crush and Impact Resistant Without External Armoring. Arctic CIR UL Listed Type TC-ER-HL*

Transcription:

Know Your Options: 69 kv XLPE Power Cable 3

material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper and aluminum conductors can meet your requirements, the more economical solution will be a function of the metal and the cable component costs Insulation thickness For cables with a radial moisture barrier, Southwire Standard Wall reduced insulation thicknesses within the stress limits in AEIC specification CS9 are recommended Cables referred to by Traditional Wall insulation (650 mils) follow the traditional insulation wall practice referenced in ICEA standard S-108-720 appendix F as still specified by a number of customers and utilities For applications requiring smaller cable diameters, specific designs are available upon request Section 2 69 kv Power Cables Sheath material Copper and aluminum corrugated sheaths offer the best mechanical and moisture protection for your HV cable, and copper will provide better short circuit performance and improved connectability Full wall cables with concentric neutrals are an economical option for mostly dry environments Composite laminate sheaths in both copper and aluminum that offer excellent protection against moisture ingress Jacket Standard outer jacket: extruded LLDPE with a co-extruded outer semi-conductive polyethylene layer for jacket integrity testing Halogen Free Fire Retardant (HFFR) compounds are available upon request for installations in cable trays and ventilated troughs 4

69 kv Power Cables 69 kv XLPE Copper Traditional Wall 650 mil XLPE Copper Corrugated Sheath Cable Construction Reverse Concentric Stranded Copper, Compressed or Milliken Super Smooth Shield Super Clean XLPE Insulation Traditional Wall - 650 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Copper Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kv) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( o C) Nominal 90 Max. Emergency 105 Short Circuit 250 Minimum Installation -10 Design Characteristics Design Standards AEIC, IEC Typical Test Voltages 120 kv / 15 min. XLPE Loss Factor 0.0005 Relative Permittivity 2.3 5

Size in kcmil 1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000 Dimensional Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Nominal in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1 in 2.21 2.39 2.53 2.67 2.79 2.90 3.00 3.26 3.42 3.58 3.71 mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2 82.8 86.9 90.8 94.2 in 2.68 2.88 3.04 3.19 3.32 3.44 3.56 3.85 4.03 4.20 4.34 mm 68.1 73.2 77.2 81.0 84.3 87.4 90.4 97.8 102.3 106.6 110.3 in 2.96 3.16 3.33 3.47 3.60 3.72 3.84 4.13 4.31 4.48 4.62 mm 75.2 80.3 84.6 88.1 91.4 94.5 97.5 104.9 109.4 113.7 117.4 Total Weight lbs/ft 4.8 5.9 6.9 7.9 8.8 9.8 10.7 12.9 14.8 16.7 18.5 Min. Bending Radius (install/perm.) in Maximum Pulling Tension Typical Shipping Reel Size in 59/44 63/47 67/50 69/52 72/54 74/56 77/58 83/62 86/65 90/67 92/69 lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000 Flange x Width in 126x95 126x95 126x95 126x95 126x95 126x95 150x95 158x95 150x95 150x95 150x95 Shipping Reel Capacity* ft 3,000 3,000 3,000 3,000 3,000 2,950 3,000 2,800 2,500 2,200 1,975 Electrical Electrical Stress @ U o Shield kv/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 3.2 3.1 3.1 3.1 Insulation Shield kv/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9 Short Circuit for 0.5s 3 ka 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410 Sheath ka 33.6 36.1 38.2 40 41.6 43.2 44.6 48.3 50.5 52.6 54.4 Resistance DC @ 20 o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003 DC @ 90 o C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003 Capacitance pf/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7 76.5 81.5 86.2 90.3 Charging Current Amps/ kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 1.15 1.22 1.29 1.36 Ampacity @ 90 o C per circuit Typical Single Ductbank 4 Amps 600 740 820 960 1040 1110 1180 1390 1506 1595 1673 Power Rating MVA 72 89 98 115 125 133 142 167 180 191 200 Typical Double Ductbank 4 Amps 510 630 710 810 880 940 990 1181 1276 1432 1517 Power Rating MVA 61 76 85 97 106 113 119 142 153 172 182 Section 2 69 kv Power Cables Traditional Wall 650 mil XLPE Copper Corrugated Sheath 1 2500-4000 kcmil conductors are 5 segment Milliken conductors. 2 Increased shipping reel capacity can be accommodated on request. 3 Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current. 4 4ft top of duct, 1 o C-m/W native, 0.8 o C-m/W ductbank backfill, 25 o C Ambient, 75% lf, 9 spacing, single-point or cross bonded 6

69 kv Power Cables 69 kv XLPE Copper SW Standard Wall XLPE Copper Corrugated Sheath Cable Construction Reverse Concentric Stranded Copper, Compressed or Milliken Super Smooth Shield Super Clean XLPE Insulation 430 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Copper Corrugated Sheath Polyethylene Jacket with Extruded Semi- Conductive Outer Layer Cable Data Voltage Characteristics (kv) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( o C) Nominal 90 Max. Emergency 105 Short Circuit 250 Minimum Installation -10 Design Characteristics Design Standards AEIC, IEC Typical Test Voltages 120 kv / 15 min. XLPE Loss Factor 0.0005 Relative Permittivity 2.3 7

Size in kcmil 1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000 Dimensional Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Nominal in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1 mils 520 490 470 450 450 440 430 430 440 450 450 mm 13.2 12.4 11.9 11.4 11.4 11.2 10.9 10.9 11.2 11.4 11.4 in 1.95 2.07 2.18 2.27 2.39 2.48 2.56 2.82 2.92 3.1 3.23 mm 49.5 52.5 55.4 57.7 60.7 63.0 65.0 71.6 74.2 78.7 82.0 in 2.39 2.51 2.63 2.73 2.87 2.96 3.05 3.35 3.44 3.64 3.78 mm 60.7 63.8 66.8 69.3 72.9 75.2 77.5 85.0 87.4 92.5 96.0 in 2.67 2.80 2.91 3.01 3.15 3.24 3.33 3.63 3.72 3.92 4.06 mm 67.8 71.0 73.9 76.5 80.0 82.3 84.6 92.1 94.5 99.6 103.1 Total Weight lbs/ft 4.2 5.2 6.1 6.9 7.9 8.8 9.6 11.7 13.3 15.3 17 Min. Bending Radius (install/ perm.) Maximum Pulling Tension Typical Shipping Reel Size in 53/40 56/42 58/44 60/45 63/47 65/49 67/50 73/54 74/56 78/59 81/61 lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000 Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 126x95 150x95 150x95 158x95 Shipping Reel Capacity 2 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,750 2,400 2,100 Electrical Electrical Stress @ U o Shield kv/mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.2 4.1 Insulation Shield kv/mm 2.1 2.4 2.6 2.7 2.8 2.9 3.0 3.0 3.0 3.0 3.0 Short Circuit for 0.5s 3 ka 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410 Sheath ka 29.9 31.5 33 34.2 35.9 37.1 38.2 41.9 43.1 45.5 47.4 Resistance DC @ 20 o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003 DC @ 90 o C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003 Capacitance pf/ft 51.1 60.6 68.9 77.1 82.4 88.9 95.3 107.1 108.6 113.3 119.2 Charging Current Amps/ kft 0.74 0.91 1.04 1.16 1.24 1.34 1.43 1.31 1.63 1.7 1.79 Ampacity @ 90 o C per circuit Typical Single Ductbank 4 Amps 600 750 870 970 1060 1130 1200 1422 1544 1632 1714 Power Rating MVA 72 90 104 116 127 136 144 170 185 196 205 Typical Double Ductbank 4 Amps 520 640 740 820 890 950 1000 1202 1303 1377 1445 Power Rating MVA 63 77 89 98 107 114 120 144 156 165 173 Section 2 69 kv Power Cables SW Standard Wall XLPE Copper Corrugated Sheath 1 2500-4000 kcmil conductors are 5 segment Milliken conductors. 2 Increased shipping reel capacity can be accommodated on request. 8 3 Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current. 4 4ft top of duct, 1 o C-m/W native, 0.8 o C-m/W ductbank backfill, 25 o C Ambient, 75% lf, 9 spacing, single-point or cross bonded

69 kv Power Cables 69 kv XLPE - Aluminum Traditional Wall 650 mil XLPE Aluminum Corrugated Sheath Cable Construction Reverse Concentric Stranded Aluminum, Compressed Super Smooth Shield Super Clean XLPE Insulation Traditional Wall - 650 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Aluminum Corrugated Sheath Polyethylene Jacket with Extruded Semi- Conductive Outer Layer Cable Data Voltage Characteristics (kv) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( o C) Nominal 90 Max. Emergency 105 Short Circuit 250 Minimum Installation -10 Design Characteristics Design Standards AEIC, IEC Typical Test Voltages 120 kv / 15 min. XLPE Loss Factor 0.0005 Relative Permittivity 2.3 9

Size in kcmil 500 750 1000 1250 1500 1750 2000 Dimensional Nominal Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 Diameter over Insulation in 2.21 2.39 2.53 2.67 2.79 2.90 3.00 mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2 Diameter over Sheath in 2.78 2.98 3.15 3.30 3.43 3.55 3.67 mm 70.6 75.7 80.0 83.7 87.1 90.2 93.2 Overall Jacket Diameter in 3.06 3.26 3.43 3.58 3.71 3.83 3.95 mm 77.7 82.8 87.1 90.8 94.2 97.3 100.3 Total Weight lbs/ft 3.2 3.6 4.1 4.5 4.9 5.3 5.7 Min. Bending Radius (install/perm.) in 61/46 65/49 69/51 72/54 74/56 77/57 79/59 Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000 Typical Shipping Reel Size Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 150x95 150x95 Shipping Reel Capacity 1 ft 3,000 3,000 3,000 3,000 2,950 3,000 3,000 Electrical Electrical Stress @ U o Shield kv/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 Insulation Shield kv/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 Short Circuit for 0.5s 2 ka 33.8 50.8 67.7 84.6 101.5 118.5 135.4 Sheath ka 38 40.7 43 45 46.9 48.6 50.1 Resistance DC @ 20 o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009 DC @ 90 o C Ω/kft 0.044 0.030 0.022 0.018 0.015 0.013 0.011 Capacitance pf/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7 Charging Current Amps/ kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 Ampacity @ 90 o C per circuit Typical Single Ductbank 3 Amps 470 580 680 770 840 910 970 Power Rating MVA 57 70 82 93 101 109 116 Typical Double Ductbank 3 Amps 400 500 580 650 710 770 820 Power Rating MVA 48 60 70 78 85 93 98 1 Increased shipping reel capacity can be accommodated on request. 2 Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current. 3 4ft top of duct, 1 o C-m/W native, 0.8 o C-m/W ductbank backfill, 25 o C Ambient, 75% lf, 9 spacing, single-point or cross bonded Section 2 69 kv Power Cables Traditional Wall 650 mil XLPE Aluminum Corrugated Sheath 10

69 kv Power Cables 69 kv XLPE - Aluminum SW Standard Wall XLPE Aluminum Corrugated Sheath Cable Construction Reverse Concentric Stranded Aluminum, Compressed Super Smooth Shield Super Clean XLPE Insulation 430 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Aluminum Corrugated Sheath Polyethylene Jacket with Extruded Semi- Conductive Outer Layer Cable Data Voltage Characteristics (kv) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( o C) Nominal 90 Max. Emergency 105 Short Circuit 250 Minimum Installation -10 Design Characteristics Design Standards AEIC, IEC Typical Test Voltages 120 kv / 15 min. XLPE Loss Factor 0.0005 Relative Permittivity 2.3 11

Size in kcmil 500 750 1000 1250 1500 1750 2000 Dimensional Nominal Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 Insulation Thickness mils 520 490 470 450 450 440 430 mm 13.2 12.4 11.9 11.4 11.4 11.2 10.9 Diameter over Insulation in 1.95 2.07 2.18 2.27 2.39 2.48 2.56 mm 49.5 52.6 55.4 57.7 60.7 63.0 65.0 Diameter over Sheath in 2.47 2.61 2.73 2.83 2.96 3.06 3.15 mm 62.7 66.3 69.3 71.9 75.2 77.7 80.0 Overall Jacket Diameter in 2.75 2.89 3.01 3.11 3.24 3.34 3.43 mm 69.9 73.4 76.5 79.0 82.3 84.8 87.1 Total Weight lbs/ft 2.7 3.0 3.4 3.7 4.1 4.4 4.7 Min. Bending Radius (install/perm.) in 55/41 58/43 60/45 62/47 65/49 67/50 69/51 Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000 Typical Shipping Reel Size Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 Shipping Reel Capacity 1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 Electrical Electrical Stress @ U o Shield kv/mm 4.5 4.5 4.5 3.4 4.5 4.5 4.5 Insulation Shield kv/mm 2.1 2.4 2.6 1.8 2.8 2.9 3.0 Short Circuit for 0.5s 2 ka 33.8 50.8 67.7 84.6 101.5 118.5 135.4 Sheath ka 33.8 35.6 37.3 38.7 40.5 41.8 43.1 Resistance DC @ 20 o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009 DC @ 90 o C Ω/kft 0.044 0.030 0.022 0.018 0.015 0.013 0.011 Capacitance pf/ft 51.1 60.6 68.9 77.1 82.4 88.9 95.3 Charging Current Amps/ kft 0.77 0.91 1.04 1.16 1.24 1.34 1.43 Ampacity @ 90 o C per circuit Typical Single Ductbank 3 Amps 470 590 690 780 860 920 990 Power Rating MVA 57 71 83 94 103 110 119 Typical Double Ductbank 3 Amps 410 510 590 660 720 780 820 Power Rating MVA 49 61 71 79 87 94 98 1 Increased shipping reel capacity can be accommodated on request. 2 Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current. 3 4ft top of duct, 1 o C-m/W native, 0.8 o C-m/W ductbank backfill, 25 o C Ambient, 75% lf, 9 spacing, single-point or cross bonded Section 2 69 kv Power Cables SW Standard Wall XLPE Aluminum Corrugated Sheath 12

69 kv Power Cables 69 kv XLPE - Copper Traditional Wall 650 mil XLPE Copper Concentric Neutrals Cable Construction Reverse Concentric Stranded Copper, Compressed or Milliken Super Smooth Shield Super Clean XLPE Insulation Traditional Wall - 650 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Concentric Neutrals Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kv) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( o C) Nominal 90 Max. Emergency 105 Short Circuit 250 Minimum Installation -10 Design Characteristics Design Standards AEIC, IEC Typical Test Voltages 120 kv / 15 min. XLPE Loss Factor 0.0005 Relative Permittivity 2.3 13

Size in kcmil 1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000 Dimensional Diameter Diameter over Insulation Diameter over Neutrals Overall Jacket Diameter Nominal in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1 in 2.21 2.39 2.53 2.67 2.79 2.90 3.00 3.18 3.34 3.5 3.63 mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2 80.8 84.9 88.9 92.2 in 2.56 2.74 2.88 3.02 3.14 3.25 3.35 3.53 3.69 3.84 3.98 mm 65.0 69.6 73.2 76.7 79.8 82.6 85.1 89.6 93.7 97.6 101.1 in 2.86 3.04 3.18 3.32 3.44 3.55 3.66 3.83 3.99 4.15 4.28 (mm) 72.6 77.2 80.8 84.3 87.4 90.2 93.0 97.4 101.4 105.4 108.7 Total Weight lbs/ft 4.2 5.2 6.1 7.1 8.0 8.9 9.8 11.6 13.4 15.2 17 Min. Bending Radius (install/ perm.) Maximum Pulling Tension Typical Shipping Reel Size in 57/43 61/46 64/48 66/50 69/52 71/53 73/55 77/57 80/60 83/62 86/64 lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000 Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 150x95 150x95 150x95 150x95 Shipping Reel Capacity 2 ft 3,000 3,000 3,000 3,000 3,000 3,000 2,950 3,000 2,700 2,400 2,150 Electrical Electrical Stress @ U o Shield kv/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 3.2 3.1 3.1 3.0 Insulation Shield kv/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9 Short Circuit for 0.5s 3 ka 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410 Nuetrals ka 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6 Resistance DC @ 20 o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003 DC @ 90 o C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003 Capacitance pf/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7 74.4 81.4 83.7 90.3 Charging Current Amps/ kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 1.12 1.22 1.26 1.36 Ampacity @ 90 o C per circuit Typical Single Ductbank 4 Amps 610 760 880 980 1070 1150 1210 1456 1600 1709 1814 Power Rating MVA 73 91 106 118 128 138 145 175 192 205 217 Typical Double Ductbank 4 Amps 520 640 740 830 900 960 1020 1226 1341 1432 1517 Power Rating MVA 63 77 89 100 108 115 122 147 161 172 182 1 2500-4000 kcmil conductors are 5 segment Milliken conductors. 2 Increased shipping reel capacity can be accommodated on request. 3 Declared Values are for 80 x 14 AWG copper wire. Larger wires can accommodate more current. 4 4ft top of duct, 1 o C-m/W native, 0.8 o C-m/W ductbank backfill, 25 o C Ambient, 75% lf, 9 spacing, single-point or cross bonded Section 2 69 kv Power Cables Traditional Wall 650 mil XLPE Copper Concentric Neutrals 14

69 kv Power Cables 69 kv XLPE - Aluminum Traditional Wall 650 mil XLPE Copper Concentric Neutrals Cable Construction Reverse Concentric Stranded Aluminum, Compressed Super Smooth Shield Super Clean XLPE Insulation Traditional Wall - 650 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Concentric Neutrals Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kv) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( o C) Nominal 90 Max. Emergency 105 Short Circuit 250 Minimum Installation -10 Design Characteristics Design Standards AEIC, IEC Typical Test Voltages 120 kv / 15 min. XLPE Loss Factor 0.0005 Relative Permittivity 2.3 15

Size in kcmil 500 750 1000 1250 1500 1750 2000 Dimensional Nominal Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 Diameter over Insulation in 2.21 2.39 2.53 2.67 2.79 2.90 3.00 mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2 Diameter over Neutral in 2.56 2.74 2.88 3.02 3.14 3.25 3.35 mm 65.0 69.6 73.2 76.7 79.8 82.6 85.1 Overall Jacket Diameter in 2.86 3.04 3.18 3.32 3.44 3.55 3.66 mm 72.6 77.2 80.8 84.3 87.4 90.2 93.0 Total Weight lbs/ft 3.1 4.1 4.5 4.9 5.2 5.6 6.0 Min. Bending Radius (install/perm.) in in 57/43 61/46 64/48 66/50 69/52 71/53 73/55 Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000 Typical Shipping Reel Size Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 Shipping Reel Capacity 1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 Electrical Electrical Stress @ U o Shield kv/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 Insulation Shield kv/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 Short Circuit for 0.5s 2 ka 33.8 50.8 67.7 84.6 101.5 118.5 135.4 Nuetrals ka 35.6 35.6 35.6 35.6 35.6 35.6 35.6 Resistance DC @ 20 o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009 DC @ 90 o C Ω/kft 0.044 0.030 0.022 0.018 0.015 0.013 0.011 Capacitance pf/ft 43.9 49.5 54.2 58.4 62.1 65.5 68.7 Charging Current Amps/ kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 Ampacity @ 90 o C per circuit Typical Single Ductbank 3 Amps 480 600 700 780 860 930 1000 Power Rating MVA 58 72 84 94 103 112 120 Typical Double Ductbank 3 Amps 410 510 590 660 730 780 830 Power Rating MVA 49 61 71 79 88 94 100 1 Increased shipping reel capacity can be accommodated on request. 2 Declared Values are for 80 x 14 AWG copper wire. Larger wires can accommodate more current. 3 4ft top of duct, 1 o C-m/W native, 0.8 o C-m/W ductbank backfill, 25 o C Ambient, 75% lf, 9 spacing, single-point or cross bonded Section 2 69 kv Power Cables Traditional Wall 650 mil XLPE Copper Concentric Neutrals 16

69 kv Power Cables 69 kv XLPE - Copper TRADITIONAL WALL 650 MIL XLPE Copper neutrals with copper composite Laminate sheath Cable Construction Reverse Concentric Stranded Copper, Compressed or Milliken Super Smooth Shield Super Clean XLPE Insulation Traditional Wall - 650 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Concentric Neutrals with Copper Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kv) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( o C) Nominal 90 Max. Emergency 105 Short Circuit 250 Minimum Installation -10 Design Characteristics Design Standards AEIC, IEC Typical Test Voltages 120 kv / 15 min. XLPE Loss Factor 0.0005 Relative Permittivity 2.3 17

Size in kcmil 1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000 Dimensional Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Nominal in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.78 1.98 2.08 2.21 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 45.2 50.2 52.8 56.1 in 2.21 2.39 2.54 2.67 2.79 2.90 3.00 3.18 3.34 3.5 3.63 mm 56.1 60.7 64.5 67.8 70.9 73.7 76.2 80.8 84.8 88.9 92.2 in 2.59 2.77 2.92 3.06 3.18 3.29 3.39 3.59 3.75 3.91 4.04 mm 65.8 70.4 74.2 77.7 80.8 83.6 86.1 91.2 95.3 99.3 102.6 in 2.91 3.09 3.24 3.38 3.50 3.61 3.71 3.91 4.07 4.23 4.36 mm 73.9 78.5 82.3 85.9 88.9 91.7 94.2 99.3 103.4 107.4 110.7 Total Weight lbs/ft 4.5 5.5 6.5 7.4 8.4 9.3 10.2 12.1 13.8 15.7 17.5 Min. Bending Radius (install/ perm.) Maximum Pulling Tension Typical Shipping Reel Size in 58/44 62/46 65/49 68/51 70/53 72/54 74/56 78/59 81/61 85/63 87/65 lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000 Flange x Width in 126x95 126x95 126x95 138x95 138x95 138x95 150x95 150x95 150x95 150x95 150x95 Shipping Reel Capacity 2 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,650 2350 2100 Electrical Electrical Stress @ U o Shield kv/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 3.2 3.1 3.1 3.0 Insulation Shield kv/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9 Short Circuit for 0.5s 3 ka 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410 Sheath ka 42.3 42.8 43.2 43.5 43.9 44.1 44.4 44.9 45.4 45.8 46.1 Resistance DC @ 20 o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003 DC @ 90 o C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003 Capacitance pf/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7 74.4 81.4 83.7 90.3 Charging Current Amps/ kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 1.12 1.22 1.26 1.36 Ampacity @ 90 o C per circuit Typical Single Ductbank 4 Amps 610 760 880 980 1070 1150 1210 1456 1600 1709 1814 Power Rating MVA 73 91 106 118 128 138 145 175 192 205 217 Typical Double Ductbank 4 Amps 520 640 740 830 900 960 1020 1226 1341 1432 1517 Power Rating MVA 63 77 89 100 108 115 122 147 161 172 182 1 2500-4000 kcmil conductors are 5 segment Milliken conductors. 2 Increased shipping reel capacity can be accommodated on request. 3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current. 4 4ft top of duct, 1 o C-m/W native, 0.8 o C-m/W ductbank backfill, 25 o C Ambient, 75% lf, 9 spacing, single-point or cross bonded Section 2 69 kv Power Cables Traditional Wall 650 Mil XLPE Copper Neutrals with Copper Composite Laminate Sheath 18

69 kv Power Cables 69 kv XLPE - Copper SW Standard Wall XLPE Copper neutrals with copper composite laminate sheath Cable Construction Reverse Concentric Stranded Copper, Compressed or Milliken Super Smooth Shield Super Clean XLPE Insulation 430 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Copper Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kv) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( o C) Nominal 90 Max. Emergency 105 Short Circuit 250 Minimum Installation -10 Design Characteristics Design Standards AEIC, IEC Typical Test Voltages 120 kv / 15 min. XLPE Loss Factor 0.0005 Relative Permittivity 2.3 19

Size in kcmil 1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000 Dimensional Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Nominal in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.78 1.98 2.08 2.21 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 45.2 50.2 52.8 56.1 mils 520 490 470 450 450 440 430 430 440 450 450 mm 13.2 12.4 11.9 11.4 11.4 11.2 10.9 10.9 11.2 11.4 11.4 in 1.95 2.07 2.18 2.27 2.39 2.48 2.56 2.74 2.92 3.1 3.23 mm 49.5 52.5 55.4 57.7 60.7 63.0 65.0 69.6 74.2 78.7 82.0 in 2.33 2.45 2.56 2.66 2.78 2.87 2.95 3.16 3.41 3.51 3.64 mm 59.3 62.2 65.0 67.4 70.5 72.8 74.9 80.3 86.6 89.1 92.5 in 2.65 2.77 2.88 2.98 3.10 3.19 3.27 3.48 3.73 3.83 3.96 mm 67.3 70.4 73.2 75.7 78.6 80.9 83.0 88.4 94.7 97.2 100.6 Total Weight lbs/ft 4.9 6.0 6.3 7.1 8.0 8.9 9.7 11.7 13.5 15.4 17.1 Min. Bending Radius (install/ perm.) Maximum Pulling Tension Typical Shipping Reel Size in 53/40 55/42 58/43 60/45 62/46 64/48 65/49 70/52 75/56 77/57 79/59 lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000 Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 138x95 150x95 150x95 150x95 Shipping Reel Capacity 2 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,800 2,500 2,200 Electrical Electrical Stress @ U o Shield kv/mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.2 4.1 Insulation Shield kv/mm 2.1 2.4 2.6 2.7 2.8 2.9 3.0 3.0 3.0 3.0 3.0 Short Circuit for 0.5s 3 ka 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410.0 Sheath ka 41.7 42 42.3 42.5 42.8 43.1 43.3 43.8 44.5 44.7 45.1 Resistance DC @ 20 o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003 DC @ 90 o C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003 Capacitance pf/ft 51.1 60.6 68.9 77.1 82.4 88.9 95.3 103.8 112.1 113.3 119.24 Charging Current Amps/ kft 0.77 0.91 1.04 1.16 1.24 1.34 1.43 1.56 1.68 1.702 1.791 Ampacity @ 90 o C per circuit Typical Single Ductbank 4 Amps 620 770 900 1010 1100 1180 1250 1471 1609 1730 1836 Power Rating MVA 75 93 108 121 132 142 150 176 193 207 220 Typical Double Ductbank 4 Amps 520 640 740 830 900 960 1010 1235 1346 1444 1530 Power Rating MVA 63 77 89 100 108 115 121 148 161 173 183 Section 2 69 kv Power Cables standard wall xlpe Copper Neutrals with Copper Composite Laminate Sheath 1 2500-4000 kcmil conductors are 5 segment Milliken conductors. 2 Increased shipping reel capacity can be accommodated on request. 20 3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current. 4 4ft top of duct, 1 o C-m/W native, 0.8 o C-m/W ductbank backfill, 25 o C Ambient, 75% lf, 9 spacing, single-point or cross bonded

69 kv Power Cables 69 kv XLPE - Aluminum Traditional Wall 650 mil XLPE Copper neutrals with aluminum composite laminate sheath Cable Construction Reverse Concentric Stranded Aluminum, Compressed Super Smooth Shield Super Clean XLPE Insulation Traditional Wall - 650 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Aluminum Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kv) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( o C) Nominal 90 Max. Emergency 105 Short Circuit 250 Minimum Installation -10 Design Characteristics Design Standards AEIC, IEC Typical Test Voltages 120 kv / 15 min. XLPE Loss Factor 0.0005 Relative Permittivity 2.3 21

Size in kcmil 500 750 1000 1250 1500 1750 2000 Dimensional Nominal Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 Diameter over Insulation in 2.21 2.39 2.54 2.67 2.79 2.90 3.00 mm 56.1 60.7 64.4 67.8 70.9 73.7 76.2 Diameter over Sheath in 2.60 2.78 2.93 3.06 3.18 3.29 3.39 mm 66.0 70.5 74.3 77.7 80.7 83.5 86.1 Overall Jacket Diameter in 2.92 3.10 3.25 3.38 3.50 3.61 3.71 mm 74.1 78.7 82.4 85.8 88.9 91.7 94.2 Total Weight lbs/ft 3.7 4.2 4.7 5.1 5.5 5.8 6.2 Min. Bending Radius (install/perm.) in 58/44 62/46 65/49 68/51 70/52 72/54 74/56 Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000 Typical Shipping Reel Size Flange x Width in 126x95 126x95 126x95 138x95 138x95 138x95 150x95 Shipping Reel Capacity 1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 Electrical Electrical Stress @ U o Shield kv/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 Insulation Shield kv/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 Short Circuit for 0.5s 2 ka 33.8 50.8 67.7 84.6 101.5 118.5 135.4 Sheath ka 41.6 42 42.3 42.6 42.9 43.1 43.4 Resistance DC @ 20 o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009 DC @ 90 o C Ω/kft 0.043 0.028 0.021 0.017 0.014 0.012 0.011 Capacitance pf/ft 43.9 49.5 54.2 58.4 62.1 65.5 68.7 Charging Current Amps/ kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 Ampacity @ 90 o C per circuit Typical Single Ductbank 3 Amps 480 600 700 780 860 930 1000 Power Rating MVA 58 72 84 94 103 112 120 Typical Double Ductbank 3 Amps 410 510 590 660 730 780 830 Power Rating MVA 49 61 71 79 88 94 100 1 Increased shipping reel capacity can be accommodated on request. 2 Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current. 3 4ft top of duct, 1 o C-m/W native, 0.8 o C-m/W ductbank backfill, 25 o C Ambient, 75% lf, 9 spacing, single-point or cross bonded Section 2 69 kv Power Cables traditional wall 650 mil xlpe Copper Neutrals with aluminum Composite Laminate Sheath 22

69 kv Power Cables 69 kv XLPE - Aluminum SW Standard Wall XLPE copper neutrals with aluminum laminate sheath Cable Construction Reverse Concentric Stranded Aluminum, Compressed Super Smooth Shield Super Clean XLPE Insulation 430 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Aluminum Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Cable Data Voltage Characteristics (kv) Max Voltage Rating 72.5 BIL Rating 350 Temperatures ( o C) Nominal 90 Max. Emergency 105 Short Circuit 250 Minimum Installation -10 Design Characteristics Design Standards AEIC, IEC Typical Test Voltages 120 kv / 15 min. XLPE Loss Factor 0.0005 Relative Permittivity 2.3 23

Size in kcmil 500 750 1000 1250 1500 1750 2000 Dimensional Nominal Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 Insulation Thickness mils 520 490 470 450 450 440 430 mm 13.2 12.4 11.9 11.4 11.4 11.2 10.9 Diameter over Insulation in 1.95 2.07 2.18 2.27 2.39 2.48 2.56 mm 49.5 52.5 55.3 57.7 60.7 63.0 65.1 Diameter over Sheath in 2.34 2.46 2.57 2.66 2.78 2.87 2.95 mm 59.4 62.4 65.2 67.5 70.6 72.9 75.0 Overall Jacket Diameter in 2.66 2.78 2.89 2.98 3.10 3.19 3.27 mm 67.5 70.5 73.3 75.7 78.7 81.0 83.1 Total Weight lbs/ft 3.3 3.7 4.0 4.3 4.7 5.0 5.3 Min. Bending Radius (install/perm.) in 53/40 56/42 58/43 60/45 62/46 64/48 65/49 Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000 Typical Shipping Reel Size Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 138x95 138x95 Shipping Reel Capacity 1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 Electrical Electrical Stress @ U o Shield kv/mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 Insulation Shield kv/mm 2.1 2.4 2.6 2.7 2.8 2.9 3.0 Short Circuit for 0.5s 2 ka 33.8 50.8 67.7 84.6 101.5 118.5 135.4 Sheath ka 41 41.2 41.5 41.7 42 42.2 42.4 Resistance DC @ 20 o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009 DC @ 90 o C Ω/kft 0.043 0.028 0.021 0.017 0.014 0.012 0.011 Capacitance pf/ft 51.1 60.6 68.9 77.1 82.4 88.9 95.3 Charging Current Amps/ kft 0.77 0.91 1.04 1.16 1.24 1.34 1.43 Ampacity @ 90 o C per circuit Typical Single Ductbank 3 Amps 485 608 712 803 884 957 1023 Power Rating MVA 58 73 86 96 106 115 123 Typical Double Ductbank 3 Amps 408 507 590 661 724 780 829 Power Rating MVA 49 61 71 79 87 94 100 1 Increased shipping reel capacity can be accommodated on request. 2 Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current. 3 4ft top of duct, 1 o C-m/W native, 0.8 o C-m/W ductbank backfill, 25 o C Ambient, 75% lf, 9 spacing, single-point or cross bonded Section 2 69 kv Power Cables standard wall xlpe Copper Neutrals with Aluminum Composite Laminate Sheath 24