Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables
|
|
|
- Martina McCarthy
- 10 years ago
- Views:
Transcription
1
2 Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Classically both cables have a single AWG 8 copper conductor or a cross section of 6.0 mm 2. In most cases, the conductor is equipped with a conductor shield formed by a semi-conductive layer, covered by an XLPE insulation. Unshielded cables may have an outer sheath directly extruded above the insulation. The shielded version has another semi-conductive layer above the XLPE insulation covered by a metallic screen (braid or metallic foil) and an outer sheath. Both cables perform well in primary airfield lighting circuits. Nevertheless, the unshielded cable shows a rather high sensitivity to the tracking phenomenon under specific circumstances, leading to service interruption of the lighting circuit. 01. CCR, transformer, lights and cable The fig. 1 shows a typical primary airfield lighting circuit, where a constant current regulator (CCR) feeds the primary airfield cable, the transformers and the lights. fig. 1 T: Transformer L: Light Cable: Airfield Lighting Cable I C : Constant Current T 1, T 2 : CCR Terminals V: CCR Output Voltage 2
3 02. Shielded cables The screen of the cable determines a defined voltage across the dielectric of the cable. The screen is earthed and the voltage to earth is V/2 at the terminals of the CCR, V being the voltage generated by the CCR to draw the preset current I c. The transformers and the lights are represented in fig. 2 by their equivalent resistance R L. A voltage drop at each transformer and its light occurs and in case of a balanced circuit as shown in fig. 2, where the transformers are equally distributed along the cable path, the voltage appearing between conductor and screen is zero at a point situated somewhere in the middle of the circuit. Shielded Primary Airfield Lighting Cable V 03. Unshielded cables L : The local voltage across the dielectric of unshielded cables is not as well determined as is the case of shielded cables. The voltage drop across the transformer terminals and especially the capacitive voltage distribution along the cable path determines the voltage to earth. R L : Resistance Light + Transformer C C : Cable Capacitance I C : Constant Current V: CCR Output Voltage Local Voltage fig. 2 In proximity of the terminals T1 and T2, the voltage to earth is V/2. Along the cable path the voltage on the dielectric depends on the local earth resistance and the local capacitance of the cable to earth. In places where the cable lays in direct contact with a humid soil, the earth resistance is low and the capacitance is high. The voltage is fully supported by the insulation. The voltage-to-earth appearing in those places across the outer surface of the dielectric is very low. In other places, where the soil is dry, the resistance to earth is high and the local voltage is distributed between the cable insulation and the soil. The electric potential-to-earth appearing on the surface of the dielectric is high. If these two circumstances of wet and dry soil appear locally close to each other, a voltage difference V L is build up along the surface of the dielectric; this is shown schematically in fig. 3. Unshielded Primary Airfield Lighting Cable R L : Resistance Light + Transformer C 1... C n : Local Cable Capacitance R 1... R n : Local Earth Resistance V L : Local Voltage on Insulation Surface V: CCR Output Voltage I C : Constant Current fig. 3 3
4 An example illustrates this situation in a very simple manner, as shown in fig. 4. The unshielded cable is placed on an earthed metallic cable-ladder. On the steps, the cable surface has a low resistance to earth; between the steps, the resistance to earth is very high. Thus the electric potential to earth on the surface laying on the steps is zero while the electric potential on the cable surface laying between the steps is high; the voltage across the cable surface and the steps corresponds approximately to the applied voltage, e.g. V/2, when this cable ladder is used close to the constant current regulator. From a safety point of view the potential difference on the cable surface in such a situation can reach a dangerous level. Additionally there is a risk of surface tracking when the cable surface is wet or dirty. The risk increases at higher CCR output voltage level. Earthed Metallic Plate (1) Unshielded Primary Airfield Lighting Cable Earthed Metallic Plate (2) Conductor Insulation Air Conductor Insulation Surface Earth fig Unshielded cables placed on or over a metallic plate Fig. 5 shows an unshielded cable placed at a height h over an earthed metallic plate. The electric field is unequally distributed in the cable dielectric and the air between the dielectric and the metallic plate. The following table gives the maximum electric field strength in that air gap in function of the height h for an unshielded 5 kv AWG 8 - cable with 2,8 mm XLPE insulation according to FAA Specification L-824. The field E is given in kv/mm for a peak voltage of 1 kv conductor to earth. Unshielded Cable over Metallic Plate Insulation Metallic Plate h fig. 5 Height h/mm E air (peak) kv/mm 0 1,18 0,1 1,10 0,2 0,95 0,5 0,75 1,0 0,58 2,0 0,42 Table 1: Electric field in air gap; conductor to metallic plate voltage is 1 kv 4
5 05. Measurements Voltage measurements have been realised on several 10 kva CCR with a digital storage oscilloscope. The latter is equipped with one differential input composed by one inverting and one non-inverting input; both inputs are fitted with HV-probes; the oscilloscope is earthed. Fig. 6 shows the voltage of a normally working CCR; the RMS voltage is 1,23 kv; the peak voltage to earth 2,12 kv. Fig. 7 shows the voltage of a circuit, where several lights were blown out. In this case, the cores of the transformers of these lights go into magnetic saturation and the CCR therefore delivers a much higher peak voltage. Under these circumstances the measured peak voltage is 2,72 kvp to earth. fig. 6 CCR voltage to earth under normal condition fig. 7 CCR voltage to earth with blown out lights 5
6 06. Risk of tracking discharges If the unshielded cable is laying on a metallic plate, the field in the air gap between the cable and the plate will be for h = 0,1 mm and 1 kvp (see table 1): E air = 1,1 kv/mm At the measured peak voltage of 2.72 kv, the electrical field strength in the air gap will be: E air = 1.1 * 2.72 kv/mm = 2.99 kv/mm This field strength corresponds to the disruptive field strength in air; an electrical discharge starts at each half cycle of the voltage; ozone formation and erosion of the dielectric risk to damage the cable surface by tracking. 07. Recommendations The described tracking risk doesn t exist with shielded cables; also from a safety point of view the use of shielded cables is to be preferred. The risk introduced by the tracking phenomenon is well known and introduced in different standards. The US Standard ICEA-S , 4.2.2, applicable to airfield lighting cables, states: "Shielding should be considered where any of the following conditions exits: 1. connections to aerial lines; 2. transition from conducting to non conducting environment; 3. transition from moist to dry earth; 4. dry soil, such in the desert; or 5. damp conduits." In the Appendix G "Shielding" of this standard several other provisions are made concerning the use of shielding, especially in G3.1.3: "Likewise, damage to non-shielded cable may result when the surface of the cable is moist or covered with soot, soapy grease, or other conducting film and the external field is partly confined by such conducting film so that the charging current is carried by the film to some spot where it can discharge to ground. The resultant intensity of discharge may be sufficient to cause burning of the insulation or jacket." 6
7 08. Conclusions The use of unshielded cables introduces several problems especially if the CCR output voltage exeeds the 2000 V-level: safety: the risks of electrical discharges should not be neglected. tracking: the cable may be damaged and cable failures will provoke more maintenance and repair costs. burning: under unfavourable circumstances, fire hazard becomes a reality. The use of shielded cables avoids those problems: no safety problems: the cable jacket may be touched without any risk. no tracking phenomenon: drastically reduced outages. reduced fire hazard. costs: reduced maintenance and repair costs. long lasting investment. 7
8 Malmedyer Str EUPEN - BELGIUM Tel.: +32(0) Fax: +32(0) [email protected] ISO Certified Company 03/
Fault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE
Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both
KNOW YOUR OPTIONS: 230 KV POWER CABLES
KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common
Section 5 161 kv Power Cables
Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper
General Calculations. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE
Excerpt from PRYMIAN WIRE AND CABLE ENGINEERING GUIDE Page 1 of 0 Voltage Rating The selection of the cable insulation level to be used in a particular installation shall be made on the basis of the applicable
Cable Solutions for Servo and Variable Frequency Drives (VFD)
Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect
LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m
FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2
APPLICATION ORIENTED DESIGN OF CABLES
APPLICATION ORIENTED DESIGN OF CABLES Mrs. Rohini Bhattacharyya, Dubai cables Ltd.P. O. Box 11529,Dubai. [email protected] Mr. Nawaf Ahmad Al Mohaideb Dubai Cables Ltd. P. O. Box 11529, Dubai. [email protected]
Model 1756 Test Lead Kit
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you
Industrial Cable Solutions for Variable Frequency Drives
Industrial Cable Solutions for Variable Frequency Drives Tough challenges call for innovative solutions, and General Cable is your worldwide source for new products and a wide range of industry-leading
Festoon 715 P PUR cable for flexible application in festoon systems
CABLES FOR CRANE AND CONVEYOR APPLICATIONS Festoon 715 P PUR cable for flexible application in festoon systems S AB BRÖCKSKES D-VIERSEN Festoon 715 P 1 x 16.0 mm 2 C Marking for Festoon 715 P 07150162:
Screened cable and data cable segregation
December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED
Unarmored Variable Frequency Drive (VFD) Cable Termination Guide
Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored
UGVCL/SP/591/11KV HT AB CABLE
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched
100% EMI Emission Containment
100% EMI Emission Containment Designed for Longer Service Life Highly Flexible for Easier Handling and Faster Installation Authorized Distributor Industrial VFD Cables Index n Variable Frequency Drive
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
PROFIBUS cable. for PROFIBUS-PA and -DP 10/63-6.46 EN
for PROFIBUS-PA and -DP 10/63-6.46 EN CPN 080/CPE 080-Ex PROFIBUS-PA basis cable AWG 18, 0.88 mm 2 Use For fixed installation indoor and outdoor, on racks and in conduits. Application Fieldbus cable for
SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS
SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS Michael Hensel HIGHVOLT Prüftechnik Dresden GmbH 2 3 Content 1 Introduction Test parameters and their significance Differences
Network Standard Advice No. 1420C 9/6/2011
Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides
Gulf Cable & Electrical Ind. Co.
CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC
HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities
HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities RELY ON OUR EXPERIENCE... EXPERIENCE OUR CAPABILITIES For close to half a century, Silec
HARTING Ethernet Cabling 4-poles Overview
Overview RJ45 Connectors [on page 8] System cables [on page 10] Distribution modules and Outlets [on page 20] HARTING PushPull Connectors [on page 22] System cables [on page 24] Panel feed-throughs [on
Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards
Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry
4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters
8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
FIRE RESISTANT CABLE CONSTRUCTION OF CABLES
FIRE RESISTANT CABLE In all fire disasters, fire smoke, heat and toxic fumes are the main obstacles to safe evacuation of a building or area. A major contribution towards overcoming these hazards is the
An Ethernet Cable Discharge Event (CDE) Test and Measurement System
An Ethernet Cable Discharge Event (CDE) Test and Measurement System Wei Huang, Jerry Tichenor ESDEMC Technology LLC Rolla, MO, USA [email protected] Abstract A Cable Discharge Event (CDE) is an electrostatic
Electrical Resistance Resistance (R)
Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed
Flexible and safe solutions, for decades. Cables for alarmand safety systems
Flexible and safe solutions, for decades. Cables for alarmand safety systems 2 We offer the widest range of cables on the market for every kind of installation. It s all about reliability. It is always
Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable
Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable Dr. Uchida Katsumi*, Youichi Katou*, Dr. Hiroyuki Kon, Dr. Kazuo Watanabe and Takenori
Protection Systems. A UTC Fire & Security Company F-73-01. Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS
Effective: May 2007 AlarmLine TM R Protection Systems Linear Heat Detector A UTC Fire & Security Company F-73-01 FEATURES Integrating Type Linear Heat Detector Analog Sensing Field Adjustable Alarm Set
THE PATHWAY TO POWER HIGH-VOLTAGE CABLES
THE PATHWAY TO POWER HIGH-VOLTAGE CABLES TABLE OF CONTENTS HIGH-VOLTAGE CABLES 3 Advantages of XLPE-insulated cable systems 3 PROPOSAL 4 Cable systems 4 Providing System Solutions 4 Continuous temperature
Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
MV CABLE TYPE C 33-226
MV CABLE TYPE C 33-226 Standards : CENELEC HD 620 C 33-226 Rated voltage Rated voltage : 12/20 (24) kv Design 1 Stranded aluminium, class 2 conductor 2 Extruded conducting screen on conductor 3 XLPE insulation
COAX Cables Radio Frequency Cables
COAX Cables Radio Frequency Cables Contents Page Table of contents Pictographs General information Introduction Types and abbreviations Temparature range Construction Characteristics Special constructions
Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW
Complete One Stop Solution for OPGW Cable and Fittings for OPGW 53, Justice Chandra Madhav Road, Kolkata - 700020. India. Phone: 91-33-24748575 / 7565 Fax: 91-33-2476-1955 Email: [email protected] Website:
Commercial Coaxial Cable
Commercial Coaxial Cable For the Best in COMMERCIAL TV Reception Solutions! Do you require a Digital TV reception system for your next project? Matchmaster can supply For The Best Design and supply of
MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES
MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES Riccardo BODEGA, Prysmian Cables and Systems, The Netherlands, [email protected] Henk GEENE,
How To Monitor Water Penetration In A Cable Screen
Detection and location of high voltage cable sheath damage with Water Penetration Monitoring*) Purpose of Monitoring System The expected lifetime of high voltage underground cables is more than 40 years,
Specification SFTP CAT6 Network Cable 23AWG CU
Specification SFTP CAT6 Network Cable 23AWG CU S/FTP CAT6 Shielded S/FTP PVC Cable 23AWG 4pair Solid, Wooden drum 1000 Grey CAT6 600MHZ CM Shielded (S/FTP) Solid Cable: Our CAT6 600MHZ Shielded (S/FTP)
HV Submarine Cable Systems Design, Testing and Installation
HV Submarine Cable Systems Design, Testing and Installation CIGRE Ireland Technical Seminar 6 th October 2010 Robert Donaghy Senior Consultant Engineer, ESB International Presentation Overview Applications
Joslyn Clark Controls, Inc.
Joslyn Clark Controls, Inc. CAPACITOR SWITCHING VACUUM CONTACTORS vs. AIR BREAK CONTACTORS APPLICATION PRECAUTIONS & CALCULATIONS TO LIMIT HIGH FREQUENCY & HIGH CURRENT 2 QUESTION: WHY IS A VACUUM CONTACTOR
Dielectric Withstand Testing in a Production Environment
Dielectric Withstand Testing in a Production Environment Performing a routine product safety test should not in itself represent a shock hazard to the operator who is conducting the test, yet anytime you
Industrial Ethernet The Perfect Cable for an Imperfect Environment
1 Industrial Ethernet The Perfect Cable for an Imperfect Environment Written by: David Fausz, Engineer, Communications Products TABLE OF CONTENTS BACKGROUND 1 APPLICATIONS AND 2 ELECTRICAL PERFORMANCE
Explaining and avoiding faults Increasing availability
Explaining and avoiding faults Increasing availability > Cables > Cable joints > Cable terminals Cables, cable joints, cable terminals Increasing availability A cable breakdown usually means an unexpected
Cat7/Class F New Installation Concept New infrastructure. Handbook
Cat7/Class F New Installation Concept New infrastructure Handbook contents 1 Introduction 3 2 What is the Cat7/Class F installation concept 3 3 Distribution centre 3 3.1 Patch Modules 3 4 How to handle
Insulation Resistance Testing of Low Voltage Cables in the Field
Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4
East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE
SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,
Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks
Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks Introduction This document presents the fundamental aspects of cable and conductor selection for connecting pad mounted shunt
Directions for use : Dosing chutes type DSX.
Pag. 1-10 Directions for use : Dosing chutes type DSX. Introduction The linear vibrations of STILETTO consist of a drive part and a movable part which are connected to leave springs. The purpose of the
Explosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
Good EMC Design Principles: cable routing
Good EMC Design Principles: cable routing Keith Armstrong describes three important techniques for cable routing in metal cabinets, whether the cables are bundles of individual wires, or individual or
SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.
SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.
Crosstalk effects of shielded twisted pairs
This article deals with the modeling and simulation of shielded twisted pairs with CST CABLE STUDIO. The quality of braided shields is investigated with respect to perfect solid shields. Crosstalk effects
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
HIGH VOLTAGE XLPE CABLE SYSTEMS. Technical User Guide
HIGH VOLTAGE XLPE CABLE SYSTEMS Technical User Guide Content 1. General information on High Voltage XLPE Cable Systems 1.1. Introduction 1.2. Cable selection process 1.3. Service life 3 3 3 4 2. Cable
Outdoor Carrier Class Shielded Ethernet Cable. Datasheet. Models: PRO, CARRIER, Connectors. Increase Performance. Extreme Weatherproof
Datasheet Outdoor Carrier Class Shielded Ethernet Cable Models: PRO, CARRIER, Connectors Increase Performance Extreme Weatherproof ESD Damage Protection Extended Cable Support 1 2Datasheet Protect your
Transformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
M. GELDON Brugg Kabel CZ. Ing. D. RÚŽEK PREdistribuce. Switzerland Czech Rep. Czech Rep. Czech Rep., Switzerland Germany
21, rue d Artois, F-75008 PARIS Paper number CIGRE 2012 http : //www.cigre.org 6 characters (to be provided later) Correlation between calculated transmission capacity and actual one D. WALD* Eifelkabel
The proof is here!! Ron Goethals, Philadelphia; June 18, 2014
The proof is here!! The proof is here!! The proof is here!! The proof is here!! The proof is here!! The proof is here!! Highly flame-retarded non-halogen bedding compounds show remarkable effects on: BURNING
Session 14 Cable Support Systems
Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load
Sheath fault location on power cables. Sheath testing, Sheath fault location and Location of earth faults
Sheath fault location on power cables Sheath testing, Sheath fault location and Location of earth faults Table of Contents 1. Introduction... 3 2. Why Sheath testing... 3 2.1 Sheath test devices... 4 2.2
WIRE AND CABLE ENGINEERING GUIDE
DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a
A Study of a MV Cable Joint
SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 7, No. 1, May 2010, 1-11 UDK: 621.315.35:537.212 A Study of a MV Cable Joint Radiša Dimitrijević 1, Neda Pekarić-Nađ 2, Miodrag Milutinov 3 Abstract: Construction
Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note
Coaxial Cable Entry Panels, Coax and Grounding Connectors Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Surge Protection Solutions for PTC 2 Coaxial Cable Entry Panels, Coax
MEDIUM VOLTAGE POWER CABLES
MEDIUM VOLTAGE POWER CABLES CONTENTS 1 GENERAL INTRODUCTION 4 TECHNICAL INFORMATION 15 25 35 45 Single Core XLPE Insulated PVC Sheathed Cables UNARMOURED CABLES COPPER UNARMOURED CABLES ALUMINUM ALUMINUM
e-mobility Special cables for electric vehicles Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies
www.echtzeit.com e-mobility Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies Special cables for electric vehicles Wittener Straße 271 D-42279 Wuppertal Phone +49(0)202.2681.228 Fax +49(0)202.2681.360
DRAFT. University of Pennsylvania Moore School of Electrical Engineering ESE319 Electronic Circuits - Modeling and Measurement Techniques
University of Pennsylvania Moore School of Electrical Engineering ESE319 Electronic Circuits - Modeling and Measurement Techniques 1. Introduction. Students are often frustrated in their attempts to execute
The Contractor shall furnish and install all shielded power cable suitable for use on this project.
Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS
HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING
HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING There are several ways to wire multiple batteries to achieve the correct battery voltage or capacity for a particular DC
Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow
ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations
ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION
ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION Ref: WG 21.06 (TB 177) JTF 21.15 (TB 210) TF B1.10 (Electra 212) Henk Geene Presentation overview Accessories function Accessory design Accessory types
WHITEPAPER. Cable and Connector for Hiperface dsl motor drive applications
WHITEPAPER Cable and Connector for Hiperface dsl motor drive applications information for cable manufacturers Version 02 Content Information for cable manufacturers...3 Communication...3 Crosstalk & shielding...3
Temperatures of Bundled Electrical Cables Installed in Bored Holes in Residential Wood Framing
Temperatures of Bundled Electrical Cables Installed in Bored Holes in Residential Wood Framing Copper Development Association Inc. 260 Madison Avenue New York, NY 16 SUMMARY As part of a larger study of
Respecting the environment
MAIN FEATURE CHAPTER I RESEARCH WITH AN EYE ON THE FUTURE Respecting the environment Low power losses and a lesser visual impact on the landscape make Gas-Insulated Lines (GIL) a very environmentally friendly
SICK AG WHITEPAPER. Information for cable manufacturers Note-2_03
SICK AG WHITEPAPER Cable and connector for HIPERFACE DSL motor drive applications Information for cable manufacturers Note-2_03 Juergen Funkhaenel Application Engineer at SICK STEGMANN GmbH Donaueschingen
High Voltage Systems. Today. The history of cables
High Voltage Cables High Voltage Systems Today Prysmian Cables and Systems B.V. is part of the Prysmian Group, a leading player in the industry of high-technology cables and systems for energy and telecommunications,
Proposed Task Group: Electrical Cable and Condition Monitoring Codes and Standards for Nuclear Power Plants
Proposed Task Group: Electrical Cable and Condition Monitoring Codes and Standards for Nuclear Power Plants Dr. Stephanie Watson Engineering Laboratory, NIST Cables in NPPs Categories Medium voltage power
BRÖCKSKES D-VIERSEN PV1-F 4,0 mm BRÖCKSKES D-VIERSEN PV1-F 4,0 mm d d 2 2 C VDE-REG.-Nr. 8292 10/2009
d BRÖCKSKES BRÖCKSKES D-VIERSEN D-VIERSEN PV1-F PV1-F 4,0 mm 4,0 2 mm VDE-REG.-Nr. 2 C 8292 10/2009 s - THE COMPANY DIN EN ISO 9001 More than 60 years of experience in temperature measurement and control
Planar versus conventional transformer
Planar versus conventional transformer Majid Dadafshar, Principal Engineer Gerard Healy, Field Application Engineer Pulse, a Technitrol Company Power Division Usually the first step on any power supply
EE301 Lesson 14 Reading: 10.1-10.4, 10.11-10.12, 11.1-11.4 and 11.11-11.13
CAPACITORS AND INDUCTORS Learning Objectives EE301 Lesson 14 a. Define capacitance and state its symbol and unit of measurement. b. Predict the capacitance of a parallel plate capacitor. c. Analyze how
Chapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
XLPE Land Cable Systems User s Guide. Rev 5
XLPE Land Cable Systems User s Guide Rev 5 CONTENT XLPE Land Cable Systems Introduction... 3 Design, installation and testing... 4 XLPE cables... 4 Cable accessories... 4 Installation of XLPE cable systems...
ALARMLINE ANALOGUE Linear Heat Detection System
ALARMLINE ANALOGUE Alarmline Analogue sensor cable senses temperature variations by continuously monitoring the resistance of specially doped N.T.C. polymeric insulation. A change in temperature produces
EARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
MEDIUM VOLTAGE CABLES Up to and including 36 KV
MEDIUM VOLTAGE CABLES Up to and including 6 KV NOTICE As this catalogue is not intendedto cover all of LIBAN CABLES SAL possibilities in special cables manufacturing, the hereafter listing of the types
SUBJECT: NO MORE 300 VOLTS IN PLTC PRINT LEGEND
Belden Electronics Division P.O. Box 1980 Richmond, Indiana 47375-1980 2200 U.S. Highway 27 South Richmond, Indiana 47374-7279 Telephone: 765 983 5200 Facsimile: 765 983 5825 SUBJECT: NO MORE 300 VOLTS
Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
Section B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
Understanding Shielded Cable
Understanding Shielded Cable Industrial applications such as the factory floor are typically electrically noisy environments. Electrical noise, either radiated or conducted as electromagnetic interference
MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003
MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU
E-Highway2050 WP3 workshop April 15 th, 2014 Brussels
E-Highway2050 WP3 workshop April 15 th, 2014 Brussels High voltage underground and subsea cable technology options for future transmission in Europe Ernesto Zaccone, Chairman Europacable High Voltage Systems
Integrated Development and Assessment of New Thermoplastic High Voltage Power Cable Systems
21, rue d Artois, F-75008 PARIS B1-215 CIGRE 2012 http : //www.cigre.org Integrated Development and Assessment of New Thermoplastic High Voltage Power Cable Systems Mike FAIRHURST (1), Ankit GOWADIA (1),
DEHN + SÖHNE. DEHNconductor System No Problems with Proximities
DEHN + SÖHNE DEHNconductor System No Problems with Proximities DEHNconductor System - New Possibilities for controling Proximities. For preventing dangerous flashovers among parts of external lightning
ScottishPower Distribution Cables & Equipment. Metal Theft
ScottishPower Distribution Cables & Equipment Metal Theft April 2012 As an aid to deterring to metal theft this booklet has been put together to help identify the types of utility power cables and associated
SEISMIC VELOCITY TRANSDUCER T1-40
SEISMIC VELOCITY TRANSDUCER T1-40 Measurement of Omnidirectional Absolute Vibrations Certified according to ATEX 94/9/CE directive OPERATION Transducer T1-40 serves for seismic measurement of the absolute
AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
Max. Length of HTS Cables in the Future
Max. Length of HTS Cables in the Future K. Schippl, Nexans Deutschland Industries, Hannover, Germany TOPICS: Limitation of the cable design: 1. Physical limitations 2. Shipping limitations 3. Maintenance
EDS 02-0027 11KV TRIPLEX CABLE
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 02-0027 ENGINEERING DESIGN STANDARD EDS 02-0027 11KV TRIPLEX CABLE Network(s): EPN, LPN, SPN Summary:
